The words you are searching are inside this book. To get more targeted content, please make full-text search by clicking here.

Frenger Systems is a world-renowned specialist manufacturer of space conditioning products for indoor climate / environments.

Discover the best professional documents and content resources in AnyFlip Document Base.
Search
Published by webmaster, 2017-02-23 09:09:00

Frenger Systems Company Profile

Frenger Systems is a world-renowned specialist manufacturer of space conditioning products for indoor climate / environments.

Installation

Wall Mounted

Performance Features

The Wall Mounted Aluminium Frengerwarm Radiant Panel
is designed to provide heat output in excess of 460 W / m²,
(based on F&R 82 / 71°C, RT 21°C and 150mm tube centres),
whilst maintaining its aesthetic qualities and strength as
required for environments such as sports halls, assembly
rooms and other large open plan areas.

Panel Dimensions

Panels are available between 400 - 1100mm high / wide
mounted vertically off the wall utilizing purpose made wall
mounting brackets and M8 adjustable tie rods at an angle
variant of between 20 - 30° (adjustable dependent on
project requirements). Panel run lengths sized in order to meet
heating requirements and space restrictions comprise dummy
sections for access and main active section lengths.

Optional Extras

Purpose made top and end closure plates in order to deflect
foreign objects from the reverse of the panels, painted to suit,
available as required.

Free Hanging

Performance Features

The Free Hanging Aluminium Frengerwam Radiant Panel
is designed to provide heat output in excess of 450 W / m²,
(based on F&R 82 / 71°C, RT 21°C and 150mm tube
centres), whilst maintaining its aesthetic qualities and
unobtrusive design as required for environments where wall
space is at a premium.

Panel Dimensions

Panels available between 400 - 1100mm wide mounted
horizontally using M8 expansion anchors, M8 threaded rod
secured to the panel via 38 x 19mm suspension channel
generally located at 1.5m centres. Panel run lengths sized in
order to meet heating requirements and spce restrictions
comprise main active section lengths with access plates
concealing interconnections.

101

Surface Mounted

Performance Features

The Ceiling Mounted / Recessed Aluminium Frengerwarm
Radiant Panel is designed to provide heat output in excess of
450 W / m², (based on F&R 82 / 71°C, RT 21°C and 150mm
tube centres), whilst maintaining its aesthetic qualities and
unobtrusive design as required for environments where wall
space is at a premium.

Panel Dimensions

Panels between 400 - 1100mm wide mounted horizontally
using ‘Torx’ head screws (or similar) fitted via M6 countersunk
holes to pre-located angle iron. Panel run lengths sized in
order to meet heating requirements and space restrictions
comprise main active section lengths with access plates
concealing interconnections.

Optional Extras

Purpose made top and end closure plates in order to deflect
foreign objects from the reverse of the panels, painted to suit,
available as required.

Recessed

Performance Features

The Ceiling Mounted / Recessed Aluminium Frengerwarm
Radiant Panel is designed to provide heat output in excess
of 450 W / m², (based on F&R 82°C / 71°C, RT 21°C and
150mm tube centres), whilst maintaining its aesthetic qualities
and unobtrusive design as required for environments where
wall space is at a premium.

Panel Dimensions

Panels available between 400 - 1100mm wide mounted
horizontally using M8 expansion anchors, M8 threaded rod or
‘Gripple’ hang fast wiring secured to the panel via 38 x 19mm
suspension channel generally located at 1.5m centres. Panel
run lengths sized in order to meet heating requirements and
space restrictions comprise main active section lengths with
access plates concealing interconnections.

102

Heating Effect

Q W / m²

10 30 40 50 60

56.5

tw-tro°C

Graph detailing heat emission for ceiling mounted Aluminium Frengerwarm. Output in W / m².

103

Coupling & Connection

Connection to the pipework should be diagonal corners of the
panels or groups of panels, to ensure an even flow through the
pipe system an allowance must be made in the
interconnecting pipework for venting and draining if this is not
designed into the panel pipe system.

Thermal Expansion

The panels will accommodate their own pipe system
expansion but allowance should be made in the
interconnecting pipework. The design of the installation will
allow for expansion of the heated panels in relation to other
parts of the building structure and either a small gap or cover
strip is provided to accommodate the movement. The design
of the system must give turbulent flow in the pipes.

Typical section through Frengerwarm extrusion

104

Dimensions

Width, Depth mm

69mm

Minimum 100mm upwards
(W)

Lengths mm

(Upto 3000mm as a single panel) N/A
(L)
Dependent on size
Weight & Water Volume and design

Weight of the operating system is dependent on the design of Approx 1.5mm
the system but does not exceed 37 kg / m² and can be as low
as 21 kg / m².

Panel Weight, kg / linear metre
Water content, litres / linear metre
Expansion at 55°C above ambient

Copper pipe specification

The copper pipe used in the manufacture of the Frengerwarm
heating panel is compatible with the European Standard for
Copper Tubes EN12449 / EN12735-2. The dimensional
specification are as follows;

Outside Diameter (D): 15mm
Wall Thickness (T): 0.38mm
Minimum Straight Length (L): 35mm

105

Testing Protocols

Testing Protocols

All pipework manufactured on Frengerwarm panels are
pressure tested to 7 bar.

Thermal Insulation

Frengerwam is supplied as standard with 60mm thick Mineral
Wool blankets backed with Class ‘O’ reinforced heat reflecting
metal foil.

Panels

Material depends on the application.
Aluminium - 1.5 - 2.0mm thich NS3 / H4 aluminium sheet.
The radiating panel can be supplied with edges formed to suit
the individual application. Non radiating ‘in fill’ panels can be
supplied to form a continuous covering for the wall, column or
ceiling. Access panels with ‘secret’ fixings are a standard part
of the range.

Pipework attachment system

Aluminium Frengerwarm - the copper tube coil is inserted
within a patented extruded aluminium heat carrier. The
aluminium heat carrier is bonded to the panel. Heat transfer
paste is used at all interfaces for both types of Frengerwarm.

106

Fixing

Fixing

An installation service is provided by Frenger. However, supply
only can be accommodated. The following notes are provided
so that during design of the heating system for the building,
due account can be taken of the various requirements for
fixing Frengerwarm.
Frengerwarm is wall, column or ceiling mounted and
individually tailored for the installation.

Attachment

As each Frengerwarm installation is individually designed, the
means of attachment will be engineered for the specific
situation. Frengerwarm may therefore be attached to any
substantial building structure.

Pipework

Connection to the pipework should be at diagonal corners of
the panels or groups of panels, to ensure an even flow through
the pipe system an allowance must be made in the
interconnecting pipework for venting and draining if this is not
designed into the panel pipe system.
Expansion: The panels will accommodate their own pipe
system expansion buy allowance should be made in the
interconnecting pipework. The design of the installation will
allow for expansion of the heated panels in relation to other
parts of the building structure and either a small gap or cover
strip is provided to accommodate the movement. The design
of the system must give turbulent flow in the pipes.

Installation of panels and insulation

Frengerwarm is supplied as completed panels with the
pipework and insulation attached, it is therefore important to
protect the surface of the panel from damage during
construction or to schedule the fixing of Frengerwarm as one
of the final constructin operations. All the necessary water
piping can be installed at an earlier date as this is normally
hidden behind the Frengerwarm panels.

107

Optional Extras

The following optional extras are available for Frengerwarm.

Panels

Unheated ‘dummy’ panels and cover strips. A range of
extruded aluminium edge and tee trims. Radius Edges
(Bullnosed).

Pipework

15MM OD copper, to EN12449 / EN12735-2 Final flow and
return connections to suit customer’s requirements.
Thermostatic controls and air vents.

Colours

RAL 9010 Matt White powdercoat as standard. However other
RAL colours are available.

Operations &
maintenance

Frengerwam is incorporated into a building’s heating / cooling
system and is completely trouble free, however a few simple
precautions should be taken and inspections made during
start up and maintenance.

Operations

There will be no problems when starting up the system on hot
or cold water if the drain valves are shut and any air has been
vented from the system.

Any thermostatic controls on the panels should be set to the
required temperature.

Maintenance

Apart from cleaning any strainers no maintenance should be
required on the pipework system. Any descaling of pipework
should be carried out in the same way as for normal heating
systems,

Operation of the thermostatic controls should be checked
periodically.

During a period when the heating / cooling system is not in use
the opportunity should be taken to inspect any damaged
panels. Damage to a panel may cause the water pipes to
become detached and hence reduce their heating effect.

Cleaning the panels

The outside of the panels hmaavyebbeeccolemaneesdoiulesdin.g a damp cloth
and mild detergent if they

108

PCP Frengerwarm Ceiling Panel

Introduction

The PCP Frengerwarm Ceiling Panel is a secure and efficient
space heating product with achievable capacities of up to 378
w / m @ 57.5 dtK - performance data in accordance with the
latest European Standard EN14037.

The PCP panel heats via water-carrying copper coils which
are fixed within extruded Aluminium pipe seats. In turn, the
pipe seats are securely bonded to the robost 2.0mm thick
Steel outer casing. To optimise heat emission the heat is
directed into the room by a layer of mineral wool insulation
fitted to the reverse of the panel over the copper coil. The units
are made up into sets comprising at least one active
section and a number of ‘dummy’ sections all to suit any
particular environment and to simplify the installation process.
All panels are finished in a tough polyester paint finish.

Installation

The PCP Frengerwarm ceiling panel is designed to be
installed utilising the pre-drilled mounting rails supplied within
the kit. For maximum security and to ensure full NOMS
custodial property compliance it is important to install the
product level and that any gaps due to building tolerance
concealed are with suitable NOMS approved non-pickable
sealant.

All fixing joints between the panel and pre-drilled rail should be
secured using suitable NOMS approved (M6 x 20 Stainless
Steel countersunk screw) secure fixings and loctite compound.

Key Product Features

Manufactured from robust 2.0mm thich Steel plate.
Interleaf joints and angles side profiles with pre-drilled holes
to allow for secure fixing using suitable NOMS approved
(M6 x 20 Stainless Steel countersunk screw) fixings and
Loctite compound.
Standardised active sections are integrated with
‘manufacturerd to suit’ dummy sections - each installation
tailored to meet the requirements of the selected
environment.
Three standardised panel widths to match most project
requirements.
Slimline panel depth of just 61mm.
Simple to clean and hygienic.
Maintenance panel allows for simple but secure access to
connection details and valve arrangements.

109

Dimensions

Panel Widths

The PCP Ceiling panel is available in three widths as
standard, 70mm, 420mm and 560mm. The width selected
depend on room aesthetics and heating capacity
requirements.

Panel Lengths

The PCP Ceiling panel sections are supplied with heating
circuit (active sections) or without heating circuit (dummy
sections).

A panel set is usually a combination of at least one active
section and a number of dummy sections tailored to suit the
particulat environment.

Active panel sections are available in any length up to
3000mm and are sized to meet the heating requirements.
Each panel set may include more than one active section
dependant on space and capacity requirements.

Dummy panels provided to finish a set and gain access to the
pipe connections are available in lengths from 150mm up to
3000mm as required.

Panel Depth

All panel variants are 61mm deep as standard.

Surface finish

Each PCP Ceiling panel section is powder coat finished to
RAL 9010 (20% Gloss) as standard - with an emissivity of
0.94.

Connections

All active sections will arrive complete with 15mm Dia
EN12449 / EN 12735 -2 Copper pipework circuits ready for on
site connection to the mains flow and return water services.

Insulation

Each active section is supplied complete with up to 50mm
thick - up to 45kg / m³ density mineral wool Class ‘O’ foil
b@ac1k0e°dCinassuslatatinodnawrdit.h a thermal conductivity of 0.040 W / mk

Panel Width PCP 420 Panel Type PCP 700
420mm PCP 560 700mm
Dry Weight 20.5 kg/m 560mm 29.1 kg/m
0.64 l/m 24.8 kg/m 1.28 l/m
Water Content 100mm 0.96 l/m 100mm

Minimum Distance 8.7 BAR 100mm 8.7 BAR
Between Fixings
13.0 BAR 8.7 BAR 13.0 BAR
Maximum Working
Pressure 13.0 BAR

Hydraulic Test
Pressure

110

Components

1. Ceiling Rails
3mm thick angles Zintec Steel rail with M6 Hex nutcerts
fitted to the reverse.

2. Casing
Panel casing manufactured from 2.0mm thick Zintec Steel
sheet - Outer face powder coated RAL9010 (20% Gloss +/-
5%).

3. Pipe work
Individual Pipework circuits manufactured from 15mm Dia
EN12449 / EN12735-2 Copper Tube. All joints completed
via standard solder fittings.

4. Pipe Seats
Manufactured from cut-to-length heat treated aluminium
6000 series alloy die extrusion.

5. End Wall Support Rail
3mm thick Zintec Steel rail with M6 Hex nutcerts fitted to the
reverse.

6. Insulation
Manufactured from factory clad up to 50mm thick Class ‘O’
foil backed mineral wool quilt - upto 45kg / m³ density
mineral wool.

7. Sealant
NOMS approved non pickable sealant to be applied to all
exposed gaps (Sealant supplied and applied by others).

8. Security fixings
NOMS approved M6 x 20 Stainless Steel coutersunk
security screw (Torx Head or similar) to be used to fix all
joints (Suitable screw to be supplied and fitted by others)
- A suitable thread locking compound should be used in con
junction with any fixings.

The amount of fixings per panel run will be determined by the
actual panel set length - however hole centres will be uniform
to provide maximum strength and security.

6 Insulation not shown for clarity.
Wall and ceiling fixings to be supplied by others.

111

Installation Guide

1. Site measurement as necessary for wall to wall installation 2. Install purpose made ‘cut to length’ ceiling mounting rails
to be provided (by others). Active sections to be standard and end support rails at the required centres. Ensure rails
length ‘dummy’ sections to be sized to complete overall are level and true to ensure secure panel interconnections.
panel set dimensions within the given space.

3. Install and fix active panel sections to the preinstalled level 4. Once Active panel sections are in position make mains
and true mounting rails using NOMS approved (M6 x 20 connections and install purpose made dummy sections.
Stainless Stell countersunk screws) security fixings and Use NOMS Approved (M6 x 20 Stainless Steel countersunk
thread locking compound. screws) security fixings and suitable thread locking
compound.

5. Apply NOMS approved non pickable sealant to all exposed 6. Remove ‘low-tack’ protective covering and clean exposed

gaps that may be created due to building tolerances. panel set surfaces.

Installation instructions are provided for guidance purposes only and may need to be modified dependant on the given
environment. Always ensure that mandatory and appropriate health and safety procedures are applied during the installation
process and that appropriate protective equipment worn.

112

Product Performance

Product performance based on and in accordance with EN14037.

PCP420 Panel PCP420 / 4-Pipe

741-p°iCpe unit, assuming water flow @ 82°C and water return @ Room Temp °C Capacity (W / lm)

21 178

20 181

19 185

18 189

k = 1.528*

PCP560 Panel PCP560 / 6-Pipe

761-p°iCpe unit, assuming water flow @ 82°C and water return @ Room Temp °C Capacity (W / lm)

21 267

20 272

19 278

18 284

k = 2.295*

PCP700 Panel PCP700 / 8-Pipe

Room Temp °C Capacity (W / lm)

21 355

20 363

19 371

78-1p°iCpe unit, assuming water flow @ 82°C and water return @ 18 378
k = 3.056*

Q = k (∆ T) ⁿ Q = Output w/m ‘Active Section
n = 1.1842

Prison Ceiling Panel - Heating Capacity k = Constant see table ‘*’

Heating Capacity (Watts / Linear metre)

Temperature Differential dtK
The thermal performance of Freger’s Prison Ceiling Panel has been tested in accordance with the European Standard EN14037.

Example: at water flow 82°C and return 71°C with a room temperature of 19°C, the PCP560 panel provides 278 W / lm heating capacity.
Please contact our Technical Services Department for advice on flow rates and pressure drops.
Pressure drop <5.0 kPa based on 3.0m panel with maximum flow rate of 0.08 kg/s.

113

PNP Frengerwarm Cornice Panel

Introduction

The PNP Frengerwarm Cornice Panel is a secure and efficient
space heating product with acievable capacities of up to 378
w / m @ 57.5 dtK - performance data in accordance with the
latest European Standard EN 14037.

The PNP panel heats via water-carrying copper coils which
are fixed within extruded aluminium pipe seats. In turn, the
pipe seats are securely bonded to the robust 2.0mm thick steel
outer casing to optimise heat emission. The heat is directed
into the room by a layer of mineral wool insulation fitted to the
reverse of the panel over the copper coil. The units are made
up into sets comprising at least one active section and a
number of ‘dummy’ sections all to suit any particular
environment and to simplify the installation process. All panels
are finished in a tough polyester paint finish.

Installation

The PNP Frengerwam Cornice panel is designed to be
installed utilising the pre-drilled mounting rails supplied with the
kit. For maximum security and to ensure full NOMS custodial
property compliance it is important to install the product level
and that any gaps due to building tolerance concealed are with
suitable NOMS approved non-pickable sealant.

All fixing joints between the panel and pre-drilled rail should be
secured using suitable NOMS approved (M6 x 20 Stainless
steel countersunk screws) secure fixings and loctite
compound.

Key Product Features

Manufactured from robust 2.0mm thick Steel plate.
Interleaf joints and angles side profiles with pre-drilled holes
to allow for secure fixing using suitable NOMS approved
fixings (M6 x 20 Stainless steel countersunk screws) and
Loctite compound.
Standardised active sections are integrated with
manufactured to suit dummy sections - each installation
tailored to meet the requirements of the selected
environment.
Three srandardised panel widths to match most project
requirements.
Simple to clean and hygienic.
Maintenance panels allows for simple but secure access to
connection details and valve arrangements.

114

Dimensions

Panel Widths

The PNP Cornice panel is available in three variants as
standard: 335mm, 434mm and 533mm. The variant selected
will depend on room aesthetics and heating capacity
requirements.

Panel Lengths

The PNP Cornice panel sections are supplied with heating
circuit (active sections) or without heating circuit (dummy
sections).

A panel set is usually a combination of at least one active
section and a number of dummy sections tailored to suit the
particular environment.

Active panel sections are available in any length up to
3000mm and are sized to meet the heating requirements.
Each panel set may include more than one active section
dependant on space and capacity requirements.

Dummy panels provided to finish a set and gain access to the
pipe connections are available in lengths from 150mm up to
3000mm as required.

Panel Depth

The Cornice panel vairants are available in three overall
product depths as standard - 335mm, 434mm and 533mm.

Surface Finish

Each PNP Cornice panel section is powder coat finished to
RAL9010 (20% Gloss) as standard - with an emissivity of 0.94.

Connections

All active sections will arrive complete with 15mm Dia
EN12449 / EN12735-2 Copper pipework circuits ready for on
site connection to the mains flow and return water services.

Instulation

Each active section is supplied complete with up to 50mm
thick - upto 45 kg / m³ density mineral wool Class ‘O’ foil
b@ac1k0e°dCinassuslatatinodnawrdit.h a thermal conductivity of 0.040 W / mk

Panel Depth PNP 335 Panel Type PNP 533
335mm PNP 434 533mm
Dry Weight 21.9 kg/m 434mm 29.9 kg/m
0.64 l/m 26.2 kg/m 1.28 l/m
Water Content 100mm 0.96 l/m 100mm

Minimum Distance 8.7 BAR 100mm 8.7 BAR
Between Fixings
13.0 BAR 8.7 BAR 13.0 BAR
Maximum Working
Pressure 13.0 BAR

Hydraulic Test
Pressure

115

Components

1. Ceiling / Wall Rails 6. Insulation
3mm thick angled Zintec Steel rail with M6 Hex nutcerts Manufactured from factory clad up to 50mm thich Class ‘O’
fitted to the reverse. foil backed mineral wool quilt - upto 45 kg / m³ density
mineral wool.
2. Casing
Panel casing manufactured from 2.0mm thick Zintec Steel 7. Sealant
sheet - Outer face powder coated to RAL9010 (20% Gloss NOMS approved non pickable sealant to be applied to all
+/- 5%). exposed gaps (Sealant supplied and applied by others).

3. Pipe Work 8. Security Fixings
Individual Pipe work circuits manufactured from 15mm Dia NOMS approved M6 x 20 Stainless Steel countersunk
EN12449 / EN12735-2 Copper tube. All joints completed via security screws (Torx Head or similar) to be used to fix
standard solder fittings. all joints (Suitable screws to be supplied and fitted by
others) - A suitable thread locking compound should be
4. Pipe Seats used in conjunction with any fixings.
Manufactured from cut-to-length heat treated aluminium
6000 series alloy die extrusion. The amount of fixings per panel run will be determined by the
actual panel set length - however hole centres will be uniform
5. End Wall Support Rail to provide maximum strength and security.
3mm thick Zintec Steel rail with M6 Hex nutcerts fitted to the
reverse.

6 Insulation not shown for clarity. 7
Wall and ceiling fixings to be supplied by others.

116

Installation Guide

1. Site measurement as necessary for wall to wall installation 2. Install purpose made ‘cut-to-length’ ceiling mounting rails
to be provided (by others). Active sections to be standard and end support rails at the required centres. Ensure rails
length ‘dummy’ sections to be sized to complete overall are level and true to ensure secure panel interconnections.
panel set dimensions within the given space.

3. Install and fix active panel sections to the pre-installed level 4. Once active panel sections are in position make mains
and true mounting rails using NOMS approved (M6 x 20 connections and install purpose made dummy sections.
Stainless steel countersunk screws) security fixings and Use NOMS Approved (M6 x 20 Stainless steel countersunk
thread locking compound. screws) security fixings and suitable thread locking
compound.

5. Apply NOMS approved non-pickable sealant to all exposed 6. Remove ‘low-tack’ protective covering and clean exposed

gaps that may be created due to building tolerances. panel set surfaces.

Installation instruction are provided for guidance purposes only and may need to be modified dependant on the given
environment. Always ensure that mandatory and appropriate health and safety procedures are applied during the installation
process and that appropriate protective equipment worn.

117

Product Performance

Product performance based on and in accordance with BS PNP335 / 4-Pipe
EN442-2:1997
Room Temp °C Capacity (W / lm)
PNP335 Panel
21 178
4-pipe unit, assuming waterflow @
82°C and water return @ 71°C. 20 182

19 185

18 189

k = 1.528*

PNP434 Panel PNP434 / 6-Pipe

6-pipe unit, assuming waterflow @ Room Temp °C Capacity (W / lm)
82°C and water return @ 71°C.
21 267

20 272

19 278

18 284

k = 2.295*

PNP533 Panel PNP533 / 8-Pipe

8-pipe unit, assuming waterflow @ Room Temp °C Capacity (W / lm)
82°C and water return @ 71°C.
21 356

20 363

19 371

18 378

k = 3.056*

Q = k (∆ T) ⁿ Q = Output w/m ‘Active Section
n = 1.1842
k = Constant see table ‘*’
Prison Cornice Panel - Heating Capacity

Heating Capacity Watts / Linear Metre

Temperature Differential dtK
The thermal performance of Freger’s Prison Ceiling Panel has been tested in accordance with the European Standard EN14037.

Example: at water flow 82°C and return 71°C with a room temperature of 19°C, the PNP434 panel provides 278 W / lm heating capacity.
Please contact our Technical Services Department for advice on flow rates and pressure drops.
Pressure drop <5.0 kPa based on 3.0m panel with maximum flow rate of 0.08 kg / s.

118

PR Frengerwarm Wall
Mounted Panel Radiator

Introduction

The PR Frengerwarm Radiator is a secure and efficient space
heating product with achievable capacities of up to 560 W / m
@ 57.5 dtK - performance data in accordance with
BS EN 442-2:1997 test data.

The PR Frengerwarm Radiator heats via water-carrying
copper coils which are fixed within extruded Aluminium pipe
seats. In turn, the pipe seats are securely bonded to the robust
3.0mm thick steel outer casing to optimise heat emission. The
heat is directed into the room by a layer of mineral wool
insulation fitted to the reverse of the panel over the copper coil.
The units are made into sets comprising at least one active
section and a number of ‘dummy’ sections all to suit any
particular environment. All panels are finished in a tough
polyester paint finish.

Installation

The PR Frengerwarm Radiator is designed to be installed
utilising the pre-drilled mounting rails and to simplify the
intallation process. For maximum security and to ensure full
NOMS custodial property compliance it is important to install
the product level utilising the purpose made floor and wall rails
with any gaps due to building tolerance concealed are with
suitable NOMS approved non-pickable sealant.

All fixings joints between the panel and pre-drilled rail should
be secured using suitable NOMS approved (M6 x 20 Stainless
steel countersunk screws) secure fixings and Loctite
compound.

Key Product Features

Manufactured from robust 3.0mm thich Steel plate.
Interleaf joints and angled side profiles with pre-drilled
holes to allow for the secure fixing using suitable NOMS
approved (M6 x 20 Stainless steel countersunk screws)
secure fixings and Loctite compound.
Sets comprise standardised active sections are
integrated with manufactured to suit dummy sections - each
installation tailored to meet the requirements of any
environment.
Three standardised panel heights to match most project
requirements.
Slimeline panel depth of just 150mm.
Simple to clean and hygienic.
Maintenance panel allows for simple but secure access to
connection details and valve arrangements.

119

Dimensions

Panel Widths

The PR Radiator is available in three heights as standard:
395mm, 535mm and 675mm. The width selected will depend
on room aesthetics and heating capacity requirements.

Panel Lengths

The PR Radiator sections are supplied with heating circuit
(active sections) or without heating circuit (dummy sections).

A radiator set is usually a combination of at least one active
section and a number of dummy sections tailored to suit the
particular environment.

Active radiator sections are available in any length up to
3000mm long and are sized to meet the heating requirements.
Each panel set may include more that one active section
dependent on space and capacity requirements.

Dummy radiator sections provided to finish a set and gain
access to the pipe connections are available in lengths from
150mm up to 3000mm as required.

Panel Depth

All radiators are 150mm deep as standard.

Surface Finish

Each PR Radiator section is powder coat finished to RAL9010
(20% Gloss) as standard - with an emissivity of 0.94.

Connections

All active sections will arrive complete with 15mm Dia
EN12449 / EN12735-2 Copper pipework circuits ready for on
site connection to the mains flow and return water services.

Insulation

Each active section is supplied complete with up to 50mm
thick - upto 45 kg / m³ density mineral wool Class ‘O’ foil
@bac1k0e°dCinassuslatatinodnawrdit.h a thermal conductivity of 0.040 W / mk

Panel Depth PR395-4 Panel Type PR535-8
395mm PR395-6 535mm
Dry Weight 26.45 kg/m 395mm 33.61 kg/m
0.7 l/m 28.1 kg/m 1.3 l/m
Water Content 100mm 1.0 l/m 100mm

Minimum Distance 8.7 BAR 100mm 8.7 BAR
Between Fixings
13.0 BAR 8.7 BAR 13.0 BAR
Maximum Working
Pressure 13.0 BAR

Hydraulic Test
Pressure

120

Components

1. Floor Rails 6. Insulation
3mm thick angles Zintec Steel rail with M6 Hex nutcerts Manufactured from factory clad upto 50mm thick Class ‘O’
fitted to the reverse. foil backed mineral wool quilt - upto 45 kg / m³ density
mineral wool.
2. Casing
Panel casing manufactured from 3.0mm thick Zintec Steel 7. Sealant
sheet - Outer face powder coated to RAL9010 (20% Gloss NOMS approved non pickable sealant to be applied to
+/- 5%). all exposed gaps (Sealant supplied and applied by others).

3. Pipe Work 8. Security Fixings
Individual Pipe work circuits manufactured from 15mm Dia NOMS approved M6 x 20 Stainless steel countersunk
EN12449 / EN12735-2 Copper tube. All joints completed via security screws (Torx Head or similar) to be used to fix
standard solder fittings. all joints (Suitable screws to be supplied and fitted by
others) - A suitable thread locking compound should be
4. Pipe Seats used in conjunction with any fixings.
Manufactured from cut-to-length heat treated aluminium
6000 series allow die extrusion. The amount of fixings per panel run will be determined by the
actual panel set length - however hole centres will be uniform
5. End Wall Support Rail to profive maximum strength and security.
3mm thick Zintec Steel rail with M6 Hex nutcerts fitted to the
reverse.

6 Insulation not shown for clarity.
Wall and ceiling fixings to be supplied by others.

121

Installation Guide

1. Site measurement as necessary for wall to wall installation 2. Install purpose made ‘cut to length’ wall & floor mounting
to be provided (by others). Active sections to be standard rails with end support rails at the required centres. Ensure
length, ‘dummy’ sections to be sized to complete overall rails are installed level and true to ensure secure panel
panel set dimensions within the given space. fixing interconnections.

3. Install and fix active panel sections to the preinstalled level 4. Once active panel sections are in position make mains
and true mounting rails using NOMS approved (M6 x 20 connections and install purpose made dummy sections.
stainless steel countersunk screws) security fixings and Use NOMS Approved (M6 x 20 Stainless steel countersunk
thread locking compound. screws) secuirty fixings and suitable thread locking
compound.

5. Apply NOMS approved non-pickable sealant to all exposed 6. Remove ‘low-tack’ protective covering and clean exposed

gaps that may be created due to building tolerances. panel set surfaces.

Installation instructions are provided for guidance purposes only and may need to be modified dependent on the given
environment. Always ensure that mandatory and appropriate health and safety procedures are applied during the installation
process and that appropriate protective equipment worn.

122

Product Performance

Product performance based on and in accordance with BS
EN442-2:1997.

PNP335 Panel PNP395-6 Panel PR395 / 4-Pipe

Room Temp °C Capacity (W / lm)

4-pipe unit, assuming 6-pipe unit, assuming 21 202
water flow @ 82°C and water flow @ 82°C and
water return @ 71°C. water return @ 71°C. 20 206

19 210

18 214

k = 1.934*

PR395 / 6-Pipe

Room Temp °C Capacity (W / lm)

21 302

20 308

19 315

18 321

k = 2.897*

PR535-5 Panel PR675-10 Panel PR535 / 8-Pipe

8-pipe unit, assuming 10-pipe unit, assuming Room Temp °C Capacity (W / lm)
water flow @ 82°C and water flow @ 82°C and
water return @ 71°C. water return @ 71°C. 21 416

20 425

19 433

18 442

k = 3.988*

PR675 / 10-Pipe

Room Temp °C Capacity (W / lm)

21 526

20 537
19 548

18 559
k = 5.042*

Q = k (∆ T) ⁿ Q = Output w/m ‘Active Section
n = 1.1842
k = Constant see table ‘*’

123

Heating Capacity (watts / linear metre)The thermal performance characteristics of Frenger’s Prison Radiator has been tested at BSRIA’s radiator test facility in
accordance with BS EN 442-2:1997.

Radiator Heating Capacity

Temperature Differential dtK
Example: at water flow 82°C and return 71°C with a room temperature of 19°C, the PR535 radiator provides 433 W / lm heating
capacity.
Pressure drop <5.0 kPa based on 3.0m panel with maximum flowrate of 0.08 kg / s.
Please contact our Technical Services Department for advice on flowrates and pressure drops.

124

HOepaedraetrioTnitsle& Maintenance

Application and Suitability Clearance & Maintenance

All secure NOMS compliant radiant heating panels are The PCP / PNP panel should be cleaned as required. The
suitable for internal use only. frequency of cleaning depends on the cleanliness of the indoor
environment where the panel is positioned. The cleanliness of
Operation, Performance, Control & the panel should be inspected every 6 months and cleaned as
Testing necessary to prevent any reduction in the heating
performance.
Product Control
For temperature control, refer to the operation and Access to the copper coil connections is normally gained from
maintenance guidelines specific to the building management the removal of necessary dummy sections. Access is gained
system (BMS) - as such the control system os not supplied by the clearing of any non-pickable sealant and the removal of
with the radiant panels and is not within Frenger Systems Ltd any fixings (NB - utilise the necessary tool required for the type
remit of works. of Security Screw employed):

Performance Accreditation a. Use suitable access equipment to allow safe and
Heating effect is measured in accordance with the relevant comfortable operation.
testing protocols.
b. Whilst supporting the dummy piece as necessary remove
PCP / PNP panels - All in accordance with EN14037 European all fixings.
radiant heating panel test standard.
PR Radiators - All in accordance with BS EN-442-2:1997. c. Remove the dummy sections by either gently sliding away
from or by holding to one side of the positioned active panel.
Pressure Testing
Maximum test pressure: 10 bar. It is now possible to inspect the copper coil connection
assembly.
Connections
Product Packaging
Each panel will be supplied with 15mm Dia EN12449 /
EN12735-2 Copper pipework coils - Water connections should All products are palletised and packaged suitable for delivery
be either of Tectite or compressing coupling. direct to site with pallets containing panels / radiators of a
common size where appropriate.
NB: If compression coupling is used, a support sleeve is to be
fitted in the products connection pipe. Panels will be neatly and securely stacked on wooden pallets
suitable for forklift truck unloading.
DO NOT SOLDER; DO NOT TWIST THE PIPES.
Number of product / panels per pallet will be dependent on
Water Quality actual lengths and height of the ordered product.

A specialist water treatment contractor should carry out water All delivery products should be stored in dry conditions, off the
preparation and maintenance. floor on pallets.

The heating water system must be air tight to prevent oxygen All panels are covered with a low-tack film protective film to
entering the pipework. The pipework must also be equipped protect the product during the installation process.
with automatic air vents (supplied and fitted by others) to
prevent air entering the system. Typical Packaging photo detailed below:

The water quality must have a pH-value of approximately 6-9.

The water velocities should not exceed 1 m / s.

In-line strainers are to be used to remove particles from the
water.

Product Labelling

All panel sections have an identification label positioned on
the inside of the product, indication the product type, reference
and / or size etc - project specific labelling to include cell / room
reference number etc can be provided on request.

125



Electric Heating

Radiant Heaters Surface Mounted Air Curtain
EnergoCassette Radiant Heater
Electric Radiant Heating is a highly effective method of heating EnergoStrip Radiant Heater
a room. Electric Heating Panels heat all of the rooms
surfaces (desks, floor, etc.), which in turn heat up the air within
a room. Consequently, electric radiant heating panels afford an
extremely comfortable indoor environment, where there is
little risk of the person feeling too cold under the table or too
hot on the head. Furthermore, electric radiant heating focuses
on the areas where heating is most required – the coolest
items in the room (usually the external walls or windows).
Unlike convective heating, an increase in ceiling height does
not significantly increase the amount of heating required.

Product benefits can be summarised as follows:

Immediate heat.
Discreet.
Mounting heights up to 40m.
Recessed mounting option.
Ceiling mounting option.

Air Curtains

Frenger’s range of Air Curtains create an air barrier, which
helps to prevent cold draughts thus creating a comfortable
indoor climate. Energy losses through openings are reduced,
which means considerable savings.

When the doors are closed, the Air Curtains will contribute
towards the heating around the entrance area if required.
The heated air from the air curtains will also help to dry any
water / sleet dragged in to an entrance, as such assisting in
creating a safer environment.

Although our Air Curtains emit warm air, the main purpose
of an Air Curtain is not to provide general heating in a space
but to balance temperature differentials and maintain these
differentials by using a pressurised stream of air.

Product benefits can be summarised as follows:

Compact.
Low noise.
Suitable for doors of almost any width.
Suitable for doors heights up to 4m.
Ambient, electric or water heated designs.

EnergoInfra Radiant Heater

127



EnergoStrip Introduction

EnergoStrip Radiant Heater The EnergoStrip is an electric radiant heater that will supply
gentle, even and comfortable heat in various applications
from small stores or bathrooms to large industrial units. The
heaters can be used to provide general heating, or to raise the
temperature in certain areas (spot heating).

The heat is concentrated in the occupied area, thus minimising
energy losses through the stratification of heated air. The
system is simple and inexpensive to install and maintenance
free.

EnrgoStrip emits a gentle, pleasant radiant heat (infrablack,
long wave), not to be confused with high - temperature
shortwave infrared heat. The product is consequently ideal to
use for general heating of small or large areas where
installation heights are between 2 - 40m from floor height.

Benefits omfainRtaaind3ia- 6n°Ct Heating than with

Possible to lower air temperature

conventional heating.

Concentrates heat to the occupied zone.

Minimising warm - up times.

Benefits of EnergoStrip

No moving parts equates to reduced maintenance costs.
Ceiling mounted unit frees up wall and floor space.
Suitable for mounting between 2 - 40m from floor level.
Large selection of outputs available.
Splash proof IP44.

129

Technical Data

Part No. Heating Voltage (V) Heating Size (LxWxD) mm Weight (Kg)
Capacity (W) Element
EE6 230 960 x 160 x50 5.0
EE10 600 230 1 1680 x 160 x 50 8.0
EE8 1000 230 1 650 x 290 x 50 6.0
EE12 800 230 2 960 x 290 x 50 8.5
EE16 1200 230 2 1360 x 290 x 50 11.5
EE20 1600 230 2 1680 x 290 x 50 14.0
EE24 2000 230 2 1360 x 430 x 50 16.5
EE36 2400 400 3 1680 x 430 x 50 21.0
3600 3

Control Design

Frenger can supply a range of suitable thermostats to be used The EnergoStrip is a discreet aesthetically pleasing heater that
with EnergoStrip at an additional cost. Should you require offers easy installation with the included mounting brackets.
any assistance in selection please contact our technical sales The EnergoStrip casing is made of white powder coated sheet
department. steel except EE36 where the casing is manufactured from
naturally galvanised sheet steel.

130

Mounting & Installation

The EnergoStrip offers easy installation with the included
mounting brackets. Alternatively panels can be installed with
drop rods or chain (supplied by others), however we would
recommend the EE24 and EE36 units are installed with the
fixing brackets provided.

Part No. EE6 EE10 EE8 EE12 EE16 EE20 EE24 EE36
820 1030 820 1030
Dimension ‘E’ (mm) 600 1030 370 600

Mounting fixing dimensions Minimum Distance

Minimum Mounting Distances 150mm (250mm EE36)
EE6-EE20 - 300mm, EE24-EE36 - 800mm
Description
1800mm
A Heater to wall EE6-EE10 - 70mm, EE8-EE20 - 70mm, EE24-EE36 - 120mm
B Heater to flammable material
C Heater to floor
D Heater to ceiling

Minimum mounting distances

131



EnergoCassette Introduction

EnergoCassette Radiant Heater The EnergoCassette is an electric radiant heater that will
supply gentle even and comfortable heat in various
applications. The heaters can be used to provide general
heating, or to raise the temperature in certain areas (spot
heating).

As the EnergoCassette uses radiant heat, the heat is
concentrated in the occupied area, thus minimising energy
losses through stratification of heated air. The system is simple
and inexpensive to install and maintenance free.

EnergoCassette emits a gentle, pleasant black radiant heat
(long wave), not to be confused with high - temperature
shortwave infrared heat and the low surface temperature
makes the EnergoCassette ideal to use for general heating of
small or large areas where installation heights are between
2 - 3.5m from floor height.

Benefits of Radiant Heating

Possible to maintain 3 - 6°C lower air temperature than with
conventional heating.
Concentrates heat to the occupied zone.
Minimising warm - up times.

Benefits of EnergoCassette

No moving parts equates to reduced maintenance costs.
Ceiling mounted unit frees up wall and floor space.
Can be integrated into a 600 x 600 suspended ceiling
system.
Contemporary design with flat plate.
Splash proof IP55.

133

Technical Data

Part No. Heating Voltage (V) Size (LxWxD) Weight (Kg) Surface
Capacity (W) mm* Temperature
5.5
ENC300 300 230 600 x 600 x 45 10.0 Upto 100°C

ENC600 600 230 1200 x 600 x 45 Upto 100°C

*Size is nominal less 7mm to suit a standard 600x600mm ceiling grid.

Control Design

Frenger can supply a range of suitable thermostats to be used The EnergoCassette consists of a heating coil encased in a
with EnergoCassette at an additional cost. Should you require white painted steel panel. The unit is approved to IP55 (jet
any assistance in selection please contact our technical sales proof) making it suitable to use in wet, dry and fire hazardous
department. areas.

134

Mounting & Installation

The EnergoCassette is a universal model designed for fitting
flush into a T-bar (15-24mm) suspended ceiling, or mounted
directly onto the ceiling with the supplied mounting brackets
thus freeing valuable floor and wall space.

For vertical mounting instructions please contact Frenger’s
Technical department.

Part No. ENC300 ENC600

Dimension ‘E’ (mm) 550 740
Dimension ‘F’ (mm) 350 540

Supplied mounting bracket

Fixings for mounting bracket Minimum Distance

Minimum Mounting Details 50mm
200mm
Description 1800mm
A Heater to wall 45mm
B Heater to flammable material
C Heater to floor
D Heater to ceiling

Minimum mounting distances

135

Header Title

136

EnergoInfra Introduction

EnergoInfra Radiant Heater The EnergoInfra is a versatile and effective infrared heater.
The output and format of the heater makes it ideal for
installations in conservatories, balconies, patios and outdoor
restaurants as well as being a good alternative for general
heating of industrial buildings with high heat losses or air
infiltration losses. The EnergoInfra is also often used to
provide spot heating to loading bays, manufacturing facilities
and various agricultural buildings.

The heaters are approved to IP44 and can as such be used in
wet and dry areas alike.

Beneftis of Radiant Heating

Possible to maintain 3 - 6°C lower air temperature that with
conventional heating.
Concentrated heat to the occupied zone.
Minimising warm - up times.

Benefits of EnergoInfra

No moving parts equates to reduced maintenance costs.
Suitable for mounting between 2 - 5cm from floor level.
Suitable for wall or ceiling mounting with included brackets.
Suitable for outdoor applications.
Splash proof IP44.

137

Technical Data

Part No. Heating Voltage (V) Size (LxWxD) Weight (Kg)
Capacity (W) mm
EIR500 230 1.5
EIR1000 500 230 700 x 75 x 40 2.0
EIR1500 230 3.0
1000 1170 x 75 x 40

1500 1680 x 75 x 40

Control Design

Frenger can supply a range of suitable thermostats to be used The EnergoInfra consists of a heating element and shiny
with the EnergoInfra at an additional cost. Should you require anodised aluminium reflectors encased in a stainless steel
any assistance in selection please contact our technical sales casing to ensure optimum corrosion resistance yet still being
department. aesthetically pleasing.

138

Mounting & Installation

The EnergoInfra offers easy installation using the included
adjustable mounting brackets. The Brackets can be adjusted
to angle the heater in different positions enabling direction of
the heat to the desired areas.

The heaters can also be suspended from chains, wires etc...
(suspension equipment by others)

Part No. EIR500 EIR1000 EIR1500
810 1100
Dimension ‘E’ (mm) 500

Mounting bracket dimensions Adjustable mounting bracket

Minimum Mounting Distances Minimum Distance
300mm
Description 800mm
A Heater to adjacent wall 1800mm
B Heater to flammable material 150mm
C Heater to floor
D Heater to ceiling

Minimum mounting distances

139

Header Title

140

EnergoInfra Industry

EnergoInfra Radiant Heater Introduction

The EnergoInfra Industry provides energy efficient heating for
most applications and working environments with high ceiling
heights (approx. 3 - 40m or 3.5m in zone heating applications).
Heat accumulation in floors, walls and other surfaces means
that the air temperature can be lowered giving 25 - 50%
energy savings and yet achieving the same ambient
temperature. The EnergoInfra Industry is also often used to
provide spot heating to loading bays, manufacturing facilities
and various agricultural buildings.

The heaters are approved to IP44 and can as such be used in
wet and dry areas alike.

Beneftis of Radiant Heating

Possible to maintain 3 - 6°C lower air temperature than with
conventional heating.
Concentrates heat to the occupied zone.
Minimising warm - up times.

Benefits of EnergoInfra Industry

No moving parts equates to reduced maintenance costs.
Ceiling mounted unit frees up wall and floor space.
Suitable for mounting between 5 - 40m from floor level.
Robost design.
Splash proof IP44.

141

Technical Data

Part No. Heating Voltage (V) Size (LxWxD) Weight (Kg)
Capacity (W) mm
EIR3000 400 7.0
EIR4500 3000 400 1300 x 300 x 80 7.0
EIR6000 400 8.5
4500 1360 x 300 x 80

6000 1680 x 300 x 80

Control Design

Frenger can supply a range of suitable thermostats to be used The EnergoInfra Industry consists of a heating element and
with the EnergoInfra Industry at an additional cost. Should you shiny anodised aluminium reflectors encased in a galvanised
require any assistance in selection please contact our sheet steel in grey finish (not colour coated) offering a robust
technical sales department. design.

142

HMeoaudnetirnTgit&leInstallation

Bracket Distances

The EnergoInfra Industry offers easy installation using the
included adjustable mounting brackets. The brackets can be
adjusted to angle the heater in different positions enabling
direction of the heat to the desired areas.

The heaters can also be suspended from chains, wires etc.. Supplied bracket maintains the minimum
(suspension equipment by others). mounting distance for the selected product
(distance D, below).

Part No. EIR3000 EIR4500 EIR6000
Dimension ‘E’ (mm) 820 820 1030

Adjustable mounting bracket

Mounting bracket dimensions Minimum Distance

Minimum Mounting Distances 500mm
1500mm
Description 2300mm
A Heater to wall 200mm - if wall mounted, 300mm - if ceiling mounted
B Heater to flammable material
C Heater to floor
D Heater to ceiling

Minimum mounting distances

143

Air Curtains

Introduction

Frenger also offer an extensive range of heated, ambient
and water fed Air Curtains which can be surface mounted or
recessed and are suitable for opening heights of up to 4m.

Air curtains increase energy efficiency and improve comfort
in retail, commercial, architectural and industrial applications.
They can be installed in any frequently used entrance, but
typical applications include: Hight Street Stores, Shopping
Centres, Hospitals and Hotels etc.

Technical Data All Frenger Air Curtains are designed with energy efficiency
in mind and with the introduction of Ecopower technology,
for surface Mounted Air Curtain end users can now benefit from energy saving and climate
enhancing innovation.

Ambient Air Curtain Our Air Curtains are available in two models;
FRA model - Suitable for opening heigths of up to 3.0m
FRB model - Suitable for opening heights of up to 4.0m

Part No. Heat output Loading Max velocity Max air volume Weight Size (LxWxH) Supply (50Hz) dB (A) Mounting Height
(W) (A) (l / s) (m³ / h) (kg) mm @3m** (m)

Model A

FRA-100 A - 0.7 9 1250 15 1137 x 275 x 198 230V ~ 1 P & N 55 2-3

FRA-150 A - 0.9 9 1800 21 1669 x 275 x 198 230V ~ 1 P & N 55 2-3

FRA-200 A - 1.1 9 2500 31 2200 x 275 x 198 230V ~ 1 P & N 56 2-3

Model B

FRB-100 A - 1.3 12 2880 29 1196 x 377 x 255 230V ~ 1 P & N 59 3-4

FRB-150 A - 1.8 12 4020 43 1746 x 377 x 255 230V ~ 1 P & N 60 3-4

FRB-200 A - 2.7 12 5760 58 2296 x 377 x 255 230V ~ 1 P & N 61 3-4

Electric Air Curtain

Part No. Heat output Loading Max velocity Max air volume Weight Size (LxWxH) Supply (50Hz) dB (A) Mounting Height
(W) (A) / Phase (l / s) mm @3m** (m)
(m³ / h) (kg)
9 2-3
Model A 9 2-3
9 2-3
FRA-100 E 4.5 / 9 13.7 1250 16 1137 x 275 x 198 400V ~ 3 P & N 55
12 1800 23 1669 x 275 x 198 400V ~ 3 P & N 55 3-4
FRA-150 E 6 / 12 18.3 12 2500 33 2200 x 275 x 198 400V ~ 3 P & N 56 3-4
12 3-4
FRA-200 E 9 / 18 27.2

Model B

FRB-100 E 6 / 12 18.7 2880 32 1196 x 377 x 255 400V ~ 3 P & N 59
4020 45 1746 x 377 x 255 400V ~ 3 P & N 60
FRB-150 E 9 / 18 27.9 5760 62 2246 x 377 x 255 400V ~ 3 P & N 61

FRB-200 E 12 / 24 37.5

LTHW Air Curtain

Part No. Heat output Loading Max velocity Max air volume Weight Size (LxWxH) Supply (50Hz) dB (A) Mounting Height
(W)* (A) (l / s) mm @3m** (m)
(m³ / h) (kg)

Model A

FRA-100 W 6 0.7 8.5 1180 18 1137 x 275 x 198 230V ~ 1 P & N 55 2-3

FRA-150 W 9 0.9 8.5 1700 26 1669 x 275 x 198 230V ~ 1 P & N 55 2-3

FRA-200 W 12 1.1 8.5 2360 37 2200 x 275 x 198 230V ~ 1 P & N 56 2-3

Model B

FRB-100 W 12 1.3 11 2630 35 1196 x 377 x 255 230V ~ 1 P & N 59 3-4

FRB-150 W 18 1.8 11 3670 47 1746 x 377 x 255 230V ~ 1 P & N 60 3-4

FRB-200 W 24 2.7 11 5260 64 2246 x 377 x 255 230V ~ 1 P & N 61 3-4

*Output based on a Water Flow / Return Temperature of 82 / 71°C with an air entering temperature of 20°C.
**Sound pressure levels (dBA) at 3m, as given in our brochure, are for a single air curtain mounted at its maximum mounting height, operating in a room
with average acoustic characteristics as defined in CIBSE Guide B5 (reverberation time 0.7s) and a room size equivalent to 8 air changes per hour (ac/h).
Care needs to be taken when selecting air curtains for an installation as noise levels can be several dB higher if the mounting height is reduced, if the
room is more “live” (i.e. hard surfaces, no furnishings or absorbent materials), if the room is smaller than 8 ac / h equivalent or a combination of these
factors. Noise levels will also increase if more than one air curtain is installed at the same doorway (e.g. + 3dBA for 2 equal point sources: direct field).

144

Header Title

Technical Data Features

for Recessed Air Curtain Low sound levels.
Corrosion proof housing finished in RAL 9010.
Option of non-standard colours.
Optimized airflow technology.
Units can be mounted together to create longer runs.
IP21 Rated.
Available in electric, water or ambeint versions.
Supplied with tangential fans.
3 way valve supplied with water units.
FRA model with optional filter on surface mounted water and
ambient units.
FRA models includes low inertia high efficiency energy
heating coils in electric heating units.
FRB models available with 82 / 71°C and 60 / 40°C
low-grade water coils.

Ambient Air Curtain

Part No. Heat Loading Max Velocity Max Air Volume Weight Size (LxWxH) mm Grille Size Supply (50Hz) dB (A) Mounting
Output (kg) (mm) @3m** Height (m)
Model A (A) (l/s) (m³/h)
FRA-100A R (kW)
FRA-150A R 0.7 9 1190 19 1200 x 301 x 206 1209 x 353 230V ~ 1 P & N 55 2 - 2.75
- 0.9 9 1730
- 25 1600 x 301 x 206 1609 x 353 230V ~ 1 P & N 55 2 - 2.75

FRA-200A R - 1.1 9 2380 35 2100 x 301 x 206 2120 x 353 230V ~ 1 P & N 56 2 - 2.75
Model B
FRB-100A R - 1.3 11.5 2750 33 1150 x 436 x 296 1104 x 436 230V ~ 1 P & N 59 2.75 - 3.75
FRB-150A R - 1.8 11.5 3840 47 1650 x 436 x 296 1604 x 436 230V ~ 1 P & N 60 2.75 - 3.75
FRB-200A R - 2.7 11.5 5500 63 2240 x 436 x 296 2190 x 436 230V ~ 1 P & N 61 2.75 - 3.75

Electric Air Curtain

Part No. Heat Loading Max Veloci- Max Air Volume Weight Size (LxWxH) mm Grille Size Supply (50Hz) dB (A) Mounting
Output (kW) (A) / ty (l/s) (m³/h) (kg) (mm) @3m** Height (m)

Model A 4.5 / 9 phase 9 1190 20 1200 x 301 x 206 1209 x 353 400V ~ 3 P & N 55 2 - 2.75
FRA-100E R
13.7

FRA-150E R 6 / 12 18.3 9 1730 27 1600 x 301 x 206 1609 x 353 400V ~ 3 P & N 55 2 - 2.75
FRA-200E R 9 / 18 27.2
Model B 9 2380 37 2100 x 301 x 206 2120 x 353 400V ~ 3 P & N 56 2 - 2.75
FRB-100E R 6 / 12 18.7
FRB-150E R 9 / 18 27.9 11.5 2750 37 1150 x 436 x 296 1104 x 436 400V ~ 3 P & N 59 2.75 - 3.75

11.5 3840 53 1650 x 436 x 296 1604 x 436 400V ~ 3 P & N 60 2.75 - 3.75

FRB-200E R 12 / 24 37.5 11.5 5500 71 2240 x 436 x 296 2190 x 436 400V ~ 3 P & N 61 2.75 - 3.75

LTHW Air Curtain

Part No. Heat Output Loading Max Velocity Max Air Volume Weight Size (LxWxH) mm Grille Size Supply (50Hz) dB (A) Mounting
(kW) (A) (l/s) (m³/h) (kg) (mm) @3m** Height (m)

Model A 0.7 8.5 1120 22
0.9 8.5 1630 30
FRA-100W R 6 1.1 8.5 2240 41 1200 x 301 x 206 1209 x 353 230V ~ 1 P & N 55 2 - 2.75
1600 x 301 x 206 1609 x 353 230V ~ 1 P & N 55 2 - 2.75
FRA-150W R 9 1.3 10 2250 40 2100 x 301 x 206 2120 x 353 230V ~ 1 P & N 56 2 - 2.75
1.8 10 3150 55
FRA-200W -R 12 2.7 10 4510 73

Model B

FRB-100W R 12 1150 x 436 x 296 1104 x 436 230V ~ 1 P & N 59 2.75 - 3.75
1650 x 436 x 296 1604 x 436 230V ~ 1 P & N 60 2.75 - 3.75
FRB-150W R 18 2240 x 436 x 296 2190 x 436 230V ~ 1 P & N 61 2.75 - 3.75

FRB-200W R 24

*Output based on a Water Flow / Return Temperature of 82 / 71°C with an air entering temperature of 20°C.
**Sound pressure levels (dBA) at 3m, as given in our brochure, are for a single air curtain mounted at its maximum mounting height, operating in a room
with average acoustic characteristics as defined in CIBSE Guide B5 (reverberation time 0.7s) and a room size equivalent to 8 air changes per hour (ac/h).
Care needs to be taken when selecting air curtains for an installation as noise levels can be several dB higher if the mounting height is reduced, if the
room is more “live” (i.e. hard surfaces, no furnishings or absorbent materials), if the room is smaller than 8 ac / h equivalent or a combination of these
factors. Noise levels will also increase if more than one air curtain is installed at the same doorway (e.g. + 3dBA for 2 equal point sources: direct field).

145



Acoustic Lighting and Heating Rafts

Frengers Acoustic Lighting and Heating Rafts, otherwise Heating Raft Type 1
known as Multi Service Radiant Panels (MSRP’s) consist Figure 1
essentially of a free hanging radiant heating panel coupled
with other services such as:-

Lighting.
Acoustic Sound absorbing materials.
Apertures for sprinkler heads.
Compartment trunking for other electrical services.
Apertures for PA and VA speakers.
Lighting Control, PIR and Photocells.

Radiant Heating

The radiant heating element is the same technology as utilised
for Frenger’s tried and tested Modula panels.

The panel is constructed from zinc coated steel which is
perforated and folded to the project specific requirements
before being polyester powder coat finished to any RAL
colour as required, (RAL 9010 is standard).

The panel utilises Frenger’s optimised extruded aluminium
heat exchanges and seamless copper tube heating elements.

Lighting

Virtually any type of lighting solution can be accommodated
by Frenger’s MSRP and all lighting is manufactured in house
and bespoke to the project solution. Direct only, indirect only,
combination of direct and indirect lighting from either the
same light source or different sources can be accommodated.

T5 florescent or LED light sources, aluminium louvers, micro
lens optics, opal acrylic or even extruded acrylics for
continuous / seamless lighting can be accommodated.

All lighting is designed in house using lighting software design
packages and the prototyped and photometered in Frenger’s
in house Photometric Laboratory and Integration Chamber
for L.O.R (Light Output Ratios). Frenger convert to Lumdat
files and produce lighting calculations for the space
requirement using Relux / Dilux for compliance to CIBSE
Lighting Guides LG3/7.

Acoustic Sound Absorbing Materials

The perforated areas of the radiant panel are covered with
black tissue faced insulating material with a foil backing
effectively sandwiched in the middle of two layers of acoustic
insulating material, the top layer of which has black tissue
acoustic material face upwards as shown in the figure 1.

Frenger’s have their own in house sound laboratory and also
make use of third party acoustic testing for verifications.

Note: Acoustic Absorption Area (m²) figures detailed below are per linear m of MSRP, hence the
absorption area’s should be multiplied by the chosen MSRP length. Data based upon independent
testing conducted by SRL (Sound Research Laboratories) Ref. C/21760/R01 to BS EN ISO
354:2000.

Heating Raft Type 2

147

Frenger’s Large
Project Experience

Frenger has vast experience and a proven track record of
successfully delivering large complex UK and international
projects.

“Frenger designed, manufactured, “The extensive refurbishment of 101 “Frenger successfully designed and
supplied and installed in excess of 4500 New Cavendish Street has been a supplied over 1,100 linear meters of
Active Multiservice Chilled Beams for most distinguished project “Radiant”/convective Passive Multiservice
the prestigious 55 Baker Street project incorporating nearly 2 kilometers of Chilled Beams to the new HML HQ
- the UK’s largest MSCB project to date.” Frenger’s Active Multiservice Chilled building, a subsidiary of Skipton Building
Beams over 4-floor levels.” Society.”

148

Frenger’s Project References

Common Wealth Bank Neo Bankside Grosvenor Hill CISCO Langley Point
of Australia, Sydney - 2012 London, UK - 2012 London, UK - 2012 Reading, UK - 2012 Birmingham, UK - 2012
Active Multiservice Passive Multiservice Active Multiservice Passive Chilled Beams
Passive Chilled Beams

5 Murray Rose Avenue Exeter University Stafford College Wyre Forest Trinity Grammer
Sydney, Australia - 2012 Exeter, UK - 2012 Stafford, UK - 2012 Kidderminster, UK - 2012 Trinidad & Tobago - 2012
Passive Chilled Beams Active Chilled Beams Active Chilled Beams
Active Multiservice Passive Chilled Beams

Cambridge Metallurgy Tate Modern 65 Southwark Street 700 Bourke Street Veolia Environmental
Cambridge, UK - 2012 London, UK - 2012 London, UK - 2012 Australia - 2012 Cannock, UK - 2012
Passive Chilled Beams Passive Chilled Beams Active Multiservice
Passive Chilled Beams Passive Chilled Beams

Domino’s Pizza HQ Eskom, Megawatt Park Vodafone Innovation Wollongong University World Park
Milton Keynes, UK - 2011 South Africa - 2011 South Africa - 2011 NSW. Australia - 2011 Adelaide, Australia - 2011

Passive Multiservice Passive Chilled Beams Passive Chilled Beams Passive Chilled Beams Passive Chilled Beams

Walthamstow Station King Saud Bin Abdul Gatwick Search Area All Saints Academy 24 Britton Street
Walthamstow, UK - 2011 Saudi Arabia - 2011 London, UK - 2011 Cheltenham, UK - 2011 London, UK - 2011
Passive Chilled Beams Active Chilled Beams Passive Chilled Beams Passive Multiservice
Passive Chilled Beams

University of Botswana Royal London Hospital City Centre Tower 8 HML Headquarters Melbourne University
Botswana - 2011 London, UK - 2011 Australia - 2011 Skipton, UK - 2010 Australia - 2010
Active Multiservice
Active Chilled Beams Active Multiservice Passive Chilled Beams Active Chilled Beams

149

Five Rivers Good Hope Hospital 1 Lancaster Circus Telcom Square 123 Albert Street
Trinidad - 2010 Sutton, UK - 2010 Birmingham, UK - 2010 New Zealand - 2010 Brisbane, Australia - 2010
Passive Chilled Beams
Active Chilled Beams Passive Multiservice Passive Chilled Beams Passive Chilled Beams

500 Collins Street Google Headoffice Royal Hobart Hospital RMIT 9 Belconnen Police
Australia - 2010 Sydney, Australia - 2010 Hobart, Tasmania - 2010 Australia - 2010 Australia - 2010
Passive Chilled Beams Active Chilled Beams Active Chilled Beams
Active Multiservice Passive Chilled Beams

Sudima Hotel New Scotland Yard CIT Kingswood Lakeside Meridian Court
New Zealand - 2010 London, UK - 2010 Canberra, Australia - 2010 Cannock, UK - 2010 Edinburgh, UK - 2010
Active Chilled Beams Active Chilled Beams
Passive Chilled Beams Active Multiservice Passive Chilled Beams

Liverpool College Knightsbridge Hotel Anglia University Transport House St Barts Hospital
Liverpool, UK - 2010 London, UK - 2010 Cambridge, UK - 2010 Sydney, Australia - 2009 London, UK - 2009
Active Chilled Beams Passive Multiservice Active Chilled Beams
Passive Chilled Beams Active Multiservice

Newcastle University Civic Offices Loxford School Cheshire Police New Cavendish Street
Newcastle, UK - 2009 Southampton, UK - 2009 London, UK - 2009 Cheshire, UK - 2009 London, UK - 2009
Active Chilled Beams Active Chilled Beams Active Chilled Beams Active Multiservice
Active Chilled Beams

1 Shelly Street South Australia Police Kingston Aged Care Monash University Warnambool Hospital
Sydney, Australia - 2009 Adelaide, Australia - 2009 Australia - 2009 Australia - 2009 Australia - 2009

Passive Chilled Beams Passive Chilled Beams Active Chilled Beams Active Chilled Beams Active Chilled Beams

Kings College Batman Street Edmund Barton 55 Baker Street Sydney Water House
London, UK - 2009 Australia - 2009 Canberra, Australia - 2009 London, UK - 2008 Australia - 2008
Passive Chilled Beams Active Multiservice
Passive Chilled Beams Active Chilled Beams Passive Chilled Beams

150


Click to View FlipBook Version