Functions Making and breaking under load condition Providing safety isolation for terminal distribution system Used in residential building, non-residential building Technical specifications Instruction of type code Rated current (A): 32, 63, 80, 100, 125 Number of poles: 1, 2, 3, 4 Series code B71G 2 032 Features The handle provides a clear indication of the contact position Adequate printing of all data on the front provides longterm identification Based on the technology of MCB series 3SB71, similar design to series 3SB71 Matched with series 3SB71 Switch Disconnectors Series 3SB71G 1 www.sassin.com V 27.1 Super Series / 1-195 Type Standard Rated current In Number of poles Rated voltage Un Rated insulation voltage Ui Rated short-time withstand current Icw Degree of protection Electrical life Mechanical life Mounting position Conductor cross-sections Solid and stranded Finely stranded with end sleeve Terminal tightening torque Ambient temperature Storage temperature Altitude 3SB71G-125 DC IEC 60947-3 63, 80, 100, 125 1P 230 V DC 1000 12 In IP20, with connected conductors 1500 8500 Any 0.75-35 0.75-25 2-2.5 -25 ~ +45, max. 95% humidity -40 ~ +70 Max. 2000 (A) (V) (A) (times) (times) 2 (mm ) 2 (mm ) (N·m) (°C) (°C) (meter) 2P 400 V DC 3P 750 V DC 4P 1000 V DC 3SB71G-125 IEC 60947-3 32, 63, 100, 125 1P, 2P, 3P, 4P 230/400 V AC 500 20 In IP20, with connected conductors 10,000 20,00 Any 0.75-35 0.75-25 2-2.5 -25 ~ +45, max. 95% humidity -40 ~ +75 Max. 2000
Selection and ordering data 1 2 1 3 2 4 1 3 5 2 4 6 Rated current Pack. In (A) Number of poles (P) 1 2 3 4 Type code Order code 12 12 12 12 32 B71G 1032 63 100 125 B71G 1063 B71G 1100 B71G 1125 6 6 6 6 32 B71G 2032 63 100 125 B71G 2063 B71G 2100 B71G 2125 4 4 4 4 32 B71G 3032 63 100 125 B71G 3063 B71G 3100 B71G 3125 3 3 3 32 B71G 4032 63 100 B71G 4063 B71G 4100 125 B71G 4125 3 22899 22900 22901 38876 22902 22903 22904 38877 22905 22906 22907 38878 22908 22909 22910 38879 1 3 5 7 2 4 6 8 Number of poles (P) Rated voltage Un (V) Rated current Pack. In (A) 1 2 3 4 230 400 750 1000 12 12 12 12 6 6 6 6 4 4 4 4 3 3 3 3 63 80 100 125 63 80 100 125 63 80 100 125 63 80 100 125 39195 24361 24365 24383 39196 24362 24366 24384 39197 24363 24367 24385 39198 24364 24382 24386 B71G 163D B71G 180D B71G 1100D B71G 1125D B71G 263D B71G 280D B71G 2100D B71G 2125D B71G 363D B71G 380D B71G 3100D B71G 3125D B71G 463D B71G 480D B71G 4100D B71G 4125D Type code Order code 3SB71G-125 DC 3SB71G-125 Switch Disconnectors Series 3SB71G 1 1-196 / V 27.1 Super Series www.sassin.com 4 2 1 3 Load 2 4 1 3 Load 2 1 1 2 Load 4 3
Outline and installation dimensions unit in mm 45 44 86 35 71 90 18 36 54 72 Switch Disconnectors Series 3SB71G 1 www.sassin.com V 27.1 Super Series / 1-197 3SB71G-125
Frame current: 25, 63 Functions Remote switching and controlling of power circuits Used in building automation, controlling of small pumps, ventilations, heating systems, lighting systems, and so on Instruction of type code Coil code Rated current Series code CH8 25 2 10 Technical specifications 11 Number of poles: 2, 4 Type Standards Number of poles Type of current Frequency (Hz) Rated voltage Un (V) Rated current In in AC-7a / AC1 (A) Rated current In in AC-7b / AC1 (A) Rated power in AC3 (Kw) 230 V 400 V Control circuit voltage (V) Mechanical life (times) Electrical life (times) AC-7a / AC1 AC-7b / AC1 Degree of protection Conductor cross-sections Solid and stranded (mm²) Finely stranded with end sleeve (mm²) Terminals Terminal tightening torque (N·m) Ambient temperature (°C) Storage temperature (°C) Connection capacity (mm²) 2, 4 AC 50/60 230/400 24, 230 300,000 IP20, with connected conductors 2-25 2-25 0.8-2.4 -5 ~ +40, max. 95 % humidity -40 ~ +75 1-25 3SCH8-25 IEC 61095 10, 16, 20, 25 4, 5.5, 7, 8.5 2-5 6-13 10,000 50,000 3SCH8-63 IEC 60947-4-1 25, 32, 40, 63 8.5, 12, 15, 25 5-13 15-40 80,000 40,000 B7 Quantity of auxiliary contact Modular Contactors Series 3SCH8 1 1-198 / V 27.1 Super Series www.sassin.com
(1) Please contact us if any other coil voltage required 2 4 Selection and ordering data Type code Order code Number of poles 25896 25897 25898 25899 25900 25901 25902 25903 26156 26157 26158 26159 26160 26161 26162 26163 Rated control Power in (kW) Control voltage (V AC) Contact position Rated current In (A) Width 18 mm mods AC-7a AC AC-7b AC AC-7a /230 V AC-7b /230 V 1NO+1NC CH825 210 11B7 2NO 1NO+1NC 2NO 1NO+1NC 2NO 1NO+1NC 2NO 1NO+1NC 2NO 1NO+1NC 2NO 1NO+1NC 2NO 1NO+1NC 2NO 10 24 16 20 25 24 24 24 24 24 24 24 CH825 210 20B7 CH825 216 11B7 CH825 216 20B7 CH825 220 11B7 CH825 220 20B7 CH825 225 11B7 CH825 225 20B7 CH825 210 11P7 CH825 210 20P7 CH825 216 11P7 CH825 216 20P7 CH825 220 11P7 CH825 220 20P7 CH825 225 11P7 CH825 225 20P7 2 2 3.2 3.2 4 4 5 5 2 2 3.2 3.2 4 4 5 5 10 16 20 25 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 230 230 230 230 230 230 230 230 10 16 20 25 10 16 20 25 4 5.5 7 8.5 4 5.5 7 8.5 4 5.5 7 8.5 4 5.5 7 8.5 0.75 1.0 1.0 1.2 1.2 0.75 1.4 1.4 0.75 1.0 1.0 1.2 1.2 0.75 1.4 1.4 CH825 410 22B7 25904 25905 25906 25907 25908 25909 25910 25911 25912 25913 25914 25915 25916 25917 25918 25919 26164 26165 26166 26167 26168 26169 26170 26171 26172 26173 26174 26175 26176 26177 26178 26179 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC CH825 410 31B7 CH825 410 40B7 CH825 410 04B7 CH825 416 22B7 CH825 416 31B7 CH825 416 40B7 CH825 416 04B7 CH825 420 22B7 CH825 420 31B7 CH825 420 40B7 CH825 420 04B7 CH825 425 22B7 CH825 425 31B7 CH825 425 40B7 CH825 425 04B7 CH825 410 22P7 Ch825 410 31P7 CH825 410 40P7 CH825 410 04P7 2.2 3 3 3 3 3.5 3.5 3.5 3.5 4 4 4 4 CH825 416 22P7 CH825 416 31P7 CH825 416 40P7 CH825 416 04P7 CH825 420 22P7 CH825 420 31P7 CH825 420 40P7 CH825 420 04P7 CH825 425 22P7 CH825 425 31P7 CH825 425 40P7 CH825 425 04P7 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 10 25 10 25 25 25 20 20 20 20 16 16 16 16 10 10 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 10 25 10 25 25 25 20 20 20 20 16 16 16 16 10 10 4 8.5 4 8.5 8.5 8.5 7 5.5 4 4 5.5 5.5 5.5 7 7 7 4 8.5 4 8.5 8.5 8.5 7 5.5 4 4 5.5 5.5 5.5 7 7 7 6.2 10 13 15 15 15 15 6.2 6.2 6.2 10 10 10 13 13 13 2.2 2.2 2.2 6.2 10 13 15 15 15 15 6.2 6.2 6.2 10 10 10 13 13 13 2.2 3 3 3 3 3.5 3.5 3.5 3.5 4 4 4 4 2.2 2.2 2.2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Modular Contactors Series 3SCH8 A1 A2 2 4 6 R2 220/240 V~ 1 3 5 R1 A1 A2 R2 2 4 R4 220/240 V~ R1 1 3 R3 A1 A2 2 4 6 8 220/240 V~ 1 3 5 7 A1 A2 R2 R4 R6 R8 220/240 V~ R1 R3 R5 R7 A1 A2 2 4 220/240 V~ 1 3 A1 A2 2 R2 220/240 V~ 1 R1 1 www.sassin.com V 27.1 Super Series / 1-199
(1) Please contact us if any other coil voltage required 2 4 Selection and ordering data 25932 25933 25934 25935 25936 25937 25938 25939 25940 25941 25942 25943 25944 25945 25946 25947 26192 26193 26194 26195 26196 26197 26198 26199 26200 26201 26202 26203 26204 26205 26206 26207 1NO+1NC 2NO 2NC 1NO+1NC 2NO 2NC 1NO+1NC 2NO 2NC 1NO+1NC 2NO 2NC 1NO+1NC 2NO 2NC 1NO+1NC 2NO 2NC 1NO+1NC 2NO 2NC 1NO+1NC 2NO 2NC 25 5 5 5 6.5 6.5 6.5 8.5 8.5 8.5 13 13 13 25 25 32 32 32 40 40 40 63 63 63 24 24 24 24 24 24 24 24 24 24 24 24 25 25 25 32 32 32 40 40 40 63 63 63 230 230 230 230 230 230 230 230 230 230 230 230 8.5 8.5 8.5 12 12 12 15 15 15 25 25 25 8.5 8.5 8.5 12 12 12 15 15 15 25 25 25 1.4 1.4 1.4 2 2 2 2.5 2.5 2.5 4 4 4 5 5 5 6.5 6.5 6.5 8.5 8.5 8.5 13 13 13 1.4 1.4 1.4 2 2 2 2.5 2.5 2.5 4 4 4 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 CH863 225 11B7 25920 25921 25922 25923 25924 25925 25926 25927 25928 25929 25930 25931 26180 26181 26182 26183 26184 26185 26186 26187 26188 26189 26190 26191 CH863 225 20B7 CH863 225 02B7 CH863 232 11B7 CH863 232 20B7 CH863 232 02B7 CH863 240 11B7 CH863 240 20B7 CH863 240 02B7 CH863 263 11B7 CH863 263 20B7 CH863 263 02B7 CH863 225 11P7 CH863 225 20P7 CH863 225 02P7 CH863 232 11P7 CH863 232 20P7 CH863 232 02P7 CH863 240 11P7 CH863 240 20P7 CH863 240 02P7 CH863 263 11P7 CH863 263 20P7 CH863 263 02P7 2NO+2NC CH863 425 22B7 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC 2NO+2NC 3NO+1NC 4NO 4NC CH863 425 31B7 CH863 425 40B7 CH863 425 04B7 CH863 432 22B7 CH863 432 31B7 CH863 432 40B7 CH863 432 04B7 CH863 440 22B7 CH863 440 31B7 CH863 440 40B7 CH863 440 04B7 CH863 463 22B7 CH863 463 31B7 CH863 463 40B7 CH863 463 04B7 CH863 425 22P7 CH863 425 31P7 CH863 425 40P7 CH863 425 04P7 CH863 432 22P7 CH863 432 31P7 CH863 432 40P7 CH863 432 04P7 CH863 440 22P7 CH863 440 31P7 CH863 440 40P7 CH863 440 04P7 CH863 463 22P7 CH863 463 31P7 CH863 463 40P7 CH863 463 04P7 63 63 63 63 40 40 40 40 32 32 32 32 25 25 25 25 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 63 63 63 63 40 40 40 40 32 32 32 32 25 25 25 25 15 15 15 15 21 21 21 21 26 26 26 26 40 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 8.5 8.5 8.5 12 12 12 15 15 15 25 25 25 25 15 12 8.5 8.5 8.5 8.5 12 12 12 15 15 15 25 25 25 25 15 12 8.5 40 40 40 15 15 15 15 21 21 21 21 26 26 26 26 40 40 40 40 4 4 4 4 6.5 6.5 6.5 6.5 7.5 7.5 7.5 7.5 13 13 13 13 4 4 4 4 6.5 6.5 6.5 6.5 7.5 7.5 7.5 7.5 13 13 13 13 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Modular Contactors Series 3SCH8 Type code Order code Number of poles Rated control Power in (kW) Control voltage (V AC) Contact position Rated current In (A) Width 18 mm mods AC-7a AC AC-7b AC AC-7a /230 V AC-7b /230 V A1 A2 2 4 6 R2 220/240 V~ 1 3 5 R1 A1 A2 R2 2 4 R4 220/240 V~ R1 1 3 R3 A1 A2 2 4 6 8 220/240 V~ 1 3 5 7 A1 A2 R2 R4 R6 R8 220/240 V~ R1 R3 R5 R7 A1 A2 2 4 220/240 V~ 1 3 A1 A2 2 R2 220/240 V~ 1 R1 A1 A2 R2 R4 220/240 V~ R1 R3 1 1-200 / V 27.1 Super Series www.sassin.com
18 65.5 49.5 85 35 45 67 49.5 85 35 45 36 3SCH8-25 2P 36 67 49.5 85 35 45 54 67 49.5 85 35 45 3SCH8-25 4P 3SCH8-63 2P 3SCH8-63 4P Outline and installation dimensions unit in mm Modular Contactors Series 3SCH8 1 www.sassin.com V 27.1 Super Series / 1-201
Functions The pushbuttons are used for remote control in every kind of electric installation. The indicator lamps signal any event in every kind of electric installation. 3SB71P, 3SB71D, 3SB71PD may match with MCB series 3SB71-63 Technical specifications Standard: IEC 60947-5-1 Rated voltage Ue (V): 230 Rated current In (A): 6 Conventional glowing current (A): 16 Frequency (Hz): 50/60 Modules (18mm): 1 Utilization category: AC14, DC13 Degree of protection: IP20, with connected conductors Conductor cross-sections Solid and stranded (mm²): 1-10 Finely stranded with end sleeve (mm²): 1-4 Terminal tightening torque (N·m): 0.5 Ambient temperature (°C): -5 ~ +40, max. 95% humidity Storage temperature (°C): -40 ~ +75 Connection capacity (mm²): 1-16 Outline and installation dimensions unit in mm 70.9 50.3 69 18 91.5 35 45 75 27 35 Modular Pushbuttons and Indicators Series 3SB71P / 3SB71D / 3SB71PD 1 1-202 / V 27.1 Super Series www.sassin.com
Pushbutton Pushbutton Pushbutton Indicator Indicator Indicator Color Color Color 1 NO + 2 NC 1 NO + 2 NC 2 NO + 1 NC 2 NO + 1 NC 2 NO + 2 NC 2 NO + 2 NC 3 NO 3 NO 3SB71P Pushbutton 3SB71PD Pushbutton + Indicator 3SB71D Indicator Voltage AC/DC (V) Voltage AC/DC (V) 12 V AC/DC 24 V AC/DC 110 V AC/DC 230 V AC/DC Selection and ordering data Type code Type code Type code Type code Type code Type code Type code Type code Type code Type code Type code Type code Order code Order code Order code Order code Order code Order code Order code Order code Order code Order code Order code Order code Green B71P G12 16185 B71P G21 16186 B71P G22 16187 B71P G30 16188 Red - B71P R12 16189 B71P R21 16190 B71P R22 16191 B71P R30 16192 Black - B71P H12 16193 B71P H21 16194 B71P H22 16195 B71P H30 16196 Yellow - B71P Y12 16197 B71P Y21 16198 B71P Y22 16199 B71P Y30 16200 Blue - B71P B12 16201 B71P B21 16202 B71P B22 16203 B71P B30 16204 - - - - - - Red Red B71PD R12V12 16208 B71PD R21V12 16209 - - B71PD R30V12 16210 White White B71PD W12V12 16211 B71PD W21V12 16212 - - B71PD W30V12 16213 Yellow Yellow B71PD Y12V12 16214 B71PD Y21V12 16215 - - B71PD Y30V12 16216 Blue Blue B71PD B12V12 16217 B71PD B21V12 16218 - - B71PD B30V12 16219 Green B71PD G12V24 16220 B71PD G21V24 16221 - - B71PD G30V24 16222 White B71PD W12V24 16226 B71PD W21V24 16227 - - B71PD W30V24 16228 Yellow B71PD Y12V24 16229 B71PD Y21V24 16230 - - B71PD Y30V24 16231 Blue B71PD B12V24 16232 B71PD B21V24 16233 - - B71PD B30V24 16234 Green B71PD G12V110 16235 B71PD G21V110 16236 - - B71PD G30V110 16237 Red B71PD R12V110 16238 B71PD R21V110 16239 - - B71PD R30V110 16240 White B71PD W12V110 16241 B71PD W21V110 16242 - - B71PD W30V110 16243 Yellow B71PD Y12V110 16244 B71PD Y21V110 16245 - - B71PD Y30V110 16246 Blue B71PD B12V110 16247 B71PD B21V110 16248 - - B71PD B30V110 16249 Green B71PD G12V230 16250 B71PD G21V230 16251 - - B71PD G30V230 16252 Red B71PD R12V230 16253 B71PD R21V230 16254 - - B71PD R30V230 16255 White B71PD W12V230 16256 B71PD W21V230 16257 - - B71PD W30V230 16258 Yellow B71PD Y12V230 16259 B71PD Y21V230 16260 - - B71PD Y30V230 16261 Blue B71PD B12V230 16262 B71PD B21V230 16263 - - B71PD B30V230 16264 Green Green B71PD G12V12 16205 B71PD G21V12 16206 - - B71PD G30V12 16207 Red B71PD R12V24 16223 B71PD R21V24 16224 - - B71PD R30V24 16225 12 12 12 12 12 24 24 24 24 24 110 110 110 110 110 230 230 230 230 230 B71D G12 B71D G24 B71D G110 B71D G230 B71D R12 B71D R24 B71D R110 B71D R230 B71D W12 B71D W24 B71D W110 B71D W230 B71D Y12 B71D Y24 B71D Y110 B71D Y230 B71D B12 B71D B24 B71D B110 B71D B230 16265 16266 16267 16268 16269 16270 16271 16272 16273 16274 16275 16276 16277 16278 16279 16280 16281 16282 16283 16284 - - - - - Modular Pushbuttons and Indicators Series 3SB71P / 3SB71D / 3SB71PD 1 www.sassin.com V 27.1 Super Series / 1-203
Modular Time Swtiches Series 3SE8, 3SUL181H, 3SRC18, 3SHC18A Functions Controlling circuit opening and closing according to the scheduled program. Can be set on the scheduled program Available on hourly, daily and weekly version and equipped with a 16 A contact Fitting applications such as shop lighting systems, public buildings, schools, heating and irrigation systems and so forth. Technical specifications Type Standard Rated supply voltage (V) Contact type Switching capacity resistive load (A) inductive load (A) Rated frequency (Hz) Full time range Minimum setting unit Electrical life (times) Mechanical life (times) Modules (18 mm) Operating temperature (°C) Storage temperature (°C) Mounting Terminal size for cable (mm²) 3SE8 - 16 7 minutes 0.5 minutes 5 10 times 7 10 times 1 3SE8 3SUL181H 3SRC18 3SHC18A Type code Order code Rated current In (A) Full time range 7 minutes 24 hours 20 minutes 24 hours or one week E8 SUL181H ALC18 HC18A 24776 13684 24780 24777 16 16 16 16 Selection and ordering data IEC 60730-1 AC 220-240 4 50/60 -5 ~ +40, max. 95 % humidity -40 ~ +75 ON DIN RAIL 2.5 3SUL181H - 16 24 minutes 30 minutes 5 10 times 7 10 times 3 3SRC18 - 16 20 minutes 0.5 minutes 5 10 times 7 10 times 1 3SHC18A 1NC OR 1NO 16 24 hours or one week - 5 10 times 7 10 times 2 Outline and installation dimensions unit in mm 3SE8 3SUL181H 3SRC18 3SHC18A 45.5 45 15 60 66.5 52.5 110 90 35 86 45.5 65 48 65.7 18 45 81.3 20 15 10 5 0.5 N L 1 2 1 1-204 / V 27.1 Super Series www.sassin.com
Doorbell Transformer Series BT8 Technical specifications Rated input voltage AC (V): 230 Rated output voltage AC (V): 4, 6, 8, 12, 16, 24 Rated frequency (Hz): 50/60 Rated output power (VA): 6 Consumption (W): 1.15 Pollution class: 2 Rated output power Selection and ordering data Pack. 8 VA Type code Order code BT8-8 24751 1 66 50 28 13.5 36 6 36 88 82 64 45 Outline and installation dimensions unit in mm 1 www.sassin.com V 27.1 Super Series / 1-205
Functions Widely used in terminal distribution system Being complete series of terminal distribution system together with series 3SB71 Technical specifications Standard: IEC 60884-1 Rated current (A): 16 Modules: 2.5 Rated voltage Ue (V): 230/400 Conductor cross-sections Solid and stranded (mm²): 0.75-35 68.3 35 45 92 Outline and installation dimensions unit in mm Rated current In (A) Selection and ordering data Number of poles (P) 2+E Type code Order code 16 MS71 17727 Modular Sockets Series MS71 1 1-206 / V 27.1 Super Series www.sassin.com
Functions Equipped with various modular electric for the function of terminal power distribution . Suited for the installation of all Sassin individual modular devices. (RCDs, MCBs, RCBO’s, switch disconnectors etc). Used in residential building, non-residential building, industry. Technical specifications Standard: IEC 61439-3 Modules (No.): 4, 6, 8, 12, 18, 24, 36 Row : Single row for 4, 6, 8, 12, 18 modules 2 rows for 24 modules 3 rows for 36 modules Rated frame current In (A): 63, 100 Color: White RAL 9003 and grey RAL 7035 The color of door: Transparent, non transparent Mounting type: Surface, Flush. Degree of protection: IP30 Material: HIPS for body SAN for door (4-18 modules) PC for door (24 & 36 modules) Fire resistence: 650 °C / 30 s Ambient temperature (°C): -5 ~ +40, max. 95 % humidity Storage temperature (°C): -40 ~ +75 Rated frame current Instruction of type code Number of modules Color of visor Series code D5 6 W T 08 Color of base Rated frame current Instruction of type code Number of modules Color of visor Series code D6 6 W T 08 Color of base Distribution Boxes Series 3SD5 & 3SD6 1 www.sassin.com V 27.1 Super Series / 1-207
Flush mounting 3SD5 63 100 Selection and ordering data White Transparent Grey Transparent White Transparent Grey Transparent Type code Order code 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 White Grey Rated current In (A) Color of base Color of door Number of module D506WW04 23157 D506WT04 23159 D506WW06 23163 D506WT06 23165 D506WW08 23169 D506WT08 23171 D506WW12 23137 D506WT12 23139 D506WW18 23143 D506WT18 23145 D506WW24 23149 D506WT24 23150 D506WW36 23153 D506WT36 23154 D506GG04 24555 D506GT04 24556 D506GG06 24557 D506GT06 24558 D506GG08 24559 D506GT08 24560 D506GG12 24563 D506GT12 24564 D506GG18 24565 D506GT18 24566 D506GG24 24567 D506GT24 24568 D506GG36 24569 D506GT36 24570 D510WW04 30655 D510WT04 30656 D510WW06 30657 D510WT06 30658 D510WW08 30659 D510WT08 30660 D510WW12 30663 D510WT12 30664 D510WW18 30665 D510WT18 30666 D510WW24 30667 D510WT24 30668 D510WW36 30669 D510WT36 30670 D510GG04 30697 D510GT04 30698 D510GG06 30699 D510GT06 30700 D510GG08 30701 D510GT08 30702 D510GG12 30705 D510GT12 30706 D510GG18 30707 D510GT18 30708 D510GG24 30709 D510GT24 30710 D510GG36 30711 D510GT36 30712 White Grey Distribution Boxes Series 3SD5 & 3SD6 1 1-208 / V 27.1 Super Series www.sassin.com
Surface mounting 3SD6 63 100 Selection and ordering data White Transparent Grey Transparent White Transparent Grey Transparent 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 4 6 8 12 18 24 36 White Grey White Grey 23161 23162 23167 23168 23173 23174 23141 23142 23147 23148 23151 23152 23155 23156 24571 24572 24573 24574 24575 24576 24579 24580 24581 24582 24583 24584 24585 24586 30671 30672 30673 30674 30675 30676 30679 30680 30681 30682 30683 30684 30685 30686 30713 30714 30715 30716 30717 30718 30721 30722 30723 30724 30725 30726 30727 30728 D606WW04 D606WW06 D606WW08 D606WW12 D606WW18 D606WW24 D606WW36 D606WT04 D606WT06 D606WT08 D606WT12 D606WT18 D606WT24 D606WT36 D606GG04 D606GG06 D606GG08 D606GG12 D606GG18 D606GG24 D606GG36 D606GT04 D606GT06 D606GT08 D606GT12 D606GT18 D606GT24 D606GT36 D610WW04 D610WW06 D610WW08 D610WW12 D610WW18 D610WW24 D610WW36 D610WT04 D610WT06 D610WT08 D610WT12 D610WT18 D610WT24 D610WT36 D610GG04 D610GG06 D610GG08 D610GG12 D610GG18 D610GG24 D610GG36 D610GT04 D610GT06 D610GT08 D610GT12 D610GT18 D610GT24 D610GT36 Distribution Boxes Series 3SD5 & 3SD6 Type code Order code Rated current In (A) Color of base Color of door Number of module 1 www.sassin.com V 27.1 Super Series / 1-209
Ø16 200 90 4, 6, 8 &12 » 24 » 24 » 18 » 100 112 150 Ø25 Ø25 Ø25 Ø32 Ø25 4 » 6 » 185 Ø25 Ø32 Ø25 258 Ø25 Ø32 Ø32 Ø32 Ø25 8 » 12 » 366 Ø25 Ø32 Ø32 Ø32 Ø32 Ø32 Ø25 18 » 4, 6, 8 &12 » 136 172 207 279 221 251 397 18 » 305 345 24 » 98 456 36 » 341 505 36 » 296 36 » 260 98 315 Ø16 Outline and installation dimensions (3SD5) unit in mm Fitting inside of the enclose Attached with sticky label for marking on wire front panel; ready equipped with zero line and earth terminal bar and attached with zero bar, earth bar marks and alarm mark; users can select to connect with wire or insulating busbar method. 6 6 6 6 6 6 8 8 8 8 8 8 3M4X7+M4X7 3M4X7+M4X7 4M4X7+M4X7 6M4X7+M4X7 9M4X7+M4X7 6M4X7+2M4X7 29.5 29.5 37 52 74.5 28+28 4M4X7+M4X7 6M4X7+M4X7 8M4X7+M4X7 10M4X7+2M4X7 13M4X7+2M4X7 20M4X7+4M4X7 37 52 67 37+52 74.5+37 60+60+28+28 60+60+60+28 24M4X7+4M4X7 60+28 10M4X7+2M4X7 6 8 Neutral Neutral bar length (mm) Neutral bar holes (piece) Earth bar length (mm) Earth bar holes (piece) Width (mm) Height (mm) Distribution Boxes Series 3SD5 & 3SD6 4 6 8 12 18 24 36 220 1 1-210 / V 27.1 Super Series www.sassin.com
Outline and installation dimensions (3SD6) unit in mm 99 18 » 94.5 Ø16 4, 6, 8 & 12 » 199 112 183 255 148 4, 6, 8 & 12 》 220 362 18 》 24 » 97 36 » 36 » 306.3 473.7 Ø16 Ø25 4 » Ø16 Ø25 6 » Ø20 Ø32 18 » Ø16 Ø32 8 » Ø20 Ø16 Ø25 Ø16 Ø16 Ø32 12 » Ø16 Ø20 Ø16 Ø25 Ø25 Ø16 24 » 36 » 92 326 271 24 » Distribution Boxes Series 3SD5 & 3SD6 Ø16 Ø20 Ø32 Ø25 Ø16 Ø20 Ø32 Ø25 Ø20 Ø16 Ø25 Ø32 Ø20 Ø20 Ø32 Ø32 1 www.sassin.com V 27.1 Super Series / 1-211
Functions Equipped with various modular electric for the function of terminal power distribution. Suited for the installation of all Sassin individual modular devices. (RCDs, MCBs, RCBO’s, switch disconnectors etc). Used in residential building, non-residential building, industry. Rated frame current Instruction of type code Number of modules Color of visor Series code D8 6 W T 08 Color of base 3SD8 Surface Mounting 100 Selection and ordering data White Transparent Type code Order code White Rated current In (A) Color of base Color of door Number of module 23176 23178 23180 23182 23184 23186 23175 23177 23179 23181 23183 23185 D810WW04 D810WW07 D810WW10 D810WW13 D810WW16 D810WW21 D810WT04 D810WT07 D810WT10 D810WT13 D810WT16 D810WT21 4 7 10 13 16 21 4 7 10 13 16 21 Distribution Boxes Series 3SD8 Technical specifications Standard: IEC 61439-3 Modules: 4, 7, 10, 13, 16, 21 Row: Single Rated voltage In (A): 100 Color: White RAL 9003 Color of door: Transparent, non transparent Mounting type: Surface Degree of protection: IP30 Material: HIPS for body AS for door Fire resistence: 650 °C / 30 s Ambient temperature (°C): -5 ~ +40, max. 95 % humidity Storage temperature (°C): -40 ~ +75 1 1-212 / V 27.1 Super Series www.sassin.com
Outline and installation dimensions (3SD8) unit in mm Fitting inside of the enclose Attached with sticky label for marking on wire front panel; ready equipped with zero line and earth terminal bar and attached with zero bar, earth bar marks and alarm mark; users can select to connect with wire or insulating busbar method. 141.4 225.4 194.8 226.4 248.5 226.4 226.4 225.4 225.4 301.8 354 443.2 110 110 110 225.4 218 130 226.4 218 130 226.4 218 130 141.4 132.4 66.4 194.8 185.8 119.4 248.5 239.4 173.2 301.8 292.6 226.6 354 344.8 280 443.2 434.5 369 4 4 4 110 226.4 218 130 4 110 225.4 218 130 4 110 225.4 218 130 4 1xØ6 + 1xØ5.8 + 3xØ5.4 1xØ6 + 1xØ5.8 + 6xØ5.4 1xØ6 + 1xØ5.8 + 10xØ5.4 1xØ6 + 1xØ5.8 + 8xØ5.4 1xØ6 + 1xØ5.8 + 8xØ5.4 1xØ6 + 1xØ5.8 + 8xØ5.4 1xØ6 + 1xØ5.8 + 6xØ5.4 1xØ6 + 1xØ5.8 + 8xØ5.4 1xØ6 + 1xØ5.8 + 11xØ5.4 1xØ6 + 1xØ5.8 + 3xØ5.4 1xØ6 + 1xØ5.8 + 4xØ5.4 1xØ6 + 1xØ5.8 + 8xØ5.4 1xØ6 + 1xØ5.8 + 11xØ5.4 1xØ6 + 1xØ5.8 + 14xØ5.4 1xØ6 + 1xØ5.8 + 18xØ5.4 4 module 7 module 10 module 13 module 16 module 21 module The Number of Module Neutral bar holes 1 Neutral bar holes 2 Earth bar holes - - - 3SD8-04 3SD8-07 3SD8-10 3SD8-13 3SD8-16 3SD8-21 Distribution Boxes Series 3SD8 1 www.sassin.com V 27.1 Super Series / 1-213
Functions Equipped with various modular electric for the function of the terminal power distribution Suited for the installation of all the Sassin individual modular device (RCDs, MCBs, RCBOs, switch disconnectors etc.) Used in the residential buildings, non-residential buildings and industry Lifting installation rail, easy for installation Distribution Boxes Series 3SD5T (Metal Base) Technical specifications Standard: IEC 61439-3 Modules: 4, 6, 8, 12, 18 Row: Single Rated frame current In (A): 63 Color: White RAL 9003, Grey RAL7035 The color of the door: Transparent, non transparent Mounting type: Flush Degree of the protection: IP40 Material: HIPS for the body SAN for the door Metal for the base Fire resistence: 650 ºC / 30 s Ambient temperature (ºC): -5 ~ +40, 50% humidity permitted under max +40 ºC Storage temperature (ºC): -40 ~ +75 Outline and installation dimensions unit in mm A B C D Hmax Flush mounting 3SD5T 63 Selection and ordering data Transparent Grey Type code Order code Grey Rated current In (A) Color of base Color of door Number of module 23160 23166 23172 23140 23146 23158 23164 23170 23138 23144 4 6 8 12 18 4 6 8 12 18 D5T06GT04 D5T06GT06 D5T06GT08 D5T06GT12 D5T06GT18 D5T06GG04 D5T06GG06 D5T06GG08 D5T06GG12 D5T06GG18 3SD5T-04 3SD5T-06 3SD5T-08 3SD5T-12 3SD5T-18 221 221 221 221 251 190.5 190.5 190.5 190.5 223.5 136 172 207 279 397 108.5 142.5 180.5 252.5 360.5 102 102 102 102 103 A (mm) B (mm) C (mm) D (mm) H max (mm) Type 1 1-214 / V 27.1 Super Series www.sassin.com
Functions 3SDTN2 series distribution box are fit for AC 50/60 Hz, rated voltage 400 V, rated current to 125 A in the home and similar field circuit, for the redistribution of electrical energy, offering overload and shortcircuit protection through the switch. Distribution Boxes Series 3SDTN2 Technical specifications Standard: IEC/EN 61439-3 The base, top and buckle cover are made of metal alloy. Rated operaional voltage Un (Ue) (V): 220/400 Rated operaional current In (Ie) (A): 125, 100, 80, 63 and below Rated impulse withstand voltage Uimp (A): 6 K Mounting type: surface Degree of protection: IP 2XC Outline and installation dimensions unit in mm 125 Selection and ordering data Grey Type code Order code Grey Rated current In (A) Color of base Color of door Number of module 15227 15228 15229 15230 15231 15232 4 8 12 16 18 22 DTN2 04 DTN2 08 DTN2 12 DTN2 16 DTN2 18 DTN2 22 3SDTN2-4 3SDTN2-8 3SDTN2-12 3SDTN2-16 3SDTN2-18 3SDTN2-22 235 264 264 264 264 264 128 199 271 343 379 451 105 123 123 123 123 123 L (mm) W (mm) D (mm) Type W L D 1 www.sassin.com V 27.1 Super Series / 1-215
Shock-protection caps Feeder terminals DIN Rails Busbar systems Suitable for cutting Selection and ordering data Type code Type code Type code Type code Order code Order code Order code Order code Connection type Phases Discription Discription Discription Rated current (A) Length (cm) Phases 63 63 63 63 63 63 63 63 1×54 2×27 3×18 4×14 1×54 2×27 3×18 4×14 For 1P For 2P For 3P For 4P Yellow Connection capacity: 6-25 mm² Max. electrical load: 63 A Max. tightening torque 2 N·m Aluminum, 100 cm Connection capacity: 6-25 mm² Max. electrical load: 63 A Max. tightening torque 2 N·m Iron plated zinc, 100 cm 24760 24762 24764 24766 24761 24763 24765 24767 32676 32677 32678 32679 32680 32929 32931 32930 32932 SA-BB101 SA-BB201 SA-BB301 SA-BB401 SA-BB102 SA-BB202 SA-BB302 SA-BB402 SA-BBEC1 SA-BBEC2 SA-BBEC3 SA-BBEC4 SA-BBSCY5 FT1B DR1 FT2G DR2 100 100 100 100 100 100 100 100 100 100 100 100 5 parts PIN type Fork type End caps 1 1-216 / V 27.1 Super Series www.sassin.com Accessories for Distribution Boxes
6 9 30.5 Ø6 8 29.5 Ø5 6 Terminal bars with screws Selection and ordering data Type code Order code Rated Way current (A) Screw size Sectioncross of brass (mm) 63 M4×7 M4×7 M4×7 M4×7 M4×7 M4×7 M4×7 M4×7 6×8 6×8 6×8 6×8 6×8 6×8 6×8 6×8 TBS0631 TBS0641 TBS0661 TBS0662 TBS0681 TBS0691 TBS06102 TBS06132 6×8 M4×7 M4×7 M4×7 M4×7 M4×7 M4×7 M4×7 M4×7 M4×7 M4×7 6×9 6×9 6×9 6×9 6×9 6×9 6×9 6×9 6×9 TBS06204 TBS1031 TBS1041 TBS1061 TBS1062 TBS1081 TBS1091 TBS10102 TBS10132 TBS10204 32933 32934 32935 32936 32937 32938 32939 32940 32941 32942 32943 32944 32945 32946 32947 32948 32949 32950 100 3+1 4+1 6+1 6+2 8+1 9+1 10+2 13+2 20+4 3+1 4+1 6+1 6+2 8+1 9+1 10+2 13+2 20+4 9 38 Ø6 6 9 53 Ø6 6 9 68 Ø6 6 9 75.5 Ø6 6 9 60.5 Ø6 6 9 90.5 Ø6 6 9 113 Ø6 6 9 180.5 Ø6 6 8 37 Ø5 6 8 52 Ø5 6 8 67 Ø5 6 8 74.5 Ø5 6 8 59.5 Ø5 6 8 89.5 Ø5 6 8 112 Ø5 6 8 179.5 Ø5 6 1 www.sassin.com V 27.1 Super Series / 1-217 Accessories for Distribution Boxes
Terminal blocks Terminals with insulation holder for quick fastening onto DIN rails Selection and ordering data Type code Order code Way Installation size (mm) Screw size Sectioncross of brass (mm) 32951 32952 32953 32954 32955 32956 7 8 10 12 13 15 100 6×9 6×9 6×9 6×9 6×9 6×9 100 100 100 100 100 35×7.5 35×7.5 35×7.5 35×7.5 35×7.5 35×7.5 50×21 57×21 70×21 84×21 91×21 104×21 M5×8 M5×8 M5×8 M5×8 M5×8 M5×8 TBS1007 TBS1008 TBS1010 TBS1012 TBS1013 TBS1015 Rated current (A) Dimension (mm) Blanking plates Matched with distribution boxes for device covers Type code Order code Discription width: 1 module = 17.5 mm, White MBP1 32957 width: 0.5 module = 9 mm, White MBP2 32958 Accessories for Distribution Boxes 1 1-218 / V 27.1 Super Series www.sassin.com
Applications and functions for AC contactor Used for controlling 3-phase motors and generally for controlling power circuits. Used for many other applications such as isolation, capacitor switching and lighting. Instruction of type code Coil code Quantity of contact 01: 3NO+1NC 10: 3NO+1NO 004: 4NO 008: 2NO+2NC Rated operational current in category AC-3 at 400V: 06, 09, 12 Series code C8 06 10 P5 Contactors Series 3SC8-K For contactor Code of auxiliary contact N02: 2NC N11: 1NO+1NC N20: 2NO N04: 4NC N13: 1NO+3NC N22: 2NO+2NC N31: 3NO+1NC N40: 4NO Model code Series code C8 A1 N02 For auxiliary contactor K Model code 1 www.sassin.com V 27.1 Super Series / 1-219 /
Technical specifications for type 3SC8-K Type Standard Number of contacts Rated conventional thermal current Ith (A) Rated operational voltage Ue (V) Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV) Rated frequency (Hz) Rated operational current (A) Number of poles Rated operational power in category AC-3 (KW) Rated making capacity (A) Rated breaking capacity (A) Short-circuit protection (A) Average impedance per pole (mW) Add-on auxiliary contact blocks Reversing contactor type Associated thermal overload relays Operation cycles(times/hour) 4 Electrical life (× 10 times) 4 Mechanical life (× 10 times) Matching fuse model Tightening torque (N·m) Connection Screw clamp terminals Degree of protection Ambient air temperature (ºC) Storage temperature (ºC) Maximum operating altitude (meters) Flame resistance AC-1 AC-3 380/400 V AC-4 380/400 V 220/230/240 V 380/400 V 660/690 V 380 V 690 V gG fuse U ≤ 440 V Front Side Front time delay Front dust and damp protected 3 Pins/5 Pins Electrical AC-3 Electrical AC-4 Mechanical AC-3 AC-4 solid conductor (mm²) Flexible conductor without cable end (mm²) Flexible conductor with cable end (mm²) Conforming to UL 94 3SC8-K0610, 3SC8-K0601, 3SC8-K06004, 3SC8-K06008 IEC 60947-4-1 3NO+1NO, 3NO+1NC, 4NO, 2NO+2NC 20 690 690 6 50/60 6 2.6 3,4 1.5 2.2 3 110 100 70 25 3 3SC8-A1/KN - - - 3SC8-KN 3SR8-K 1200 300 3600 100 20 1000 RT16-16 0.8 Max. 1×4+1×2.5 Max. 2×2.5 Max. 1×1.5+1×2.5 IP20 -5 to +40, max. 95 % humidity -40 ~ +75 2000 V1 3SC8-K1210, 3SC8-K1201, 3SC8-K12004, 3SC8-K12008 12 5 3,4 3 5.5 5.5 114 100 70 3SC8-K0910, 3SC8-K0901, 3SC8-K09004, 3SC8-K09008 9 3.5 3,4 2.2 4 4 110 100 70 120 RT16-20 Contactors Series 3SC8-K Technical specifications for auxiliary contact incorporated in the contactor type 3SC8-K Standard: IEC 60947-5-1 Number of auxiliary contact: 2, 4 Mounting type: Front Conventional heating current (A): 10 Rated operational voltage Ue (V): Up to 690 Rated insulation voltage Ui (V): 690 Conventional thermal current Ith (A): 10 Minimum switching capacity Im (mA): 5 Short circuit protection (A): 10 Rated making capacity (A): 110 1 1-220 / V 27.1 Super Series www.sassin.com
Coil voltage of contactor 3SC8-K Coil voltage Us (V) 115 FE5 - FE7 240 U5 U6 U7 660/690 Y5 Y6 Y7 50 Hz 60 Hz 50/60 Hz 550/600 600/660 - - X7 550 SC5 - - 480 T5 - - 415 N5 - N7 380 Q5 Q6 Q7 127 FC5 - FC7 220 M5 M6 M7 12 J5 - J7 24 B5 B6 B7 36 - - CC7 48 E5 E6 E7 100 - - K7 120 G5 - - 265 - - W7 600 X5 - - 500 S5 - S7 440 R5 R6 R7 400 V5 - V7 208 LE5 - - 230 P5 - P7 20 - - Z7 32 C5 - C7 42 D5 - D7 60 - - EE7 110 F5 F6 F7 3SC8-K contactor 3SC8-KN reversing contactors Selection and ordering data Type code Order code Rated operational current in category AC-3 400 V (A) Number of poles Instantaneous auxiliary contacts 6 9 12 6 9 12 6 9 12 3 - 3 - 3 - 3 - 3 - 3 - 4 - 2 2 4 - 2 2 4 - 2 2 3 - 4 - 3 - 4 - 3 - 4 - 11373 11374 11377 11378 11381 11382 11375 11376 11379 11380 11383 11384 15576 15697 15703 15577 15698 15704 15578 15699 15705 C8 K0601P5 C8 K0610P5 C8 K0901P5 C8 K0910P5 C8 K1201P5 C8 K1210P5 C8 K06004P5 C8 K06008P5 C8 K09004P5 C8 K09008P5 C8 K12004P5 C8 K12008P5 C8 KN0601P5 C8 KN0610P5 C8 KN06004P5 C8 KN0901P5 C8 KN0910P5 C8 KN09004P5 C8 KN1201P5 C8 KN1210P5 C8 KN12004P5 - 1 1 - - 1 1 - - 1 1 - - - - - - - - - - - - - - 1 1 - - - - 1 1 - - - - 1 1 - - - 3 - 3 - 3 - 230 V 50 Hz Please contact us for other coil voltage Auxiliary contacts Type code Order code 0 1 2 0 1 2 3 4 C8K A1/N02 C8K A1/N11 C8K A1/N20 C8K A1/N04 C8K A1/N13 C8K A1/N22 C8K A1/N31 C8K A1/N40 33032 33033 33034 33035 33036 33037 33038 33039 2 1 0 4 3 2 1 0 3SC8-A1/KN Contactors Series 3SC8-K Outline and installation dimensions unit in mm F4-(F4)K 35 57 58 4XØ4 50 45 35 57 58 50 80 90 F4-(F4)K 8XØ4 35 5 5 5 5 1 www.sassin.com V 27.1 Super Series / 1-221
Applications and functions for AC contactor 3SC8 Used for controlling 3-phase motors and generally for controlling power circuits. Used for many other applications such as isolation, capacitor switching and lighting. Instruction of type code Coil code Quantity of contact 10: 3 NO + 1 NO (Ie ≤ 32A) 01: 3 NO + 1 NC (Ie ≤ 32A) 11: 3 NO + 1 NO + 1 NC 004: 4 NO (except Ie = 18 A & Ie = 32 A) 008: 2 NO + 2 NC (except Ie = 18 A & Ie = 32 A) Rated working current in category AC-3 at 400 V AC (A): 09, 12, 18, 25, 32, 40, 50, 65, 80, 95 Series code C8 09 10 P7 Contactors Series 3SC8 1 1-222 / V 27.1 Super Series www.sassin.com
Technical specifications for type 3SC8 Type Standard Number of poles Rated operational current Ie (A) Rated operational voltage Ue (V) Frequency limits of the operational current (time/h) Rated conventional thermal current Ith (A) Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV) Rated frequency (Hz) Rated making capacity (A) Rated breaking capacity (A) Rated operational power in category AC-3 (kw) Fuse protection against short-circuit (A) Average impedance per pole (mΩ) Add-on auxiliary contact blocks Reversing contactor type Associated thermal overload relays Operation cycles (times/hour) Electrical life (× 10³ times) 6 Mechanical life (× 10 times) Matching fuse model Tightening torque (N · m) Connection Cabling cross section (CU) Screw size Degree of protection Ambient air temperature (ºC) Storage temperature (ºC) Maximum operating altitude (meters) Flame resistance 3SC8-09 3SC8-12 3SC8-18 3SC8-25 3SC8-32 3SC8-40 3SC8-50 3SC8-65 3SC8-80 3SC8-95 3, 4 3, 4 3 3, 4 3 3, 4 3, 4 In AC-3 In AC-4 In AC-3 In AC-4 In AC-1 9 12 18 25 32 40 50 20 25 32 40 50 60 80 Up to 25 25 32 40 50 60 80 400 V 400 V 220/230/240 V 380/400 V 660/690 V Without thermal overload relay, Gg fuse Type 1 Type 2 With thermal overload relay 2.2 3 4 5.5 7.5 11 15 4 5.5 7.5 11 15 18.5 22 5.5 7.5 10 15 18.5 30 33 20 25 32 40 50 63 80 20 20 25 32 40 50 63 2.5 2.5 2.5 2 2 1.5 1.5 Front Side Front time delay Front dust and damp protected Electrical AC-3 Electrical AC-4 Mechanical AC-3 AC-4 1200 1200 1200 1200 600 600 600 300 300 300 300 300 300 300 3600 3600 3600 3600 3600 3600 3600 1000 1000 1000 1000 800 800 600 200 200 200 200 200 150 150 10 10 10 10 8 8 8 RT16-20 RT16-20 RT16-32 RT16-40 RT16-50 RT16-63 RT16-80 1.2 1.2 1.7 2.0 2.5 5 5 1/2.5 1/2.5 1/4 1/4 1.5/4 2.5/10 2.5/10 1/4 1/4 1.5/6 1.5/6 2.5/10 2.5/16 2.5/16 1/4 1.5/4 1.5/6 1.5/6 1.5/10 2.5/25 2.5/25 M3.5 M3.5 M3.5 M4 M4 M8 M8 Conforming to UL 94 3SR8-25 3SR8-93 3, 4 3, 4 3, 4 65 80 95 80 110 125 80 125 125 18.5 22 25 30 37 45 37 45 45 80 125 160 80 150 150 1.5 0.8 0.8 600 600 600 300 300 300 3600 3600 3600 600 600 600 150 100 100 8 6 6 RT16-80 RT16-100 RT16-125 5 9 9 2.5/10 4/16 4/16 2.5/16 4/25 4/25 2.5/25 4/50 4/50 M8 M10 M10 6.6 8.9 12 18 21 34 39 42 49 55 1.5 2 3.8 4.4 7.5 9 12 14 17.3 21.3 380 V 660 V 440 V 3.5 5 7.7 8.5 12 18.5 24 28 37 44 IEC 60947-4-1 690 25-400 690 8 50/60 10 × Ie AC-3 or 12 × Ie AC-4 8 × I e AC-3 or 10 × Ie AC-4 see specification and ordering data of 3SR8, for aM or gG fuse ratings corresponding to the associated thermal overload relay 3SC8-A1 and 3SC8-A1D 3SC8-A1C 3SC8-A2 3SC8-DN IP20 -5 to +40, max. 95 % humidity -40 ~ +75 2000 V1 Flexible cable with cold-pressed 2 socket (mm²) Flexible cable without cold-pressed 2 socket (mm²) Inflexible 2 cable (mm²) 3SR8-36 Contactors Series 3SC8 1 www.sassin.com V 27.1 Super Series / 1-223
Technical specifications for auxiliary contacts incorporated in the contactor 3SC8 Standard: IEC 60947-5-1 Number of auxiliary contacts: 2, 4 Mounting type: Front, side Conventional heating current (A): 10 Rated operational voltage Ue (V): Up to 690 Rated insulation voltage Ui (V): 690 Conventional thermal current Ith (A): 10 Minimum switching capacity Imin (mA): 5 Short circuit protection (A): gG fuse: 10 A Rated making capacity (A): 140 Technical specifications for time delay contact incorporated in the contactor 3SC8 Standard: IEC 60255-5 Number of contacts: 2 Mounting type: Front Delay time type making time delay, breaking time delay Timing ranges: 0.1-3, 0.1-30, 10-180 Repeat accuracy: ± 3 % (10 ms minimum) Reset time During time delay period (ms): 150 After time delay period (ms): 50 Conventional heating current (A): 10 Rated operational voltage Ue (V): Up to 690 Rated insulation voltage Ui (V): 250 Conventional thermal current Ith (A): 10 Technical specifications for coil incorporated in contactor 3SC8 Pick-up (VA) Holding (VA) Power (W) Coil consumption Type 3SC8-09 3SC8-12 3SC8-18 3SC8-25 3SC8-32 3SC8-40 3SC8-50 3SC8-65 3SC8-80 3SC8-95 70 9.0 10 2~3.5 100 10 11 3~4 245 30 32 6~10 50 Hz, 60 Hz 50/60 Hz 245 30 32 6~10 245 30 32 6~10 245 30 32 6~10 245 30 32 6~10 100 10 11 3~4 70 9.0 10 2~3.5 70 9.0 10 2~3.5 Coil voltage of contactor 3SC8 Coil voltage Us (V) 115 FE5 - FE7 240 U5 U6 U7 660/690 Y5 Y6 Y7 50 Hz 60 Hz 50/60 Hz 550/600 600/660 - - X7 550 SC5 - - 480 T5 - - 415 N5 - N7 380 Q5 Q6 Q7 127 FC5 - FC7 220 M5 M6 M7 12 J5 - J7 24 B5 B6 B7 36 - - CC7 48 E5 E6 E7 100 - - K7 120 G5 - - 265 - - W7 600 X5 - - 500 S5 - S7 440 R5 R6 R7 400 V5 - V7 208 LE5 - - 230 P5 - P7 20 - - Z7 32 C5 - C7 42 D5 - D7 60 - - EE7 110 F5 F6 F7 Contactors Series 3SC8 1 1-224 / V 27.1 Super Series www.sassin.com
230 Selection and ordering data Type code Order code 50/60 Standard control circuit voltages (V AC) Rated frequency (Hz) Rated operational current in category AC-3 400 V (A) Number of poles Instantaneous auxiliary contacts 9 3 - 1 - 3 - - 1 4 3 - - - 1 - 1 12 2 2 - - 3 - 1 - 3 - - 1 4 3 - - - 1 - 1 3 3 - - 1 1 2 2 1 1 - - 3 - 1 - 3 3 - - - 1 1 1 18 C8N 0910P7 C8N 0901P7 C8N 0911P7 C8N 09004P7 C8N 09008P7 C8N 1210P7 C8N 1201P7 C8N 1211P7 C8N 12004P7 C8N 12008P7 C8N 1810P7 C8N 1801P7 C8N 1811P7 C8N 2510P7 C8N 2501P7 C8N 2511P7 C8N 25004P7 C8N 25008P7 C8N 3210P7 C8N 3201P7 C8N 3211P7 C8N 4011P7 C8N 40004P7 C8N 40008P7 C8N 5011P7 C8N 50004P7 C8N 50008P7 C8N 6511P7 C8N 65004P7 C8N 65008P7 C8N 8011P7 C8N 80004P7 C8N 80008P7 C8N 9511P7 C8N 95004P7 C8N 95008P7 27432 27431 27433 27451 27452 27435 27434 27436 27453 27454 27438 27437 27439 27441 27440 27442 27455 27456 27444 27443 27445 27446 27457 27458 27447 27459 27460 27448 27461 27462 27449 27463 27464 27450 27465 27466 4 - - - 2 2 - - 4 - - - 2 2 - - 40 3 - 1 - 3 - - 1 32 3 - 1 1 50 65 80 95 4 - - - 2 2 - - 3 - 1 1 4 - - - 2 2 - - 3 - 1 1 4 - - - 2 2 - - 3 - 1 1 4 - - - 2 2 - - 3 - 1 1 3 - 1 - 3 - - 1 25 Please contact us for other coil voltage and frequency listed in "coil voltage of contactor" on page 1-222 Type code Order code 9 12 18 25 32 40 50 65 80 95 Rated operating current 400 V AC-3 (A) Standard power ratings of 3 phase motors 50-60 Hz AC-3 220 V 230 V (KW) 230 V 50 Hz Please contact us for other coil voltage 2.2 3 4 5.5 7.5 11 15 18.5 22 25 4 5.5 7.5 11 15 18.5 22 30 37 45 4 5.5 9 11 15 22 30 37 45 45 C8 DN9P5 C8 DN12P5 C8 DN18P5 C8 DN25P5 C8 DN32P5 C8 DN40P5 C8 DN50P5 C8 DN65P5 C8 DN80P5 C8 DN95P5 15913 15914 15915 15916 15917 15918 15919 15920 15921 15922 3SC8-DN reversing contactors 4 5.5 9 11 15 22 25 37 45 45 3 3 3 3 3 3 3 3 3 3 5.5 7.5 10 15 18.5 30 33 37 45 45 Please contact us for other coil voltage and frequency listed in "coil voltage of contactor" on page 1-222 Poles 380 V 400 V (KW) 415 V (KW) 440 V (KW) 660 V 690 V (KW) 230 V 50/60 Hz Please contact us for other coil voltage Contactors Series 3SC8 1 www.sassin.com V 27.1 Super Series / 1-225
Type code Order code Standard control circuit voltage (V AC) Rated frequency (Hz) Coil for contactor 3SC8 Voltage code 3SC8X-D2 for AC contactor 3SC8-9...18 3SC8X-D4 for AC contactor 3SC8-25...32 3SC8X-D6 for AC contactor 3SC8-40...95 24 48 110 127 220 230 240 380 400 440 24 48 110 127 220 230 240 380 400 440 24 48 110 127 220 230 240 380 400 440 24 48 110 127 220 230 240 380 400 440 24 48 110 127 220 230 240 380 400 440 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 B7 E7 F7 FC7 M7 P7 U7 Q7 V7 R7 B7 E7 F7 FC7 M7 P7 U7 Q7 V7 R7 B7 E7 F7 FC7 M7 P7 U7 Q7 V7 R7 B7 E7 F7 FC7 M7 P7 U7 Q7 V7 R7 B7 E7 F7 FC7 M7 P7 U7 Q7 V7 R7 C8X-D2B7 C8X-D2E7 C8X-D2F7 C8X-D2FC7 C8X-D2M7 C8X-D2P7 C8X-D2U7 C8X-D2Q7 C8X-D2V7 C8X-D2R7 C8X-D4B7 C8X-D4E7 C8X-D4F7 C8X-D4FC7 C8X-D4M7 C8X-D4P7 C8X-D4U7 C8X-D4Q7 C8X-D4V7 C8X-D4R7 C8X-D2NB7 C8X-D2NE7 C8X-D2NF7 C8X-D2NFC7 C8X-D2NM7 C8X-D2NP7 C8X-D2NU7 C8X-D2NQ7 C8X-D2NV7 C8X-D2NR7 C8X-D4NB7 C8X-D4NE7 C8X-D4NF7 C8X-D4NFC7 C8X-D4NM7 C8X-D4NP7 C8X-D4NU7 C8X-D4NQ7 C8X-D4NV7 C8X-D4NR7 C8X-D6B7 C8X-D6E7 C8X-D6F7 C8X-D6FC7 C8X-D6M7 C8X-D6P7 C8X-D6U7 C8X-D6Q7 C8X-D6V7 C8X-D6R7 17359 25323 32043 32046 17362 32049 32052 32055 27278 32058 17360 25324 32044 32047 17363 32050 32053 32056 27279 32059 14101 14102 14103 14104 14105 14106 14107 14108 14109 14110 14111 14112 14113 14114 14115 14116 14117 14118 14119 14120 17361 25325 32045 32048 17364 32051 32054 32057 27280 32060 Please contact us for other coil voltages. Suitable for contactors with auxiliary contact 1NO or 1NC Suitable for contactors with auxiliary contact 1NO+1NC Suitable for contactors with auxiliary contact 1NO or 1NC Suitable for contactors with auxiliary contact 1NO+1NC Selection and ordering data Contactors Series 3SC8 1 1-226 / V 27.1 Super Series www.sassin.com
Model code A1: Front type A1C: Side type A1D: Front type Delay type A2: Making time-delay A3: Breaking time-delay Auxiliary contact Code of auxiliary contact 02: 2NC 11: 1NO+1NC 20: 2NO 04: 4NC 13: 1NO+3NC 22: 2NO+2NC 31: 3NO+1NC 40: 4NO Delay scope T0: 0.1-30 s (A2) T2: 0.1-30 s (A2) T4: 10-180 s (A2) R0: 0.1-30 s (A3) R2: 0.1-30 s (A3) R4: 10-180 s (A3) Series code Series code C8 C8 A1 A2 02 T0 Instruction of type code Time-delay auxiliary contact Instruction of type code Auxiliary contacts Auxiliary contacts Selection and ordering data Mounting type Delay type Front Front Front Side making time-delay breaking time-delay Type code Type code Order code Order code 0 1 2 0 1 2 3 4 1 0 1 1 C8 A1/02 C8 A1/11 C8 A1/20 C8 A1/04 C8 A1/13 C8 A1/22 C8 A1/31 C8 A1/40 C8 A1D/10 C8 A1D/01 C8 A1C C8 A2/T0 C8 A2/T2 C8 A2/T4 C8 A3/R0 C8 A3/R2 C8 A3/R4 29578 29579 29580 29581 29582 29583 29584 29585 29587 29588 29586 29589 29590 29591 29592 29593 29594 2 1 0 4 3 2 1 0 0 1 1 1 Auxiliary contact blocks Time-delay auxiliary contact 0.1~3 s 0.1~30 s 10~180 s 0.1~3 s 0.1~30 s 10~180 s Delay scope 3SC8-09...32 3SC8-40...95 Type code Order code 3SC8-A4X 3SC8-A4D 29595 29596 Mechanical interlock Matched contactor Contactors Series 3SC8 1 www.sassin.com V 27.1 Super Series / 1-227
Derivative products of AC contactor Time-delay auxiliary contact Thermal relay Time-delay auxiliary contact Contactor DOL Starter Star-delta starter Mechanical interlock Auxiliary block Reversing contactor Capacitor Switching Contactor Auxiliary contact block Contactors Series 3SC8 1 1-228 / V 27.1 Super Series www.sassin.com
For breaking control when AC-3 type work. ( Ue ≤ 440 V) The breaking current is equal to rated making current. operating times(million) Notes: Asynchronous, P = 5.5 kW, Ue = 400 V, Ie = 11 A, Ic = Ie = 11 A motor or asynchronous, P = 5.5 kW, Ue = 415 V, Ie = 11 A, Ic = Ie = 11 A For 30 million electrical life. Frequency (kW-50 Hz) 10 8 6 4 2 1.5 1 0.8 0.6 0.5 2 3 4 5 6 7 8 9 10 12 15 18 20 25 30 32 40 50 65 80 95115 150 200 kW kW kW 0.55 0.75 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 1.5 25 220 V 380 V 440 V 0.75 1.5 2.2 4 1.5 2.2 4 5.5 5.5 7.5 7.5 11 11 15 15 18.5 18.5 22 22 30 30 37 45 55 75 3SC8-E 3SC8-K 3SC8-09 3SC8-12 3SC8-18 3SC8-25 3SC8-32 3SC8-40 3SC8-50 3SC8-65 3SC8-80 3SC8-95 3SC8-115 3SC8-150 Breaking current (A) Electrical life curve for AC contactor 3SC8 Outline and installation dimensions unit in mm D (A1) / E (A2) C B b A Ø B C D (A1) / E (A2) b A a Ø 3SC8-09...32 3SC8-40...95 3SC8-09...12 3SC8-18 3SC8-25 3SC8-32 3SC8-40...65 3SC8-80...95 3SC8-09...12 3SC8-25 3SC8-40...65 3SC8-80...95 3 4 2-Ø4.5 2-Ø4.5 2-Ø4.5 2-Ø4.5 3-Ø6.5 3-Ø6.5 2-Ø4.5 2-Ø4.5 3-Ø6.5 3-Ø6.5 Notes: The dimensions in brackets are for 008 (4P) type Type A max B max C max D max E max a b Ø 47 47 57 57 77 87 47 57 86 97 76 76 86 86 129 129 76 86 129 129 82 87 95 100 116 127 82 95 116 (129) 127 (140) 113 118 126 131 145 156 113 126 145 156 133 138 146 151 165 176 133 146 165 176 34/35 34/35 40 40 40 40 34/35 40 40 40 50/60 50/60 48 48 100/110 100/110 50/60 48 100/110 100/110 a Contactors Series 3SC8 1 www.sassin.com V 27.1 Super Series / 1-229
Applications and functions for AC contactor 3SC8-F Used for controlling 3-phase motors and generally for controlling power circuits. Used for many other applications such as isolation, capacitor switching and lighting. Instruction of type code Number of poles (P): 3, 4 Rated operating current in category AC-3 at 400 V AC (A): 115, 150, 185, 225, 265, 330, 400, 500, 630, 780 Model code Series code C8 F 115 3 Contactors Series 3SC8-F P5 Coil code Technical specifications for contactor 3SC8-F In AC-3 In AC-1 Up to 400 V 220/230/240 V 380/400 V 660/690 V Motor circuit (type aM) With thermal overload relay (type gG) gG fuses Front Side Front time delay Front dust and damp protected In AC-3 IEC 60947-4-1 1000 16-200 1000 8 50/60 10 × In AC-3 or 12 × In AC-4 8 × In AC-3 or 10 × In AC-4 identical to those used on 3SC8 contactors - identical to those used on 3SC8 contactors - 3SC8-FN IP20 -5 to +40, max. 95 % humidity -40 ~ +70 2000 Conforming to UL 94 V1 Model Standard Number of poles Rated operational current Ie (A) Rated operational voltage Ue (V) Frequency limits of the operational current (time/h) Rated conventional thermal current Ith (A) Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV) Rated frequency (Hz) Rated making capacity (A) Rated breaking capacity (A) Rated operational power in category AC-3 (kw) Short-circuit protection by fuse (A) Average impedance per pole (mW) Add-on auxiliary contact blocks Reversing contactor type Associated thermal overload relays Operation cycles (times/hour) 6 Electrical life (× 10 times) 6 Mechanical life (× 10 times) Matching fuse model Tightening torque (N·m) Connection Cabling cross section CU (mm²) Screw size Degree of protection Ambient air temperature (ºC) Storage temperature (ºC) Maximum operating altitude (meters) Flame resistance 3SC8-F115 3SC8-F150 3SC8-F185 3SC8-F225 3SC8-F265 3SC8-F330 3SC8-F400 3SC8-F500 3SC8-F630 3SC8-F780 3, 4 3, 4 3, 4 3, 4 3 3 3, 4 115 150 185 225 265 330 400 200 250 275 315 350 400 500 3, 4 3, 4 3, 4 500 630 780 700 1000 1600 200 250 275 315 350 400 500 700 1000 1600 30 40 55 68 75 100 129 55 75 90 100 132 160 200 80 100 120 129 180 220 280 125 160 200 250 315 400 400 200 200 315 315 500 500 630 0.37 0.35 0.33 0.32 0.3 0.28 0.26 3SR8-F73 1200 1200 600 600 600 600 600 1.2 1.2 1 1 0.8 0.8 0.8 10 10 6 6 6 6 6 RT16-1 RT16-1 RT16-2 RT16-2 RT16-2 RT16-3 RT16-3 0.8 0.8 0.8 1.2 1.2 1.2 1.2 95 120 150 185 240 240 2 x 150 M6 M8 M8 M10 M10 M10 M10 3SR8-F53 147 200 220 250 335 400 355 450 475 500 630 800 800 0.18 0.12 0.1 600 600 600 0.8 0.8 0.8 6 6 6 RT16-4 RT16-4 RT16-4 1.2 4 4 2 x 240 240 300 M12 M12 M4 200 250 315 315 400 500 500 800 1000 - - 1 1-230 / V 27.1 Super Series www.sassin.com
Selection and ordering data Type code Order code 115 150 185 225 265 330 400 500 630 780 Rated operating current 400 V AC-3 (A) Standard power ratings of 3 phase motors 50-60 Hz AC-3 220 V 230 V (KW) 230 V 50 Hz Please contact us for other coil voltage 200 220 275 315 350 400 500 700 1000 1500 55 75 90 110 132 165 200 250 335 400 C8 F1153P5 C8 F1154P5 C8 F1503P5 C8 F1504P5 C8 F1853P5 C8 F1854P5 C8 F2253P5 C8 F2254P5 C8 F2653P5 C8 F2654P5 C8 F3303P5 C8 F3304P5 C8 F4003P5 C8 F4004P5 C8 F5003P5 C8 F5004P5 C8 F6303P5 C8 F6304P5 C8 F7803P5 C8 F7804P5 12093 12103 12094 12104 12095 12105 12096 12106 12097 12107 12098 12108 12099 12109 12100 12110 12101 12111 12102 12112 3SC8-F contactor 30 40 55 63 75 100 115 147 200 220 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 59 80 100 110 140 180 220 280 375 425 Poles 380 V 400 V (KW) 415 V 440 V (KW) Conventional thermal current (A) Type code Order code 115 150 185 225 265 330 400 500 630 780 Rated operating current 400 V AC-3 (A) Standard power ratings of 3 phase motors 50-60 Hz AC-3 220 V 230 V (KW) 230 V 50 Hz Please contact us for other coil voltage 200 250 275 315 350 400 500 700 1000 1500 55 75 90 110 132 165 200 250 335 400 C8 FN115P5 C8 FN1154P5 C8 FN150P5 C8 FN1504P5 C8 FN185P5 C8 FN1854P5 C8 FN225P5 C8 FN2254P5 C8 FN265P5 C8 FN2654P5 C8 FN330P5 C8 FN3304P5 C8 FN400P5 C8 FN4004P5 C8 FN500P5 C8 FN5004P5 C8 FN630P5 C8 FN6304P5 C8 FN780P5 C8 FN7804P5 15718 15719 15720 15721 15722 15723 15724 15725 15726 15727 15728 15729 15730 15731 15732 15733 15734 15735 15736 15737 3SC8-FN reversing contactors 30 40 55 63 75 100 115 147 200 220 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 60 80 100 120 140 180 220 280 375 425 Poles 380 V 400 V (KW) 415 V 440 V (KW) Conventional thermal current (A) Contactors Series 3SC8-F 1 www.sassin.com V 27.1 Super Series / 1-231
Selection and ordering data 3SC8X-FF for AC contactor 3SC8-F115...150 3SC8X-FG for AC contactor 3SC8-F185...225 3SC8X-FH for AC contactor 3SC8-F265...330 3SC8X-FJ for AC contactor 3SC8-F400 3SC8X-FK for AC contactor 3SC8-F500 3SC8X-FL for AC contactor 3SC8-F630 3SC8X-FX for AC contactor 3SC8-F780 Type code Order code Standard control circuit voltage (V AC) Rated frequency (Hz) Coil for contactor 3SC8-F Voltage code 240 50/60 U7 440 50/60 R7 230 50/60 P7 380 50/60 Q7 230 50/60 P7 240 50/60 U7 380 50/60 Q7 440 50/60 R7 230 50/60 P7 240 50/60 U7 380 50/60 Q7 440 50/60 R7 230 50/60 P7 240 50/60 U7 380 50/60 Q7 440 50/60 R7 230 50/60 P7 240 50/60 U7 380 50/60 Q7 440 50/60 R7 230 50/60 P7 240 50/60 U7 380 50/60 Q7 440 50/60 R7 230 50/60 P7 240 50/60 U7 380 50/60 Q7 440 50/60 R7 C8X-FFP7 32002 C8X-FFU7 32003 C8X-FFQ7 32004 C8X-FFR7 32006 C8X-FGP7 32008 C8X-FGU7 32009 C8X-FGQ7 32010 C8X-FGR7 32012 C8X-FHP7 32014 C8X-FHU7 32015 C8X-FHQ7 32016 C8X-FHR7 32018 C8X-FJP7 32020 C8X-FJU7 32021 C8X-FJQ7 32022 C8X-FJR7 32024 C8X-FKP7 32026 C8X-FKU7 32027 C8X-FKQ7 32028 C8X-FKR7 32030 C8X-FLP7 32032 C8X-FLU7 32033 C8X-FLQ7 32034 C8X-FLR7 32036 C8X-FXP7 32038 C8X-FXU7 32039 C8X-FXQ7 32040 C8X-FXR7 32042 Contactors Series 3SC8-F 1 1-232 / V 27.1 Super Series www.sassin.com
Outline and installation dimensions (Series 3SC8-F) unit in mm 3SC8-F115...330 163.5 200.5 163.5 200.5 168.5 208.5 168.5 208.5 201.5 244.5 213 261 115 150 185 225 265 330 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 21.5 21.5 20.5 20.5 f = minimum distance required for coil removal 171 171 171 171 181 181 181 181 213 213 219 219 106 143 106 143 111 151 111 151 142 190 154.5 202.5 106 106 106 106 106 106 106 106 106 106 106 106 107 107 107 107 113.5 113.5 113.5 113.5 141 141 145 145 37 37 40 40 40 40 48 48 48 48 48 48 60 60 57.5 55.5 59.5 59.5 51.5 47.5 66.5 66.5 74 74 26 26 34 34 34 34 44.5 44.5 44.5 44.5 44.5 44.5 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 162 162 170 170 174 174 197 197 203 203 206 206 131 131 131 131 130 130 130 130 147 147 147 147 80 80 80 80 80 80 80 80 96 96 96 96 120 120 120 120 120 120 120 120 120 120 120 120 147 147 150 150 154 154 172 172 178 178 181 181 29.5 29.5 26 26 29 29 21 17 39 34 43 43 20 20 20 20 20 20 25 25 25 25 25 25 44 44 44 44 44 44 44 44 38 38 38 38 137 137 137 137 137 137 137 137 145 145 145 145 265 265 301 301 305 305 364 364 375 375 375 375 3SC8-F a b b1 b2 c f G G1 J J1 L M P Q Q1 S 1 Y Z F115 M6X25 F150 M8X25 F185 M8X25 F225 M10X355 F265 M10X355 F330 M10X355 S M Q P P Q1 a f X1 II X1 c L II b b2 3xØ6.5 Z II II II b1 J J1 G1 G Y II unit in mm 3SC8-F400...500 S 44.5 6xM10x35 M Q P P Q1 a f X1 56 X1 L c II II 209 b b2 8xØ8.5 120 180 G 23.5 G1 II II II II J 213 213 261 233 233 288 400 500 25 25 25 30 30 30 119 119 119 141 141 141 66 66 66 66 66 66 170 170 170 170 170 230 192 192 240 210 210 265 145 145 145 146 146 146 48 48 48 55 55 55 96 74 74 102 77 77 2P 3P 4P 2P 3P 4P 206 206 206 238 238 288 80 80 80 80 80 140 102 102 150 120 120 175 156 156 156 156 156 156 19.5 19.5 67.5 39.5 39.5 34.5 181 181 181 208 208 208 69 43 43 76 46 46 375 375 375 400 400 400 219 219 219 232 232 232 3SC8-F a b b2 c f G* G min. G max. G1* G1 min. G1 max. J L M P Q Q1 S Contactors Series 3SC8-F 1 www.sassin.com V 27.1 Super Series / 1-233
72 280 304 464 X1 X1 II II 155 197 255 40 64 6xM12x45 264 181 a Q 80 80 Q1 4xØ10.5 60.5 G J1 II II180 unit in mm 3SC8-F630...800 630 630, 800 630 2P 3P 4P 180 180 240 100 100 150 195 195 275 68.5 68.5 68.5 102 60 60 127 89 89 309 309 309 3SC8-F a G G min. G max. J1 Q Q1 Outline and installation dimensions (Series 3SC8-F) 165 255 X1 X1 II II280 434 183 191 160 160 191 3P=702, 4P=862 183 60 12xM12x45 26 II II 26 22 348 400 unit in mm 3SC8-F780 Contactors Series 3SC8-F 1 1-234 / V 27.1 Super Series www.sassin.com
Technical specifications 220/230 V 380/400 V 660/690 V 400 V Starting Holding 2NO 2NC 1NO + 1NC 2NO + 1NC 1NO + 2NC 4 10 4 10 screws 35mm DIN-rail 75mm DIN-rail max. Type Rated insulating voltage Ui Rated conventional thermal current Ith Controllable power AC-6b Rated current of capacitor Rated working current 1.3Ie Restrained surge capacity Coil consumed power Auxiliary contact type Mechanical life Electrical life Operating frequency Pollution grade Installation category Installation type Ambient air temperature Altitude 2 Coil sectional area (mm ) Tightening torque (N·m) Applications and functions Switching parallel connection capacitance from low voltage reactive power compensating equipments Reducing efficiently the impact to capacitor and restraining overvoltage when switching ON/OFF with special flow-cut equipment Instruction of type code Quantity of auxiliary contact 11: 1NO+1NC 02: 2NC 20: 2NO Rated thermal current Series code C19 25 11 P5 Coil code 3SC19-25 3SC19-32 3SC19-43 3SC19-50 3SC19-63 3SC19-95 3SC19-125 690 690 690 690 690 690 690 25 6 12 12 17.3 22.5 ≤ 20 Ie 70 9 √ √ √ - 300 10 120 3 3 - -5 ~ +40 2000 32 8.5 16 16 23 30 ≤ 20 Ie 100 10 √ √ √ - 300 10 120 3 3 - -5 ~ +40 2000 43 10 20 20 29 37.7 100 10 √ √ √ - 300 10 120 3 3 - -5 ~ +40 2000 50 12 25 25 36 47 245 30 - - - 100 6 120 3 3 - -5 ~ +40 2000 63 15 30 30 43 56 245 30 - - - √ √ 100 6 120 3 3 -5 ~ +40 2000 95 23 45 45 65 85 245 30 - - - √ √ 80 6 120 3 3 -5 ~ +40 2000 125 25 50 50 72 94 245 30 - - - √ √ 80 6 120 3 3 -5 ~ +40 2000 - - - 3SC19-80 ≤ 20 Ie ≤ 20 Ie ≤ 20 Ie ≤ 20 Ie ≤ 20 Ie 690 80 22 37 37 53 69 245 30 - - - √ √ 100 6 120 3 3 -5 ~ +40 2000 ≤ 20 Ie 4 6 10 10 16 25 35 50 1.7 2.0 2.5 5 5 5 9 9 V A Kvar Kvar Kvar A A VA VA times times times/h ºC meter Capacitor Switching Contactors Series 3SC19 √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ 1 www.sassin.com V 27.1 Super Series / 1-235
3SC19-2511 3SC19-3211 3SC19-4311 3SC19-2520 3SC19-3220 3SC19-4320 3SC19-2502 3SC19-3202 3SC19-4302 3SC19-5012 3SC19-6312 3SC19-8012 3SC19-9512 3SC19-12512 3SC19-5021 3SC19-6321 3SC19-8021 3SC19-9521 3SC19-12521 A2 A1 R R 13 21 NO NC 1 2 5 2 4 6 T1 T2 T3 L1 L2 L3 14 32 A2 A1 R R 13 23 NO NO 1 2 5 2 4 6 T1 T2 T3 L1 L2 L3 14 34 A2 A1 R R 21 31 NC NC 1 2 5 2 4 6 T1 T2 T3 L1 L2 L3 22 32 A2 A1 R R 13 21 NO NC 1 2 5 2 4 6 T1 T2 T3 L1 L2 L3 14 22 33 NO 34 A2 A1 R R 13 21 NO NC 1 2 5 2 4 6 T1 T2 T3 L1 L2 L3 14 22 31 NC 32 D C 35 B b a A 2רd D C n-Ø 35 b Selection and ordering data Terminal and electric diagram unit in mm Type 3SC19-25 3SC19-32 3SC19-43 3SC19-50 3SC19-63 3SC19-80 3SC19-95 3SC19-125 Outline dimensions Installation dimensions A B C a b C 47 57 57 77 77 77 87 87 76 86 86 129 129 129 129 129 124 132 136 152 152 152 162 162 100 110 110 155 155 155 165 165 34/35 40 40 40 40 40 40 40 2-Ø4.5 2-Ø4.5 2-Ø4.5 3-Ø6.5 3-Ø6.5 3-Ø6.5 3-Ø6.5 3-Ø6.5 50/60 50/60 50/60 100/110 100/110 100/110 100/110 100/110 D Outline and installation dimensions B a A Capacitor Switching Contactors Series 3SC19 Type code Order code Rated conventional thermal current Ith (A) Controllable power 220 V 230 V (KW) 230 V AC 50Hz Please contact us for other coil specifications Auxiliary 380 V contact 400 V (KW) 660 V 690 V (KW) 25 6 12 12 1 1 C19 2511 P5 27308 0 2 C19 2502 P5 27309 2 0 C19 2520 P5 27310 32 8.5 16 16 1 1 C19 3211 P5 27311 0 2 C19 3202 P5 27312 2 0 C19 3220 P5 27313 43 10 20 20 1 1 C19 4311 P5 27314 0 2 C19 4302 P5 27315 2 0 C19 4320 P5 27316 50 12 25 25 1 2 C19 5012 P5 27317 2 1 C19 5021 P5 27318 63 15 30 30 1 2 C19 6312 P5 27319 2 1 C19 6321 P5 27320 80 22 37 37 1 2 2 1 125 25 50 50 1 2 C19 12512 P5 27323 2 1 C19 12521 P5 27324 95 23 45 45 1 2 C19 9512 P5 25496 2 1 C19 9521 P5 25686 C19 8012P5 27321 C19 8021P5 27322 1 1-236 / V 27.1 Super Series www.sassin.com
Applications and functions for thermal relay Protecting the loads from overload and phase failure Implementing short-circuit protection by means of a fuse or circuit breaker. Used for the protection of motors. Instruction of type code Thermal overload relays Series 3SR8-K Code of setting current range Model code Series code R8 K 0301 Number of pins 3: 3 pins 5: 5 pins 3 Techinical specifications for assembled thermal relay of type 3SC8-K Type: 3SR8-K Standard: IEC 60947-4-1 Tripping class: 10 A Number of connecting pin: 4 Rated operational voltage Ue (V): up to 690 Rated insulation voltage Ui (V): 690 Rated impulse withstand voltage Uimp (kV): 6 Rated current range In (A): 0.11-0.16, 0.16-0.23, 0.23-0.36, 0.36-0.54, 0.54-0.8, 0.8-1.2, 1.8-2.6, 2.6-3.7, 3.7-5.5, 5.-8, 8-11.5, 10-14 Signalling: Trip indicator Tightening torque (N·m): 0.8 Degree of protection: IP20 Ambient air temperature (ºC): -5 to +40, max. 95 % humidity Storage temperature (ºC): -40 ~ +75 Maximum operating altitude (meters): 2000 Flame resistance: V1 Mounting: directly under the contactor Selection and ordering data 3SR8-K 5 Pins 3SR8-K thermal relay matched with contactor 3SC8-K Type code Order code 0.11-0.16 0.16-0.23 0.23-0.36 0.36-0.54 0.54-0.8 0.8-1.2 1.8-2.6 2.6-3.7 3.7-5.5 5.-8 8-11.5 10-14 Current setting range (A) Fuses to be used with selected relay aM Type (A) gG Type (A) 15594 15595 15596 15597 15598 15599 15600 15601 15602 15603 15604 15605 R8 K0301/5 R8 K0302/5 R8 K0303/5 R8 K0304/5 R8 K0305/5 R8 K0306/5 R8 K0308/5 R8 K0310/5 R8 K0312/5 R8 K0314/5 R8 K0316/5 R8 K0321/5 0.5 0.5 1 1.6 2 6 8 10 16 20 25 32 0.25 0.25 0.5 1 1 2 4 4 6 8 10 16 1 www.sassin.com V 27.1 Super Series / 1-237
Tripping curve of thermal relay 3SR8-K Average operating time related to multiples of the current setting (Class 10 A) Balanced 3-phase operation, from cold state Time 2h 1h 20 min 1h 40min 20min 10min 6min 4min 2min 1min 40s 20s 10s 6s 4s 2s 1s 1 1.2 1.5 2 3 4 5 6 8 10 15 X setting current (lr) 1 2 Balanced operation with 2 phases only, from cold state Time 2h 1h 20 min 1h 40min 20min 10min 6min 4min 2min 1min 40s 20s 10s 6s 4s 2s 1s 1 1.2 1.5 2 3 4 5 6 8 10 15 X setting current (lr) 1 Setting: at lower end of scale 2 Setting: at upper end of scale Outline and installation dimensions (3SC8-K, 3SR8-K) unit in mm 45 13 8.6 66.5 68.1 Thermal overload relays Series 3SR8-K 1 1-238 / V 27.1 Super Series www.sassin.com
1 Applications and functions for thermal relay 3SR8 Protecting the loads from overload and phase failure Implementing short-circuit protection by means of a fuse or circuit breaker. Used for the protection of motors. Instruction of type code Thermal overload relays Series 3SR8 Max. setting current range (A): 0.16: 0.1-0.16 0.25: 0.16-0.25 0.4: 0.25-0.4 0.63: 0.4-0.63 1: 0.63-1 1.6: 1-1.6 2: 1.25-2 2.5: 1.6-2.5 4: 2.5-4 6: 4-6 8: 5.5-8 Rated frame current (A): 25, 36, 93 Series code R8 25 0.16 10: 7-10 13: 9-13 18: 12-18 25: 17-25 32: 23-32 36: 28-36 40: 30-40 50: 37-50 65: 48-65 70: 55-70 80: 63-80 93: 80-93 Technical specifications for assembled thermal relay of type 3SR8 3SR8-D23 36 23-36 3SR8-D33 93 23-93 3SR8-D13 25 0.1-25 Type Standard Tripping class Rated working current Ie (A) Setting range (A) Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV) Signalling Trip indicator Tightening torque (N·m) Degree of protection Ambient air temperature (ºC) Storage temperature (ºC) Maximum operating altitude (meters) Flame resistance Mounting IEC 60947-4-1 10 A 690 6 Trip indicator 0.8 IP20 -5 to +40, max. 95 % humidity -40 ~ +75 2000 V1 Directly under the contactor 1 www.sassin.com V 27.1 Super Series / 1-239
Series 3SR8 Selection and ordering data Type code Order code 25 0.1~0.16 0.25 2 3SC8-09 R8 25/0.16 0.16~0.25 0.25 2 3SC8-09 R8 25/0.25 0.25~0.4 1 2 3SC8-09 R8 25/0.40 0.4~0.63 1 2 3SC8-09 R8 25/0.63 0.63~1 2 4 3SC8-09 R8 25/1 1~1.6 2 4 3SC8-09 R8 25/1.6 1.25~2 4 6 3SC8-09 R8 25/2 1.6~2.5 4 6 3SC8-09 R8 25/2.5 2.5~4 6 10 3SC8-09 R8 25/4 4~6 8 16 3SC8-09 R8 25/6 5.5~8 12 20 3SC8-09 R8 25/8 7~10 12 20 3SC8-12 R8 25/10 9~13 16 25 3SC8-12 R8 25/13 12~18 20 35 3SC8-18 R8 25/18 17~25 25 50 3SC8-25 R8 25/25 36 23~32 40 63 3SC8-32 R8 36/32 28~36 40 80 3SC8-32 R8 36/36 23~32 40 63 3SC8-40 R8 93/32 30~40 40 100 3SC8-40 R8 93/40 37~50 63 100 3SC8-50 R8 93/50 48~65 63 100 3SC8-65 R8 93/65 55~70 80 125 3SC8-80 R8 93/70 63~80 80 125 3SC8-80 R8 93/80 80~93 100 160 3SC8-95 R8 93/93 93 22875 22876 22877 22878 22879 22880 22881 22882 22883 22884 22885 22886 22887 22888 22889 22890 22891 22892 22893 22894 22895 22896 22897 22898 Current setting range (A) Matched AC gG contactor (A) aM (A) Rated frame Matched fuse type current (A) Mounting block Type code Order code Matechd relay 15971 15972 15973 R8 25 R8 36 R8 93 C8 A7D1064 C8 A7D2064 C8 A7D3064 Thermal overload relays Series 3SR8 1 1-240 / V 27.1 Super Series www.sassin.com
Outline and installation dimensions 3SR8-25 3SR8-36 3SR8-93 FU 3SC8 3SR8 SB1 SB2 1 3 5 A1 2 4 6 A2 1 3 5 2 4 6 97 98 95 96 U V W M 98 97 95 96 NO NC 56max 94max 78max 3SR8-36 2T1 4T2 6T3 NO NC 98 97 95 96 72max 117max 3SR8-93 2T1 4T2 6T3 83max unit in mm 98 97 95 96 NO NC 46max 94max 66max 3SR8-25 2T1 4T2 6T3 FU - fuse 3SC8 - AC contactor 3SR8 - thermal relay SB1 - stop button SB2 - start button Operating principle diagram of overload relay Action characterisitics for thermal relay 3SR8 Average operating time related to multiples of the current setting (Class 10 A) Balanced 3-phase operation, from cold state Time 2h 1h 20 min 1h 40min 20min 10min 6min 4min 2min 1min 40s 20s 10s 6s 4s 2s 1s 1 1.2 1.5 2 3 4 5 6 8 10 15 X setting current (lr) 1 2 Balanced operation with 2 phases only, from cold state Time 2h 1h 20 min 1h 40min 20min 10min 6min 4min 2min 1min 40s 20s 10s 6s 4s 2s 1s 1 1.2 1.5 2 3 4 5 6 8 10 15 X setting current (lr) 1 Setting: at lower end of scale 2 Setting: at upper end of scale Tripping curve for thermal relay 3SR8 1. Equilibrium running, 3 phase, start from cold state 2. Equilibrium running, 2 phase, start from cold state 3. Equilibrium running, 3 phase, after long period of setting current (hot state) 10A grade 0.8 1 2 4 6 10 17 20 0.8 1 2 4 10 20 40 1 2 4 10 20 40 1 2 1 2 3 Time Hours Minutes Seconds X times of current setting value Thermal overload relays Series 3SR8 1 www.sassin.com V 27.1 Super Series / 1-241
Applications and functions for thermal relay 3SR8-F Protecting the loads from overload and phase failure Implementing short-circuit protection by means of fuse or circuit breaker. Used for the protection of motors. Instruction of type code Thermal overload relays Series 3SR8-F Frame code F53 F73 Model code Series code R8 F 53 Max. setting range 50 Techinical specifications for thermal relay 3SR8-F IEC 60947-4-1 10 A, 20 A 1000 Manual on front of relay 1000 6 0.8 IP20 -5 to +40, max. 95 % humidity -40 ~ +75 2000 V1 3SR8-F73 630 200-630 3SR8-F53 220 30-220 Type Standard Tripping class Rated operational voltage Ue (V) Rated working current Ie (A) Setting range (A) Reset Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV) Tightening torque (N·m) Degree of protection Ambient air temperature (ºC) Storage temperature (ºC) Maximum operating altitude (meters) Flame resistance Selection and ordering data Type code Order code 30-50 48-80 60-100 90-150 132-220 200-330 300-500 380-630 Current setting range (A) Fuses to be used with selected relay maximum rating aM Type (A) 50 80 100 160 250 400 500 630 3SC8-F115…F185 3SC8-F115…F185 3SC8-F115…F185 3SC8-F115…F185 3SC8-F225…F265 3SC8-F225…F500 3SC8-F225…F500 3SC8-F400…F630 R8 F53/50 R8 F53/80 R8 F53/100 R8 F53/150 R8 F53/220 R8 F73/330 R8 F73/500 R8 F73/630 15710 15711 15712 15713 15714 15715 15716 15717 3SR8-F thermal relay matched with contactor 3SC8-F 80 125 200 250 315 500 800 800 Matched contactor gG Type (A) 1 1-242 / V 27.1 Super Series www.sassin.com
Time X current setting (1r) 2h 1h 40mm 20mm 10mm 4mm 2mm 1mm 40s 20s 10s 4s 2s 1s 0.8s 0.8 1 2 4 6 10 17 20 Tripping curve for thermal relay 3SR8-F 123.5 3 56.8 3 46.8 44.8 101 76 48 48 25 125 Ø11 120 5.5 60 50 50 4xØ5.5 71 127.6 42.2 6 44.8 30 14 108.8 22 25 6 82 136.8 Ø11 4xØ5.5 51.5 51.5 66 66 150 70 Outline and installation dimensions (Series 3SR8-F) unit in mm 3SR8-F53 3SR8-F73 Thermal overload relays Series 3SR8-F 1 www.sassin.com V 27.1 Super Series / 1-243
Technical specifications Applications and functions Controlling the direct start and halt of the electromotor Protecting the motor from overload and phase failure Used in remote making and breaking circuit and frequently starting and controlling motor. Instruction of type code Rated working current in category AC-3 Series code Q1 09 P5 Coil code Type: 3SQ1 Standards: IEC 60947-4-1, IEC 60439-1 Rated working current (A): 09, 12, 18, 25, 32, 40, 50, 65, 80, 95 Rated operational voltage Ue (V): 690 Rated insulation voltage Ui (V): 690 Rated impulse withstand voltage Uimp (kV): 8 Rated frequency (Hz): 50/60 Control (2 pushbuttons mounted on enclosure cover): 1 green Start button “I”; 1 red Stop/Reset button “O” Enclosure: 3SQ1-09/12/18 Double insulated, degree of protection IP65; 3SQ1-25/32 Double insulated, degree of protection IP55; 3SQ1-40/50/65/80/95 Metal, degree of protection IP65 5 Electrical life (× 10 times): 5 5 Mechanical life (× 10 times): 50 The model of matched AC contactor: 3SC8 The model of matched thermal relay: 3SR8 Ambient air temperature (ºC): -5 to +40, max. 95 % humidity Storage temperature (ºC): -40 ~ +75 Maximum operating altitude (meters): 2000 Rated working current in category AC-3, 380 V (A) Conventional thermal current Ith (A) Type code of matched contactor Type code of matched thermal relay Type code Order code Standard power ratings of 3 phase motors 50-60 Hz in category AC-3 220 V 230 V (KW) 230 V 50 Hz Please contact us for other coil voltage 380 V 400 V (KW) 660 V 690 V (KW) 2.2 5.5 9 20 R8 D13 Q1 09P5 25606 3 7.5 12 20 R8 D13 Q1 12P5 25607 4 9 18 32 R8 D13 Q1 18P5 25608 5.5 15 25 40 R8 D13 Q1 25P5 25609 7.5 18.5 32 50 R8 D13 Q1 32P5 25610 11 30 40 60 R8 D33 Q1 40P5 25611 15 33 50 80 R8 D33 Q1 50P5 25612 4 5.5 7.5 11 15 18.5 22 C809 C812 C818 C825 C832 C840 C850 18.5 37 65 80 R8 D33 Q1 65P5 25613 22 45 80 110 R8 D33 Q1 80P5 25614 25 30 37 45 45 95 125 R8 D33 Q1 95P5 25615 C865 C880 C895 Selection and ordering data Dol Starters Series 3SQ1 1 1-244 / V 27.1 Super Series www.sassin.com