PRODUCT PORTFOLIO
Control and Reducer Panel
3.4 CONTROL AND REDUCER PANEL
The 2nd stage pressure regulator units are equipped with line pressure regulators of 25–438m³/h
3.4.1 Low and middle pressure reducers up to 30bars
TYPE OF TYPE OF GAS INLET MIN. INLET OUTLET (m³/h) CONNECTION
REDUCER PRESSURE (P1) PRESSURE (P1) PRESSURE (P2) (inches)
LPR/GS1-L4 O2, N2O, Air, CO2, N2 25 (4bar)
LPR/GS2-L8 Air800 8bar 6bar 4/5bar 28 (8bar) 3/8”
LPR/GS2D-L4 S/L 10bar 9bar 7/8bar 50 (4bar) 3/8”
LPR/GS2D-L8 S/L O2, N2O, Air, CO2, N2 8bar 6bar 4/5bar 56 (8bar) 3/8”
LPR/GS3D-L4/8A S/L Air800 10bar 9bar 7/8bar 56 (8bar) 3/8”
LPR/GS3-DL 10bar 9bar 4/5 & 7/8bar 144 (8bar) 3/8”
LPR/GS4-DV Air / Air800 8/10bar 6/9bar 4/5 & 7/8bar 438 (8bar) 1/2”
LPR/GS5-DV O2, N2O, Air, CO2, N2 / Air800 8/10bar 6/9bar 4/5 & 7/8bar 3/4”
O2, N2O, Air, CO2, N2 / Air800 8/16bar 4/5, 7/8, 10/12bar –
O2, N2O, Air, CO2, N2 / Air800 – –
140 140 NEW
product
5 26.5
1 2
10EN 837-1 4 6EN 837-1
5
28
15
65 68.5 0 6 6 0 10 9
40
3 11 4
12
0653 G.S.
O2, N2O, Air, CO2
LPR GS LOT 0513
P1=8bar P2=4,5bar
G3/8" connection 7 11
12.5 10
49.5 35 OFF P1=8bar - P2=4.5bar
ON ON OFF
Oxygen-O2
89 8
108 13
LPR GS1-L4, LPR GS2-L8, LPR/GS5-DV
200 260
170 230
100 5 130 5
3 +- 3 + -
6 6
0653 G.S. 4 1 4
7 O2, N2O, Air, CO2 6 7
7 LPR GS LOT 4414 7 0653 G.S. 6
6 P1=8bar P2=4,5bar O2, N2O, Air, CO2 10
30 45 6
30 75 LPR GS LOT 4414 5
6
P1=8bar P2=4,5bar
8
G.SAMARAS S.A. 10 4 EoNxS8yg37e-n1 6 2 G.SAMARAS S.A. 4 EoNxS8yg37e-n1 6 2
28 28
medical gas systems medical gas systems
0 bar 10 0 bar 10
219 OFF P1=8bar - P2=4.5bar CL.2,5 OFF P1=8bar - P2=4.5bar CL.2,5
115
ON ON G.Samaras S.A. ON ON G.Samaras S.A.
MEDICAL GAS SYSTEMS MEDICAL GAS SYSTEMS
AIR OFF OXYGEN OFF
69 9
12 12
+ 1+
5
5 --
13
LPR GS1D-L4S, LPR GS2D-L8S LPR GS1D-L4L, LPR GS2D-L8L
G. Samaras S.A. MEDICAL GAS SYSTEMS 53
170 370 170
5 170
100
-+ 5 ⌀67
+- 1/2" 1/2"
4 3 0653 G.S. 4
Air800 6
6 0653 G.S. 6 6 72 7 G.S.
O2, N2O, Air, CO2 7 LPR GS2 LOT 4414 O
P1=10bar P2=8bar
LPR GS LOT 4414 7 LOT 4414
P P2=4,5bar
P1=8bar P2=4,5bar
m
4S6 7 10 G.S. 10 S 10 3 4
EoNx8yg37e-n1 7 G.SAMARAS S.A. O G.SAMARAS S.A. 5 EoNx8yg37e-n1 30 2
2 P 5 LOPEoN2TxS8y=g37e4-n41 4,1510b4ar 1 145
28 medical gas systems medical gas systems
0 bar 10 OFF P1=8bar - P2=4.5bar bar 15 OFF P1=10ar - P2=8bar bar 15
CL.2,5 16 16
0 0
G.Samaras S.A.
MEDICAL GAS SYSTEMS ON ON CL.2,5 ON ON CL.2,5
G.Samaras S.A. G.Samaras S.A.
AIR OFF AIR800 OFF
MEDICAL GAS SYSTEMS MEDICAL GAS SYSTEMS
96 66 69
12
5
12
-+ - +
-+
5 5
LPR/GS3D-L4/8S Line pressure reducer
144m3/h LPR GS3-DL
130 230 490 230 ⌀114
230
5 5 G1/2"RH
1/2" G3/4"RH
-+ +-
3/4" G1"RH
1"
83 7
4 3 4 4
2
6 0653 G.S. 6 6 0653 G.S. 6 41 3
O2, N2O, Air, CO2 10 7 Air800 10 213 5
LPR GS LOT 4414 6 7 LPR GS2 LOT 4414 6
6 P1=10bar P2=8bar
P1=8bar P2=4,5bar
2 4 EoNxS8yg37e-n1 6 7 G.SAMARAS S.A. 5 EoNxS8yg37e-n1 10 G.SAMARAS S.A. 5 EoNxS8yg37e-n1 10 1
28 7
medical gas systems medical gas systems
0 bar 10
CL.2,5 OFF P1=8bar - P2=4.5bar bar 15 OFF P1=10ar - P2=8bar bar 15
16 16
G.Samaras S.A. 0 0
MEDICAL GAS SYSTEMS
ON ON CL.2,5 ON ON CL.2,5
G.Samaras S.A. G.Samaras S.A.
AIR OFF AIR800 OFF
MEDICAL GAS SYSTEMS MEDICAL GAS SYSTEMS
96 9
12
12
- +
5 5
LPR/GS3D-L4/8L Line pressure reducer
438m3/h LPR GS4-DV
INDEX Manometer Ø40 0÷16bar 8 G1/8’’ female corner connection
1 Manometer Ø40 0÷10bar (set with 11)
2 Inlet connection (high pressure)
3 Outlet connection (low pressure) 9 NIST emergency outlet
4 Adjustment screw
5 On/off plastic ball valve Optional O2/Air/N2O outlet/NIST
6 Access plug to the filter and the pressure 10 Support bracket
7 regulators valve 11 Fitting with Ø 0,4mm hole
12 Digital pressure switch (ON/OFF)
13 Analogue transducer (4÷20mA, 16bar)
54 visit us on www.gsamaras.gr
PRODUCT PORTFOLIO
Control and Reducer Panel
3.4.2 Second Stage Pressure Regulator Unit (Y/S GS N S/D) 93/42 MED
The 2nd stage pressure regulator unit con- GASES
trols and isolates the medical gases (O2,
N2O, Air, CO2) that feed the gas outlets. Second reducer panels O2 N2O AIR/MA4 Vac Air800SA7 Special gas
The 2nd stage panel is suitable for flash or 1. One gas single
chased distribution networks, contains re- 2. One gas double •
ducers, shut-off valves (upstream and down- 3. Two gas single
stream of reducers), pressure gauges, 4. Two gas double •
gas-specific connectors and low-high pres- 5. Three gas single
sure switches, according to EN ISO 7396-1, 6. Three gas double ••
HTM 02-01 standards. 7. Four gas single
8. Four gas double ••
Output @ 4bar 9. Five gas single
10. Five gas double • ••
26m³/h 11. Six gas single
144 m3/h 12. Six gas double • ••
180 m3/h
438 m3/h ••• •
2 x 26m³/h
2 x 144 m3/h ••• •
2 x 180 m3/h
2 x 438 m3/h ••• ••
Y/S GS N S/D ••• ••
N: Number of gases ••• •••
S: Single
D: Double ••• •••
• Sensors: can be analog 4-20mA or digital On/Off
• Alarm panels: can be set or separate
• Emergency inlet point: can be NIST type-N or gas specific type-S (according to table 3.3)
• The 2nd Reducer Panels can be either type-E with external manometers - emergency inlet point (for easy ac-
cess) or Type-S with internal placement of manometers - Emergency Inlet Point visable through plexiglass cover.
Flow rate with nitrogen refers to normal pressure and temperature conditions.
For the other gases multiply the values for nitrogen by the following coefficients:
AIR = 0.98
OXYGEN = 0.93
NITROUS OXIDE = 0.79
CARBON DIOXIDE = 0.79
2nd stage Reducer Panel of 3 gases O2, Air, Vac (double reducers)
2×25m³/h, Type-E
G. Samaras S.A. MEDICAL GAS SYSTEMS 55
Second stage pressure regulator units with alarm panel
EARTH 3x2,50mm EARTH 3x2,50mm EARTH 3 3x2,50mm
1x 4mm 230V, 50/60Hz 1x 4mm 230V, 50/60Hz 1x 4mm 230V, 50/60Hz
0653 G.S . G.S . G.S . G.S . 0653 G.S . G.S . G.S . G.S . G.S . 0653 G.S . G.S . 0653 G.S . G.S . G.S . G.S . G.S .
O2, N2O, Air, C O2 O O O O2, N2O, Air, C O2 O O O O O2, N2O, Air, C O2 O O2, N2O, Air, C O2 O O OO
L PR G S L OT 3511 L OT L OT L PR G S L OT 3511 L OT L PR G S L OT 3511 L OT L PR G S L OT 3511 L OT
P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar
4 6 4 6 400 300 4 6 4 6
2 8 2 8 500 200 2 8 2 8
0 10 0 10 600 0 10 0 10
100
700
760 mmHg
OFF P 1=8 bar - P 2=4.5bar OFF P 1=8 bar - P 2=4.5bar OFF P 1=8 bar - P 2=4.5bar OFF P 1=8 bar - P 2=4.5bar
A IR
ON ON ON ON VAC ON ON ON ON
OXY GE N OXY GE N OXY GE N
OFF OFF OFF OFF
650 450
450SYSTEM GAS O2 Air Vac N2O Air800 CO2 SYSTEM GAS O2 Air Vac N2O Air800 CO2 SYSTEM GAS O2 Air Vac N2O Air800 CO2
ACT Normal ACT Normal ACT Normal
700LINK LINK LINK
450SILENCEMENUTEST SILENCE MENU TEST SILENCE MENU TEST
HP HP HP
LP LP LP
+30 2310 463388 http//www.gsamaras.gr [email protected] MGSAP L6 +30 2310 463388 http//www.gsamaras.gr [email protected] MGSAP L6 +30 2310 463388 http//www.gsamaras.gr [email protected] MGSAP L6
450 450 550
Y/S GS 1D/L6 Y/S GS 2D/L6 Y/S GS 2D/L6
EARTH 3x2,50mm
1x 4mm 230V, 50/60Hz
EARTH 3x2,50mm
1x 4mm 230V, 50/60Hz
0653 G.S . G.S . G.S .
O2, N2O, Air, C O2 O O
L PR G S L OT 3511 G.S .
A
P 1=8bar P 2=4,5bar
OFF P 1=8 bar - P 2=4.5bar 4 6
2 8
0 10
ON ON OFF
NIT R O US O XIDE
400 300 400 300
500 200 500 200
600 600
100 100
700 700
760 mmHg 760 mmHg
VAC VAC
G.S . 0653 G.S . 0653 G.S . 0653 G.S . 0653 G.S . G.S .
O O2, N2O, Air, C O2 O2, N2O, Air, C O2 O2, N2O, Air, C O2 O2, N2O, Air, C O2 O
L OT L PR G S L OT 3511 L PR G S L OT 3511 L PR G S L OT 3511 L PR G S L OT 3511
P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar
OFF P 1=8 bar - P 2=4.5bar 4 6 OFF P 1=8 bar - P 2=4.5bar 4 6 4 6 4 6
2 8 2 8 2 8 2 8
0 10 0 10 0 10 0 10
OFF P 1=8 bar - P 2=4.5bar OFF P 1=8 bar - P 2=4.5bar
A IR
ON ON ON ON ON ON ON ON
OXY GE N OXY GE N OXY GE N
OFF OFF OFF OFF
SYSTEM GAS O2 Air Vac N2O Air800 CO2 SYSTEM GAS O2 Air Vac N2O Air800 CO2
ACT Normal ACT Normal
LINK LINK
SILENCE MENU TEST SILENCE MENU TEST
HP HP
LP LP
+30 2310 463388 http//www.gsamaras.gr [email protected] MGSAP L6 +30 2310 463388 http//www.gsamaras.gr [email protected] MGSAP L6
580 600
Y/S GS 3D/L6 Y/S GS 4D/L6
EARTH 3x2,50mm EARTH 3x2,50mm
1x 4mm 230V, 50/60Hz 1x 4mm 230V, 50/60Hz
400 300 400 300
500 200 500 200
600 600
100 100
700 700
760 mmHg 760 mmHg
VAC VAC
0653 G.S . 0653 G.S . 0653 G.S . 0653 G.S .
O2, N2O, Air, C O2 O2, N2O, Air, C O2 O2, N2O, Air, C O2 A ir800
L PR G S L OT 3511 L PR G S L OT 3511 L PR G S L OT 3511 L PR G S 2 LOT 3511
P 1=10ba r P 2=8bar
P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar
OFF P 1=8 bar - P 2=4.5bar 4 6 OFF P 1=8 bar - P 2=4.5bar 4 6 OFF P 1=8 bar - P 2=4.5bar 4 6 OFF P 1=10 ar - P 2=8bar 10
2 8 2 8 2 8 5
0 10 0 10 0 10 15
0 16
ON ON OFF ON ON OFF ON ON OFF ON ON OFF
OXY GE N NIT R OUS O XIDE NIT R OUS O XIDE A IR 800
950
950
0653 G.S . 0653 G.S . 0653 G.S . 0653 G.S .
O2, N2O, Air, C O2 A ir800 O2, N2O, Air, C O2 O2, N2O, Air, C O2
L PR G S L OT 3511 L PR G S 2 LOT 3511 L PR G S L OT 3511 L PR G S L OT 3511
P 1=10ba r P 2=8bar
P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar
4 6 OFF P 1=8 bar - P 2=4.5bar OFF P 1=10 ar - P 2=8bar 10 OFF P 1=8 bar - P 2=4.5bar 4 6 OFF P 1=8 bar - P 2=4.5bar 4 6
2 8 A IR 5 2 8 A IR 2 8
0 10 15 0 10 0 10
0 16
ON ON ON ON ON ON ON ON
A IR 800 OXY GE N
OFF OFF OFF OFF
SYSTEM GAS O2 Air Vac N2O Air800 CO2 SYSTEM GAS O2 Air Vac N2O Air800 CO2
ACT Normal ACT Normal
LINK LINK
SILENCE MENU TEST SILENCE MENU TEST
HP HP
LP LP
+30 2310 463388 http//www.gsamaras.gr [email protected] MGSAP L6 +30 2310 463388 http//www.gsamaras.gr [email protected] MGSAP L6
650 650
Y/S GS 5D/L6 Y/S GS 5D/L6
Y
56 visit us on www.gsamaras.gr
Second stage pressure regulator units without alarm panel PRODUCT PORTFOLIO
Control and Reducer Panel
1ExAR4TmHm² LiYCY 6x 0,75mm²
600 VAC
· GND VAC
· O2 H.P. DH1
1ExAR4TmHm²LiYCY 4x 0,75mm ² · O2 L.P. DL1 L 3511
· Air H.P. DH2 P P 2=4,5
· Air L.P. DL2
1ExAR4TmHm²LiYCY 3x 0,75mm² · Vac L.P. DL3 400 300
O2 O2 · EARTH 500 200
600
VAC 100
700
760 mmHg
O2 O2 VAC
DH1
DL1
· GND O2 O2 AIR AIR DL4 D
· O2 H.P. · ·
· O2 L.P.
· EARTH
0653 G.S . 0 G.S . 0 0653 G.S .
O2, N2O, Air, C O2 O O2, N2O, Air, C O2
L 3511 L 3511 L PR G S L OT 3511
L PR G S L OT 3511 P P 2=4,5bar P P 2=4,5bar
P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar
400 4 6 400 300 0 G.S . 0653 G.S . G.S . 0653 G.S .
2 8 500 200 O O2, N2O, Air, C O2 O O2, N2O, Air, C O2
L OT 3511
0 10 600 P P 2=4,5bar L PR G S L OT 3511 L 3511 L PR G S L OT 3511
P P 2=4,5
4 6 100 P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar L 3511
2 8 P P 2=4,5
OFF P 1=8 bar - P 2=4.5bar 700
0 10 760 mmHg
350
OFF P 1=8 bar - P 2=4.5bar ON ON OFF VAC
OXYGEN
ON ON OFF 4 6 4 6
OXYGEN 2 8 2 8
OFF P 1=8 bar - P 2=4.5bar 0 10 OFF P 1=8 bar - P 2=4.5bar 0 10
A IR
ON ON ON ON
OXYGEN
OFF OFF
· GND DH1
· O2 H.P. DL1
· O2 L.P. DL3
· Vac L.P.
· EARTH
350 450 550
Y/S GS 1D Y/S GS 2D Y/S GS 2D
LiYCY 10x 0,50mm ² 1ExAR4TmHm² LiYCY 10x 0,50mm² 1ExAR4TmHm²
· DL1 O2 AIR · DL3 VAC N2O AIR800 VAC · DL1 O2 AIR · DL3 VAC N2O AIR800 VAC
VAC VAC
· EARTH · EARTH
· GND· DH1 · DH2 · DH4 · DH5 · GND· DH1 · DH2 · DH4 · DH5
· DL2 · DL4 · DL5 · DL2 · DL4 · DL5
400 300 400 300
500 200 500 200
1ExAR4TmHm² LiYCY 8x 0,75mm² 600 600
100 100
700 700
760 mmHg 760 mmHg
VAC VAC
N2O N2O VAC O2 O2 N2O N2O N2O N2O AIR 8 AIR 8
0653 G.S . 0653 G.S . 0653 G.S . 0653 G.S .
O2, N2O, Air, C O2 O2, N2O, Air, C O2 O2, N2O, Air, C O2 A ir800
L PR G S L OT 3511 L PR G S L OT 3511 L PR G S L OT 3511
L P R G S 2 L OT 3511
P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar
P 1=10bar P 2=8bar
0653 G.S .
O2, N2O, Air, C O2 900 4 6 4 6 900 4 6
L PR G S L OT 3511 2 8 2 8 2 8
P 1=8bar P 2=4,5bar
0 10 0 10 0 10
OFF P 1=8 bar - P 2=4.5bar OFF P 1=8 bar - P 2=4.5bar OFF P 1=8 bar - P 2=4.5bar OFF P 1=10 ar - P 2=8bar 10
5
4 6 ON ON ON ON ON ON ON ON
2 8 OXYGEN NIT R OUS OXIDE NIT R OUS OXIDE A IR 800 15
0 16
0 10
OFF OFF OFF OFF
OFF P 1=8 bar - P 2=4.5bar
ON ON OFF
NIT R OUS OXIDE
400 300
500 200
600
100
700
760 mmHg
600 O2 · GND O2 AIR AIR A IR C .AIR AIR 800 O2 O2 AIR AIR
· O2 H.P. DH1
· O2 L.P. DL1
· Air H.P. DH2
· Air L.P. DL2
· Vac L.P. DL3
· N2O H.P. DH4
· N2O L.P. DL4
· EARTH
0653 G.S . 0653 G.S . 0653 G.S . 0653 G.S . 0653 G.S . 0653 G.S .
O2, N2O, Air, C O2 O2, N2O, Air, C O2 O2, N2O, Air, C O2 A ir800 O2, N2O, Air, C O2 O2, N2O, Air, C O2
L PR G S L OT 3511 L PR G S L OT 3511
L PR G S L OT 3511 L P R G S 2 LOT 3511 L PR G S L OT 3511 L PR G S L OT 3511
P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar P 1=10bar P 2=8bar
P 1=8bar P 2=4,5bar P 1=8bar P 2=4,5bar P 1=8bar P2=4,5bar
4 6 4 6 4 6 OFF P 1=8 bar - P 2=4.5bar 10 OFF P 1=10 ar - P 2=8bar 10 OFF P 1=8 bar - P 2=4.5bar 4 6 OFF P 1=8 bar - P 2=4.5bar 4 6
2 8 2 8 2 8 A IR 5 5 2 8 A IR 2 8
0 10 0 10 0 10 15 15 0 10 0 10
0 16 0 16
ON ON ON ON ON ON ON ON
P 1=8 bar - P 2=4.5bar P 1=8 bar - P 2=4.5bar A IR 800 OXYGEN
OFF OFF
A IR OFF OFF OFF OFF
ON ON ON ON
OXYGEN
OFF OFF
550 580 650
Y/S GS 4D Y/S GS 5D Y/S GS 5D
G. Samaras S.A. MEDICAL GAS SYSTEMS 57
PRODUCT PORTFOLIO
Bed Head Units
Special Infant ICU
All units are tailor-made solutions, according to each installation. The individual channels described above are closed with covers
The units can be equipped with any desirable type of electrical from aluminum profile that can be easily removed. The typical
and medical gas outlets. BHU length is about 1,80m. for normal care, if more than one bed
The available BHU models are: ELISA, KASSANDRA, THEODORO, is required then the length is multiplied by 1,80m - depending
THEODORO-R, PANORAMA, KALLIPOLIS, ALEXANDRA, ALEXAN- on the number of beds and 2,50m for special care.
DRA-R, PANDORA. Typical placement of BHU is wall-mounted and horizontal. In
The units can be either wall-mounted or suspended. The units can some cases, the same BHU profile can be placed vertical or sus-
be produced in differnt leghts up to 6 meters and one unit can pended. It is used in specific rooms where wall mounted BHU in-
serve multiple beds. The bed head units are manufactured and stallation is not possible (in cases where there are windows,
tested in accordance with standards EN ISO 7396-1, EN ISO 14971, columns or other obstacles). The suspended supply system offers
EN ISO 11197, EN793, EN 60101-1, EN 60598-1, EN 60598-2-25 a number of decisive advantages for optimum patient treatment
(lighting) and EN 12464-1. in the field of intensive care.
The BHU internally is separated in five (5) independent channels for:
• Indirect lighting, night lighting and the bodies of lightings,
ballast etc
• Lighting for reading, for examination and electric elements
(switches, sockets etc.)
• Two independent channels are used for wiring, low and high
voltage.
• Copper pipes and medical gases outlets
G. Samaras S.A. MEDICAL GAS SYSTEMS 71
72 visit us on www.gsamaras.gr 55.2 125 111.9 185 3.6.1 Single Bed Head Units
79.6 Kassandra Normal care Elisa
Emergercy
Normal care 138.55 ICU 175.1
Emergercy CCU
• • • 63 – 2 – 2 ICU •• NICU
CCU Recovery
NICUDepartments/wards Departments/wardsOPT
Recovery Wall mounted
OPTInstallation options • • • 63 – 5 1 2 Installation optionshorizontally
Wall mounted Wall mounted
Technical datahorizontally Technical datavertically
Wall mounted Ceiling suspended
vertically horizontally
Ceiling suspended Ceiling suspended
horizontally vertically
Ceiling suspended Mounted on
vertically vertical brackets
Mounted on Embedded on
vertical brackets vertical brackets
Embedded on Maximum length
vertical brackets in meters
Maximum length No of separated
in meters channels
No of separated Rail on BHU
channels Maximum medical
Rail on BHU gas pipes
Maximum medical AGSS pipe
gas pipes Lighting
AGSS pipe
Lighting
279.63 Pandora EX-R 205.6 Pandora
Normal care 84.6 Normal care 84.6
Emergercy Emergercy
•• ICU • ICU
CCU CCU
Departments/wardsNICU Departments/wardsNICU PRODUCT PORTFOLIO
Recovery Recovery
•• • OPTInstallation options •• OPTInstallation options Bed Head Units
Wall mounted Wall mounted
G. Samaras S.A. MEDICAL GAS SYSTEMS 63 2 3 1 2 Technical datahorizontally • 63 – 2 – 2 Technical datahorizontally
Wall mounted Wall mounted
vertically vertically
Ceiling suspended Ceiling suspended
horizontally horizontally
Ceiling suspended Ceiling suspended
vertically vertically
Mounted on Mounted on
vertical brackets vertical brackets
Embedded on Embedded on
vertical brackets vertical brackets
Maximum length Maximum length
in meters in meters
No of separated No of separated
channels channels
Rail on BHU Rail on BHU
Maximum medical Maximum medical
gas pipes gas pipes
AGSS pipe AGSS pipe
Lighting Lighting
73
74 visit us on www.gsamaras.gr 153.34
209.3 167.9
•• Normal care 84.6 Alexandra-R-EX •• Normal care Alexandra-R •• Normal care Alexandra
Emergercy Emergercy 84.6 Emergercy 84.6
ICU Departments/wards ICU Departments/wards ICU Departments/wards
•• CCU Installation options • 62 1 2 – 1 CCU Installation options •• CCU Installation options
62 1 3 – 1 NICU Technical data NICU Technical data 62 – 2 – 1 NICU Technical data
Recovery Recovery Recovery
OPT OPT OPT
Wall mounted Wall mounted Wall mounted
horizontally horizontally horizontally
Wall mounted Wall mounted Wall mounted
vertically vertically vertically
Ceiling suspended Ceiling suspended Ceiling suspended
horizontally horizontally horizontally
Ceiling suspended Ceiling suspended Ceiling suspended
vertically vertically vertically
Mounted on Mounted on Mounted on
vertical brackets vertical brackets vertical brackets
Embedded on Embedded on Embedded on
vertical brackets vertical brackets vertical brackets
Maximum length Maximum length Maximum length
in meters in meters in meters
No of separated No of separated No of separated
channels channels channels
Rail on BHU Rail on BHU Rail on BHU
Maximum medical Maximum medical Maximum medical
gas pipes gas pipes gas pipes
AGSS pipe AGSS pipe AGSS pipe
Lighting Lighting Lighting
213.21 116.70 116.66
94 99 84.82 PRODUCT PORTFOLIO
Normal care 129.82 Bed Head Units
Emergercy
ICUDepartments/wards Theodoro-R 25Departments/wards 84.6 Kallipolis” and “Kallipolis-L
CCU
•••• NICU •••• Normal care
Recovery Emergercy
•• Installation optionsOPT •• ICU Installation options
Wall mounted CCU
G. Samaras S.A. MEDICAL GAS SYSTEMS • • 62 1 4 1 – Technical datahorizontally • • 61 1 4 1 – NICU Technical data
Wall mounted Recovery
vertically OPT
Ceiling suspended Wall mounted
horizontally horizontally
Ceiling suspended Wall mounted
vertically vertically
Mounted on Ceiling suspended
vertical brackets horizontally
Embedded on Ceiling suspended
vertical brackets vertically
Maximum length Mounted on
in meters vertical brackets
No of separated Embedded on
channels vertical brackets
Rail on BHU Maximum length
Maximum medical in meters
gas pipes No of separated
AGSS pipe channels
Lighting Rail on BHU
Maximum medical
gas pipes
AGSS pipe
Lighting
75
76 visit us on www.gsamaras.gr 290 78 194 95 Panorama-L
•• Normal care Alexandra-DL Normal care
Emergercy Emergercy
ICUDepartments/wards •••• ICU Departments/wards
CCU CCU
•• • Installation optionsNICU •• • NICU Installation options
Recovery Recovery
64 1 4 1 2 OPTTechnical data under 62 1 2 – – OPT Technical data NEW
Wall mounted development Wall mounted product
horizontally horizontally
Wall mounted Wall mounted
vertically vertically
Ceiling suspended Ceiling suspended
horizontally horizontally
Ceiling suspended Ceiling suspended
vertically vertically
Mounted on Mounted on
vertical brackets vertical brackets
Embedded on Embedded on
vertical brackets vertical brackets
Maximum length Maximum length
in meters in meters
No of separated No of separated
channels channels
Rail on BHU Rail on BHU
Maximum medical Maximum medical
gas pipes gas pipes
AGSS pipe AGSS pipe
Lighting Lighting
PRODUCT PORTFOLIO
Bed Head Units
G. Samaras S.A. MEDICAL GAS SYSTEMS 77
78 visit us on www.gsamaras.gr 322.3 233.4 3.6.2 Combinations of Bed Head Units
167.9 154.4 116.7 116.7 Except from the single Bed Head Units, G.SAMARAS SA also provides a variety of combinations which are designed to cover special
needs that a single profile cannot fulfill (eg 2 rails on a BHU).
129.8 129.8
84.8 84.8
25 25 25
•••••• Normal care Departments/wards Alexandra + Alexandra R with one rail add-on ••••• Normal care Departments/wards Kallipolis + Kallipolis with two rails add-on
Emergercy
• •• Emergercy Installation options •• • ICU Installation options
CCU
ICU • NICU
Recovery
64 1 4 1 2 CCU Technical data 62 2 4 1 – OPT Technical data
Wall mounted
NICU horizontally
Wall mounted
Recovery vertically
Ceiling suspended
OPT horizontally
Wall mounted Ceiling suspended
horizontally vertically
Wall mounted Mounted on
vertically vertical brackets
Ceiling suspended Embedded on
horizontally vertical brackets
Ceiling suspended Maximum length
vertically in meters
Mounted on No of separated
vertical brackets channels
Embedded on Rail on BHU
vertical brackets Maximum medical
Maximum length gas pipes
in meters AGSS pipe
No of separated Lighting
channels
Rail on BHU
Maximum medical
gas pipes
AGSS pipe
Lighting
439 271.1
116.7
167.9 154.4 154.4 116.7
129.8 129.8
84.8 84.8
25 25
•••••• Normal care Departments/wards Alexandra + Kallipolis + Alexandra R with one rail add-on ••••• Normal care Departments/wards Alexandra + Kallipolis with one rail add-on
• Emergercy •• • Emergercy PRODUCT PORTFOLIO
G. Samaras S.A. MEDICAL GAS SYSTEMS • 65 1 5 1 2 ICU Installation options ICU Installation options Bed Head Units
CCU Technical data 63 1 4 1 1 CCU Technical data
NICU NICU
Recovery Recovery
OPT OPT
Wall mounted Wall mounted
horizontally horizontally
Wall mounted Wall mounted
vertically vertically
Ceiling suspended Ceiling suspended
horizontally horizontally
Ceiling suspended Ceiling suspended
vertically vertically
Mounted on Mounted on
vertical brackets vertical brackets
Embedded on Embedded on
vertical brackets vertical brackets
Maximum length Maximum length
in meters in meters
No of separated No of separated
channels channels
Rail on BHU Rail on BHU
Maximum medical Maximum medical
gas pipes gas pipes
AGSS pipe AGSS pipe
Lighting Lighting
79
VERTICAL BED HEAD UNITS 3.6.3 Power Column / Bed-side Locator
A. Power column. The power column may consist of a single or double profile. It includes
all the necessary gas and electrical outlets, as well as data and equipotential sockets. It
may also bare a rail for hanging various equipment. In case it is necessary it can include
an embedded lighting and medical gas alarm panel.
Its main advantage is that it provides a 360° access to the patient. The power column
gives to the care givers the ability to move around the bed without any obstacles and it
also provides direct access to the critical area where the head of the patient is found.
B. Bed side locator. The bed side locator is made of two different materials. A frame made
of aluminum which includes all the necessary electrical and data outlets and an internal
part made of HPL or aluminum.
It optimizes the hospital’s investment because it combines practicality and durability. Its
internal part is a hard and durable material that offers great protection to the walls from
bariatric beds and still its frame part can provide the essential to the nursing staff and
the patient electrical and data supply, by carefully placed outlets, which are protected
from damaging contacts with the bed, by having a specially designed inclined position.
It comes in various sizes in order to cover the needs of any type of bed the hospital uses
and it is very easy to install, use and clean.
C. Light. For a complete solution, bed side locators and power columns can be assisted
with a light placed on the wall behind the patient’s bed. The light can come in various
sizes and powers.
TRANSFER 150
CONNECT 125
FAULT TEST OK
POWER
SILENT
1000
Ox ygen Oxy gen C Light
0653 DIN 13260-2 0653 DIN 13260-2
Air Air
0653 DIN 13260-2 0653 DIN 13260-2
V acuum V acuum A Power column
0653 DIN 13260-2 0653 DIN 13260-2
1500
B Bed side locator
500
Power column 414 1000 150
80 visit us on www.gsamaras.gr
PRODUCT PORTFOLIO
Bed Head Units
3.6.4 Kids Bed Head Units
Our kids series of bed head units is specially designed to cre-
ate a more friendly and comfortable atmosphere to our little
friends. At the same time they cover all usual equipment of
a typical bed head unit such as medical gas outlets, electri-
cal sockets, lighting, data etc.
G.SAMARAS SA offers a various models which can cover dif-
ferent needs in horizontal or vertical layout. They are being
manufactured by extruded aluminum profiles of a great se-
lection of colors whereas the front cover with the kids theme
has the following options:
1. Direct printing on the bed head unit
2. Sticker of special design
In both options the materials that are being used are suitable for indoor use, resistant in all typical hospital detergents and disinfec-
tants and guarantee the long life of the graphics.
All bed head units are being designed and produced according to the specifications of each project there are lots of graphics available
for your choice!
G. Samaras S.A. MEDICAL GAS SYSTEMS 81
3.6.5 Ceiling Suspended Bed Head Units - ATHOS series
In cases that a bed head unit cannot be installed on the wall, it can be alternatively installed suspended from the ceiling through a
special aluminum “BR“profile or hung on it (floor to ceiling option). All medical gases and electrical connections are conducted through
the “BR“profile. Optionally they can be used in ICU instead of using ceiling pendant arms.
A. Profiles
Panorama with light type of trolleys and BR profile
60
(supports trolleys ≤80kg)
230
200 Departments/wards Technical data per profile
145
Normal care
Emergercy
ICU
CCU
NICU
Recovery
OPT
Maximum length
in meters
No of separated
channels
Rail on BHU
Maximum medical
gas pipes
AGSS pipe
Lighting
Light trolleys
Heavy trolleys
90 •••• 63 2 3 2 2–
Double Panorama L with light type of trolleys and BR
profile (supports trolleys ≤80kg)
Departments/wards Technical data per profile
Normal care
Emergercy
ICU
CCU
NICU
Recovery
OPT
Maximum length
in meters
No of separated
channels
Rail on BHU
Maximum medical
gas pipes
AGSS pipe
Lighting
Light trolleys
Heavy trolleys
•••• 62 1 2 – – –2
100 Double Panorama H with light or heavy type of
414 trolleys and BR profile (supports trolleys 80-150kg)
45 45
150
Departments/wards Technical data per profile
Normal care
Emergercy
ICU
CCU
NICU
Recovery
OPT
Maximum length
in meters
No of separated
channels
Rail on BHU
Maximum medical
gas pipes
AGSS pipe
Lighting
Light trolleys
Heavy trolleys
•••• 63 1 2 – 1 –2
82 visit us on www.gsamaras.gr
PRODUCT PORTFOLIO
Bed Head Units
3.6.7 Aluminum Structural Framing - BR Profile 100
100
BR profile is heavy profile made of thick (up to 7cm) aluminum which comes either elec-
trostatically painted or anodized. Profile “BR” for suspended BHU
This is a smart solution that can be used in various applications. It is mainly used in cases
where the BHU cannot be wall mounted and has to be suspended from the ceiling, but
it can also serve as support for fixing BHUs on the side of this profile. By using a number
of connectors it can virtually support any application or load.
One of the main advantages of this profile is that it combines practicality and aesthetics.
Any structure can be quickly and easily assembled and disassembled even without hav-
ing any special tools or skills. Its channels can also be used for hanging movable equip-
ment. Last but not least, every single profile is reusable and can be adjusted in order to
form a new structure according to the needs of the end user.
BR profile as BHU support
G. Samaras S.A. MEDICAL GAS SYSTEMS 89
3.6.8 Components of Bed Head Units
Medical gas outlets
The bed head unit will be equipped with the medical gases terminal units and copper
pipes connecting the BHU to the medical gas network all in separate channels.
The medical gases terminal units are double block type, manufactured according to EN
737-1 standard and the fitting is according to EN 737- 6 standard.
Each medical gases terminal unit is accompanied by indelible polycarbonate plate (can’t
be removed) according to EN 60601-1 regulations labeled with the name of medical gas,
the color and the chemical symbol of corresponding gas.
The copper pipes supplying the medical gases are placed inside the unit, according to EN
13348 standard, DIN 1786 and DIN 17671, type SF Cu / F 37, and are free of arsenic, free
of oil, protected to their ends, characterized according to the regulations for use in med-
ical gas installations using silver welding of 40% content in silver, in atmosphere of neu-
tral gas (N2). For further details, check also p. 40.
90 visit us on www.gsamaras.gr
Electrical sockets / Data sockets PRODUCT PORTFOLIO
Bed Head Units
The electrical sockets are being installed
on the Bed Head Units and on the Ceiling
Pendant Arms and play a very important
role for the medical staff and also for the
patients. Their importance is crucial be-
cause the medical team must always have
an access to a constant supply of electricity
to connect various monitors, tools and ma-
chines. The white sockets are used for nor-
mal electrical supply, the green for supply
from generator and the red for supply from
UPS. Various types of electrical sockets
could be installed according to different
norms which are posed in each country.
Moreover, special needs (with led indica-
tor, with cap, etc ) may be covered.
The Equipotential sockets are being placed
close to the electrical sockets to protect
the users of various machines and tools
from static.
The Data sockets provide to the users the
ability to have access through them to a
network cabling for data transfer. They are
suitable for connection with telephones,
monitors, etc.
Electrical socket installed on BHU with frame (colored or not), and without frame. British standard switched Equipotential sockets EQ DIN
Lighting system G. Samaras S.A. MEDICAL GAS SYSTEMS 91
Each B.H.U. usually includes the following lighting components:
• General lighting (indirect) with one or more fluorescent lamp of 36 or 58W
/ 220V operated from a switch placed at room’s entrance.
• Reading lighting (direct) with one or more fluorescent lamp of 1x18W / 220V
or LED operated from a nurse call hand set.
• Night Lighting 5W / 220V with LED operated from a switch on the BHU or
from a central position in the nurses station.
• Examination light (direct) with one or more fluorescent lamps control on
the BHU
All ballasts are electronic, made by Osram. All fluorescent lamps are made
by Osram too.
All light equipment is installed and protected by a transparent polycarbon-
ate accompanied with aluminum reflectors.
91 visit us on www.gsamaras.gr
Typical BHU Lights Color Temperature RL: Reading light, GL: General light, NL: Night light
827, 2700°K 830, 3000°K 840, 4000°K
(INTERNA) (Warm white) (Cool white)
High quality Electronic Control Gears Lamp Code Power 1350 lm Luminous flux 1350 lm Voltage Energy Average Length
for T5/T8/Dulux lamps Type Technology L18W 18W 1350 lm 1350 lm 1350 lm 230V, class lifetime L(mm)
RL Fluorescent (T8) HE14W 14W 2000 lm 1350 lm 2000 lm 50/60Hz 20.000 hrs
Powered by OSRAM HO24W 24W 1200 lm 2000 lm 1200 lm 230V, A 24.000 hrs 590
Fluorescent (T5) DL18W 18W 1800 lm 1200 lm 1800 lm 50/60Hz A 24.000 hrs 549
• Very high efficiency DL24W 24W 2900 lm 1800 lm 2900 lm A 20.000 hrs 549
• Lamp start with optimum filament pre- Compact DL36W 36W 3350 lm 2900 lm 3350 lm 230V, A 20.000 hrs 217
Fluorescent L36W 36W 5200 lm 3350 lm 5200 lm 50/60Hz A 20.000 hrs 317
heating L58W 58W 2100 lm 5200 lm 2100 lm A 20.000 hrs 411
• Automatic restart after lamp replacement (2G11) HE21W 21W 2900 lm 2100 lm 2900 lm 230V, A 20.000 hrs 1200
• Automatic shutdown of defective lamps GL Fluorescent HE28W 28W 3650 lm 2900 lm 3650 lm 50/60Hz A 24.000 hrs 1500
HE35W 35W 3500 lm 3650 lm 3500 lm A 24.000 hrs 849
and at end of life (EoL) (T8) HO39W 39W 4900 lm 3500 lm 4900 lm 230V, A 24.000 hrs 1149
• Dimming range: 1…100 % luminous flux Fluorescent HO49W 49W 5000 lm 4900 lm 5000 lm 50/60Hz A 24.000 hrs 1449
HO54W 54W 7000 lm 5000 lm 7000 lm A 24.000 hrs 849
(optional) (T5) HO80W 80W 3500 lm 7000 lm 3500 lm A 24.000 hrs 1449
• Life time: >100,000 h (for T = 65°C at Tc) DL40W 40W 4800 lm 3500 lm 4800 lm A 24.000 hrs 1149
RL/GL Compact DL55W 55W 6500 lm 4800 lm 6500 lm A 20.000 hrs 1449
Fluorescent DL80W 80W 6500 lm A 20.000 hrs 533
(2G11) A 20.000 hrs 533
A 565
Five years guarantee Approval marks:
Lighting performance according to EN 12464
LED lighting LED
The BHU can be equiped with LED lamp, Typical BHU LED Lights Color Temperature
with or without including dimming capa-
bility for reading lighting and night light. 830, 3000°K 840, 4000°K 855, 6500°K
(Warm white) (Cool white) (Cool daylight)
The LED solution is enviromental friendly
and economical solution as well.
RL: Reading light, GL: General light, NL: Night light
II(cd/klm) Lamp Code Power Luminous flux* Voltage Energy Average Dimensions
Type Technology 750 lm class lifetime L×W(mm)
11000 lm 230V, 30.000 hrs
90° RL LED ST8V-590 8.9W 700 lm 1700 lm 800 lm 50/60Hz A 50.000 hrs 590ר27
LED ST8A-590 8.7W 1000 lm 2100 lm 1100 lm A+ 30.000 hrs 590ר27
85 1550 lm 2500 lm 1700 lm 19.3 V A 40.000 hrs 1200ר27
60° LED ST8-HV2-1200 20 W 2000 lm 2000 lm 2100 lm 38.4 V A+ 50.000 hrs 1200ר27
2300 lm 2400 lm 2300 lm 35.2 V A+ 30.000 hrs 1200ר27
170 (Tubular ST8-HB2-1200 18 W 1850 lm 3400 lm 2100 lm 70.3 V A 40.000 hrs 1500ר27
2150 lm 760 lm 2400 lm 35 V A+ 50.000 hrs 1500ר27
255 GL -G13) ST8-HA2-1200 22.5 W 3100 lm 1530 lm 3400 lm 35 V A+ 50.000 hrs 1500ר27
770 lm 1400 lm 36 V A++ 50.000 hrs 280×24
340 ST8-HV2-1500 23 W 1480 lm 2810 lm 1040 lm 66 V A++ 50.000 hrs 560×24
30° 1360 lm 1040 lm 2080 lm 133 V A++ 50.000 hrs 280×24
ST8-HB2-1500 22 W 2790 lm 2080 lm 1260 lm A++ 50.000 hrs 560×24
Light Distribution Curve 990 lm 1260 lm A++ 50.000 hrs 280×32.6
1985 lm 2230 lm A++ 560×32.6
ST8-HA2-1500 30.5 W 1200 lm 4470 lm A++ 560×32.6
A++ 560×20
LED LINEAR LLE-G3-24-280-650 5.2 W A++ 1120×20
@300mA LLE-G3-24-560-1300 10.5 W
RL/GL lm@tp=65°C LLE-G3-24-280-1250 9.6 W
@200mA LLE-G3-24-560-2400 19.3 W
lm@tp=55°C
PLVZ2-LIN-1100-280 7.1 W
@400mA PLVZ2-LIN-2200-560 14.1 W
lm@tp=55°C
LED LINEAR PLVZ2-LIN-1300-560 9.1 W
@250mA PLFZ1-LIN-2200-560 16.7 W
lm@tp=55°C
PLFZ1-LIN-4400-560 33.4 W
Typical BHU LED Lights Color Temperature
855, 5500°K 860, 6000°K RL: Reading light, GL: General light, NL: Night light
(Cool white) (Cool white)
Lamp Energy Average Dimensions
class lifetime L×W(mm)
Type Technology Code Power Luminous flux* Voltage
T26/0.8 0.8 W 65 lm 502A/3A+60+0V+H, z A++ 15.000 hrs 63×26
ΝL LED T26/1.4 1.4 W 100 lm A++ 25.000 hrs 63×26
(E14) E14/3 3W A+ 50.000 hrs 63×26
360 lm
I.C.U.
* Luminous flux @ tp=65ºC and If=350mA
92 visit us on www.gsamaras.gr
PRODUCT PORTFOLIO
Bed Head Units
Proposed BHU configurations
BHU room Equipment per bed Lighting Nurse call Switching
description operation
BHU desription Electrical Data RJ45 Direct Night In- Direct Night Indirect
Medical gas outlets* sockets ΕQ cat6 direct Operation
ELISA 18 W 0.7W 36W
KASSANDRA
THEODORO
PANORAMA
PANORAMA-Η
PANDORA
PANDORA-R-EX
ALEXANDRA
-R / -R-EX
KALLIPOLI
Generator
UPS
Bed Length Rail Rail Normal 36W Nurse 0.7W 36W
Α/Α Room (pc.) (m) on on the Extra equipment Ο2 Αir Vac N2O AGSS supply EQ Data Voice or LED or 18W or call 18W LED or
BHU wall LED** 58 W 58 W 58 W
1 Nursery 1 1,80 • • • • • 11 11 1 1 1 1 1 Yes Yes NC Yes LS
single bed
•• •
2 Nursery 2 3,60 • • • • • 11 11 111 1 Yes Yes NC Yes LS
two bed
•• •
3 Day 1 1,80 • • • • • 11 11 1 1 1 1 1 Yes Yes NC Yes LS
Clinic
•• •
4 (AIDS, SAR) 1 1,80 • • • • • 11 11 1 1 1 1 1 Yes Yes Yes LS
•• • Yes LS
5 Artificial kidney 1 1,80 • •• 11 33 1111 1 Yes LS LS
•• • LS Yes LS
6 Delivery 1 1,80 • •• Yes 11 1 22 2111 1
••
7 ICU, CCU, High 1 2,00 • Yes Yes Digital clock - 4 4 4 88 42 11 1
Dependensy •• Horizontal rail for
unit, Isolation
• • trolley /Ø38 tubes
for instruments
8 Neonatal unit 1 2,00 • • • Yes 22 2 44 22
•• •• 22
21
9 Resuscitation 1 2,00 • Yes Yes 22 222 4 4 21
•• •• 21
11
10 Recovery 1 2,00 • • Yes 22 2 44 42 1 1
• ••
11 Preparation 1 1,00 • • Yes 11 111 2 2
• ••
12 Triage 1 1,80 • • Yes 11 1 42
• ••
13 Accident and 1 1,80 • • Yes 11 22
emergency • ••
14 Suspended for 1 2,00 • Yes Horizontal rail for 4 4 4 88 Yes Yes
special rooms (double) trolley /Ø38 tubes
for instruments
NC: Nurse Call through Relay, LS: Local Switch, DS: Door Switch, R: Rail, H: Half, EX: Εχtended NOTES:
1. There are three ways of installation: a) wall mounted, b) suspended from the ceiling (using metallic columns) and c) suspended (using metallic
*The number and the type of the medical gas outlets per bed are ac-
cording to EN ISO 7396-1 & 2, HTM 02-01 columns from ceiling to floor)
**The Bed Head Unit can be equiped with LED lamps for reading light 2.Installation height (from finishing floor)
• Single profile suggestion - Elisa, Pandora, Panorama, Pandora-R-EX profile: 1,60–1,80m lower part of BHU
• Combination profile suggestion - Alexandra-R-EX, Theodoro-R, Kallipolis profile: 1,20–1,40m lower part of BHU
- Kassandra, Alexandra, Alexandra-R profile: 1,70–1,80m lower part of BHU (when used as lighting profile with Theodoro profile)
- Rail wall-mounted 0,90m – BHU mounted on Pandora-R-EX or Theodoro-R or Alexandra-R or Kallipolis or Panorama
3.The suggested profile types are the most common and there is other solutions according to the project
G. Samaras S.A. MEDICAL GAS SYSTEMS 93
94 visit us on www.gsamaras.gr
PRODUCT PORTFOLIO
Ceiling Pendant Arms
3.7 CEILING PENDANT ARMS
The ceiling pendants for special treatment rooms, are placed on the
ceiling of these rooms, such as intensive care units and operating the-
aters, above the patient’s bed or above the surgical table.
The ceiling pendant has been created for grouping all the necessary
electrical, data and medical gases services, required for use in operat-
ing theaters in anesthetic or surgical rooms and intensive care areas.
G. Samaras S.A. MEDICAL GAS SYSTEMS 95
Ceiling Pendants for OPT
G. Samaras S.A. ceiling pendants are manufactured and installed according to the costumer’s specifications to suit a particular location
and purpose. The installed position ensures that the outlets can be placed immediately above the medical equipment or the anesthetic
machine, thereby removing the hazard of trailing hoses and cables.
The ceiling mounted pendant system is manufactured totally of special extruded anodized aluminum profiles or stainless steel and
is electrostatic painted to any desired color. The ceiling mounted pendant systems are produced according to ISO 11197, EN ISO
5359, ISO 7396-1, ISO 7396-2, ISO 9170-1, ISO 9170-2, EN 60601-1 standards and they are labeled CE0653 to guarantee a high level of
safety for patients and personnel.
The available ceiling pendants models are separated in two categories: not electrically driven (circling movement) and electrically
driven (circling movement and movement in the vertical axis).
All ceiling pendant units are consisting of the following main
parts:
• Ceiling support system (tailor made depending of the ac-
tual ceiling height)
• One or two horizontal arms (made form reinforced alu-
minum profiles in deferent lengths)
• Vertical retractable or stable body (movement through
electrical motor in angle or telescopically)
• Technical box (that includes instruments shelves, drawer,
rail)
• Special ⍉38 tubes supports for instrument, monitors and
shelves support
Olympia 06
96 visit us on www.gsamaras.gr
PRODUCT PORTFOLIO
Ceiling Pendant Arms
I. Pendant arms Vergina
The horizontal motion is made manually with
pendant rotation ability of 330°. Two circling
movement is achieved with the help of cylin-
drical bearing cases. The arms revolve on
high quality bearings so that the technical
box can be moved very smoothly and se-
curely to any position. Horizontal rotation in
two or three axis can also be provided.
The rotation cylinder of the arm comes as
standard with pneumatic brake, for the stabi-
lization of pendant during the rotation in the
desirable place, while head cylinder uses ad-
justable mechanical brake. Pneumatic brakes
are optional and after request.
The telescopical vertical movement is electri-
cal by special actuator (Swiss made Mag-
netic) with lifting capacity from 5.000N to
8.000N/360W.
The carrying capacity depends on the config-
uration (from 80Kgr to 350Kgr).
II. Technical box Makedonia
- head of the pendant arm
In the head of the pendant and in separate
compartments, are installed the terminal
units of medical gases with the correspon-
ding manometers, the electric sockets and
EQ, while around the table exists a special
stainless rail of dimensions 25x10 mm, for the
suspension of various medical appliances
and tools.
For all units, tailor made solutions are offered
with all the necessary equipment.
The pendant can include different elements
(in number and type) depending on the de-
mand.
Thessaloniki Olympia 04
G. Samaras S.A. MEDICAL GAS SYSTEMS 97