Guidelines for Detailing of Reinforcement in Concrete Structures

Discover the best professional documents and content resources in AnyFlip Document Base.
Search
Published by tripleplus009, 2021-03-20 02:39:51

Guidelines for Detailing of Reinforcement in Concrete Structures

Guidelines for Detailing of Reinforcement in Concrete Structures

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

RETAINING WALLS MRW2 - Basement retaining wall
This type of structure are useful to underground building.

Page 200 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

CANTILEVER RETAINING WALLS VARIATIONS

Page 201 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

CANTILEVER RETAINING WALLS KEY

Page 202 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

CANTILEVER RETAINING WALLS VERTICAL CONTRACTION JOINTS

Page 203 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

RECOMMENDATIONS
1. Joints (a) and (b) can transmit stress. Joint (c) can only transmit
horizontal bending stress. Joints (a) and (b) may require corrosion
protection in the area around the reinforcing bar that crosses the crack
if significant amounts of water seep in through the outer side of the
member.
2. Joints (a), (b) and (c) are scantly waterproof.
3. Joints (d) and (e) are fully waterproof.
4. Vigorous vibration must be conducted with extreme care around
water stops.
5. The water stop should penetrate at least 30 cm into the wall
foundation. Welding must be performed very meticulously in long
splices.
6. The beveled and sunken edges in joints (a), (b) and (e) must reduce
the wall section by at least 25 per cent to ensure that the crack will form.

CANTILEVER RETAINING WALLS - EXPANSION JOINTS

Page 204 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

RECOMMENDATIONS
1. The failure to make J-J joints in (a) and (b) places horizontal tensile
stress in the stems and may induce torsion in the footings. In this case,
the members affected should be designed accordingly.
2. Expanded polystyrene may be replaced by any readily compressed
material.
3. The seal for joint (d) should rest on the polystyrene.
4. Vigorous vibration must be conducted with extreme care around
water stops.
5. The water stop should penetrate at least 30 cm into the wall
foundation. Welding must be performed very meticulously in long
splices.
2. STATUTORY LEGISLATION
None in place.
3. RECOMMENDED ALTERNATIVE CODES - See ACI (29).
4. SPECIFIC REFERENCES - See Chapter 14 in (27).

Page 205 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

CANTILEVER RETAINING WALLS FILLAND DRAINAGE

RECOMMENDATIONS
1. Angle e must be calculated.
2. Granular fill should be used to ensure effective drainage. Otherwise,
the thrust cannot be assessed using the usual Rankine and Coulomb
theories on earth pressure.
3. For water proofing the wall there are two systems, (b), (c). In solution
(b), waterproofing consists of a mere coat of asphalt paint. In (c), a
waterproofing membrane is used.
4. Alternative (c) is the solution of choice when water tightness must be
guaranteed.

Page 206 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

BUTTRES WALLS FOOTING

Page 207 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

BUTTRESS WALLS STEM

Page 208 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

BUTTRESS WALLS - INSIDE BUTTRESS

Page 209 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

BUTTRESS WALLS END BUTTRESS

Page 210 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

TRAY WALLS

Page 211 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

BASEMENT WALLS FACADE FOOTING

Page 212 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

Page 213 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2015 Guidelines for Detailing of Reinforcement in Concrete Structures EC2 & ACI

Page 214 Dr Luay Mohammed Al-Shather KUFA UNIVERSITY /FACULTY OF ENGINEERING

[email protected] MOBILE : IQ - 07822234399

2018‫‏‬

KUFA UNIVERSITY FACULTY OF
ENGINEERING

Dr – Luay Mohammed Al-Shather

][

SUMMARY OF ACI & EC2 CODES AND STANDARDS ON CONSTRUCTION DETAILS