Medium Voltage Power Cables

Operating Voltage (from 6/10 kV up to 18/30 kV) Cable Construction

1. Conductor

Stranded, round and compacted Copper or Aluminium conductors, according to IEC 60228 class 2.

2. Conductor screen

An extruded layer of semi conducting material applied over the conductor as voltage stress control layer.

3. Insulation

An extruded layer of cross linked polyethylene (XLPE) is applied over the inner semi conductar with
thickness as specified in IEC 60502.

4. Insulation Screen

An extruded layer at strippable or firmly banded to the insulation. Conductor screen, XLPE insulation
and insulation screen are applied at the same time using triple head extruder.

5. Metallic Screen

a. Copper Tape: an annealed Copper tape is applied helically with a suitable overlap.
b. Copper Wire: helically applied and binded with a Copper tape to achieve electrical contact

6. Assembly

In case of three core cables cores are assembled together with suitable lay length non-hygroscopic filler is applied
during assembly to fill spaces between cores then wrapped with suitable binder tape.

7. Bedding

in case of armoured cables an extruded layer of PVC or MDPE or LLDPE is applied as bedding.

8. Armouring

a. Steel Tape: double layers of steel tapes are applied helically.
b. Steel Wire: galvanized steel wires are applied helically.

9. Sheath

An extruded layer of PVC is applied with thickness as specified in IEC 60502.

Option
Lead Sheath: Upon request a layer of lead is extruded over the bedding layer.

Armouring of Single Core Cable

1. Armouring by non-magnetic material either Aluminium Tape armouring or Aluminium Wire armouring to reduce
the magnetic losses.
2. If it is required for single core cable to be armoured by steel wire armouring the magnetic circuit around the single
core cable should be interrupted by inserting insulated copper wire between the steel wires.

insulted copper Conductor Conductor
wires Insulation
Bedding Insulation
Steel Wire Bedding
Armouring Sheath

All Wire
Armouring

Sheath

Medium Voltage Power Cables

Designation Code for Medium Voltage Power Cables You can order
our product by giving the following informations

1- cable codes as per the catalogue
2- if your requirements is out of our catalogue product range, you can use the following map to
identify the code

Conductor Material Armoring & Shielding
C Copper U Unarmored
A Aluminum I Steel Tapes Armored
G Copper + Swelling Powder + S.C Tape H Galavaniz ed Steel Wires Armored
E Aluminum + Swelling Powder + S.C Tape
K A luminum Tapes Armored
C.S.A mm2 J Aluminum Wires Armored
18 50 Z Galvanize d Steel T apes Armored
1 9 70 D L ead + G alvanized Steel W ires Armored
2 0 9 5 F Lead + Aluminum Wires Armored
2 1 120 E L ead + S teel Tape s Armored
Y L ead + G alvanized Steel Tapes Armored
22 150 G L ead + A luminum Tapes Arm ored
23 1 85 N Aluminum foil Shie ld
24 2 40
25 3 00 Outer Sheathing Type
26 400
2 7 5 00 P PVC
2 8 6 30 H HDPE
2 9 800 M MDPE
30 1000 L LDPE
E LLDPE
F PVC / FR
Insulation Type S LSZH
X XLPE

Voltage Grade
4 3.6 / 6 (7.2) KV
5 6 / 10 (12) KV
6 8.7 / 15 (17.5) KV
7 12 / 20 (24) KV
8 18 / 30 (36) KV

No. of Cores
01 1
0 3 3

intelligent

Single & Three Cores Nominal Max. Conductor Inductance Current Rating
Copper Conductors Cross Resistance Trefoil Flat
XLPE Insulated and PVC Product Operating Laid in Laid in Approx. Approx
Sheathed Code Sectional DC at AC at capacitance Ground free Air Overall Weight
Area 20 OC 90 OC
Inner semi-con
Copper conductor

mm2 Ω/km Ω/km f/km A AAA A A mm kg / km

Single Core Cable

XLPE insulation C18X501UP 50 0.3870 0.4937 0.251 0.393 0.578 197 206 209 255 22.5 905
70 0.2680 0.3420 0.291 0.370 0.554 242 252 262 319 24.3 1135
PVC Sheathing Outer semi-con Binder tape & Filler C19X501UP 95 0.1930 0.2465 0.316 0.357 0.542 287 299 317 384 25.5 1390
Copper tape screen 120 0.1530 0.1956 0.345 0.344 0.529 326 339 366 443 26.9 1655
C20X501UP 150 0.1240 0.1588 0.374 0.336 0.521 364 375 416 498 28.7 2015
185 0.0991 0.1272 0.409 0.322 0.507 411 422 478 570 30.4 2390
C21X501UP 240 0.0754 0.0973 0.456 0.310 0.494 475 484 565 669 33.0 2950
300 0.0601 0.0781 0.512 0.301 0.487 535 542 650 765 35.8 3590
Description C22X501UP 400 0.0470 0.0618 0.565 0.292 0.477 591 599 745 853 38.6 4510
C23X501UP 500 0.0366 0.0490 0.635 0.282 0.467 659 674 859 975 42.2 5610
630 0.0283 0.0391 0.704 0.275 0.460 728 752 981 1103 45.9 6940
• Stranded circular compacted Copper C24X501UP 800 0.0221 0.0319 0.795 0.268 0.453 869 979 1160 1480 50.8 9195
conductor, semiconducting layer as C25X501UP
conductor screen, XLPE insulated, C26X501UP 50 2655
70 3390
semiconducting layer as non metallic C27X501UP 95 4165
120 5140
insulation screen. Copper tape or wire C28X501UP 150 5965
185 7210
as metallic insulation screen, three C29X501UP 240 Three Core Cables 9020
cores assembled together with non 300 11095

hygroscopic Polypropylene fillers, 0.3870 0.4938 0.351 - 197 - 206 -
wraped with binder tape and PVC C18X503UP 0.2680 0.3423 0.251 0.330 - 241 - 257 - 43.5
0.1930 0.2469 0.291 0.316 - 286 - 309 - 47.2
sheathed. C19X503UP 0.1530 0.1961 0.316 0.309 - 325 - 356 - 50.0
0.1240 0.1595 0.345 0.302 - 364 - 405 - 53.6
• Cables are produced according to C20X503UP 0.0991 0.1282 0.374 0.290 - 410 - 463 - 56.9
0.0754 0.0983 0.409 0.280 - 475 - 546 - 60.9
IEC 60502 or BS 6622. C21X503UP 0.0601 0.0799 0.456 0.271 - 535 - 626 - 66.3
0.512 71.9
Application C22X503UP

• These cables are generally suitable C23X503UP
for direct burial or for installation on trays C24X503UP
or in ducts. C25X503UP

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

Nominal Max. Inductance Current Rating Approx. Single & Three Cores
Cross Conductor Overall Aluminum ConductorsXLPE
Product- Resistance Operating Trefoil Flat Laid in Laid in Diameter Approx Insulated and PVC Sheathed
Code Sectional capacitance Ground free Air
Area DC at AC at Weight
20 OC 90 OC
A A A A mm kg / km Aluminum condInuncetorrsemi-con PVC Sheathing

mm2 Ω/km Ω/km f/km AA

Single Core Cable

A18X501UP 50 0.6410 0.8220 0.251 0.393 0.578 153 160 162 198 22.4 610
A19X501UP 70 0.4430 0.5681 0.291 0.370 0.554 188 196 204 248 24.0
A20X501UP 95 0.3200 0.4105 0.316 0.357 0.542 222 233 246 299 25.5 715 XLPE insulation
A21X501UP 120 0.253.0 0.3247 0.345 0.344 0.529 254 265 284 346 26.9 Outer semi-con Binder tape & Filler
A22X501UP 150 0.2060 0.2645 0.374 0.336 0.521 283 295 324 391 28.7 815 Copper tape screen
A23X501UP 185 0.1640 0.2107 0.409 0.322 0.507 321 333 373 449 30.4
A24X501UP 240 0.1250 0.1610 0.456 0.310 0.494 372 385 443 530 32.9 915
A25X501UP 300 0.1000 0.1291 0.512 0.301 0.487 421 433 511 608 35.5
A26X501UP 400 0.0778 0.1009 0.565 0.292 0.477 478 483 593 693 38.6 1115
A27X501UP 500 0.0605 0.0791 0.635 0.282 0.467 544 545 693 802 42.2
A28X501UP 630 0.0469 0.0621 0.704 0.275 0.460 612 617 803 921 45.8 1250 Description
A29X501UP 800 0.0367 0.0495 0.795 0.268 0.453 715 786 954 1188 50.8 1475

A18X503UP 50 0.6410 0.8220 1700 • Stranded circular compacted Aluminium
A19X503UP 70 0.4430 0.5683
A20X503UP 95 0.3200 0.4107 Three Core Cables 2120 conductor, semiconducting layer as
A21X503UP 120 0.253.0 0.3250
A22X503UP 150 0.2060 0.2649 2505 conductor screen, XLPE insulated,
A23X503UP 185 0.1640 0.2114 3000 semiconducting layer as non metallic
A24X503UP 240 0.1250 0.1618 3670 insulation screen. Copper tape or wire
A25X503UP 300 0.1000 0.1302
as metallic insulation screen, three cores

assembled together with non hygroscopic

0.251 0.351 - 153 - 160 - 42.9 1800 Polypropylene fillers, wraped with binder
0.291 0.330 - 187 - 200 - 46.5
0.316 0.316 - 222 - 240 - 50.0 2100 tape and PVC sheathed.
0.345 0.309 - 253 - 277 - 53.2
2440 • Cables are produced according to IEC
0.374 0.302 - 283 - 314 - 56.9
2780 60502 or BS 6622.
0.409 0.290 - 320 - 361 - 60.9
0.456 0.280 - 371 - 427 - 66.1 3280 Application
0.512 0.271 - 420 - 491 - 71.3
3790 • These cables are generally suitable for
4555 direct burial or for installation on trays or in
5360 ducts.

Member Pioneer Holding

254

intelligent

Inner semi-con STA ( Seel tape armored )
Copper or Aluminum conductor

Three Cores Copper or

Aluminum Conductors, XLPE

Insulated, Steel Tape Armoured

and PVC Sheathed XLPE insulation Inner Sheathing PVC Sheathing
Outer semi-con Binder tape & Filler
Description
Copper tape screen

• Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated,
semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation screen,

three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC

sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Max. Conductor Current Rating Approx.
Resistance Overall
Nominal Cross Operating Diameter Approx
Product-Code Sectional Area DC at AC at Capacitance Inductance Laid in Laid in Weight
20 OC 90 OC mh/km Ground Free Air mm
C18X503IP mm2 f/km kg / km
C19X503IP Ω/km Ω/km A A 47.9
C20X503IP 50 51.8 3625
C21X503IP 70 Three Cores Copper Conductor Cables 54.6 4470
C22X503IP 95 57.8 5305
C23X503IP 120 0.3870 0.4938 0.251 0.352 185 192 61.7 6205
C24X503IP 150 0.2680 0.3423 0.291 0.330 226 237 65.5 7290
C25X503IP 185 0.1930 0.2469 0.316 0.316 269 286 71.3 8595
240 0.1530 0.1961 0.345 0.311 306 328 77.1 10595
A18X503IP 300 0.1240 0.1595 0.374 0.302 342 371 12835
A19X503IP 0.0991 0.1282 0.409 0.290 386 424 47.3
A20X503IP 50 0.0754 0.0986 0.456 0.280 446 497 51.1 2760
A21X503IP 70 0.0601 0.0799 0.512 0.272 502 566 54.6 3170
A22X503IP 95 57.8 3585
A23X503IP 120 Three Cores Aluminium Conductor Cables 61.7 3995
A24X503IP 150 65.5 4605
A25X503IP 185 0.6410 0.8220 0.251 0.351 144 149 71.1 5175
240 0.4430 176 184 76.5 6120
C18X503HP 300 0.3200 0.5683 0.291 0.330 209 222 7085
C19X503HP 0.2530 238 255 51.1
C20X503HP 50 0.2060 0.4107 0.316 0.316 266 288 55.0 5085
C21X503HP 70 0.1640 301 331 57.8 6000
C22X503HP 95 0.1250 0.3250 0.345 0.309 349 389 61.4 6920
C23X503HP 120 0.1000 394 444 64.9 8090
C24X503HP 150 0.2649 0.374 0.302 68.9 9130
C25X503HP 185 0.3870 187 195 76.6 10630
240 0.2680 0.2114 0.409 0.290 227 241 82.2 13700
A18X503HP 300 0.1930 269 289 16165
A19X503HP 0.1530 0.1618 0.456 0.280 305 331 50.5
A20X503HP 50 0.1240 340 372 54.3 4185
A21X503HP 70 0.0991 0.1302 0.512 0.271 381 423 57.8 4705
A22X503HP 95 0.754 436 494 61.0 5195
A23X503HP 120 0.0601 Three Cores Copper Conductor Cables 485 556 64.9 5725
A24X503HP 150 68.9 6445
A25X503HP 185 0.4938 0.251 0.352 76.4 7160
240 0.3423 0.291 0.330 81.6 9130
300 0.2469 0.316 0.316 10315
0.1961 0.345 0.311
0.1595 0.374 0.302
0.1282 0.409 0.290
0.0986 0.456 0.280
0.799 0.512 0.272

Three Cores Aluminium Conductor Cables

0.6410 0.8220 0.251 0.351 145 152
0.4430 0.5683 0.291 0.330 177 188
0.3200 0.4107 0.316 0.316 210 225
0.2530 0.3250 0.345 0.309 238 259
0.2060 0.2649 0.374 0.302 265 291
0.1640 0.2114 0.409 0.290 300 332
0.1250 0.1618 0.456 0.280 346 391
0.1000 0.1302 0.512 0.271 387 442

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

Member Pioneer Holding 255

intelligent

Multicore Cables, with Stranded Inner semi-con PVC Sheathing
Aluminum Copper conductor
Conductors XLPE Insulated and
PVC Sheathed XLPE insulation
Outer semi-con Binder tape & Filler
Description Copper tape screen

• Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated,
semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation screen,
three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC
sheathed, • Cables are produced according to IEC 60502 or BS 6622

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Max. Conductor Resistance Inductance Current Rating Approx.
Trefoil Flat Overall
Nominal Cross DC at AC at Operating Laid in ground Laid in free Diameter Approx
Product-Code Sectional Area 20 OC 90 OC capacitance air Weight

C18X601UP mm2 Ω/km Ω/km f/km mh/km mh/km A AAA mm kg / km
C19X601UP
C20X601UP 50 0.3870 0.4937 Single Core Cable 0.597 197 206 209 255 24.7 999
C21X601UP 70 0.2680 0.3420 0.572 242 252 262 319 26.5 1230
C22X601UP 95 0.1930 0.2465 0.204 0.412 0.558 287 299 317 384 27.7 1479
C23X601UP 120 0.1530 0.1956 0.234 0.387 0.546 326 339 366 443 29.3 1761
C24X601UP 150 0.1240 0.1588 0.253 0.373 0.536 364 375 416 498 30.9 2111
C25X601UP 185 0.0991 0.1272 0.522 411 422 478 570 32.8 2512
C26X601UP 240 0.0754 0.0973 0.275 0.361 0.509 475 484 565 669 35.4 3083
C27X601UP 300 0.0601 0.0781 0.498 535 542 650 765 38.0 3718
C28X601UP 400 0.0470 0.0618 0.297 0.351 0.489 591 599 745 853 41.0 4661
C29X601UP 500 0.0366 0.0490 0.324 0.338 0.478 659 674 859 975 44.6 3808
630 0.0283 0.0391 0.470 728 752 981 1103 48.3 7127
C18X603UP 800 0.0221 0.0319 0.360 0.324 0.462 869 979 1160 1480 53.2 9010
C19X603UP
C20X603UP 50 0.3870 0.4938 0.402 0.313 - 197 - 206 - 48.3 2990
C21X603UP 70 0.2680 0.3423 0.442 0.304 - 241 - 257 - 52.3 3725
C22X603UP 95 0.1930 0.2469 - 286 - 309 - 55.1 4505
C23X603UP 120 0.1530 0.1961 0.495 0.293 - 325 - 356 - 58.4 5410
C24X603UP 150 0.1240 0.1595 - 364 - 405 - 62.0 6415
C25X603UP 185 0.0991 0.1282 0.548 0.285 - 410 - 463 - 65.9 7685
240 0.0754 0.0986 0.616 0.277 - 475 - 546 - 71.10 9540
Product-Code 300 0.0601 0.0799 Three Core Cable - 535 - 626 - 76.9 11590

C18X503HP 0.204 0.376
C19X503HP
C20X503HP 0.234 0.354
C21X503HP
C22X503HP 0.253 0.340
C23X503HP
C24X503HP 0.275 0.329
C25X503HP
0.297 0.320
A18X503HP
A19X503HP 0.324 0.308
A20X503HP
A21X503HP 0.360 0.295
A22X503HP
A23X503HP 0.402 0.288
A24X503HP
A25X503HP Max. Conductor Current Rating Approx.
Resistance Overall
Nominal Cross Operating Diameter Approx
Sectional Area DC at AC at Capacitance Inductance Laid in Laid in Weight
20 OC 90 OC Ground Free Air mm
mm2 kg / km
Ω/km Ω/km f/km mh/km A A 51.1
50 55.0 5085
70 Three Cores Copper Conductor Cables 57.8 6000
95 61.4 6920
120 0.3870 0.4938 0.251 0.352 187 195 64.9 8090
150 0.2680 0.3423 0.291 0.330 227 241 68.9 9130
185 0.1930 0.2469 0.316 0.316 269 289 76.6 10630
240 0.1530 0.1961 0.345 0.311 305 331 82.2 13700
300 0.1240 0.1595 0.374 0.302 340 372 16165
0.0991 381 423 50.5
50 0.754 0.1282 0.409 0.290 436 494 54.3 4185
70 0.0601 485 556 57.8 4705
95 0.0986 0.456 0.280 61.0 5195
120 0.6410 145 152 64.9 5725
150 0.4430 0.799 0.512 0.272 177 188 68.9 6445
185 0.3200 210 225 76.4 7160
240 0.2530 Three Cores Aluminium Conductor Cables 238 259 81.6 9130
300 0.2060 265 291 10315
0.1640 0.8220 0.251 0.351 300 332
0.1250 0.5683 0.291 0.330 346 391
0.1000 0.4107 0.316 0.316 387 442
0.3250 0.345 0.309

0.2649 0.374 0.302

0.2114 0.409 0.290
0.1618 0.456 0.280

0.1302 0.512 0.271

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

Member Pioneer Holding

256

intelligent

Single & Three Cores Copper Inner semi-con
Conductors, XLPE Insulated and Copper conductor
PVC Sheathed

XLPE insulation PVC Sheathing
Outer semi-con Binder tape & Filler
Description Copper tape screen

• Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated,

semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation screen,

three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC

sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application
• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Nominal Cross Max. Conductor Resistance Inductance Current Rating Approx. Approx
Sectional Area Trefoil Flat Laid in ground Laid in free air Overall Weight
Product-Code DC at AC at Operating Diameter
mm2 20 OC 90 OC capacitance mh/km mh/km AAAA kg / km
A18X601UP mm
A19X601UP 50 Ω/km Ω/km f/km 700
A20X601UP 70 24.6 800
A21X601UP 95 Single Core Cable 26.2 905
A22X601UP 120 27.7 1020
A23X601UP 150 0.6410 0.8220 0.204 0.412 0.597 153 160 162 198 29.3 1215
A24X601UP 185 0.4430 0.5681 0.234 0.387 0.572 188 196 204 248 30.9 1370
A25X601UP 240 0.3200 0.4105 0.253 0.373 0.558 222 233 246 299 32.8 1595
A26X601UP 300 0.2530 0.3247 0.275 0.361 0.546 254 265 284 346 35.3 1825
A27X601UP 400 0.2060 0.2645 0.297 0.351 0.536 283 295 324 391 37.7 2270
A28X601UP 500 0.1640 0.2107 0.324 0.338 0.522 321 333 373 449 41 2670
A29X601UP 630 0.1250 0.1610 0.360 0.324 0.509 372 385 443 530 44.6 3180
800 0.1000 0.1291 0.402 0.313 0.498 421 433 511 608 48.2 3870
A18X603UP 0.0778 0.1009 0.442 0.304 0.489 478 483 593 693 53.2
A19X603UP 50 0.0605 0.0791 0.495 0.293 0.478 544 545 693 802 2040
A20X603UP 70 0.0469 0.0621 0.548 0.288 0.470 612 617 803 921 47.6 2375
A21X603UP 95 0.0367 0.0495 0.616 0.277 0.462 715 786 954 1188 51.3 2730
A22X603UP 120 54.7 3120
A23X603UP 150 Three Core Cable 58 3645
A24X603UP 185 61.6 4205
A25X603UP 240 0.6410 0.8220 0.204 0.376 153 160 65.7 4975
300 0.4430 0.5683 0.234 0.354 187 200 70.4 5775
0.3200 0.4107 0.253 0.340 222 240 76
0.2530 0.3250 0.275 0.329 253 277
0.2060 0.2649 0.297 0.320 283 314
0.1640 0.2114 0.324 0.308 320 361
0.1250 0.1618 0.360 0.295 371 427
0.1000 0.1302 0.402 0.288 420 491

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

Member Pioneer Holding 257

intelligent

Single & Three Cores Inner semi-con
Allmunium Conductors, XLPE Aluminum conductor
Insulated and PVC Sheathed

XLPE insulation PVC Sheathing
Outer semi-con Binder tape & Filler
Description Copper tape screen

• Stranded circular compacted Aluminium conductor, semiconducting layer as conductor screen, XLPE
insulated, semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation
screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape
and PVC sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application
• These cables are generally suitable for direct burial or for installation on trays or in ducts. .

Nominal Cross Max. Conductor Resistance Inductance Current Rating Approx. Approx
Sectional Area Trefoil Flat Laid in ground Laid in free air Overall Weight
Product-Code DC at AC at Operating Diameter
mm2 20 OC 90 OC capacitance mh/km mh/km AAAA kg / km
A18X601UP mm
A19X601UP 50 Ω/km Ω/km f/km 700
A20X601UP 70 24.6 800
A21X601UP 95 Single Core Cable 26.2 905
A22X601UP 120 27.7 1020
A23X601UP 150 0.6410 0.8220 0.204 0.412 0.597 153 160 162 198 29.3 1215
A24X601UP 185 0.4430 0.5681 0.234 0.387 0.572 188 196 204 248 30.9 1370
A25X601UP 240 0.3200 0.4105 0.253 0.373 0.558 222 233 246 299 32.8 1595
A26X601UP 300 0.2530 0.3247 0.275 0.361 0.546 254 265 284 346 35.3 1825
A27X601UP 400 0.2060 0.2645 0.297 0.351 0.536 283 295 324 391 37.7 2270
A28X601UP 500 0.1640 0.2107 0.324 0.338 0.522 321 333 373 449 41 2670
A29X601UP 630 0.1250 0.1610 0.360 0.324 0.509 372 385 443 530 44.6 3180
800 0.1000 0.1291 0.402 0.313 0.498 421 433 511 608 48.2 3870
A18X603UP 0.0778 0.1009 0.442 0.304 0.489 478 483 593 693 53.2
A19X603UP 50 0.0605 0.0791 0.495 0.293 0.478 544 545 693 802 2040
A20X603UP 70 0.0469 0.0621 0.548 0.288 0.470 612 617 803 921 47.6 2375
A21X603UP 95 0.0367 0.0495 0.616 0.277 0.462 715 786 954 1188 51.3 2730
A22X603UP 120 54.7 3120
A23X603UP 150 Three Core Cable 58 3645
A24X603UP 185 61.6 4205
A25X603UP 240 0.6410 0.8220 0.204 0.376 153 160 65.7 4975
300 0.4430 0.5683 0.234 0.354 187 200 70.4 5775
0.3200 0.4107 0.253 0.340 222 240 76
0.2530 0.3250 0.275 0.329 253 277
0.2060 0.2649 0.297 0.320 283 314
0.1640 0.2114 0.324 0.308 320 361
0.1250 0.1618 0.360 0.295 371 427
0.1000 0.1302 0.402 0.288 420 491

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

Member Pioneer Holding

258

intelligent

Single & Three Cores Copper Inner semi-con STA ( Seel tape armored )
Conductors, XLPE Insulated and Copper or Aluminum conductor
PVC Sheathed

XLPE insulation Inner Sheathing PVC Sheathing
Outer semi-con Binder tape & Filler

Description Copper tape screen

• Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated,

semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation screen,

three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC

sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application
• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Max. Conductor Resistance Current Rating Approx.
Overall
Product-Code Nominal Cross DC at AC at Operating Inductance Laid in Laid in Free Diameter Approx
Sectional Area 20 OC 90 OC Capacitance mh/km groung Air Weight
C18X603IP mm
C19X603IP mm2 Ω/km Ω/km f/km A A kg / km
C20X603IP
C21X603IP 50 Three Cores Copper Conductor Cables
C22X603IP 70
C23X503IP 95 0.3870 0.4938 0.204 0.376 185 192 52.7 4055
C24X603IP 120 0.2680 0.3423 0.234 0.354 226 237 56.7 4875
C25X603IP 150 0.1930 0.2469 0.253 0.340 269 286 59.9 5790
185 0.1530 0.1961 0.275 0.330 306 328 63.4 6790
A18X603IP 240 0.1240 0.1595 0.297 0.320 342 371 67 7865
A19X603IP 300 0.0991 0.1282 0.324 0.308 386 424 70.9 9220
A20X603IP 0.0754 0.0986 0.360 0.296 446 497 76.2 11225
A21X603IP 50 0.0601 0.0799 0.402 0.288 502 566 83.7 14265
A22X603IP 70
A23X603IP 95 Three Cores Aluminium Conductor Cables
A24X603IP 120
A25X603IP 150 0.6410 0.8220 0.204 0.376 144 149 52.4 3160
185 0.4430 0.5683 0.234 0.354 176 184 56.1 3575
Product-Code 240 0.3200 0.4107 0.253 0.340 209 222 59.7 4040
300 0.2530 0.3250 0.275 0.329 238 255 63.2 4530
C18X603HP 0.2060 0.2649 0.279 0.320 266 288 67.0 5180
C19X603HP Nominal Cross 0.1640 0.2114 0.324 0.308 301 331 70.9 5800
C20X603HP Sectional Area 0.1250 0.1618 0.360 0.295 349 389 76.0 6755
C21X603HP 0.1000 0.1302 0.402 0.288 394 444 83.0 8500
C22X603HP mm2
C23X603HP Max. Conductor Resistance Current Rating Approx. Approx
C24X603HP 50 Overall Weight
C25X603HP 70 DC at AC at Operating Inductance Laid in Laid in Free Diameter
95 20 OC 90 OC Capacitance mh/km groung Air kg / km
A18X603HP 120 mm
A19X603HP 150 Ω/km Ω/km f/km A A
A20X603HP 185
A21X603HP 240 Three Cores Copper Conductor Cables
A22X603HP 300
A23X603HP 0.3870 0.4938 0.204 0.376 187 195 55.9 5715
A24X603HP 50 0.2680 0.3423 0.234 0.354 227 241 59.9 6650
A25X603HP 70 0.1930 0.2469 0.253 0.34 269 289 63.1 7655
95 0.1530 0.1961 0.275 0.330 305 331 66.6 8765
120 0.1240 0.1595 0.297 0.320 340 372 72.3 10935
150 0.0991 0.1282 0.324 0.308 381 423 76.2 12450
185 0.0754 0.0986 0.360 0.296 436 494 81.5 14735
240 0.0601 0.0799 0.402 0.288 485 556 87.6 17230
300
Three Cores Aluminium Conductor Cables 145 152 55.6 4715
177 188 59.3 5245
0.6410 0.8220 0.204 0.376 210 225 62.9 5825
0.4430 0.5683 0.234 0.354 238 259 66.4 6400
0.3200 0.4107 0.253 0.340 265 291 72.3 8095
0.2530 0.3250 0.275 0.329 300 332 76.2 8865
0.2060 0.2649 0.279 0.320 346 391 81.1 9850
0.1640 0.2114 0.324 0.308 387 442 86.9 11135
0.1250 0.1618 0.360 0.295
0.1000 0.1302 0.402 0.288

Member Pioneer Holding 259

intelligent

8.7/15 (17.5) kV Inner semi-con
Three Cores Copper or Copper conductor

Aluminum Conductors,

XLPE Insulated , Steel Tape

Armoured and PVC Sheathed XLPE insulation PVC Sheathing
Outer semi-con Binder tape & Filler
Description Copper tape screen

• Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated,

semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation screen,

three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC

sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Nominal Cross Max. Conductor Resistance Inductance Current Rating Approx. Approx
Sectional Area Trefoil Flat Laid in ground Laid in free Air Overall Weight
Product-Code DC at AC at Operating Diameter
mm2 20 OC 90 OC capacitance mh/km mh/km AAAA kg / km
mm
Ω/km Ω/km f/km

Single Core Cable

C18X701UP 50 0.3870 0.4937 0.177 0.428 0.613 197 206 209 255 26.7 1070
C19X701UP
C20X701UP 70 0.2680 0.3420 0.202 0.403 0.588 242 252 262 319 28.7 1320
C21X701UP
C22X701UP 95 0.1930 0.2465 0.217 0.389 0.573 287 299 317 384 29.9 1575
C23X701UP
C24X701UP 120 0.1530 0.1956 0.236 0.376 0.561 326 339 366 443 31.5 1860
C25X701UP
C26X701UP 150 0.1240 0.1588 0.254 0.365 0.550 364 375 416 498 33.1 2220
C27X701UP
C28X701UP 185 0.0991 0.1272 0.276 0.350 0.535 411 422 478 570 35.0 2625
C29X701UP
240 0.0754 0.0973 0.305 0.335 0.520 475 484 565 669 37.4 3185

300 0.0601 0.0781 0.340 0.325 0.510 535 542 650 765 40.2 3845

400 0.0470 0.618 0.373 0.313 0.498 591 599 745 853 43.0 4780

500 0.0366 0.0490 0.417 0.302 0.487 659 674 859 975 46.6 5930

630 0.0283 0.0391 0.460 0.293 0.478 728 752 981 1103 50.3 7265

800 0.0221 0.0319 0.516 0.285 0.470 869 979 1160 1480 55.4 9200

Three Core Cable

C18X703UP 50 0.3870 0.4938 0.177 0.394 - 197 - 206 - 52.8 3255
C19X703UP
C20X703UP 70 0.2680 0.3423 0.202 0.370 - 241 - 257 - 56.9 4035
C21X703UP
C22X703UP 95 0.1930 0.2469 0.217 0.357 - 286 - 309 - 59.7 4865
C23X703UP
C24X703UP 120 0.1530 0.1961 0.236 0.345 - 325 - 356 - 63.1 5800
C25X703UP
150 0.1240 0.1595 0.254 0.336 - 364 - 405 - 66.7 6835

185 0.0991 0.1282 0.276 0.321 - 410 - 463 - 70.2 8110

240 0.0754 0.0986 0.305 0.308 - 485 - 546 - 75.6 9960

300 0.0601 0.0799 0.340 0.299 - 535 - 626 - 81.6 12085

The above data is approximate and subjected to manufacturing tolerance.

Member Pioneer Holding

260

intelligent

12/20 (24) kV Inner semi-con
Single & Three Cores Copper Aluminum conductor
Conductors, XLPE Insulated and
PVC Sheathed

XLPE insulation PVC Sheathing
Outer semi-con Binder tape & Filler
Description Copper tape screen

• Stranded circular compacted Aluminium conductor, semiconducting layer as conductor screen, XLPE

insulated, semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation

screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape

and PVC sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Nominal Cross Max. Conductor Resistance Inductance Current Rating Approx. Approx
Sectional Area Trefoil Flat Laid in ground Laid in free Air Overall Weight
Product-Code DC at AC at Operating Diameter
mm2 20 OC 90 OC capacitance mh/km mh/km AAAA kg / km
A18X701UP mm
A19X701UP 50 Ω/km Ω/km f/km 775
A20X701UP 70 26.6 890
A21X701UP 95 Single Core Cable 28.4 1000
A22X701UP 120 29.9 1125
A23X701UP 150 0.6410 0.8220 0.177 0.428 0.613 153 160 162 198 31.5 1320
A24X701UP 185 0.4430 0.5681 0.202 0.403 0.588 188 196 204 248 33.1 1475
A25X701UP 240 0.3200 0.4105 0.217 0.389 0.573 222 233 246 299 35.0 1700
A26X701UP 300 0.2530 0.3247 0.236 0.376 0.561 254 265 284 346 37.3 1945
A27X701UP 400 0.2060 0.2645 0.254 0.365 0.550 283 295 324 391 39.9 2390
A28X701UP 500 0.1640 0.2107 0.276 0.350 0.535 321 333 373 449 43.0 2800
A29X701UP 630 0.1250 0.1610 0.305 0.335 0.520 372 385 443 530 46.6 3325
800 0.1000 0.1291 0.340 0.325 0.510 421 433 511 608 50.2 4060
A18X703UP 0.0778 0.1009 0.373 0.313 0.498 478 483 593 693 55.4
A19X703UP 50 0.0605 0.0791 0.417 0.302 0.487 544 545 693 802 2295
A20X703UP 70 0.0469 0.0621 0.460 0.293 0.478 612 617 803 921 52.0 2650
A21X703UP 95 0.0367 0.0495 0.516 0.285 0.470 715 786 954 1188 55.6 3060
A22X703UP 120 59.1 3470
A23X703UP 150 Three Core Cable 62.3 4025
A24X703UP 185 65.9 4605
A25X703UP 240 0.6410 0.8220 0.177 0.394 - 153 - 160 - 70.0 5420
300 0.4430 0.5683 0.202 0.370 - 187 - 200 - 75.2 6175
0.3200 0.4107 0.217 0.357 - 222 - 240 - 80.3
0.2530 0.3250 0.236 0.345 - 253 - 277 -
0.2060 0.2649 0.254 0.336 - 283 - 314 -
0.1640 0.2114 0.276 0.321 - 320 - 361 -
0.1250 0.1618 0.305 0.308 - 371 - 427 -
0.1000 0.1302 0.340 0.299 - 420 - 491 -

The above data is approximate and subjected to manufacturing tolerance.

Member Pioneer Holding 261

intelligent

Three Cores Copper or Inner semi-con STA ( Seel tape armored )
Aluminum Conductors, Copper or Aluminum conductor
XLPE Insulated , Steel Tape
Armoured and PVC Sheathed XLPE insulation Inner Sheathing PVC Sheathing
Outer semi-con Binder tape & Filler
Description
Copper tape screen

• Stranded circular compacted copper or aluminium conductor, semiconducting layer as conductor screen.
XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as a metallic
insulation screen, three cores assembled together with non hygroscopic polypropylene fillers,warpped with
binder tape , covered with layer of PVC compound as bedding , steel tape armoured and PVC sheathed
• Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Max. Conductor Resistance Current Rating Approx.
Overall
Product-Code Nominal Cross DC at AC at Operating Inductance Laid in Laid in Free Diameter Approx
Sectional Area 20 OC 90 OC Capacitance mh/km ground Air Weight
mm
mm2 Ω/km Ω/km f/km A A kg / km

Three Cores Copper Conductor Cables

C18X703IP 50 0.3870 0.4938 0.177 0.394 185 192 57.6 4490
C19X703IP 0.370 226 237 61.6 5360
C20X703IP 70 0.2680 0.3423 0.202 0.357 269 286 64.7 6290
C21X703IP 0.345 306 328 67.9 7265
C22X703IP 95 0.1930 0.2469 0.217 0.336 342 371 71.5 8380
C23X703IP 0.321 386 424 75.4 9810
C24X703IP 120 0.1530 0.1961 0.236 0.308 446 497 82.4 12590
C25X703IP 0.299 502 566 88.4 14920
150 0.1240 0.1595 0.254

185 0.0991 0.1282 0.276

240 0.0754 0.0986 0.305

300 0.0601 0.0799 0.340

Three Cores Aluminium Conductor Cables

A18X703IP 50 0.6410 0.8220 0.177 0.394 144 149 57.2 3570
A19X703IP 0.370 176 184 60.8 4010
A20X703IP 70 0.4430 0.5683 0.202 0.357 209 222 64.5 4535
A21X703IP 0.345 238 255 68.1 5085
A22X703IP 95 0.3200 0.4107 0.217 0.336 266 288 71.7 5730
A23X703IP 0.321 301 331 75.4 6390
A24X703IP 120 0.2530 0.3250 0.236 0.308 349 389 82.1 8110
A25X703IP 0.299 394 444 87.9 9180
150 0.2060 0.2649 0.254

185 0.1640 0.2114 0.276

240 0.1250 0.1618 0.305

300 0.1000 0.1302 0.340

Three Cores Copper Conductor Cables

C18X703HP 50 0.3870 0.4938 0.177 0.394 187 195 60.8 6295
C19X703HP 0.370 227 241 64.9 7280
C20X703HP 70 0.2680 0.3423 0.202 0.357 269 289 67.9 8300
C21X703HP 0.345 305 331 73.2 10350
C22X703HP 95 0.1930 0.2469 0.217 0.336 340 372 76.8 11670
C23X703HP 0.321 381 423 80.5 13225
C24X703HP 120 0.1530 0.1961 0.236 0.308 436 494 86.3 15515
C25X703HP 0.299 485 556 92.5 18095
150 0.1240 0.1595 0.254

185 0.0991 0.1282 0.276

240 0.0754 0.0986 0.305

300 0.0601 0.0799 0.340

Three Cores Aluminium Conductor Cables

A18X703HP 50 0.6410 0.8220 0.177 0.394 145 152 60.4 5270
A19X703HP 0.370 177 188 64.0 5820
A20X703HP 70 0.4430 0.5683 0.202 0.357 210 225 67.7 6460
A21X703HP 0.345 238 259 73.2 8045
A22X703HP 95 0.3200 0.4107 0.217 0.336 265 291 76.8 8815
A23X703HP 0.321 300 332 81.1 9675
A24X703HP 120 0.2530 0.3250 0.236 0.308 346 391 86.0 10775
A25X703HP 0.299 387 442 91.8 12050
150 0.2060 0.2649 0.254

185 0.1640 0.2114 0.276

240 0.1250 0.1618 0.305

300 0.1000 0.1302 0.340

This data is applicable for 12.7 / 22 KV cables
The above data is approximate and subjected to manufacturing tolerance.

Member Pioneer Holding

262

intelligent

18/30 (36) kV Inner semi-con SWA Steel Wire Armored
Three Cores Copper or Copper or Aluminum conductor

Aluminum Conductors,

XLPE Insulated , Steel Tape

Armoured and PVC Sheathed XLPE insulation Inner Sheathing
Outer semi-con Binder tape & Filler
Description PVC Sheathing
Copper tape screen

• Stranded circular compacted copper or aluminium conductor, semiconducting layer as conductor screen. XLPE

insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as a metallic insulation

screen, three cores assembled together with non hygroscopic polypropylene fillers,warpped with binder tape ,

covered with a layer of PVC compound as bedding , steel tape armoured and PVC sheathed
• Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Max. Conductor Resistance Current Rating Approx.
Overall
Product-Code Nominal Cross DC at AC at Operating Inductance Laid in Laid in Free Diameter Approx
Sectional Area 20 OC 90 OC Capacitance mh/km ground Air Weight
mm
mm2 Ω/km Ω/km f/km A A kg / km

Three Cores Copper Conductor Cables

C18X803IP 50 0.3870 0.4938 0.138 0.436 185 192 69.4 5730
C19X803IP 0.410
C20X803IP 70 0.2680 0.3423 0.156 0.395 226 237 73.7 6725
C21X803IP 0.381
C22X803IP 95 0.1930 0.2469 0.167 0.368 269 286 76.7 7705
C23X803IP 0.353
C24X803IP 120 0.1530 0.1961 0.180 0.338 306 328 81.3 9720
C25X803IP 0.327
150 0.1240 0.1595 0.192 342 371 84.7 10680

185 0.0991 0.1282 0.208 386 424 88.6 12120

240 0.0754 0.0986 0.229 446 497 94.4 14310

300 0.0601 0.0799 0.252 502 566 100.4 16790

Three Cores Aluminium Conductor Cables

A18X803IP 50 0.6410 0.8220 0.138 0.436 144 149 69.2 4830
A19X803IP 0.410 176 184 73.0 5395
A20X803IP 70 0.4430 0.5683 0.156 0.395 209 222 76.7 5980
A21X803IP 0.381 238 255 81.3 7310
A22X803IP 95 0.3200 0.4107 0.167 0.368 266 288 84.7 7995
A23X803IP 0.353 301 331 88.6 8700
A24X803IP 120 0.2530 0.3250 0.180 0.338 349 389 94.1 9820
A25X803IP 0.327 394 444 99.7 11000
150 0.2060 0.2649 0.192

185 0.1640 0.2114 0.208

240 0.1250 0.1618 0.228

300 0.1000 0.1302 0.252

Three Cores Copper Conductor Cables

C18X803HP 50 0.3870 0.4938 0.138 0.436 187 195 74.7 8910
C19X803HP 0.410
C20X803HP 70 0.2680 0.3423 0.156 0.395 227 241 78.8 10025
C21X803HP 0.381
C22X803HP 95 0.1930 0.2469 0.167 0.368 269 289 81.8 11175
C23X803HP 0.353
C24X803HP 120 0.1530 0.1961 0.180 0.338 305 331 85.2 12500
C25X803HP 0.327
150 0.1240 0.1595 0.192 340 372 88.4 13595

185 0.0991 0.1282 0.208 381 423 92.5 15255

240 0.0754 0.0986 0.228 436 494 98.3 17665

300 0.0601 0.0799 0.252 485 556 104.5 20405

Three Cores Aluminium Conductor Cables

A18X803HP 50 0.6410 0.8220 0.138 0.436 145 152 74.3 7810
A19X803HP 0.410 177
A20X803HP 70 0.4430 0.5683 0.156 0.395 210 188 78.3 8560
A21X803HP 0.381 238
A22X803HP 95 0.3200 0.4107 0.167 0.368 265 225 81.8 9265
A23X803HP 0.353 300
A24X803HP 120 0.2530 0.3250 0.180 0.338 346 259 85.2 9995
A25X803HP 0.327 387
150 0.2060 0.2649 0.192 291 88.6 10800

185 0.1640 0.2114 0.208 332 92.5 11615

240 0.1250 0.1618 0.228 391 98.0 12880

300 0.1000 0.1302 0.252 442 103.8 14300

This data is applicable for 19 / 3 KV cables
The above data is approximate and subjected to manufacturing tolerance.

Member Pioneer Holding 263



Medium Voltage Cables

INNOVATING
FOR A SAFER WORLD

2 www.gc-3.com

Medium CABLES intelligent

Three Cores Copper or Aluminium Conductors,
XLPE Insulated, Steel Tape Armoured
and PVC Sheathed

Medium CABLES Three Cores Copper or Aluminium Conductors,
XLPE Insulated, Steel Tape Armoured
Description and PVC Sheathed

Stranded circular compacted Copper or Aluminium conductor, T
semiconducting layer as conductor screen,
T
DescriptionXLPE insulated, semiconducting layer as non metallic insulation screen,
Copper tape or wire as metallic insulation screen,
Stranded circuthlarer ecocmorpeascatsesdemCbolpepdetroogreAthluemr winiituhmnocnonhdygucrotoscr,opic Polypropylene fillers,
semiconductinwgralapypeerdaswcitohnbdinudcetor rtascpre,en,
XLPE insulatedc, osevmeriecdonwdituhcatinlagylaeryeorf aPVs Cnocnommeptoaullincdinasus laatbioendsdcinrege, n,
Copper tape sotrewelirteaapsemaermtaolluicreindsualnadtioPnVsCcrseheena,thed.
three cores assembled together with non hygroscopic Polypropylene fillers,
wrapped with•bCinadbelretsaapre,produced according to IEC 60502.
covered with a layer of PVC compound as a bedding,

steel tape armAopurpedliacnadtiPoVnC sheathed.

• Cables are p•roThdeusceedcaabclceosradrineggteonIEeCra6lly05s0u2it.able for direct burial or for installation on trays or in ducts.

Application• Nominal Max. Conductor Currentm Rating Approx.
Resistance
Cross Operating Approx.
Inductance Overall Weight
These cables aSreeAcgrteieoannaelrallDy20Cs°uaCittabAl9e0Cf°oaCrt dCireacpat cbituarniacleor for installatioLnaiodnintraysLoairdininducDtsia. meter
kg/km
ground free air
3070
mm2 Ω/km Ω/km µf/km mh/km A A mm 3475
4055
Nominal Max. Conductor Operating Currentm Rating CAOapvbpelreroasxll. Approx. 4875
Cross Resistance 0C.7a2p70acita0n.9c2e71 InduTchtraenecCeores, Copper Conductor Weig4h7t.3 5790
6790
Sectional DC at 25AC at 0.165 Laid in0.431 Laid in 140Diamete1r41 49.7 7865
Area kg/km52.7 9220
20 °C 3590 °C 0.5240 0.6684 0.183 ground0.408 free air 167 171 11225
mm2 14265
Ω/km 50Ω/km 0.387µ0f/km0.4938 mh/0k.m204 A 0.376 A 197 mm 206
2610
70 0.2680 0.3423 0.234 0.354 241 257 56.7 2850
95 0.193T0hree0.C24o6r9es, Cop0p.2e5r3Conducto0r .C34a0bles 286 309 59.9 3160
25 0.7270120 0.92710.1530 0.106.51961 00..423715 1400.330 141 325 47.3356 307603.4 3575
35 0.5240150 0.66840.1240 0.108.31595 00..420987 1607.320 171 364 49.7405 347657.0 4040
50 0.3870185 0.49380.0991 0.200.41282 00..337264 1907.308 206 410 52.7463 405750.9 4530
70 0.2680240 0.34230.0754 0.203.40986 00..335640 2401.296 257 475 56.7546 487756.2 5180
95 0.1930300 0.24690.0601 0.205.30799 00..344002 2806.288 309 535 59.9626 579803.7 5800
120 0.1530 0.1961 0.275 0.330 325 356 63.4 6790 6755
8500
150 0.1240 0.1595 0.297 Thre0e.32C0ores, Alu3m64inium Co4n0d5uctor Ca6b7l.e0s 7865

185 0.0991 250.12821.2000 0.312.45390 00.3.10685 4100.431 463 102 70.9103 922407.3
240 0.0754 350.09860.8680 0.316.01130 00.2.19863 4750.408 546 122 76.2124 1122459.7

300 0.0601 500.07990.6410 0.400.28220 00.2.28084 5350.376 626 144 83.7149 1426552.4

70 0.4430 0.5683 0.234 0.354 176 184 56.1
95 0.3T2h0r0ee C0.o4r1e0s7, Alumi0n.i2u5m3 Conduct0o.r3C40ables 209 222 59.7
25 1.2000120 1.53900.2530 0.106.53250 00..423715 1002.329 103 238 47.3255 261603.2
35 0.8680150 1.11300.2060 0.108.32649 00..420987 1202.320 124 266 49.7288 285607.0
50 0.6410185 0.82200.1640 0.200.42114 00..337264 1404.308 149 301 52.4331 316700.9
70 0.4430240 0.56830.1250 0.203.41618 00..335640 1706.295 184 349 56.1389 357756.0
95 0.3200300 0.41070.1000 0.205.31302 00..344002 2009.288 222 394 59.7444 404803.0
0.329 238 255 63.2 4530
120 0.2530 0.3250 0.275

150 0.2060 0.2649 0.297 0.320 266 288 67.0 5180

185 0.1T6h4e0 ab0o.2v1e14data is0a.3p2p4roximate0a.3n0d8 subjec3te01d to gc33m31anufact7u0r.in9 g tolera5n8c00e.

240 0.1250 0.1618 0.360 0.295 349 389 76.0 6755

300 0.1000 0.1302 0.402 0.288 394 444 83.0 8500

The above data is approximate and subjected to gc3 manufacturing tolerance.

3

Medium CABLES Three Cores Copper oarnAdluPmVCiniuShmeaXLthPeEindIntseullalitgede,nt
Steel Wire Armoured

Medium CABLES Three Cores Copper or Aluminium XLPE Insulated,
Steel Wire Armoured and PVC Sheathed
Description

Stranded circular compacted Copper or Aluminium conductor,

semiconducting layer as conductor screen,

DescriptionXLPE insulated, semiconducting layer as non metallic insulation screen,

SCtorapnpdeerdtacpirecuolar wr ciroemaps amcetteadllicCoinpsupleartioornAsclurmeeinniu, m conductor,
tshermeeicocondreuscatisnsgemlabyleerdatsocgoenthdeurcwtoitrhscnroenenh,ygroscopic Polypropylene fillers,
XwLrPaEpipnesudlawteitdh,bsienmdeicrotanpdeuc, ctinogvelareyderwaitshnaonlamyeertaolflicPVinCsuclaotmiopnosucnredeans, a bedding,
sCteoeplpweirretaaprme oour wreidreaansdmPeVtCallsicheinastuhlaetdio. n screen,

three cores assembled together with non hygroscopic Polypropylene fillers,
w• rCaapbpleeds awreithpbroindduecretdapaec,ccoordveinrgedtowIEitCh a60la50y2eroor fBPSV6C62c2o. mpound as a bedding,

steel wire armoured and PVC sheathed.

• Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Application•
Nominal Max. Conductor sCuaOitppaaebcrlaiettainfnogcredirInedcutcbtaunricael Currentm Rating Approx. ducAWtsp.epigrohxt.

TheSesCAcerrtoeicosanas abl lesD2a0CRr°eeaCstgisteannA9ec0Cer°aaCltly or for installation on traOyvseorar liln

Laid in Laid in Diameter
ground free air

Nommmin2al MΩa/xk.mCondΩu/ckmtor µf/km mh/km CAurrentm RatAing mm kg/km
Cross Resistance Approx. Approx.
CaOpTphaercreaitetainCngcoeresI,nCdoucptpaenrcCeondLuacidtoinr CablLeasid in Overall Weight
Sectional DC at AC at Diameter
Area 4530
25 200.7°2C70 900.°9C271 0.165 0.431 grou1n3d3 free1a36ir 50.5 kg50/k1m0
mm325 Ω0/.5k2m40 Ω0/.k6m684 µf/0k.1m83 mh0/.k4m08 m5m2.9
A158 A164

50 0.3870 0.4938 0.204 0.376 187 195 55.9 5715
59.9 6650
70 0.2680 0.3423 Thr0e.2e3C4 ores, Cop0p.3e5r4Conduc2to2r7Cables 241

295 0.7129370 0.29247691 0.215653 0.344310 126339 218369 6503.15 74565305

13250 0.1552340 0.61968641 0.218753 0.343080 130558 316341 6562.69 58071650

150 0.3182470 0.41959358 0.20974 0.32760 134870 319752 5725.39 15079135

17805 0.02699810 0.13428223 0.32324 0.30548 238271 424231 5796.29 1626450

29450 0.10975340 0.20948696 0.325630 0.234906 243696 428994 6831.51 17467535

31020 0.01653001 0.01979619 0.420752 0.323880 43805 353561 8676.6 187726350

150 0.1240 0.1595 0.297 0.320 340 372 72.3 10935
T0h.r3e2e4 Cores, Al0u.m30i8nium Con3d81uctor Cab42le3s 76.2 12450
185 0.0991 0.1282 00..423916 140336 140964 5801..55 144073305
22450 01..02705040 10..50399806 00..136650 5827..96 147322350
33050 00..08660810 10..10173909 00..148032 00..420888 142835 152576 55.6
50 0.6410 0.8220 0.204 0.376 145 152 4715
5245
70 0.4430 0.5683 T0h.r2e3e4 Cores, Al0u.m35i4nium Con1d77uctor Cab18le8s 59.3 45802305
64340205
295 10.230200 10.45319070 0.126553 0.433410 210130 120256 5620.95 8470195
8528465
13250 0.8256380 10.1312530 0.218735 0.342098 213283 215279 6526.49 9585250
161410305
150 0.6204160 0.82264209 0.20947 0.37260 21645 215921 5725.36 8095
8865
17805 0.4164340 0.25161843 0.32234 0.30548 317070 133882 7569.23 9850
11135
29450 0.312500 0.14611087 0.326530 0.239405 231406 322951 8621.19

13200 0.1205300 0.13235020 0.240752 0.322889 233887 245492 866.94

150 0.2060 0.2649 0.297 0.320 265 291 72.3

The1a85bove d0a.1t6a40is ap0p.2r1o1x4imate 0a.3n2d4 subjecte0d.3t0o8 gc3 ma3n00ufacturin3g32toleranc7e6..2

240 0.1250 0.1618 0.360 0.295 346 391 81.1

300 0.1000 0.1302 0.402 0.288 387 442 86.9

The above data is approximate and subjected to gc3 manufacturing tolerance.

267

intelligent Medium CABLES Single & Three Cores Copper Conductors,
XLPE Insulated and PVC Sheathed

DMesecdriiupmtioCnABLES Single & Three Cores Copper Conductors,
XLPE Insulated and PVC Sheathed

Stranded circular compacted Copper conductor, semiconducting layer as conductor
screen, XLPE insulated,

Descriptionsemiconducting layer as non metallic insulation screen, Copper tape or wire as metallic
insulation screen, three cores assembled together with non hygroscopic Polypropylene
Stranded circufilalerrsc,owmrappapceteddwCithopbpinedrecrotnadpuecatonrd, sPeVmCicsohnedauthcetidng. layer as conductor
screen, XLPE insulated,
semiconductin•gClaybelersaasrneopnromdeutcaellidc aincsucloartdioinngsctoreIeECn, 6C0o5p02peor tBaSp6e62o2r.wire as metallic
insulation screen, three cores assembled together with non hygroscopic Polypropylene
fillers, wrapped with binder tape and PVC sheathed.

• Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Application• Nominal Max. Conductor Inductance Current Rating
Cross Resistance Ground Laid in Free Air
fCoaOrppdaeicrreaittcainntgcbeuriTarel fooril Laid in Approx. Approx.
These cables SaerAcerteioganeanl eD2ra0Cl°laCyt suAitaCbalte for onFltarat ys oTrer fionilducFltast. Overall Weight
FinlasttallaTrteiofonil Diameter
90 °C

mm2 Ω/km Ω/km µf/km mh/km mh/km RaAting A AA mm kg/km
Inductance Current
Nominal Max. Conductor 915
Cross Resistance Operating Trefoil Flat LaSiidnginleGCroournedCaLbalide in Free Air Approx. Approx. 1070
0.159 Overall 2W11eight 1320
Sectional DC at A35C at 0C.5a2p4a0cit0a.6n6c8e3 0.177 0T.4re63foil 0.F6l4a8t T1re6f6oil 1F7la4t D1ia7m4 eter 25.3 1575
Area 20 °C 5900 °C 0.3870 0.4937 1860
2220
0.428 0.613 197 206 209 255 26.7 2625
3185
mm2 Ω/km 7Ω0/km 0.268µ0f/km0.3420 mh/k0m.20m2 h/km 0.40A3 0.5A88 24A2 25A2 26m2m 3k1g9 /km 28.7 3845
4780
95 0.1930 0.2465 0.217 0.389 0.573 287 299 317 384 29.9 5930
120 Single Core Cable 366 443 31.5 7265
0.1530 0.1956 0.236 0.376 0.561 326 339 9200
11570
35 0.5240 1500.6683 0.12400.1590.1588 0.4630.2540.648 0.316656 0.515704 361474 372511 41265.3 498 915 33.1
2745
50 0.3870 1805.4937 0.09901.1770.1272 0.4280.2760.613 0.315907 0.523056 412109 422255 47286.7 5701070 35.0 3255
70 0.2680 2400.3420 0.07504.2020.0973 0.4030.3050.588 0.323452 0.522502 472562 483419 56258.7 6691320 37.4 4035
95 0.1930 3000.2465 0.06001.2170.0781 0.3890.3400.573 0.322857 0.521909 533517 543284 65209.9 7651575 40.2 4865
120 0.1530 4000.1956 0.04700.2360.0618 0.3760.3730.561 0.331236 0.439389 593966 594143 74351.5 8531860 43.0 5800
6835
150 0.1240 5000.1588 0.03606.2540.0490 0.3650.4170.550 0.330624 0.438775 674416 654998 85393.1 9752220 46.6 8110
185 0.0991 6300.1272 0.02803.2760.0391 0.3500.4600.535 0.249131 0.447282 754278 725870 98315.0 11032625 50.3 9960
240 0.0754 8000.0973 0.02201.3050.0319 0.3350.5160.520 0.248755 0.447804 865965 976969 116307.4 14803185 55.4 12085

300 0.060110000.0781 0.01706.3400.0234 0.3250.6330.510 0.258315 0.456462 1086450 1187865 151450.2 18643845 65.8

400 0.0470 0.0618 0.373 0.313 0.498 599 591 745 853 43.0 4780

500 0.0366 0.0490 0.417 0.302 0.487 T6h7r4ee Co6r5e9 Cabl8e5s9 975 46.6 5930

630 0.0283 305.0391 0.52400.460.6684 0.2930.1590.478 0.472572 -728 169781 1-103 17150.3 - 7265 49.5

800 0.0221 500.0319 0.38700.5160.4938 0.2850.1770.470 0.389649 -979 1191760 1-480 20655.4 - 9200 52.8

1000 0.0176 700.0234 0.26800.6330.3423 0.2810.2020.466 0.1307804 1-188 2145115 1-864 25765.8 -11570 56.9

95 0.1930 0.2469 0.217 0.357 - 286 - 309 - 59.7
120 0.1530 0.1961 Th0r.e2e36Core C0a.3b4l5es - 325 - 356 - 63.1

35 0.5240 1500.6684 0.12400.1590.1595 0.4270.254 - 0.313667 -- 361471 - - 40549.5 - 2745 66.7

50 0.3870 1805.4938 0.09901.1770.1282 0.3940.276 - 0.312917 -- 412006 - - 46352.8 - 3255 70.2

70 0.2680 2400.3423 0.07504.2020.0986 0.3700.305 - 0.320481 -- 472557 - - 54656.9 - 4035 75.6

95 0.1930 3000.2469 0.06001.2170.0799 0.3570.340 - 0.229896 -- 533509 - - 62659.7 - 4865 81.6

120 0.1530 0.1961 0.236 0.345 - 325 - 356 - 63.1 5800

150 0.1240 Th0.e15a95mpac0it.y25f4or single0.3c3o6 re size- s 8003&641000m-m2 wa40s5based-on a si6n6g.7le end68b35onding.
185 0.0991 h0e.1a28b2ove d0a.2t7a6 is appr0o.3x2i1mate -and su4b10jected-to gc346m3 anufa-cturing70t.o2leran8c1e10.

240 0.0754 0.0986 0.305 0.308 - 475 - 546 - 75.6 9960

300 0.0601 0.0799 0.340 0.299 - 535 - 626 - 81.6 12085

The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding.
he above data is approximate and subjected to gc3 manufacturing tolerance.

268

Medium CABLES Single & Three Cores Aluminium Conductors,

XLPE Insulated and PVC Sheathed intelligent

Medium CABLES Single & Three Cores Aluminium Conductors,
XLPE Insulated and PVC Sheathed
Description

Stranded circular compacted Aluminium conductor, semiconducting layer as conductor
screen, XLPE insulated, semiconducting layer as non metallic insulation screen,

DescriptionCopper tape or wire as metallic insulation screen, three cores assembled together
with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC sheathed.
Stranded circular compacted Aluminium conductor, semiconducting layer as conductor
screen, XLPE in•suClatbeleds, saerempicroondduuccetdinagclacyoerdr iansgntoonIEmCe6ta05lli0c2inosruBlaSt6io6n22s.creen,
Copper tape or wire as metallic insulation screen, three cores assembled together
with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC sheathed.

• Cables are pAropdpucliecdaatcioconrding to IEC 60502 or BS 6622.

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Application• These cableSNesoCAcamrrtSoeirNoeiesanoCnAcsamartrgoeiloliesannMsanaD2lale0CRxre°.aaCMDC2stil0scaloRtyxaOneA.cCnAsds9tiusco0uCtieanct°danaCAt9ocut0cbcreOtlAeoCctraOfoppcareaocdrpapitiatareiencrnagiccttaietnnbgcueTIrnreidafotulriielcnoftdorauifnlocFcltraeaitnnfclsaettaLTalrleaidftotiirLnoielafniGdoirIColnoFlGuunaCrnrtrotedfuurlananrrdtteyLTRnsraaetoitdfRitonrLraeiaignlitnifidnoFgriIdlneFueFlarceAteftlirasA.tirDAOiapvDmpAeOiarperovamptexelrler.oartxell.AWr pepiWgArohpextpi.grohxt

Nominal Max. Comndmum2ctmor2 Ω/km/KmΩ/km/KmInduµfc/tkaumnf/cKem mh/mkmh/KmmhC/ukmmrrhe/nKmt RaAtinAg A A A A mmAmm kg/Kkmg/Km

Cross Resistance Operating Trefoil FlSaitngle0L.T4aCr6eid3oforienil GCraobulned Laid in Free Air Approx. Approx. 25.3 705
Sectional DC at A3C5 at Capacitance 0.159 0.6F4la8t 1Tr2e9foil 1F3l5at Overall Weight 775
20 °C 90 °C 0.8680 1.1130 D1ia35meter 164 890
Area

50 0.6410 0.8220 0.177 0.428 0.613 153 160 162 198 26.6
20m4 mA 24k8g/km 28.4
mm2 Ω/km Ω70/km 0.443µ0f/km0.5681 mh/k0m.20m2 h/km 0.40A3 0.58A8 188 19A6

95 0.3200 0.41S0in5gle Co0.r2e17Cable 0.389 0.573 222 233 246 299 29.9 1000

120 0.2530 0.3247 0.236 0.376 0.561 254 265 284 346 31.5 1125
35 0.8680 115.01130 0.20600.1590.2645 0.4630.2540.648 0.316259 0.515305 281335 291564 32245.3 391705 33.1
50 0.6410 108.58220 0.16400.1770.2107 0.4280.2760.613 0.315503 0.513650 321162 331398 37236.6 449775 35.0 1320

70 0.4430 204.05681 0.12500.2020.1610 0.4030.3050.588 0.313858 0.512906 372204 382548 44238.4 530890 37.3 1475

95 0.3200 300.04105 0.10000.2170.1291 0.3890.3400.573 0.322252 0.521303 422146 432399 51219.9 6018000 39.9 1700

120 0.2530 400.03247 0.07708.2360.1009 0.3760.3730.561 0.321534 0.429685 472884 483346 59331.5 6913125 43.0 1945

150 0.2060 500.02645 0.06005.2540.0791 0.3650.4170.550 0.320823 0.428975 543424 543591 69333.1 8012320 46.6 2390

185 0.1640 603.02107 0.04609.2760.0621 0.3500.4600.535 0.239231 0.437383 613773 614249 80335.0 9211475 50.2 2800

240 0.1250 800.01610 0.03607.3050.0495 0.3350.5160.520 0.238752 0.437805 714543 785630 95347.3 11818700 55.4 3325

300 0.1000 1000.01291 0.02901.3400.0376 0.3250.6330.510 0.248211 0.446363 865211 936708 120359.9 14618945 65.8 4060

400 0.0778 0.1009 0.373 0.313 0.498 478 483 593 693 43.0 2390 5220

500 0.0605 0.0791 0.417 0.302 0.4T8h7ree C54o4re Cab54le5 s 693 802 46.6 2800

630 0.0469 305.0621 0.86800.4601.1130 0.2930.1590.478 0.462177 6- 12 128903 -921 13530.2 - 3325 48.9 2050

800 0.0367 500.0495 0.64100.5160.8220 0.2850.1770.470 0.379145 7- 86 159354 1-188 16505.4 - 4060 52.0 2295

1000 0.0291 700.0376 0.44300.6330.5683 0.2810.2020.466 0.387602 9- 37 1182705 1-468 20605.8 - 5220 55.6 2650

95 0.3200 0.41T0h7ree Co0r.e21C7 ables 0.357 - 222 - 240 - 59.1 3060

120 0.2530 0.3250 0.236 0.345 - 253 - 277 - 62.3 3470
35 0.8680 1510.1130 0.20600.1590.2649 0.4270.254 - 0.313269 -- -- 31448.9 - 2050 65.9
281333 4025
50 0.6410 1805.8220 0.16400.1770.2114 0.3940.276 - 0.312513 -- 321060 -- 36512.0 - 2295 70.0
4605
70 0.4430 2400.5683 0.12500.2020.1618 0.3700.305 - 0.310887 -- 372100 -- 42575.6 - 2650 75.2
5420
95 0.3200 3000.4107 0.10000.2170.1302 0.3570.340 - 0.229292 -- 422040 -- 49519.1 - 3060 80.3
6175
120 0.2530 0.3250 0.236 0.345 - 253 - 277 - 62.3 3470

150 0.2060 0.2649 0.254 0.336 - 283 - 314 - 65.9 4025

185 0.1640 0.2114 0.276 0.321 - 320 - 361 - 70.0 4605

240 0.1250 0.1618 0.305 0.308 - 371 - 427 - 75.2 5420

300 0.1000 0.T1h30e2ampa0.c3i4t0y for sin0g.2le99core -sizes 804200& 1000- mm2 4w91as base- d on a80s.i3ngle e61n7d5 bonding.
he above data is approximate and subjected to gc3 manufacturing tolerance.

The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding.
he above data is approximate and subjected to gc3 manufacturing tolerance.

269

intelligent Medium CABLES Three Cores Copper or Aluminium Conductors,
XLPE Insulated, Steel Tape Armoured
and PVC Sheathed

Medium CABLES Three Cores Copper or Aluminium Conductors,
XLPE Insulated, Steel Tape Armoured
Description and PVC Sheathed

Stranded circular compacted Copper or Aluminium conductor,
semiconducting layer as conductor screen, XLPE

Descriptioninsulated, semiconducting layer as non metallic insulation screen,
Copper tape or wire as metallic insulation screen,
Stranded circuthlarer ecocmorpeascatsesdemCbolpepdetroogreAthluemr winiituhmnocnonhdygucrotoscr,opic Polypropylene fillers,
semiconductinwgralapypeerdaswcitohnbdinudcetor rtascpre,en, XLPE
insulated, semcicoovnedreudctwinigthlaylearyaers onfoPnVmCectaolmlicpionsuunladtaiosnascbreededn,ing, steel tape armoured and PVC sheathed.
Copper tape or wire as metallic insulation screen,
three cores as•seCmabbleleds atoregeptrhoedruwciethdnaocnchoyrdgirnogsctopIEicCP6o0ly5p02ro. pylene fillers,
wrapped with binder tape,
covered with a layer of PVC compound as a bedding, steel tape armoured and PVC sheathed.

Application

• Cables are produced according to IEC 60502.
• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Application• These cables aSNreeoCAcmrtrgoeioisanSensNaeanCoAlclemrrtoeioriasannDs2Mala0clylalROAxces.tCusMisDoi2ttan0aaCRdnx°bAe9cua.C0celcCsteitsOooAtcafrntondAr9cu0Cdecc°tiarCoaoetrppcaetcCrabitaOtaiunppngraceiacerailttaoinnrigncfdeourcintInasdntuaccelltaatniIocnenGLaCrooiudnugrLnrCartedoruinadurtnryieRndIsnnaottFmLinrraegiRiendfaLrAaedtiienirdugacinirtsD.AOiapvmpDeAOrerioaaptxvelmlp.erreroatxell.r Approx
WeAigphptrox.
mm2 mm2 /Km Ω/km/Km Ω/km uf/Kmµf/km mh/Kmmh/km A A AA mmmm
Max. Conductor Weight
Nominal Currentm Rating Approx.
Cross Resistance at0.52C4aO0ppaecrai0tta.i6nn6Tgc8h4ereeInCdour0ce.t1sa5,n9CcoeppeLraCido0in.n4d2u7 ctoLraCidaibn1l6e7s Approx. Weight Kg/kKgm/km
DC at 35 AC Overall
Sectional 20 °C 50 90 °C ground free air Diamet1e7r1 54.1 3875
Area 0.3870 57.6 4490
0.4938 0.177 0.394 197 206 kg/k6m1.6 5360
mm2
Ω/km 70 Ω/km0.2680 µf/k0m.3423 m0h./2k0m2 A0.370 A 241 mm 257

95 Thr0e.1e93C0ores0, .C24o6p9per Co0n.2d1u7ctor Cable0s.357 286 309 64.7 6290
120 0.1530 0.1961 0.236 0.345 325 356 67.9 7265
35 0.5240150 0.66840.1240 0.1509.1595 00..422574 1607.336 171 364 54.1 405 387751.5 8380
9810
50 0.3870185 0.49380.0991 0.1707.1282 00..329746 1907.321 206 410 57.6 463 449705.4 12590
14920
70 0.2680240 0.34230.0754 0.2002.0986 00..337005 2401.308 257 475 61.6 546 536802.4

95 0.1930300 0.24690.0601 0.2107.0799 00..335470 2806.299 309 535 64.7 626 629808.4

120 0.1530 0.1961 0.236 0.345 325 356 67.9 7265

150 0.1240 0.1595 0.254Three Core0s.3,3A6luminium36C4onducto4r0C5 ables 71.5 8380

185 0.0991 35 0.12820.8680 0.2716.1130 00..312519 4100.427 463 122 75.4 124 981504.1 3250
4705.394 546 144 82.4 149 1259507.2 3570
240 0.0754 50 0.09860.6410 0.3005.8220 00..310787 5305.370 626 176 88.4 184 1492600.8 4010

300 0.0601 70 0.07990.4430 0.3400.5683 00..229092

95 Thre0e.3C20o0res, A0.l4u1m07inium C0o.2n1d7 uctor Cab0l.e3s57 209 222 64.5 4535
0.345 238 255 68.1 5085
120 0.2530 0.3250 0.236 1202.336 124 266 54.1 288 325071.7 5730
35 0.8680150 1.11300.2060 0.1509.2649 0.427 6390
0.254 8110
50 0.6410185 0.82200.1640 0.1707.2114 0.394 1404.321 149 301 57.2 331 357075.4 9180
0.276
70 0.4430240 0.56830.1250 0.2002.1618 0.370 1706.308 184 349 60.8 389 401082.1
0.305
95 0.3200300 0.41070.1000 0.2107.1302 0.357 2009.299 222 394 64.5 444 453587.9
0.340
120 0.2530 0.3250 0.236 0.345 238 255 68.1 5085

150 0.2060 0.2649 0.254 0.336 266 288 71.7 5730

185 0.1640 0.2114 0.276 0.321 301 331 75.4 6390

240 0.1250 0.1618 0.305 0.308 349 389 82.1 8110

300 T0h.1is0d00ata i0s.1a3p02plicabl0e.3f4o0r 12.7/22k0V.2c99ables. 394 444 87.9 9180
The above data is approximate and subjected to gc3 manufacturing tolerance.

This data is applicable for 12.7/22kV cables.
The above data is approximate and subjected to gc3 manufacturing tolerance.

270

Medium CABLES Single & Three Cores Copper Conductors,

XLPE Insulated and PVC Sheatheidntelligent

DMesecdriiupmtioCnABLES Single & Three Cores Copper Conductors,
XLPE Insulated and PVC Sheathed

Stranded circular compacted Copper conductor, semiconducting layer as conductor screen,

XLPE insulated semiconducting layer as non metallic insulation screen,

DescriptionCopper tape or wire as metallic insulation screen,
three cores assembled together with non hygroscopic Polypropylene fillers,

Stranded circuwlarar pcpoemdpwacithtebdinCdoepr ptaepr ecoanndduPcVtoCr, ssheemaitchoendd.ucting layer as conductor screen,

XLPE insulated semiconducting layer as non metallic insulation screen,

Copper tape •orCwairbeleassamreetparollicduincseudlaatiocncoscrdreinegn,to IEC 60502 or BS 6622.

three cores assembled together with non hygroscopic Polypropylene fillers,

wrapped with binder tape and PVC sheathed.

Application

• Cables are produced according to IEC 60502 or BS 6622.
• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Application• Max.Conductor iInndduuccttaannccee Current Rating AOApvpperrpoaxrllo. x.
DDiaimameteerter
These cablesSSNaNeeoCAcCorAcmertrmrrtoeiooeiiosanginsansnasaeaalllnl MeD2D2ra0ca0CRRxOeel°A.lcaCysCstitissotstaaunnA9nAdi9ct0cc0auCeeOcA°bcaCttolter operating forfFlianlatsttalltaLrTLaearteiifidodofoiInilnnilGoGronrfuoFlanltuadrtnat dystLroLTearaerifdoidfioniIlniinlFdrFeurefelcaFAelttaisrAt. ir WAApeppipgrorhoxtx.

cfCoaarppadacicrietiatcanntccebeurtiTraerelfofooilril

mmmm22 Ω//Kkmm Ω//Kkmm uµf/f/Kkmm mmhh//Kkmm mmhh//Kkmm AA AA AA mmmA Kkgg//Kkmm
Inductance
Nominal Max. Conductor 1325
Cross Resistance SingleLaCidorine GCraobunled Laid in Free Air Approx. Approx. 1575
1855
Sectional DC at A50C at 0C.3a87p0acit0a.4n9c3e7 Trefoil Flat 0.T4r6e5foil 0.6F4la9t T1r9e7foil 2F0la6t D2ia09meter 255 32.1
Area 20 °C 7900 °C 0.2680 0.3420 0.138 242 252

0.156 0.436 0.621 262 319 33.9

mm2 Ω/km 9Ω5/km 0.193µ0f/km0.2465 mh/k0m.167mh/km 0.42A2 0.60A7 287 29A9 31m7 mA 38k4g/km 35.3

120 0.1530 0.1956 0.180 0.406 0.591 326 339 366 443 36.7 2140
150 0.1240 0.15S8i8ngle C0o.1re92Cable 0.395 0.580 364 375 416 498 38.5 2525

50 0.3870 108.54937 0.09901.1380.1272 0.4650.2080.649 0.317987 0.562306 412109 422255 47382.1 5701325 40.2 2930

70 0.2680 204.03420 0.07504.1560.0973 0.4360.2280.621 0.326422 0.542752 472562 483419 56353.9 6691575 42.8 3540

95 0.1930 300.02465 0.06001.1670.0781 0.4220.2520.607 0.325807 0.532599 533517 543284 65305.3 7651855 45.6 4225

120 0.1530 400.01956 0.04700.1800.0618 0.4060.2750.591 0.333276 0.523239 593966 594143 74356.7 8532140 48.4 5165

150 0.1240 500.01588 0.03606.1920.0490 0.3950.3060.580 0.332644 0.503975 674416 654998 85398.5 9752525 52.0 6350

185 0.0991 603.01272 0.02803.2080.0391 0.3780.3360.563 0.341131 0.494822 754278 725870 98410.2 11032930 55.7 7715

240 0.0754 800.00973 0.02201.2280.0319 0.3620.3740.547 0.340735 0.484884 865965 976969 116402.8 14803540 60.6 9660

300 0.0601 1000.00781 0.01706.2520.0234 0.3500.4550.535 0.259375 0.485142 1086450 1187865 151455.6 18644225 71.2 12135

400 0.0470 0.0618 0.275 0.337 0.522 599 591 745 853 48.4 5165

500 0.0366 0.0490 0.306 0.324 0.5T0h9ree C6o74re Cab6l5e9s 859 975 52.0 6350

630 0.0283 500.0391 0.3870.3360.4938 0.3130.1380.498 0.473562 -728 199781 1-103 20655.7 - 7715 63.0 3990

800 0.0221 700.0319 0.2680.3740.3423 0.3030.1560.488 0.481609 -979 2141160 1-480 25760.6 - 9660 67.1 4835

1000 0.0176 905.0234 0.1930.4550.2469 0.2970.1670.481 0.1309854 1-188 2185615 1-864 30971.2 -12135 69.9 5705

120 0.1530 0.1961 0.180 0.381 - 325 - 356 - 73.1 6645
Three Core Cables 76.3 7645
150 0.1240 0.1595 0.192 0.368 - 364 - 405 -

50 0.3870 1805.4938 0.09901.1380.1282 0.4360.208 - 0.315937 - - 412006 - - 46363.0 - 3990 82.2 9385

70 0.2680 2400.3423 0.07504.1560.0986 0.4100.228 - 0.323481 - - 472557 - - 54667.1 - 4835 85.8 10865

95 0.1930 3000.2469 0.06001.1670.0799 0.3950.252 - 0.322876 - - 533509 - - 62669.9 - 5705 91.8 13115

120 0.1530 0.1961 0.180 0.381 - 325 - 356 - 73.1 6645

150 0.1240 0.1595 0.192 0.368 - 364 - 405 - 76.3 7645

185 0.0991 0.1282 0.208 0.353 - 410 - 463 - 82.2 9385

240 0.0754 0.0986 0.228 0.338 - 475 - 546 - 85.8 10865

300 0.0601 0.0799 0.252 0.327 - 535 - 626 - 91.8 13115
The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding.

he above data is approximate and subjected to gc3 manufacturing tolerance.

The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding.
he above data is approximate and subjected to gc3 manufacturing tolerance.

271

intelligent Single & Three Cores Aluminium Conductors,
XLPE Insulated and PVC Sheathed
Medium CABLES

Medium CABLES Single & Three Cores Aluminium Conductors,
XLPE Insulated and PVC Sheathed
Description

Stranded circular compacted Aluminium conductor,
semiconducting layer as conductor screen,

DescriptionXLPE insulated semiconducting layer as non metallic insulation screen,
Copper tape or wire as metallic insulation screen,
Stranded circular compacted Aluminium conductor,

three cores assembled together with non hygroscopic Polypropylene fillers,
semiconducting layer as conductor screen,

wrapped with binder tape and PVC sheathed.
XLPE insulated semiconducting layer as non metallic insulation screen,
Copper tape or wire as metallic insulation screen,

• Cables are produced according to IEC 60502 or BS 6622.
three cores assembled together with non hygroscopic Polypropylene fillers,
wrapped with binder tape and PVC sheathed.

• Cables are pAropdpucliecdaatcioconrding to IEC 60502 or BS 6622.

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Application• These cablesSSNNeeaoCAcCoAcmrrtrmrrtoeieooeiiosaninsansnagsaaalelll nMMDe2D2a0ca0rCRRxaxOeeA°..caCClsCsltiyitsosottanasndnAu9And9cu0cic0CutceaeOctA°ocaCtbtrotlrecCfaooaOppprpaeadecracriitartiaetitnanicngncgtceebutrTriieIrnanefddoflouuoiliclcrttafaonnfrcFlcalieanttstatlLlrTLaaearefitiddoifooiIilnninlGGCororfCuunoFlanrluuardtterntrrnaedtnyRttsLraLTReaorataeifidnoirtdfiogiInilnniignlFrdFerefuelaFAceltairtAtsi.r DAODiapAOvimappevrmerpoeatxrelerlo.artxell.r WAAWpeppeipgrigorhoxhtxt.

Nominal Max. Commnmdmu22ctor Ω//Kkmm Ω//Kkmm Induuµf/fc/Ktkmamnce mmhh//Kkmm mmhhC//Kukmmrrent RAating AA AA mmmA Kkgg/K/kmm
1025
Cross Resistance Operating Laid in Ground Laid in Free Air Approx. Approx.
Overall Weight
Sectional DC at AC at Capacitance Trefoil FSliantgle CTroerfeoilCabFllaet Trefoil Flat Diameter
Area 20 °C 9500 °C 0.6410 0.8220
0.138 0.465 0.649 153 160 162 198 32.0

mm2 Ω/km Ω70/km 0.443µ0f/km0.5681 mh/km0.15m6 h/km 0.4A36 0.62A1 188 19A6 20m4 mA 24k8g/km 33.6 1140

95 0.3200 0.4105 0.167 0.422 0.607 222 233 246 299 35.3 1270

120 0.2530 0.3S2in4g7 le Cor0e.1C80able 0.406 0.591 254 265 284 346 36.7 1400

50 0.6410 105.08220 0.20600.1308.2645 0.4650.1920.649 0.319553 0.518600 281362 291598 32342.0 3911025 38.5 1630
70 0.4430 108.55681 0.16400.1506.2107 0.4360.2080.621 0.317888 0.516936 322104 332348 37333.6 4419140 40.2 1790
95 0.3200 204.04105 0.12500.1607.1610 0.4220.2280.607 0.326222 0.524373 372246 382599 44335.3 5310270 42.7 2050
120 0.2530 300.03247 0.10000.1800.1291 0.4060.2520.591 0.325504 0.523655 422184 433346 51316.7 6018400 45.3 2320
150 0.2060 400.02645 0.07780.1902.1009 0.3950.2750.580 0.323873 0.522925 473824 483391 59338.5 6913630 48.4 2775
185 0.1640 500.02107 0.06050.2008.0791 0.3780.3060.563 0.332241 0.530393 543473 544549 69430.2 8012790 52.0 3215
240 0.1250 603.01610 0.04690.2208.0621 0.3620.3360.547 0.331732 0.439885 614743 615230 80432.7 9221050 55.6 3765
300 0.1000 800.01291 0.03670.2502.0495 0.3500.3740.535 0.340231 0.448383 715511 786608 95445.3 11828320 60.6 4515
400 0.0778 1000.01009 0.02910.2705.0376 0.3370.4550.522 0.249778 0.448813 865293 936793 120458.4 14628775 71.2 5790

500 0.0605 0.0791 0.306 0.324 0T.h50re9 e Co5r4e4 Cabl5e4s5 693 802 52.0 3215
630 0.0469 803 921 55.6 3765
800 0.0367 0.0621 0.336 0.313 0.498 617 612 153 - 160 -
1000 0.0291 50 0.6410 0.8220 0.138 0.436 - 954 1188 60.6 4515 62.8 3095
0.0495 0.374 0.303 0.488 715 786 187 - 200 - 66.4 3525
70 0.4430 0.5683 0.156 0.410 - 1205 1468 71.2 5790 69.9 3985
0.0376 0.455 0.297 0.481 862 937 222 - 240 -
95 0.3200 0.4107 0.167 0.395 -

120 0.2530 0.T3h25re0e Core0.1C8a0bles 0.381 - 253 - 277 - 73.1 4435

50 0.6410 1500.8220 0.20600.1308.2649 0.4360.192 - 0.316583 - - 218630 -- 31462.8 - 3095 76.3 4960
70 0.4430 1805.5683 0.16400.1506.2114 0.4100.208 - 0.315837 - - 322000 -- 36166.4 - 3525 80.4 5555
95 0.3200 2400.4107 0.12500.1607.1618 0.3950.228 - 0.323282 - - 327410 -- 42769.9 - 3985 85.5 6390
120 0.2530 3000.3250 0.10000.1800.1302 0.3810.252 - 0.322573 - - 422707 -- 49173.1 - 4435 91.1 7350

150 0.2060 0.2649 0.192 0.368 - 283 - 314 - 76.3 4960

185 0.1640 0.2114 0.208 0.353 - 320 - 361 - 80.4 5555

240 0.1250 T0h.1e61a8 mpac0i.t2y28for sing0le.33c8ore siz- es 80037&1 1000m- m2 w4a27s based- on a s8i5n.5gle en63d90bonding.
300 0.1000 h0.e13a02bove d0.a25ta2 is app0.r3o2x7imate- and s4u2b0jected- to gc4931manuf-acturin9g1.t1olera7n3c50e.

The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding.
he above data is approximate and subjected to gc3 manufacturing tolerance.

272





intelligent

We own the power

2

Medium Voltage Power Cables

Operating Voltage (from 6/10 kV up to 18/30 kV) Cable Construction

1. Conductor

Stranded, round and compacted Copper or Aluminium conductors, according to IEC 60228 class 2.

2. Conductor screen

An extruded layer of semi conducting material applied over the conductor as voltage stress control layer.

3. Insulation

An extruded layer of cross linked polyethylene (XLPE) is applied over the inner semi conductar with
thickness as specified in IEC 60502.

4. Insulation Screen

An extruded layer at strippable or firmly banded to the insulation. Conductor screen, XLPE insulation
and insulation screen are applied at the same time using triple head extruder.

5. Metallic Screen

a. Copper Tape: an annealed Copper tape is applied helically with a suitable overlap.
b. Copper Wire: helically applied and binded with a Copper tape to achieve electrical contact

6. Assembly

In case of three core cables cores are assembled together with suitable lay length non-hygroscopic filler is applied
during assembly to fill spaces between cores then wrapped with suitable binder tape.

7. Bedding

in case of armoured cables an extruded layer of PVC or MDPE or LLDPE is applied as bedding.

8. Armouring

a. Steel Tape: double layers of steel tapes are applied helically.
b. Steel Wire: galvanized steel wires are applied helically.

9. Sheath

An extruded layer of PVC is applied with thickness as specified in IEC 60502.

Option
Lead Sheath: Upon request a layer of lead is extruded over the bedding layer.

Armouring of Single Core Cable

1. Armouring by non-magnetic material either Aluminium Tape armouring or Aluminium Wire armouring to reduce
the magnetic losses.
2. If it is required for single core cable to be armoured by steel wire armouring the magnetic circuit around the single
core cable should be interrupted by inserting insulated copper wire between the steel wires.

insulted copper Conductor Conductor
wires Insulation
Bedding Insulation
Steel Wire Bedding
Armouring Sheath

All Wire
Armouring

Sheath

Medium Voltage Power Cables

Designation Code for Medium Voltage Power Cables You can order
our product by giving the following informations

1- cable codes as per the catalogue
2- if your requirements is out of our catalogue product range, you can use the following map to
identify the code

Conductor Material Armoring & Shielding
C Copper U Unarmored
A Aluminum I Steel Tapes Armored
G C opper + Swelling Powder + S.C Tape H G alavaniz ed Steel Wires Armored
E Aluminum + Swelling Powder + S.C Tape
K A luminum Tapes Armored
C.S.A mm2 J Aluminum Wires Armored
18 50 Z G alvanize d Steel T apes Armored
1 9 70 D Lead + G alvanized Steel W ires Armored
20 95 F Lead + Aluminum Wires Armored
21 1 20 E Lead + S teel Tape s Armored
Y L ead + G alvanized Steel Tapes Armored
2 2 150 G Lead + A luminum Tapes Arm ored
2 3 185 N Aluminum foil Shie ld
24 240
25 300 Outer Sheathing Type
26 400
2 7 5 00 P PVC
2 8 630 H HDPE
29 800 M MDPE
30 1000 L LDPE
E LLDPE
F PVC / FR
Insulation Type S LSZH
X XLPE

Voltage Grade
4 3.6 / 6 (7.2) KV
5 6 / 10 (12) KV
6 8.7 / 15 (17.5) KV
7 12 / 20 (24) KV
8 18 / 30 (36) KV

No. of Cores
01 1
03 3

intelligent

Single & Three Cores Nominal Max. Conductor Inductance Current Rating
Copper Conductors Cross Resistance Trefoil Flat
XLPE Insulated and PVC Product Operating Laid in Laid in Approx. Approx
Sheathed Code Sectional DC at AC at capacitance Ground free Air Overall Weight
Area 20 OC 90 OC
Inner semi-con
Copper conductor

mm2 Ω/km Ω/km f/km A AAA A A mm kg / km

Single Core Cable

XLPE insulation C18X501UP 50 0.3870 0.4937 0.251 0.393 0.578 197 206 209 255 22.5 905
Outer semi-con Binder tape & Filler C19X501UP 70 0.2680 0.3420 0.291 0.370 0.554 242 252 262 319 24.3 1135
PVC Sheathing Copper tape screen C20X501UP 95 0.1930 0.2465 0.316 0.357 0.542 287 299 317 384 25.5 1390
120 0.1530 0.1956 0.345 0.344 0.529 326 339 366 443 26.9 1655
C21X501UP 150 0.1240 0.1588 0.374 0.336 0.521 364 375 416 498 28.7 2015
185 0.0991 0.1272 0.409 0.322 0.507 411 422 478 570 30.4 2390
Description C22X501UP 240 0.0754 0.0973 0.456 0.310 0.494 475 484 565 669 33.0 2950
C23X501UP 300 0.0601 0.0781 0.512 0.301 0.487 535 542 650 765 35.8 3590
400 0.0470 0.0618 0.565 0.292 0.477 591 599 745 853 38.6 4510
•StrandedcircularcompactedCopper C24X501UP 500 0.0366 0.0490 0.635 0.282 0.467 659 674 859 975 42.2 5610
conductor, semiconducting layer as C25X501UP 630 0.0283 0.0391 0.704 0.275 0.460 728 752 981 1103 45.9 6940
conductor screen, XLPE insulated, C26X501UP 800 0.0221 0.0319 0.795 0.268 0.453 869 979 1160 1480 50.8 9195
semiconducting layer as non metallic C27X501UP
50 2655
insulation screen. Copper tape or wire C28X501UP 70 3390
95 4165
as metallic insulation screen, three C29X501UP 120 Three Core Cables 5140
cores assembled together with non 150 5965
185 7210
hygroscopic Polypropylene fillers, C18X503UP 240 0.3870 0.4938 0.251 0.351 - 197 - 206 - 43.5 9020
wraped with binder tape and PVC C19X503UP 300 0.2680 0.3423 0.291 0.330 - 241 - 257 - 47.2 11095
sheathed. C20X503UP 0.1930 0.2469 0.316 0.316 - 286 - 309 - 50.0
• Cables are produced according to C21X503UP 0.1530 0.1961 0.345 0.309 - 325 - 356 - 53.6
IEC 60502 or BS 6622. 0.1240 0.1595 0.374 0.302 - 364 - 405 - 56.9
0.0991 0.1282 0.409 0.290 - 410 - 463 - 60.9
Application C22X503UP 0.0754 0.0983 0.456 0.280 - 475 - 546 - 66.3
C23X503UP 0.0601 0.0799 0.512 0.271 - 535 - 626 - 71.9
• These cables are generally suitable C24X503UP
for direct burial or for installation on C25X503UP
trays or in ducts.

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

Nominal Max. Inductance Current Rating Approx. Single & Three Cores
Cross Conductor Overall Aluminum ConductorsXLPE
Product- Resistance Operating Trefoil Flat Laid in Laid in Diameter Approx Insulated and PVC Sheathed
Code Sectional capacitance Ground free Air
Area DC at AC at Weight
20 OC 90 OC
A A A A mm kg / km Aluminum condInuncetorrsemi-con
mm2 Ω/km Ω/km f/km AA

Single Core Cable

A18X501UP 50 0.6410 0.8220 0.251 0.393 0.578 153 160 162 198 22.4 610 XLPE insulation
A19X501UP 70 0.4430 0.5681 0.291 0.370 0.554 188 196 204 248 24.0 715 Outer semi-con Binder tape & Filler
A20X501UP 95 0.3200 0.4105 0.316 0.357 0.542 222 233 246 299 25.5 815 Copper tape screen
A21X501UP 120 0.253.0 0.3247 0.345 0.344 0.529 254 265 284 346 26.9 915
A22X501UP 150 0.2060 0.2645 0.374 0.336 0.521 283 295 324 391 28.7 1115 Description
A23X501UP 185 0.1640 0.2107 0.409 0.322 0.507 321 333 373 449 30.4 1250
A24X501UP 240 0.1250 0.1610 0.456 0.310 0.494 372 385 443 530 32.9 1475 • Stranded circular compacted Aluminium
A25X501UP 300 0.1000 0.1291 0.512 0.301 0.487 421 433 511 608 35.5 1700 conductor, semiconducting layer as
A26X501UP 400 0.0778 0.1009 0.565 0.292 0.477 478 483 593 693 38.6 2120 conductor screen, XLPE insulated,
A27X501UP 500 0.0605 0.0791 0.635 0.282 0.467 544 545 693 802 42.2 2505 semiconducting layer as non metallic
A28X501UP 630 0.0469 0.0621 0.704 0.275 0.460 612 617 803 921 45.8 3000 insulation screen. Copper tape or wire
A29X501UP 800 0.0367 0.0495 0.795 0.268 0.453 715 786 954 1188 50.8 3670 as metallic insulation screen, three cores
assembled together with non hygroscopic
A18X503UP 50 0.6410 0.8220 Three Core Cables 1800 Polypropylene fillers, wraped with binder
A19X503UP 70 0.4430 0.5683 2100 tape and PVC sheathed.
A20X503UP 95 0.3200 0.4107 0.251 0.351 - 153 - 160 - 42.9 2440 • Cables are produced according to IEC
A21X503UP 120 0.253.0 0.3250 0.291 0.330 - 187 - 200 - 46.5 2780 60502 or BS 6622.
A22X503UP 150 0.2060 0.2649 0.316 0.316 - 222 - 240 - 50.0 3280 Application
A23X503UP 185 0.1640 0.2114 0.345 0.309 - 253 - 277 - 53.2 3790 • These cables are generally suitable for
A24X503UP 240 0.1250 0.1618 4555 direct burial or for installation on trays or in
A25X503UP 300 0.1000 0.1302 0.374 0.302 - 283 - 314 - 56.9 5360 ducts.

0.409 0.290 - 320 - 361 - 60.9
0.456 0.280 - 371 - 427 - 66.1
0.512 0.271 - 420 - 491 - 71.3

We own the power

278

intelligent

Inner semi-con STA ( Seel tape armored )
Copper or Aluminum conductor

Multicore Cables, with Stranded

Aluminum Conductors XLPE

Insulated and PVC Sheathed

XLPE insulation Inner Sheathing PVC Sheathing
Outer semi-con Binder tape & Filler

Description Copper tape screen

• Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated,

semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation screen,

three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC

sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application
• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Max. Conductor Current Rating Approx.
Resistance Overall
Nominal Cross Operating Diameter Approx
Product-Code Sectional Area DC at AC at Capacitance Inductance Laid in Laid in Weight
20 OC 90 OC mh/km Ground Free Air
C18X503IP mm2 f/km
C19X503IP Ω/km Ω/km A A mm kg / km
C20X503IP 50
C21X503IP 70 Three Cores Copper Conductor Cables
C22X503IP 95
C23X503IP 120 0.3870 0.4938 0.251 0.352 185 192 47.9 3625
C24X503IP 150 0.2680 0.3423 0.291 0.330
C25X503IP 185 0.1930 0.2469 0.316 0.316 226 237 51.8 4470
240 0.1530 0.1961 0.345 0.311
A18X503IP 300 0.1240 0.1595 0.374 0.302 269 286 54.6 5305
A19X503IP 0.0991 0.1282 0.409 0.290
A20X503IP 50 0.0754 0.0986 0.456 0.280 306 328 57.8 6205
A21X503IP 70 0.0601 0.0799 0.512 0.272
A22X503IP 95 342 371 61.7 7290
A23X503IP 120
A24X503IP 150 386 424 65.5 8595
A25X503IP 185
240 446 497 71.3 10595
Product-Code 300
502 566 77.1 12835
C18X503HP Nominal Cross
C19X503HP Sectional Area Three Cores Aluminium Conductor Cables
C20X503HP
C21X503HP mm2 0.6410 0.8220 0.251 0.351 144 149 47.3 2760
C22X503HP 0.4430 0.5683 0.291 0.330 176 184 51.1 3170
C23X503HP 50 0.3200 0.4107 0.316 0.316 209 222 54.6 3585
C24X503HP 70 0.2530 0.3250 0.345 0.309 238 255 57.8 3995
C25X503HP 95 0.2060 0.2649 0.374 0.302 266 288 61.7 4605
120 0.1640 0.2114 0.409 0.290 301 331 65.5 5175
A18X503HP 150 0.1250 0.1618 0.456 0.280 349 389 71.1 6120
A19X503HP 185 0.1000 0.1302 0.512 0.271 394 444 76.5 7085
A20X503HP 240
A21X503HP 300 Max. Conductor Operating Inductance Current Rating Approx.
A22X503HP Resistance Capacitance Overall
A23X503HP 50 Diameter Approx
A24X503HP 70 DC at AC at Laid in Laid in Weight
A25X503HP 95 20 OC 90 OC Ground Free Air
120
150 Ω/km Ω/km f/km mh/km A A mm kg / km
185
240 Three Cores Copper Conductor Cables
300
0.3870 0.4938 0.251 0.352 187 195 51.1 5085
0.2680 0.3423 0.291 0.330
0.1930 0.2469 0.316 0.316 227 241 55.0 6000
0.1530 0.1961 0.345 0.311
0.1240 0.1595 0.374 0.302 269 289 57.8 6920
0.0991 0.1282 0.409 0.290
0.754 0.0986 0.456 0.280 305 331 61.4 8090
0.0601 0.799 0.512 0.272
340 372 64.9 9130

381 423 68.9 10630

436 494 76.6 13700

485 556 82.2 16165

Three Cores Aluminium Conductor Cables

0.6410 0.8220 0.251 0.351 145 152 50.5 4185
0.4430 0.5683 0.291 0.330
0.3200 0.4107 0.316 0.316 177 188 54.3 4705
0.2530 0.3250 0.345 0.309
0.2060 0.2649 0.374 0.302 210 225 57.8 5195
0.1640 0.2114 0.409 0.290
0.1250 0.1618 0.456 0.280 238 259 61.0 5725
0.1000 0.1302 0.512 0.271
265 291 64.9 6445

300 332 68.9 7160

346 391 76.4 9130

387 442 81.6 10315

We own the power

279

intelligent

Inner semi-con STA ( Seel tape armored )
Copper or Aluminum conductor
Multicore Cables, with Stranded
Aluminum XLPE insulation Inner Sheathing PVC Sheathing
Conductors XLPE Insulated and Outer semi-con Binder tape & Filler
PVC Sheathed
Copper tape screen
Description

• Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated,
semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation screen,
three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC
sheathed, • Cables are produced according to IEC 60502 or BS 6622

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Max. Conductor Resistance Inductance Current Rating Approx.
Trefoil Flat Overall
Nominal Cross DC at AC at Operating Laid in ground Laid in free Diameter Approx
Product-Code Sectional Area 20 OC 90 OC capacitance air Weight

C18X601UP mm2 Ω/km Ω/km f/km mh/km mh/km A AAA mm kg / km
C19X601UP
C20X601UP 50 0.3870 0.4937 Single Core Cable 0.597 197 206 209 255 24.7 999
C21X601UP 70 0.2680 0.3420 0.572 242 252 262 319 26.5 1230
C22X601UP 95 0.1930 0.2465 0.204 0.412 0.558 287 299 317 384 27.7 1479
C23X601UP 120 0.1530 0.1956 0.234 0.387 0.546 326 339 366 443 29.3 1761
C24X601UP 150 0.1240 0.1588 0.253 0.373 0.536 364 375 416 498 30.9 2111
C25X601UP 185 0.0991 0.1272 0.522 411 422 478 570 32.8 2512
C26X601UP 240 0.0754 0.0973 0.275 0.361 0.509 475 484 565 669 35.4 3083
C27X601UP 300 0.0601 0.0781 0.498 535 542 650 765 38.0 3718
C28X601UP 400 0.0470 0.0618 0.297 0.351 0.489 591 599 745 853 41.0 4661
C29X601UP 500 0.0366 0.0490 0.324 0.338 0.478 659 674 859 975 44.6 3808
630 0.0283 0.0391 0.470 728 752 981 1103 48.3 7127
C18X603UP 800 0.0221 0.0319 0.360 0.324 0.462 869 979 1160 1480 53.2 9010
C19X603UP
C20X603UP 50 0.3870 0.4938 0.402 0.313 - 197 - 206 - 48.3 2990
C21X603UP 70 0.2680 0.3423 0.442 0.304 - 241 - 257 - 52.3 3725
C22X603UP 95 0.1930 0.2469 - 286 - 309 - 55.1 4505
C23X603UP 120 0.1530 0.1961 0.495 0.293 - 325 - 356 - 58.4 5410
C24X603UP 150 0.1240 0.1595 - 364 - 405 - 62.0 6415
C25X603UP 185 0.0991 0.1282 0.548 0.285 - 410 - 463 - 65.9 7685
240 0.0754 0.0986 0.616 0.277 - 475 - 546 - 71.10 9540
Product-Code 300 0.0601 0.0799 Three Core Cable - 535 - 626 - 76.9 11590

C18X503HP 0.204 0.376
C19X503HP
C20X503HP 0.234 0.354
C21X503HP
C22X503HP 0.253 0.340
C23X503HP
C24X503HP 0.275 0.329
C25X503HP
0.297 0.320
A18X503HP
A19X503HP 0.324 0.308
A20X503HP
A21X503HP 0.360 0.295
A22X503HP
A23X503HP 0.402 0.288
A24X503HP
A25X503HP Max. Conductor Current Rating Approx.
Resistance Overall
Nominal Cross Operating Diameter Approx
Sectional Area DC at AC at Capacitance Inductance Laid in Laid in Weight
20 OC 90 OC Ground Free Air mm
mm2 kg / km
Ω/km Ω/km f/km mh/km A A 51.1
50 55.0 5085
70 Three Cores Copper Conductor Cables 57.8 6000
95 61.4 6920
120 0.3870 0.4938 0.251 0.352 187 195 64.9 8090
150 0.2680 0.3423 0.291 0.330 227 241 68.9 9130
185 0.1930 0.2469 0.316 0.316 269 289 76.6 10630
240 0.1530 0.1961 0.345 0.311 305 331 82.2 13700
300 0.1240 0.1595 0.374 0.302 340 372 16165
0.0991 381 423 50.5
50 0.754 0.1282 0.409 0.290 436 494 54.3 4185
70 0.0601 485 556 57.8 4705
95 0.0986 0.456 0.280 61.0 5195
120 0.6410 145 152 64.9 5725
150 0.4430 0.799 0.512 0.272 177 188 68.9 6445
185 0.3200 210 225 76.4 7160
240 0.2530 Three Cores Aluminium Conductor Cables 238 259 81.6 9130
300 0.2060 265 291 10315
0.1640 0.8220 0.251 0.351 300 332
0.1250 0.5683 0.291 0.330 346 391
0.1000 0.4107 0.316 0.316 387 442
0.3250 0.345 0.309

0.2649 0.374 0.302

0.2114 0.409 0.290
0.1618 0.456 0.280

0.1302 0.512 0.271

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

We own the power

280

intelligent

Single & Three Cores Copper Inner semi-con
Copper conductor

Conductors,

XLPE Insulated and PVC

Sheathed XLPE insulation PVC Sheathing
Outer semi-con Binder tape & Filler
Description Copper tape screen

• Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated,

semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation screen,

three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC

sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application
• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Nominal Cross Max. Conductor Resistance Inductance Current Rating Approx. Approx
Sectional Area Trefoil Flat Laid in ground Laid in free air Overall Weight
Product-Code DC at AC at Operating Diameter
mm2 20 OC 90 OC capacitance mh/km mh/km AAAA kg / km
C18X601UP mm
C19X601UP 50 Ω/km Ω/km f/km 999
C20X601UP 70 24.7 1230
C21X601UP 95 Single Core Cable 26.5 1479
C22X601UP 120 27.7 1761
C23X601UP 150 0.3870 0.4937 0.204 0.412 0.597 197 206 209 255 29.3 2111
C24X601UP 185 0.2680 0.3420 0.234 0.387 0.572 242 252 262 319 30.9 2512
C25X601UP 240 0.1930 0.2465 0.253 0.373 0.558 287 299 317 384 32.8 3083
C26X601UP 300 0.1530 0.1956 0.275 0.361 0.546 326 339 366 443 35.4 3718
C27X601UP 400 0.1240 0.1588 0.297 0.351 0.536 364 375 416 498 38.0 4661
C28X601UP 500 0.0991 0.1272 0.324 0.338 0.522 411 422 478 570 41.0 3808
C29X601UP 630 0.0754 0.0973 0.360 0.324 0.509 475 484 565 669 44.6 7127
800 0.0601 0.0781 0.402 0.313 0.498 535 542 650 765 48.3 9010
C18X603UP 0.0470 0.0618 0.442 0.304 0.489 591 599 745 853 53.2
C19X603UP 50 0.0366 0.0490 0.495 0.293 0.478 659 674 859 975 2990
C20X603UP 70 0.0283 0.0391 0.548 0.285 0.470 728 752 981 1103 48.3 3725
C21X603UP 95 0.0221 0.0319 0.616 0.277 0.462 869 979 1160 1480 52.3 4505
C22X603UP 120 55.1 5410
C23X603UP 150 Three Core Cable 58.4 6415
C24X603UP 185 62.0 7685
C25X603UP 240 0.3870 0.4938 0.204 0.376 - 197 - 206 - 65.9 9540
300 0.2680 0.3423 0.234 0.354 - 241 - 257 - 71.10 11590
0.1930 0.2469 0.253 0.340 - 286 - 309 - 76.9
0.1530 0.1961 0.275 0.329 - 325 - 356 -
0.1240 0.1595 0.297 0.320 - 364 - 405 -
0.0991 0.1282 0.324 0.308 - 410 - 463 -
0.0754 0.0986 0.360 0.295 - 475 - 546 -
0.0601 0.0799 0.402 0.288 - 535 - 626 -

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

We own the power

281

intelligent

Single & Three Cores Copper Inner semi-con
Conductors, XLPE Insulated and Aluminum conductor
PVC Sheathed

XLPE insulation PVC Sheathing
Outer semi-con Binder tape & Filler
Description Copper tape screen

• Stranded circular compacted Aluminium conductor, semiconducting layer as conductor screen, XLPE
insulated, semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation
screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape
and PVC sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application
• These cables are generally suitable for direct burial or for installation on trays or in ducts. .

Nominal Cross Max. Conductor Resistance Inductance Current Rating Approx. Approx
Sectional Area Trefoil Flat Laid in ground Laid in free air Overall Weight
Product-Code DC at AC at Operating Diameter
mm2 20 OC 90 OC capacitance mh/km mh/km AAAA kg / km
A18X601UP mm
A19X601UP 50 Ω/km Ω/km f/km 700
A20X601UP 70 24.6 800
A21X601UP 95 Single Core Cable 26.2 905
A22X601UP 120 27.7 1020
A23X601UP 150 0.6410 0.8220 0.204 0.412 0.597 153 160 162 198 29.3 1215
A24X601UP 185 0.4430 0.5681 0.234 0.387 0.572 188 196 204 248 30.9 1370
A25X601UP 240 0.3200 0.4105 0.253 0.373 0.558 222 233 246 299 32.8 1595
A26X601UP 300 0.2530 0.3247 0.275 0.361 0.546 254 265 284 346 35.3 1825
A27X601UP 400 0.2060 0.2645 0.297 0.351 0.536 283 295 324 391 37.7 2270
A28X601UP 500 0.1640 0.2107 0.324 0.338 0.522 321 333 373 449 41 2670
A29X601UP 630 0.1250 0.1610 0.360 0.324 0.509 372 385 443 530 44.6 3180
800 0.1000 0.1291 0.402 0.313 0.498 421 433 511 608 48.2 3870
A18X603UP 0.0778 0.1009 0.442 0.304 0.489 478 483 593 693 53.2
A19X603UP 50 0.0605 0.0791 0.495 0.293 0.478 544 545 693 802 2040
A20X603UP 70 0.0469 0.0621 0.548 0.288 0.470 612 617 803 921 47.6 2375
A21X603UP 95 0.0367 0.0495 0.616 0.277 0.462 715 786 954 1188 51.3 2730
A22X603UP 120 54.7 3120
A23X603UP 150 Three Core Cable 58 3645
A24X603UP 185 61.6 4205
A25X603UP 240 0.6410 0.8220 0.204 0.376 153 160 65.7 4975
300 0.4430 0.5683 0.234 0.354 187 200 70.4 5775
0.3200 0.4107 0.253 0.340 222 240 76
0.2530 0.3250 0.275 0.329 253 277
0.2060 0.2649 0.297 0.320 283 314
0.1640 0.2114 0.324 0.308 320 361
0.1250 0.1618 0.360 0.295 371 427
0.1000 0.1302 0.402 0.288 420 491

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

We own the power

282

intelligent

Single & Three Cores Copper Inner semi-con STA ( Seel tape armored )
Conductors, XLPE Insulated and Copper or Aluminum conductor
PVC Sheathed

XLPE insulation Inner Sheathing PVC Sheathing
Outer semi-con Binder tape & Filler

Description Copper tape screen

• Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated,

semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation screen,

three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC

sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application
• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Max. Conductor Resistance Current Rating Approx.
Overall
Product-Code Nominal Cross DC at AC at Operating Inductance Laid in Laid in Free Diameter Approx
Sectional Area 20 OC 90 OC Capacitance mh/km groung Air Weight
C18X603IP mm
C19X603IP mm2 Ω/km Ω/km f/km A A kg / km
C20X603IP
C21X603IP 50 Three Cores Copper Conductor Cables
C22X603IP 70
C23X503IP 95 0.3870 0.4938 0.204 0.376 185 192 52.7 4055
C24X603IP 120 0.2680 0.3423 0.234 0.354 226 237 56.7 4875
C25X603IP 150 0.1930 0.2469 0.253 0.340 269 286 59.9 5790
185 0.1530 0.1961 0.275 0.330 306 328 63.4 6790
A18X603IP 240 0.1240 0.1595 0.297 0.320 342 371 67 7865
A19X603IP 300 0.0991 0.1282 0.324 0.308 386 424 70.9 9220
A20X603IP 0.0754 0.0986 0.360 0.296 446 497 76.2 11225
A21X603IP 50 0.0601 0.0799 0.402 0.288 502 566 83.7 14265
A22X603IP 70
A23X603IP 95 Three Cores Aluminium Conductor Cables
A24X603IP 120
A25X603IP 150 0.6410 0.8220 0.204 0.376 144 149 52.4 3160
185 0.4430 0.5683 0.234 0.354 176 184 56.1 3575
Product-Code 240 0.3200 0.4107 0.253 0.340 209 222 59.7 4040
300 0.2530 0.3250 0.275 0.329 238 255 63.2 4530
C18X603HP 0.2060 0.2649 0.279 0.320 266 288 67.0 5180
C19X603HP Nominal Cross 0.1640 0.2114 0.324 0.308 301 331 70.9 5800
C20X603HP Sectional Area 0.1250 0.1618 0.360 0.295 349 389 76.0 6755
C21X603HP 0.1000 0.1302 0.402 0.288 394 444 83.0 8500
C22X603HP mm2
C23X603HP Max. Conductor Resistance Current Rating Approx. Approx
C24X603HP 50 Overall Weight
C25X603HP 70 DC at AC at Operating Inductance Laid in Laid in Free Diameter
95 20 OC 90 OC Capacitance mh/km groung Air kg / km
A18X603HP 120 mm
A19X603HP 150 Ω/km Ω/km f/km A A
A20X603HP 185
A21X603HP 240 Three Cores Copper Conductor Cables
A22X603HP 300
A23X603HP 0.3870 0.4938 0.204 0.376 187 195 55.9 5715
A24X603HP 50 0.2680 0.3423 0.234 0.354 227 241 59.9 6650
A25X603HP 70 0.1930 0.2469 0.253 0.34 269 289 63.1 7655
95 0.1530 0.1961 0.275 0.330 305 331 66.6 8765
120 0.1240 0.1595 0.297 0.320 340 372 72.3 10935
150 0.0991 0.1282 0.324 0.308 381 423 76.2 12450
185 0.0754 0.0986 0.360 0.296 436 494 81.5 14735
240 0.0601 0.0799 0.402 0.288 485 556 87.6 17230
300
Three Cores Aluminium Conductor Cables 145 152 55.6 4715
177 188 59.3 5245
0.6410 0.8220 0.204 0.376 210 225 62.9 5825
0.4430 0.5683 0.234 0.354 238 259 66.4 6400
0.3200 0.4107 0.253 0.340 265 291 72.3 8095
0.2530 0.3250 0.275 0.329 300 332 76.2 8865
0.2060 0.2649 0.279 0.320 346 391 81.1 9850
0.1640 0.2114 0.324 0.308 387 442 86.9 11135
0.1250 0.1618 0.360 0.295
0.1000 0.1302 0.402 0.288

We own the power

283

intelligent

Single & Three Cores Copper Inner semi-con
Conductors, XLPE Insulated and Copper conductor
PVC Sheathed

XLPE insulation PVC Sheathing
Outer semi-con Binder tape & Filler
Description Copper tape screen

• Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated,
semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation screen,
three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC
sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Nominal Cross Max. Conductor Resistance Inductance Current Rating Approx. Approx
Sectional Area Trefoil Flat Laid in ground Laid in free Air Overall Weight
Product-Code DC at AC at Operating Diameter
mm2 20 OC 90 OC capacitance mh/km mh/km AAAA kg / km
C18X701UP mm
C19X701UP 50 Ω/km Ω/km f/km 1070
C20X701UP 70 26.7 1320
C21X701UP 95 Single Core Cable 28.7 1575
C22X701UP 120 29.9 1860
C23X701UP 150 0.3870 0.4937 0.177 0.428 0.613 197 206 209 255 31.5 2220
C24X701UP 185 0.2680 0.3420 0.202 0.403 0.588 242 252 262 319 33.1 2625
C25X701UP 240 0.1930 0.2465 0.217 0.389 0.573 287 299 317 384 35.0 3185
C26X701UP 300 0.1530 0.1956 0.236 0.376 0.561 326 339 366 443 37.4 3845
C27X701UP 400 0.1240 0.1588 0.254 0.365 0.550 364 375 416 498 40.2 4780
C28X701UP 500 0.0991 0.1272 0.276 0.350 0.535 411 422 478 570 43.0 5930
C29X701UP 630 0.0754 0.0973 0.305 0.335 0.520 475 484 565 669 46.6 7265
800 0.0601 0.0781 0.340 0.325 0.510 535 542 650 765 50.3 9200
C18X703UP 0.0470 0.618 0.373 0.313 0.498 591 599 745 853 55.4
C19X703UP 50 0.0366 0.0490 0.417 0.302 0.487 659 674 859 975 3255
C20X703UP 70 0.0283 0.0391 0.460 0.293 0.478 728 752 981 1103 52.8 4035
C21X703UP 95 0.0221 0.0319 0.516 0.285 0.470 869 979 1160 1480 56.9 4865
C22X703UP 120 59.7 5800
C23X703UP 150 Three Core Cable 63.1 6835
C24X703UP 185 66.7 8110
C25X703UP 240 0.3870 0.4938 0.177 0.394 - 197 - 206 - 70.2 9960
300 75.6 12085
0.2680 0.3423 0.202 0.370 - 241 - 257 - 81.6

0.1930 0.2469 0.217 0.357 - 286 - 309 -

0.1530 0.1961 0.236 0.345 - 325 - 356 -

0.1240 0.1595 0.254 0.336 - 364 - 405 -

0.0991 0.1282 0.276 0.321 - 410 - 463 -

0.0754 0.0986 0.305 0.308 - 485 - 546 -

0.0601 0.0799 0.340 0.299 - 535 - 626 -

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

We own the power

284

intelligent

Single & Three Cores Copper Inner semi-con
Conductors, XLPE Insulated and Aluminum conductor
PVC Sheathed

XLPE insulation PVC Sheathing
Outer semi-con Binder tape & Filler
Description Copper tape screen

• Stranded circular compacted Aluminium conductor, semiconducting layer as conductor screen, XLPE
insulated, semiconducting layer as non metallic insulation screen. Copper tape or wire as metallic insulation
screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape
and PVC sheathed, • Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Nominal Cross Max. Conductor Resistance Inductance Current Rating Approx. Approx
Sectional Area Trefoil Flat Laid in ground Laid in free Air Overall Weight
Product-Code DC at AC at Operating Diameter
mm2 20 OC 90 OC capacitance mh/km mh/km AAAA kg / km
A18X701UP mm
A19X701UP 50 Ω/km Ω/km f/km 775
A20X701UP 70 26.6 890
A21X701UP 95 Single Core Cable 28.4 1000
A22X701UP 120 29.9 1125
A23X701UP 150 0.6410 0.8220 0.177 0.428 0.613 153 160 162 198 31.5 1320
A24X701UP 185 0.4430 0.5681 0.202 0.403 0.588 188 196 204 248 33.1 1475
A25X701UP 240 0.3200 0.4105 0.217 0.389 0.573 222 233 246 299 35.0 1700
A26X701UP 300 0.2530 0.3247 0.236 0.376 0.561 254 265 284 346 37.3 1945
A27X701UP 400 0.2060 0.2645 0.254 0.365 0.550 283 295 324 391 39.9 2390
A28X701UP 500 0.1640 0.2107 0.276 0.350 0.535 321 333 373 449 43.0 2800
A29X701UP 630 0.1250 0.1610 0.305 0.335 0.520 372 385 443 530 46.6 3325
800 0.1000 0.1291 0.340 0.325 0.510 421 433 511 608 50.2 4060
A18X703UP 0.0778 0.1009 0.373 0.313 0.498 478 483 593 693 55.4
A19X703UP 50 0.0605 0.0791 0.417 0.302 0.487 544 545 693 802 2295
A20X703UP 70 0.0469 0.0621 0.460 0.293 0.478 612 617 803 921 52.0 2650
A21X703UP 95 0.0367 0.0495 0.516 0.285 0.470 715 786 954 1188 55.6 3060
A22X703UP 120 59.1 3470
A23X703UP 150 Three Core Cable 62.3 4025
A24X703UP 185 65.9 4605
A25X703UP 240 0.6410 0.8220 0.177 0.394 - 153 - 160 - 70.0 5420
300 0.4430 0.5683 0.202 0.370 - 187 - 200 - 75.2 6175
0.3200 0.4107 0.217 0.357 - 222 - 240 - 80.3
0.2530 0.3250 0.236 0.345 - 253 - 277 -
0.2060 0.2649 0.254 0.336 - 283 - 314 -
0.1640 0.2114 0.276 0.321 - 320 - 361 -
0.1250 0.1618 0.305 0.308 - 371 - 427 -
0.1000 0.1302 0.340 0.299 - 420 - 491 -

This data is applicable for 6.35 / 11 KV cables
The ampacity for single core sizes 800 mm2 was based on a single end bonding

The above data is approximate and subjected to manufacturing tolerance.

We own the power

285

intelligent

Three Cores Copper or Inner semi-con STA ( Seel tape armored )
Copper or Aluminum conductor

Aluminum Conductors,

XLPE Insulated , Steel Tape

Armoured and PVC Sheathed XLPE insulation Inner Sheathing PVC Sheathing
Outer semi-con Binder tape & Filler
Description
Copper tape screen

• Stranded circular compacted copper or aluminium conductor, semiconducting layer as conductor screen.

XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as a metallic

insulation screen, three cores assembled together with non hygroscopic polypropylene fillers,warpped with

binder tape , covered with layer of PVC compound as bedding , steel tape armoured and PVC sheathed

• Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Max. Conductor Resistance Current Rating Approx.
Overall
Product-Code Nominal Cross DC at AC at Operating Inductance Laid in Laid in Free Diameter Approx
Sectional Area 20 OC 90 OC Capacitance mh/km ground Air Weight
C18X703IP mm
C19X703IP mm2 Ω/km Ω/km f/km A A kg / km
C20X703IP
C21X703IP 50 Three Cores Copper Conductor Cables
C22X703IP 70
C23X703IP 95 0.3870 0.4938 0.177 0.394 185 192 57.6 4490
C24X703IP 120 0.2680 0.3423 0.202 0.370 226 237 61.6 5360
C25X703IP 150 0.1930 0.2469 0.217 0.357 269 286 64.7 6290
185 0.1530 0.1961 0.236 0.345 306 328 67.9 7265
A18X703IP 240 0.1240 0.1595 0.254 0.336 342 371 71.5 8380
A19X703IP 300 0.0991 0.1282 0.276 0.321 386 424 75.4 9810
A20X703IP 0.0754 0.0986 0.305 0.308 446 497 82.4 12590
A21X703IP 50 0.0601 0.0799 0.340 0.299 502 566 88.4 14920
A22X703IP 70
A23X703IP 95 0.6410 Three Cores Aluminium Conductor Cables
A24X703IP 120 0.4430
A25X703IP 150 0.3200 0.8220 0.177 0.394 144 149 57.2 3570
185 0.2530 0.5683 0.202 0.370 176 184 60.8 4010
Product-Code 240 0.2060 0.4107 0.217 0.357 209 222 64.5 4535
300 0.1640 0.3250 0.236 0.345 238 255 68.1 5085
C18X703HP 0.1250 0.2649 0.254 0.336 266 288 71.7 5730
C19X703HP Nominal Cross 0.1000 0.2114 0.276 0.321 301 331 75.4 6390
C20X703HP Sectional Area 0.1618 0.305 0.308 349 389 82.1 8110
C21X703HP 0.1302 0.340 0.299 394 444 87.9 9180
C22X703HP mm2
C23X703HP Max. Conductor Resistance Current Rating Approx. Approx
C24X703HP 50 Overall Weight
C25X703HP 70 DC at AC at Operating Inductance Laid in Laid in Free Diameter
95 20 OC 90 OC Capacitance ground Air kg / km
A18X703HP 120 mm
A19X703HP 150 Ω/km Ω/km f/km mh/km AA
A20X703HP 185
A21X703HP 240 Three Cores Copper Conductor Cables
A22X703HP 300
A23X703HP 0.3870 0.4938 0.177 0.394 187 195 60.8 6295
A24X703HP 50 0.2680 0.3423 0.202 0.370 227 241 64.9 7280
A25X703HP 70 0.1930 0.2469 0.217 0.357 269 289 67.9 8300
95 0.1530 0.1961 0.236 0.345 305 331 73.2 10350
120 0.1240 0.1595 0.254 0.336 340 372 76.8 11670
150 0.0991 0.1282 0.276 0.321 381 423 80.5 13225
185 0.0754 0.0986 0.305 0.308 436 494 86.3 15515
240 0.0601 0.0799 0.340 0.299 485 556 92.5 18095
300
0.6410 Three Cores Aluminium Conductor Cables 145 152 60.4 5270
0.4430 177 188 64.0 5820
0.3200 0.8220 0.177 0.394 210 225 67.7 6460
0.2530 0.5683 0.202 0.370 238 259 73.2 8045
0.2060 0.4107 0.217 0.357 265 291 76.8 8815
0.1640 0.3250 0.236 0.345 300 332 81.1 9675
0.1250 0.2649 0.254 0.336 346 391 86.0 10775
0.1000 0.2114 0.276 0.321 387 442 91.8 12050
0.1618 0.305 0.308
0.1302 0.340 0.299

We own the power

286

intelligent

Copper or Aluminum conIdnuncetrorsemi-con STA ( Seel tape armored )

Single & Three Cores Copper XLPE insulation
Conductors, XLPE Insulated and Outer semi-con
PVC Sheathed

Inner Sheathing PVC Sheathing
Binder tape & Filler

Description
• Stranded circular compacted copper or aluminium conductor, semiconducting layer as conductor screen. XLPE
insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as a metallic insulation
screen, three cores assembled together with non hygroscopic polypropylene fillers,warpped with binder tape ,
covered with a layer of PVC compound as bedding , steel tape armoured and PVC sheathed
• Cables are produced according to IEC 60502 or BS 6622.

Application

• These cables are generally suitable for direct burial or for installation on trays or in ducts.

Max. Conductor Resistance Current Rating Approx.
Overall
Product-Code Nominal Cross DC at AC at Operating Inductance Laid in Laid in Free Diameter Approx
Sectional Area 20 OC 90 OC Capacitance mh/km ground Air Weight
mm
mm2 Ω/km Ω/km f/km A A kg / km

Three Cores Copper Conductor Cables

C18X803IP 50 0.3870 0.4938 0.138 0.436 185 192 69.4 5730
C19X803IP 0.410
C20X803IP 70 0.2680 0.3423 0.156 0.395 226 237 73.7 6725
C21X803IP 0.381
C22X803IP 95 0.1930 0.2469 0.167 0.368 269 286 76.7 7705
C23X803IP 0.353
C24X803IP 120 0.1530 0.1961 0.180 0.338 306 328 81.3 9720
C25X803IP 0.327
150 0.1240 0.1595 0.192 342 371 84.7 10680
A18X803IP
A19X803IP 185 0.0991 0.1282 0.208 386 424 88.6 12120
A20X803IP
A21X803IP 240 0.0754 0.0986 0.229 446 497 94.4 14310
A22X803IP
A23X803IP 300 0.0601 0.0799 0.252 502 566 100.4 16790
A24X803IP
A25X803IP Three Cores Aluminium Conductor Cables

50 0.6410 0.8220 0.138 0.436 144 149 69.2 4830
0.410 176 184 73.0 5395
70 0.4430 0.5683 0.156 0.395 209 222 76.7 5980
0.381 238 255 81.3 7310
95 0.3200 0.4107 0.167 0.368 266 288 84.7 7995
0.353 301 331 88.6 8700
120 0.2530 0.3250 0.180 0.338 349 389 94.1 9820
0.327 394 444 99.7 11000
150 0.2060 0.2649 0.192

185 0.1640 0.2114 0.208

240 0.1250 0.1618 0.228

300 0.1000 0.1302 0.252

Max. Conductor Resistance Current Rating Approx.
Overall
Product-Code Nominal Cross DC at AC at Operating Inductance Laid in Laid in Free Diameter Approx
Sectional Area 20 OC 90 OC Capacitance mh/km ground Air Weight
mm
mm2 Ω/km Ω/km f/km A A kg / km

Three Cores Copper Conductor Cables

C18X803HP 50 0.3870 0.4938 0.138 0.436 187 195 74.7 8910
C19X803HP 0.410
C20X803HP 70 0.2680 0.3423 0.156 0.395 227 241 78.8 10025
C21X803HP 0.381
C22X803HP 95 0.1930 0.2469 0.167 0.368 269 289 81.8 11175
C23X803HP 0.353
C24X803HP 120 0.1530 0.1961 0.180 0.338 305 331 85.2 12500
C25X803HP 0.327
150 0.1240 0.1595 0.192 340 372 88.4 13595
A18X803HP
A19X803HP 185 0.0991 0.1282 0.208 381 423 92.5 15255
A20X803HP
A21X803HP 240 0.0754 0.0986 0.228 436 494 98.3 17665
A22X803HP
A23X803HP 300 0.0601 0.0799 0.252 485 556 104.5 20405
A24X803HP
A25X803HP Three Cores Aluminium Conductor Cables

50 0.6410 0.8220 0.138 0.436 145 152 74.3 7810
0.410
70 0.4430 0.5683 0.156 0.395 177 188 78.3 8560
0.381
95 0.3200 0.4107 0.167 0.368 210 225 81.8 9265
0.353
120 0.2530 0.3250 0.180 0.338 238 259 85.2 9995
0.327
150 0.2060 0.2649 0.192 265 291 88.6 10800

185 0.1640 0.2114 0.208 300 332 92.5 11615

240 0.1250 0.1618 0.228 346 391 98.0 12880

300 0.1000 0.1302 0.252 387 442 103.8 14300

We own the power

287



intelligent

Mediume Voltage Cables 1

We Deliver ... Your Power

intelligent

We Deliver ... Your Power 3

intelligent

We Deliver ... Your Power 291

intelligent

292 We Deliver ... Your Power

intelligent

We Deliver ... Your Power 293

intelligent

294 We Deliver ... Your Power

intelligent

We Deliver ... Your Power 295

intelligent

296 We Deliver ... Your Power

intelligent

We Deliver ... Your Power 297

intelligent

298 We Deliver ... Your Power

intelligent

We Deliver ... Your Power 299

intelligent

300 We Deliver ... Your Power


Click to View FlipBook Version