ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A
© Copyright 2020 Hitachi Power Grids. RESET FROM SCADA GEN ALARM-SAM600 GENERAL ALARM-AUX. CNTL VT MCB OK
GEN ALARM
BUSCOUPLER CLOSED PROTN VT MCB - OK A

BB

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK

BANGIL +DCF204
/L20.E4
+A2.20-XDCF204-:1X0351
C1 -X51 C

2

+U2.06 -S12 +U1.06 -KF1 +U1.14 -KF2
Merging Unit - 1 -X42 5
SILENCE 14 Merging Unit - 2 -X42 5
/M31.D1 13 SAM600 IO
SAM600 IO
P4#BO.15
/Z59.B8 P4#BO.16 P4#BO.15 P4#BO.16 /L18.E2 BB1_VTOK
4 /Z59.C8 +A2.20-XDCF103:103
6
/Z63.B8 /Z63.C8 13 13

46 -F401 -F402

/D14.C4 14 /D14.C8 14

-S12 -X51 12 14

D 14 13 3 -KGAL D
/M31.D1
43 /Z66.B3 11
GENERAL ALARM-AUX.
SILENCE A1 A1 A1 BUSCOUPLER CLOSEDA1 X1

-KRST -KRST1 -KGAL -KBCL1 -L1

/Z66.B3 A2 /Z66.B4 A2 /Z66.B3 A2 /Z66.C5 A2 X2

/L20.E6 +A2.20-XDCF204:503 A1 A1

E -KLVT1 -KLVT2

/Z66.B1 A2 /Z66.B2 A2 E

/L18.E4 -DC_COM
+A2.20-XDCF103:503

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 AUXILIARY CIRCUITS M31
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language M41
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A A
© Copyright 2020 Hitachi Power Grids. MPU + BPU TRIP CB TRIP 1 CB TRIP 1
EXTERNAL RESET
SPARE SPARE

BB

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK
BANGIL

/L18.C2 QA1 Close
+A2.20-XDCF101:105
-X861
C 2 3 C
1 6 D
+U1.14 -KF2 E
+U1.06 -KF1 Merging Unit - 2 -X41 2
Merging Unit - 1 -X41 2
SAM600 IO
SAM600 IO

P4#BO.01 P4#BO.02 P4#BO.01 P4#BO.02

/Z59.B6 /Z59.B6 /Z63.B6 /Z63.B6

13 13

12 14 +U2.17 -XT4

D TSB-14
11111111111111-V
-KRST
1 3
/Z66.B3 11 /Z67.B4 4

/Z67.B4 2

45

+U2.17 -K86.1

E TRIP RELAY-1

RXMVB2 111122 221212

/Z66.C7 121 /Z66.C7 211

/L18.C4 -DCF101
+A2.20-XDCF101:505

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 LOCKOUT RELAY-1 M41
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language M42
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A A
© Copyright 2020 Hitachi Power Grids. MPU + BPU TRIP CB TRIP 2 CB TRIP 2
EXTERNAL RESET
SPARE SPARE

BB

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK
BANGIL

/L20.C2 +DCF201
+A2.20-XDCF201:104
-X862
C 2 3 C
1 6 D
+U1.14 -KF2 E
+U1.06 -KF1 Merging Unit - 2 -X41 5
Merging Unit - 1 -X41 5
SAM600 IO
SAM600 IO

P4#BO.03 P4#BO.04 P4#BO.03 P4#BO.04

/Z59.B6 /Z59.C6 /Z63.B6 /Z63.C6

46 46

42 44 +U2.17 -XT4

D TSB-14
11111111111111-V
-KRST
5 7
/Z66.B3 41 /Z67.B4 8

/Z67.B4 6

45

+U2.17 -K86.2

E TRIP RELAY-2

RXMVB2 111122 221212

/Z66.C7 121 /Z66.C7 211

/L20.C4 -DCF201
+A2.20-XDCF201:504

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 LOCKOUT RELAY-2 M42
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language M43
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A BUSBAR PROTECTION BBP TRIP BBP TRIP
B
+C1

MARSHALING KIOSK
BANGIL

B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s /L18.C3 QA1 Close
+A2.20-XDCF101:106
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. -X863
C 2 3 C
1 6 D
+U1.14 -KF2 E
+U1.06 -KF1 Merging Unit - 2 -X42 2
Merging Unit - 1 -X42 2
SAM600 IO
SAM600 IO

P4#BO.13 P4#BO.14 P4#BO.13 P4#BO.14

/Z59.B8 /Z59.B8 /Z63.B8 /Z63.B8

13 13

22 24 EXTERNAL RESET +U2.17 -XT4

D TSB-14
11111111111111-V
-KRST
9 11
/Z66.B3 21 /Z67.B4 12

/Z67.B4 10

45

+U2.17 -K86.3

E TRIP RELAY-3

RXMVB2 111122 221212

/Z66.C8 121 /Z66.C8 211

/L18.C4 -DCF101
+A2.20-XDCF101:504

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 BBP LOCKOUT RELAY-3 M43
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language M51
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 123 4 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A ALARM SILENCE ALARM RESET GENERAL ALARM GENERAL ALARM GENERAL ALARM B

+CP1 C

CONTROL AND PROTECTION PANEL D
BANGIL E

/L16.E2 +DC_COM
+A.30-XDCF102:105

B +U.19 -S11 +U.07 -KF1 +U.15 -FN1 +U.22 -FN2
RED670 MPU-X41 14 REQ650 BPU-X42 14
REC650 BCU-X42 14

SILENCE 4

/Z46.B4 3 #BO.21 #BO.22 P4#BO.09 P4#BO.10 #BO.21 #BO.22
/Z22.D6 /Z22.E6
Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s /Z12.D8 /Z12.E8 13 15 /Z32.D8 /Z32.E8

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. 13 15 13 15

12 14 GENERAL ALARM-AUX.

C -KGAL

/Z46.C5 11

A1 A1 A1
GENERAL ALARM-AUX.
-KRST -KRST1 -KGAL X1

/Z46.C5 A2 /Z46.C6 A2 /Z46.C4 A2 -L1

D X2

/L16.E4 -DC_COM
+A.30-XDCF102:505

E

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 COMMON ALARM CIRCUIT M51
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language N11
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 12 34 5 67 8

© Copyright 2020 Hitachi Power Grids. A COIL 1 - TRIP R SAM IO TRIP1 COIL 1 - TRIP T LOCKOUT RELAY 1 A
COIL 1 - TRIP S COIL 1 - TRIP R COIL 1 - TRIP S COIL 1 - TRIP T

+CP1

CONTROL AND PROTECTION PANEL

BANGIL -X1QA1

101 102 103 104

+C1

MARSHALLING KIOSK

B /L18.C2 QA1 Close QA1 Close /N12.B1 B
+A2.20-XDCF101:104 +U2.17-K86.2:113

-XQA1 103 +U1.06 -KF1

101 Merging Unit - 1 -X61 2 -X61 5

102 SAM600 IO

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s P6#BO.01 P6#BO.02 P6#BO.03 P6#BO.04

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. /Z60.B3 /Z60.B3 /Z60.B3 /Z60.C3 113 115 117
/Z66.D7 116 /Z66.D7 118
1 3 46 -K86.1

/Z66.D7 114

C +U2.17 -XT4 C

TSB-14
11111111111111-V 15 17 19

/Z67.B4 16 /Z67.C4 18 /Z67.C4 20

105 106 107 TRIP1_R /N12.C1
112 +C1.30-XQA1:108
104 119
113 114 TRIP1_S /N12.D1
-XQA1 +C1.30-XQA1:115

111 120 121 TRIP1_T /N12.D1 D
+C1.30-XQA1:122
D

118

EE

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 TRIP CIRCUIT 1 N11
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language N12
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 6 78

© Copyright 2020 Hitachi Power Grids. LOCKOUT RELAY 2 BBP LOCKOUT RELAY 3 TRIP CIRCUIT SUPERVISION 1 - POST CLOSE TRIP CIRCUIT SUPERVISION 1 - PRE CLOSE MANUAL OPEN
L1 - OPEN CMD L2 - OPEN CMD
A COIL 1 - TRIP R COIL 1 - TRIP S COIL 1 - TRIP T COIL 1 - TRIP R COIL 1 - TRIP S COIL 1 - TRIP T PHASE - R PHASE - S PHASE - T PHASE - R PHASE - S PHASE - T L3 - OPEN CMD A

+C1

MARSHALLING KIOSK

B /N11.B8 QA1 Close /L18.B2 QA1 Close B
+U2.17-K86.1:117 +A2.20-XDCF101:104 C

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s 13 15
TCS1-R TCS1-R
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
-P11 -P11
REF DWG NO: 2GSF000065-002
SH: 03 OF 13 113 115 117 113 115 117 /Z66.B4 14 13 /Z66.B5 16 15
/Z66.D8 116 /Z66.D8 118 /Z66.D8 116 /Z66.D8 118 TCS1-S TCS1-S
-K86.2 -K86.3
-P21 -P21
/Z66.D8 114 /Z66.D8 114
/Z66.B5 14 13 /Z66.B5 16 15 13 23 33
TCS1-T TCS1-T /Z66.D1 24 /Z66.D1 34
-KOC
-P31 -P31
/Z66.D1 14
C /Z66.B6 14 /Z66.B6 16

-XQA1

/N11.D8 TRIP1_R 108 109 110
116 117
+C1.30-XQA1:107 -XQA1 123

/N11.D8 TRIP1_S 115
+C1.30-XQA1:114
-XQA1
/N11.D8 TRIP1_T 124 125 126 127 128 129 130 131 132 133
+C1.30-XQA1:121 122

D D

+QA1

CIRCUIT BREAKER

/M12.D3 J3 CB IN LOCAL -X1

11 5 27 7 13
TRIP1_R

-X1

8
TRIP1_S

-X1

9
TRIP1_T

-X1

50
QA1_L1_PRE-CLOSE

-X1

51
QA1_L2_PRE-CLOSE

-X1

52
QA1_L3_PRE-CLOSE

-X1

4
QA1_TC1_L1

-X1

5
QA1_TC1_L2

-X1

6
QA1_TC1_L3
LOCAL
REMOTE
-CB LOCAL OPEN 79
REMOTE
-S13 7 -S12 CB REMOT8E -S12
8 LOCAL 10 15
12 6 28

TCS1

E 21 31 41 E
-K2 -K2 -K2
/M12.F3
24 34 44
F Based on
A AS MANUFACTURED CB CLOSE -Y2B CB OPEN
B AS BUILT POS POS

Rev. Revision note INTERNAL DC -Y2A -Y2C

1 CB TRIP COIL 1

Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
Approved 22-09-2021 MA SCHEMATIC DIAGRAM
25-03-2021 KD Project PT. PLN PERSERO DCC EFS en
22-09-2021 MR TRIP CIRCUIT 1 N12
DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language N21
Date Name ACP20051 HITACHI Sheet
Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 123 4 5 67 8

© Copyright 2020 Hitachi Power Grids. A SAM IO TRIP2 LOCKOUT RELAY 1 A
COIL 2 - TRIP R COIL 2 - TRIP S COIL 2 - TRIP T COIL 2 - TRIP R COIL 2 - TRIP S COIL 2 - TRIP T
+CP1

CONTROL AND PROTECTION PANEL
BANGIL

-X1QA1 202 203 204

201

+C1

MARSHALLING KIOSK

/L20.C2 +DCF201 +DCF201 /N22.B1
+A2.20-XDCF201:102 +U2.17-K86.2:213
B B
C
-XQA1 203 D

201

202 +U1.14 -KF2

Merging Unit - 2 -X61 2 -X61 5

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s SAM600 IO

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. P6#BO.01 P6#BO.02 P6#BO.03 P6#BO.04 213 225 227

/Z64.B3 /Z64.B3 /Z64.B3 /Z64.C3 -K86.1

/Z66.C7 214 /Z66.C7 226 /Z66.C7 228

1 3 46

C +U2.17 -XT4

TSB-14
11111111111111-V 23 25 21

24 26 22
/Z67.C4 /Z67.C4 /Z67.C4

-XQA1 205 206 207 TRIP2 /N22.C1
213 +C1.30-XQA1:208
204 220

211 212 214 TRIP2 /N22.D1
+C1.30-XQA1:215

218 219 221 TRIP2 /N22.D1
+C1.30-XQA1:222
D

EE

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 TRIP CIRCUIT 2 N21
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language N22
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 6 7 8
A
© Copyright 2020 Hitachi Power Grids. LOCKOUT RELAY 2 BBP LOCKOUT RELAY 3 TRIP CIRCUIT SUPERVISION 2 - POST CLOSE TRIP CIRCUIT SUPERVISION 2 - PRE CLOSE

A COIL 2 - TRIP R COIL 2 - TRIP S COIL 2 - TRIP T COIL 2 - TRIP R COIL 2 - TRIP S COIL 2 - TRIP T PHASE - R PHASE - S PHASE - T PHASE - R PHASE - S PHASE - T

+C1

MARSHALLING KIOSK

B /N21.B8 +DCF201 B
+U2.17-K86.1:227

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s 13 15
TCS2-R TCS2-R
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
-P12 -P12
REF DWG NO: 2GSF000065-002
SH: 04 OF 13 213 225 227 213 225 227 /Z66.C4 14 13 /Z66.C5 16 15
/Z66.C8 226 /Z66.C8 228 TCS2-S TCS2-S
-X1 -K86.2 -K86.3
-P22 -P22
11 /Z66.C8 214 /Z66.C8 214 /Z66.C8 226 /Z66.C8 228
-DCF201 /Z66.C5 14 13 /Z66.C5 16 15
TCS2-T TCS2-T

-P32 -P32

C /Z66.C6 14 /Z66.C6 16 C

-XQA1 235

/N21.D8 TRIP2 208 209 210 D

+C1.30-XQA1:207 -XQA1 29
-S12
/N21.D8 TRIP2 215 216 217
+C1.30-XQA1:214 223 30
-XQA1 -XQA1

/N21.D8 TRIP2 222 224 225 226 227 228 229 230 233 234
+C1.30-XQA1:221
25
/L20.C3 -DCF201 /L20.C2 +DCF201 26
+A2.20-XDCF201:103
+A2.20-X-DXCFQ20A1:5102 -XQA1

D 231 232

+QA1

CIRCUIT BREAKER

-X1 -X1

10 12
+DCF201 TRIP2

-X1

13
TRIP2

-X1

14
TRIP2

-X1

56
QA1_L1_PRE-CLOSE

-X1

57
QA1_L2_PRE-CLOSE

-X1

58
QA1_L3_PRE-CLOSE

-X1

59

-X1

60

-X1

61
LOCAL
REMOTE
17
CB REMOTE 18

TCS1

E 11 21 31 E
-K3 -K3 -K3
F Based on
A AS MANUFACTURED 14 24 34
B AS BUILT
CB CLOSE -Y3B CB OPEN
Rev. Revision note POS POS

1 INTERNAL DC -Y3A -Y3C

25-03-2021 CB TRIP COIL 2
22-09-2021
Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
Date KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
MR Project PT. PLN PERSERO DCC EFS en
2 TRIP CIRCUIT 2 N22
DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language N31
Name ACP20051 HITACHI Sheet
Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 5 6 7 8

© Copyright 2020 Hitachi Power Grids. A QA1 - CLOSE CMD CBF START QA1 - SF6 STAGE 2 LCK QA1 - OPEN QB1 - OPEN QB1 - CLOSE QB2 - OPEN

+C1 EXTERNAL RESET QA1 - CLOSE QB2 - CLOSE A

MARSHALING KIOSK
BANGIL

B B

+U1.06 -KF1

Merging Unit - 1 12 14 32 34 32 34 22 24 32 34 32 34 32 34 32 34

43 SAM600 IO-X42 11

-KOE -K502 -KRST -KQA1OP -KQA1CL -KQB1OP -KQB1CL -KQB2OP -KQB2CL

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s /Z66.D1 44 /Z66.C3 11 /Z66.B3 31 /Z66.E2 31 /Z66.E1 21 /Z66.E4 31 /Z66.E3 31 /Z66.E6 31 /Z66.E5 31

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. P4#BO.19 P4#BO.20

/Z59.D8 /Z59.D8

10 12

C -XBB C

12

3 4 5 6 7 8 9 10 11 12 13 14 15 16

DD

EE

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 INTERFACE - SPARE N31
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y11
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 6 78
A
© Copyright 2020 Hitachi Power Grids. SOFTWARE INTERLOCK CONTROL - REMOTE DC2 - MCB TRIP E05 KC1 ESW OK
FN1 BPU FAULTY
CONTROL - BCU CRP AC MCB HEALTHY EXTERNAL RESET A

>=E02 +CP1

CONTROL AND PROTECTION PANEL
PORONG OHL

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s BB

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. REF DWG: JBTB1.056-KIS-EM-A-002
SHT:Y63

+CP1 /L13.C2 C
/L13.C4
C CONTROL AND PROTECTION PANEL /Z46.B7

BANGIL -X811

116
+DCF101
+DCF101 -XKF1 +DCF101
+A.30-XDCF101:106 -X811 +C.40-XKF1:2
/L16.C3 /Y12.D1
2
/L16.C2 +DCF101 E05_ESW IS OK +DCF101 /Y12.D1
+A.30-XDCF101:102 +U.07-S3:2

24 ITL NORMAL 1 1 3 12 14 +U.22 -FN2 12 14 12 14 12 14 22 24 D
ITL BYPASS 2 REQ650 BPU -X11 3 1
D -S2 L/R SWITCH -S1 -F91 -F201 -F202 -K201 -KRST EXTERNAL RESET
ITL NORMAL/BYPASS SWITCH Relay ready
/Z46.B2 1 3 Remote0 1/Z46.B1 2 /Z46.B1 4 /G11.C2 11 11 11 11 /Z46.C5 21
BCU B R /Z31.B3

2

E +U.07 -KF1 E

REC650 BCU -X31 1 -X31 3 -X31 5 -X31 7 -X31 9 -X31 11 -X31 13 -X31 15

+ + + + + + + +
BYPASS SWITCH
P3#BI.02 P3#BI.03 P3#BI.04 P3#BI.05 P3#BI.06 P3#BI.07 P3#BI.08
P3#BI.01 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC
110-125VDC
/Z12.B3 - /Z12.B3 - /Z12.C3 - /Z12.C3 - /Z12.C3 - /Z12.D3 - /Z12.D3 -
/Z12.B3 -
4 6 8 10 12 14 16
2

/L16.C4 -DCF101
+A.30-XDCF101:503

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 BCU BINARY INPUTS Y11
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y12
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 SPARE 5 6 7 8
A A
© Copyright 2020 Hitachi Power Grids. SPARE SYNC OFF SPARE SPARE SPARE SPARE
B
SYNC ON

B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +CP1 9 3 10 11 4 12 13 5 15 16 C
D
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. C CONTROL AND PROTECTION PANEL

BANGIL

2

-XKF1

/Y11.C8 +DCF101
+C.40-XKF1:1

/Y11.D8 +DCF101
+B.10-KRST:24

D SYNC ON 1
SYNC OFF 2
2 4 SYNC ON/OFF SELECTOR SWITCH
3
-S3

/Z46.D1 1

E +U.07 -KF1 E

REC650 BCU -X32 1 -X32 3 -X32 5 -X32 7 -X32 9 -X32 11 -X32 13 -X32 15

++ + + + + + +

P3#BI.09 P3#BI.10 P3#BI.11 P3#BI.12 P3#BI.13 P3#BI.14 P3#BI.15 P3#BI.16
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

/Z12.B4 - /Z12.B4 - /Z12.B4 - /Z12.C4 - /Z12.C4 - /Z12.C4 - /Z12.D4 - /Z12.D4 -

24 6 8 10 12 14 16

/L16.C4 -DCF101
+A.30-XDCF101:504

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 BCU BINARY INPUTS Y12
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y21
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 5 6 7 8

© Copyright 2020 Hitachi Power Grids. A AR ON AR OFF SPAR TRAP/SPAR DEF RECEIVE REF DWG: JBTB.056-KIS-EM-E-012
SHT:10-11
+Y.01 TPAR DISTANCE RECEIVE DTT RECEIVE A
B
TELECOM PANEL > > > > C
D
B -X15-1-6 -X15-1--8 -X16-1-6 -X16-1-8

> > > >

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -X15-1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. 6
+DCF104

-X15-1

5
DISTANCE REC

-X15-1

7
DEF RECEIVE

-X16-1

5
DTT RECEIVE

-X16-1

7
COMM HEALTHY
>
>>>>

+CP1

C CONTROL AND PROTECTION PANEL

12 3 4 5

-XTEL

/L16.E6 +DCF104 COMM HEALTHY /Y22.D1
+A.30-XDCF104:105 +U.15-FN1:1 (-X32)

/L16.E6 +DCF104 +DCF104 /Y22.D1
+A.30-XDCF104:104 +B.10-KRST1:24

D AR ON 1
AR OFF 2
24 2
AR ON/OFF SWITCH
-S4 SPAR-S5
TPAR
/Z46.D3 1 3 /Z46.D4 1 3 7
STPAR
AR SP/TP SS

E +U.15 -FN1 E

MPU -X31 1 -X31 3 -X31 5 -X31 7 -X31 9 -X31 11 -X31 13 -X31 15

RED670 + + + + + + +

+ P3#BI.02 P3#BI.03 P3#BI.04 P3#BI.05 P3#BI.06 P3#BI.07 P3#BI.08
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC
P3#BI.01
110-125VDC /Z22.B2 - /Z22.B2 - /Z22.C2 - /Z22.C2 - /Z22.C2 - /Z22.D2 - /Z22.D2 -

/Z22.B2 - 4 6 8 10 12 14 16

2

/L16.E8 -DCF104 -DCF104 /Y22.F1
+A.30-XDCF104:504 +U.15-FN1:2 (-X32)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 KD Project PT. PLN PERSERO DCC EFS en
22-09-2021 MR MPU BINARY INPUTS Y21
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y22
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 12 3 4 5 6 7 8

© Copyright 2020 Hitachi Power Grids. TELE COMM GUARD OK EXT RESET SPARE SPARE SPARE SPARE SPARE

A SPARE A

BB

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +CP1 C
D
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. C CONTROL AND PROTECTION PANEL

5 6 7 8 9 10
23 4
/L16.E6 +DCF104
+A.30-XDCF104:103

1

-XFN1

/Y21.D3 +DCF104
+U.07-S5:2

D /Y21.C6 COMM HEALTHY 22 24
+A.30-XTEL:5
-KRST1 EXTERNAL RESET

/Z46.C6 21

E +U.15 -FN1 E

MPU -X32 1 -X32 3 -X32 5 -X32 7 -X32 9 -X32 11 -X32 13 -X32 15

RED670 + + + + + + +

+ P3#BI.10 P3#BI.11 P3#BI.12 P3#BI.13 P3#BI.14 P3#BI.15 P3#BI.16
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC
P3#BI.09
110-125VDC /Z22.B4 - /Z22.B4 - /Z22.C4 - /Z22.C4 - /Z22.C4 - /Z22.D4 - /Z22.D4 -

/Z22.B4 - 4 6 8 10 12 14 16

2

/Y21.F8 -DCF104

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 MPU BINARY INPUTS Y22
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y23
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A DISTANCE SEND DTT SEND
DEF SEND
+Y.01
DIRECT OPGW CONNECTION
TELECOM PANEL
REF DWG: JBTB.056-KIS-EM-E-012 B
B SHT:10

Optical budget 23dB, 1310nm Optical budget 7/11dB, 850nm, ST connectors
LONG SHORT

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -X15.1 -X15.1 Tx
Rx
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. 1 2 Tx
DC+ DISTANCE SEND Rx

-X15.1

4
DEF SEND

-X16.1

2
E04_DTT SEND

+CP1 C

C CONTROL AND PROTECTION PANEL 7 8 9 10 11

6

-XTEL

D D

+U.15 -FN1

MPU -X42 2 -X42 5 -X305 B A -X306 B A

RED670

E E

P4#BO.13 P4#BO.14 P4#BO.15 P4#BO.16 FC(Tx) FC(Rx) ST(Tx) ST(Rx)
/Z21.D6 /Z21.E6
IEC61850 IEC61850

/Z22.B8 /Z22.B8 /Z22.B8 /Z22.C8

1 3 46

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 COMMUNICATION SEND Y23
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y31
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 5 6 7 8
A
© Copyright 2020 Hitachi Power Grids. CRP DC1 FAIL PROTN RESET -KF1 BCU IED FAIL -FN1 MPU IED FAULTY SPARE SPARE

MPU DC1 MCB FAIL SPARE A

B B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +CP1 C

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. C CONTROL AND PROTECTION PANEL

BANGIL

1 5 6 46 2 47

-XFN2 -XFN2

/L19.C2 +DCF201 +DCF201 /Y32.C1
+A.30-XDCF201:104 +C.40-XFN2:3

/L19.C2 +DCF201
+A.30-XDCF201:103

D 12 14 12 14 12 14 12 14 12 14 EXTERNAL RESET +U.07 -KF1 12 14 +U.15 -FN1 D
REC650 BCU -X11 3 1 RED670 MPU-X11 3 1
-F101 -F102 -F103 -K101 -KRST -F104
Relay ready RELAY READY
/L11.C6 11
/Z11.B3 /Z21.B3
/L11.C2 11 /L11.C3 11 /L11.C5 11 /Z46.B6 11 /Z46.C5 11 2

2

E +U.22 -FN2 E

REQ650 BPU -X31 1 -X31 3 -X31 5 -X31 7 -X31 9 -X31 11 -X31 13 -X31 15

+ + + + + + + +

P3#BI.01 P3#BI.02 P3#BI.03 P3#BI.04 P3#BI.05 P3#BI.06 P3#BI.07 P3#BI.08
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

/Z32.B3 - /Z32.B3 - /Z32.B3 - /Z32.C3 - /Z32.C3 - /Z32.C3 - /Z32.D3 - /Z32.D3 -

2 4 6 8 10 12 14 16

/L19.C3 -DCF201 -DCF201 /Y32.F1
+A.30-XDCF201:503 +U.22-FN2:2 (-X32)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 BPU BINARY INPUTS Y31
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y32
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 5 6 7 8
A A
© Copyright 2020 Hitachi Power Grids. SPARE SPARE SPARE SPARE SPARE SPARE SPARE
B
SPARE

B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +CP1 C
D
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. C CONTROL AND PROTECTION PANEL

BANGIL

3 7 8 9 10 4 11 12 13 14

-XFN2

/Y31.C8 +DCF201
+C.40-XFN2:2

D

E +U.22 -FN2 E

REQ650 BPU -X32 1 -X32 3 -X32 5 -X32 7 -X32 9 -X32 11 -X32 13 -X32 15

+ + + + + + + +

P3#BI.09 P3#BI.10 P3#BI.11 P3#BI.12 P3#BI.13 P3#BI.14 P3#BI.15 P3#BI.16
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

/Z32.B4 - /Z32.B4 - /Z32.B4 - /Z32.C4 - /Z32.C4 - /Z32.C4 - /Z32.D4 - /Z32.D4 -

2 4 6 8 10 12 14 16

/Y31.F8 -DCF201
+U.22-FN2:16 (-X31)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 BPU BINARY INPUTS Y32
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y41
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 5 6 7 8

© Copyright 2020 Hitachi Power Grids. A QA1 - L1 CLOSE QA1 - L1 OPEN QA1 - L2 CLOSE QA1 - L3 CLOSE QA1 - L3 OPEN SPARE

+QA1 -X-A QA1 - L2 OPEN -X-C -X-C SPARE A
41 41 39
CIRCUIT BREAKER * NOTE: JUMPER TO BE DONE AT SITE -X2
49 -S1C
B REF DWG NO: 2GSF000065-002 -X-A -X2
SH: 07 OF 13 39 51

-X-A-S1A -S1A -S1B -S1B -S1C B

41 -X-A -X2 -X2 -X-C -X-C
+DCF102
40 52 50 42 40
-X-A QA1 L1 Open QA1 L2 Close QA1 L2 Open QA1 L3 Close QA1 L3 Open

42
QA1 L1 Close

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1 7 16 7

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK -XKF1
BANGIL

12 3 4 5 6

-XQA1

C /L18.C6 +DCF102 +DCF102 /Y42.C1 C
+A2.20-XDCF102:104 +C1.30-XQA1:8

/L18.C6 +DCF102 +DCF102 /Y44.C1
+A2.20-XDCF102:105 +A1.20-XKF1:2

DD

+U1.06 -KF1 -X31 1 -X31 3 -X31 5 -X31 7 -X31 9 -X31 11 -X31 13 -X31 15 E

E Merging Unit - 1 + + + + + + + +

SAM600 IO P3#BI.01 P3#BI.02 P3#BI.03 P3#BI.04 P3#BI.05 P3#BI.06 P3#BI.07 P3#BI.08
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

/Z57.B6 - /Z57.B6 - /Z57.B6 - /Z57.C6 - /Z57.C6 - /Z57.C6 - /Z57.D6 - /Z57.D6 -

2 4 6 8 10 12 14 16

/L18.C7 -DCF102 -DCF102 /Y42.F1
+A2.20-XDCF102:503 +U1.06-KF1:2 (-X32)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 SAM600 IO - 1 INPUTS Y41
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y42
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A CB QA1 SF6 ALARM CB QA1 SPRING CHARGED CB QA1 AC MOTOR SUPPLY FAIL CB QA1 REMOTE
CB QA1 SF6 LOCKOUT CB QA1 LOCAL B
+QA1 CB QA1 POLE DISC OPTD CB QA1 AC MCB SUPPLY FAIL

CIRCUIT BREAKERREF DWG NO: 2GSF000065-002 -X01 -X02 -X03 -X2 -X2 -X-A -X-C -X2 -X2 -X2 -X-A -X-C -X2 -X-A -X-C -X2 -X2
SH: 07 OF 13 20 20 20 21 29 17 17 25 23 27 19 19 31 21 21 61 59
B
11 11 11 41 12 12 12 41 15 21 21 21 21 21 21 19
+C1 -S3-B -S3-C -K7 -KT6 -F3 -F3A -F3C -F4 -F4A -F4C -S12 -S12
-X01 -F2 -F2 -F2 -K3 -S3-A
MARSHALING KIOSK 11 11 11 44 18 22 22 22 22 22 22 20
BANGIL 20
+DCF102 -X-A -X-C -X-A -X-C -X-A -X-C
18 18 20 20 22 22
-X01

21
CB SF6 Alarm

-X02

21
CB SF6 Alarm

-X03

21
CB SF6 Alarm

-X2

22
CB SF6 Lockout
12 12 12 42

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -X2 -X2

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. 30 26
CB Spring Charged Pole Discrepancy

-X2

24

-X2

28
CB MOTOR MCB TRIP

-X2

32
CB AC MCB Trip

-X2

62
CB Remote

-X2

60
CB Local

8 9 10 11 12 13 14 15 16

-XQA1

C /Y41.C8 +DCF102 +DCF102 /Y43.C1 C
+C1.30-XQA1:1 +C1.30-XQB1:1

A1 /Z66.D2 31

-K501 -K501

/Z66.C2 A2 32 34

A1

-K502

/Z66.C3 A2

/L18.C8 -DCF102
+A2.20-XDCF102:504

D D

/L18.C6 +DCF102 +DCF102 /Y45.C1
+A2.20-XDCF102:103 +C2.10-F93:12

12 14 22 24

-K501 -K502

/Z66.C2 11 /Z66.C3 21

+U1.06 -KF1 -X32 1 -X32 3 -X32 5 -X32 7 -X32 9 -X32 11 -X32 13 -X32 15 E

E Merging Unit - 1 + + + + + + + +

SAM600 IO P3#BI.09 P3#BI.10 P3#BI.11 P3#BI.12 P3#BI.13 P3#BI.14 P3#BI.15 P3#BI.16
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

/Z57.B8 - /Z57.B8 - /Z57.B8 - /Z57.C8 - /Z57.C8 - /Z57.C8 - /Z57.D8 - /Z57.D8 -

2 4 6 8 10 12 14 16

/Y41.F8 -DCF102 -DCF102 /Y43.F1
+U1.06-KF1:16 (-X31) +U1.06-KF1:2 (-X51)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 SAM600 IO - 1 INPUTS Y42
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y43
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 DS2 CLOSE 6 7 8
-X2:1
© Copyright 2020 Hitachi Power Grids. A DS1 CLOSE DS1 REMOTE +QB2 DS2 OPEN DS2 REMOTE DS2 MOTOR MCB FAIL
DS1 MOTOR MCB FAIL
+QB1 DS1 OPEN DISCONNECTOR -X2:3 A
BUS 2 B
DISCONNECTOR
BUS 1 REF DWG: FU10.61YMM400.LV07 -X2:1 -X2:3 -X2:54 DS REMOTE -X2:73 -X2 Motor MCB TRip REF DWG: FU10.61YMM400.LV07-QB2 -QB2 -X2:54 DS REMOTE -X2:73 Motor MCB TRip DS2 MOTOR MCB FAIL
SH: 6/10 -QB1 -QB1 SH: 6/10
B 5 51 74 5 51
-SA1 -QM1 DS1 MOTOR MCB FAIL -X2 -SA1 -QM1
6
6 52 1 52
+DCF102
-X2 4 51 DS1 REMOTE 2 4 51 DS2 REMOTE -X2
QB1 Open QB2 Close QB2 Open
1 74
+DCF102
2
QB1 Close

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK
BANGIL

1 2 3 45 12 3 4 5

-XQB1 -XQB2

C /Y42.C8 +DCF102 +DCF102 /Y44.C1 C
+C1.30-XQA1:8 +C1.20-XQB8:1

DD

+U1.06 -KF1 -X51 3 -X51 5 -X51 7 -X51 9 -X51 11 -X51 13 -X51 15 E

E Merging Unit - 1 -X51 1 + + + + + + +

SAM600 IO P5#BI.02 P5#BI.03 P5#BI.04 P5#BI.05 P5#BI.06 P5#BI.07 P5#BI.08
+ 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

P5#BI.01 /Z58.B3 - /Z58.B3 - /Z58.C3 - /Z58.C3 - /Z58.C3 - /Z58.D3 - /Z58.D3 -
110-125VDC
4 6 8 10 12 14 16
/Z58.B3 -

2

/Y42.F8 -DCF102 -DCF102 /Y44.F1
+U1.06-KF1:16 (-X32) +U1.06-KF1:2 (-X52)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 KD Project PT. PLN PERSERO DCC EFS en
22-09-2021 MR SAM600 IO - 1 INPUTS Y43
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y44
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 56 7 8

© Copyright 2020 Hitachi Power Grids. A DSL CLOSE DSL REMOTE DSL MOTOR MCB FAIL ES CLOSE SPARE

+QB8 DSL OPEN ES OPEN SPARE A

DISCONNECTOR +QC9 REF DWG: SH-SIG-06160 -XT2
DSL SH: 1/1 7
EARTH SWITCH
B -XT2
-X2:1 -X2:3 -X2:44 -X2:73 5
-QB8 -QB8
5 DS REMOTE 51 -X2 Motor MCB TRip B
-SA1 -QM1 -XT2
74
6 52 DS1 MOTOR MCB FAIL 5
+DCF102
-X2 4 41 DS1 REMOTE 6
QB1 Open ESL QC9 CLOSE
1 8
+DCF102 ESL QC9 OPEN
2
QB1 Close

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK
BANGIL

1 2 3 45 1 2 32 8 9

-XQB8 -XQC9 -XKF1 C

C /Y43.C8 +DCF102
+C1.30-XQB2:1

/Y41.C8 +DCF102 +DCF102 /Y47.C1
+A1.20-XKF1:1 +A1.20-XKF1:3

DD

+U1.06 -KF1 -X52 3 -X52 5 -X52 7 -X52 9 -X52 11 -X52 13 -X52 15 E

E Merging Unit - 1 -X52 1 + + + + + + +

SAM600 IO P5#BI.10 P5#BI.11 P5#BI.12 P5#BI.13 P5#BI.14 P5#BI.15 P5#BI.16
+ 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

P5#BI.09 /Z58.B5 - /Z58.B5 - /Z58.C5 - /Z58.C5 - /Z58.C5 - /Z58.D5 - /Z58.D5 -
110-125VDC
4 6 8 10 12 14 16
/Z58.B5 -

2

/Y43.F8 -DCF102 -DCF102 /Y45.F1
+U1.06-KF1:16 (-X51) +U1.06-KF1:2 (-X71)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 KD Project PT. PLN PERSERO DCC EFS en
22-09-2021 MR SAM600 IO - 1 INPUTS Y44
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y45
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 56 7 8
A A
© Copyright 2020 Hitachi Power Grids. MK MOTOR AC MCB FAIL SAM600 IO-2 FAIL BPU IN SERVICE SAMIO IN SERVICE
SPAREMK MAIN /HEATER MCB OK
MPU IN SERVICE BBP IN SERVICE DC2 MCB FAIL

B B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK
BANGIL

C C

/Y42.D8 +DCF102 +DCF102 /Y46.C1
+A1.10-K502:24 +U2.17-P11:25

12 14 12 14 12 14 12 14 97 +U1.14 -KF2 17 13-MPU TEST SWITCH 13 13 12 14 12 14 12 14 12 14 12 14 12 14
Merging Unit --2X11 3 1 -BPU TEST SWITCH
-F93 -F94 -F95 -F96 DSL MOTOR SU-FPP9L1Y -XT1 -XT2 -BBP TEST SWITCH-XT3-XT4 -F201 -F202 -F203 -F204 -F205 -K201
SAM600 IO -SAM IO TEST SWITCH
/G14.D3 11 /G14.D4 11 /G14.D5 11 /G14.D7 11 /G12.C3 98 /Z67.C1 18 /Z67.B2 14 /Z67.B3 14 /Z67.B4 14 /L14.C2 11 /L14.C4 11 /L14.C6 11 /L14.C7 11 /L15.C2 11 /Z66.C4 11
Internal fail
#IRF

/Z61.B3

D2 D

12 14

-F92

/G12.D8 11

+U1.06 -KF1 -X71 1 -X71 3 -X71 5 -X71 7 -X71 9 -X71 11 -X71 13 -X71 15 E

E Merging Unit - 1 + + + + + + + +
P7#BI.01
SAM600 IO 110-125VDC P7#BI.02 P7#BI.03 P7#BI.04 P7#BI.05 P7#BI.06 P7#BI.07 P7#BI.08
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC
/Z58.B6 -
2 /Z58.B6 - /Z58.B6 - /Z58.C6 - /Z58.C6 - /Z58.C6 - /Z58.D6 - /Z58.D6 -

25-03-2021 4 6 8 10 12 14 16
22-09-2021
/Y44.F8 -DCF102 -DCF102 /Y46.F1
+U1.06-KF1:16 (-X52) Date +U1.06-KF1:2 (-X72)

F Based on 2 Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT MR Project PT. PLN PERSERO DCC EFS en
SAM600 IO - 1 INPUTS Y45
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y46
Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 5 6 7 8
A
© Copyright 2020 Hitachi Power Grids. TCS 1 FAIL TCS 2 FAIL LOCKOUT OPERATED LINE PRTN VT MCB OK LINE CTL VT MCB OK EXTERNAL RESET BBP LOCKOUT OPERATED

MK ON LOCAL A

B B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK
BANGIL

C C

/Y45.C8 +DCF102 +DCF102 /Y47.C1
+A2.10-K201:12 +C2.10-F97:12

D 25 25 25 25 25 25 123 123 13 Local 12 14 12 14 12 14 123 D
14 /Z65.B2 1 0 Remote
-P11 -P21 -P31 -P12 -P22 -P32 -K86.1 -K86.2 L -KLVT1 -KLVT2 -KRST1 -K86.3
L/R SWITCH
/Z66.B5 26 /Z66.B5 26 /Z66.B6 26 /Z66.C5 26 /Z66.C5 26 /Z66.C6 26 /Z66.C7 124 /Z66.C8 124 PROTN VT MCB - OK/Z66.B1 11/Z66.B2 11/Z66.B4 11 /Z66.C8 124

CNTL VT MCB OK
EXTERNAL RESET

+U1.06 -KF1 -X72 1 -X72 3 -X72 5 -X72 7 -X72 9 -X72 11 -X72 13 -X72 15 E

E Merging Unit - 1 + + + + + + + +

SAM600 IO P7#BI.09 P7#BI.10 P7#BI.11 P7#BI.12 P7#BI.13 P7#BI.14 P7#BI.15 P7#BI.16
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

/Z58.B8 - /Z58.B8 - /Z58.B8 - /Z58.C8 - /Z58.C8 - /Z58.C8 - /Z58.D8 - /Z58.D8 -

2 4 6 8 10 12 14 16

/Y45.F8 -DCF102 -DCF102 /Y47.F1
+U1.06-KF1:16 (-X71) +U1.06-KF1:2 (-X81)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 SAM600 IO - 1 INPUTS Y46
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y47
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 23 4 5 6 7 8
A
© Copyright 2020 Hitachi Power Grids. AIRCONDITIONER SUPPLY SYNC ON TCS 2 PHASE R TCS 2 PHASE S TCS 2 PHASE T

QA1 CB MANUAL CLOSE CMD SYNC OFF SPARE A

B 27 27 27 B
C
-P12 -P22 -P32 D

/Z66.C5 28 /Z66.C5 28 /Z66.C6 28

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK
BANGIL

3 4 12 5 13 14 15

-XKF1

C /Y44.C8 +DCF102
+A1.20-XKF1:2

/Y46.C8 +DCF102
+U2.17-K86.3:123

12 14 AIRCONDITIONER SUPPLY 8+U2.06 -SQA1 2 4 SYNC ON 1
/Z65.D5 3 SYNC OFF 2
-F97 CIRCUIT BREAKER -S2 SYNC ON/OFF SELECTOR SWITCH

/G14.D8 11 QA1 OPEN/CLOSE SWITCH /Z65.B2 1

D OP 1
O2
7 C3

CL 4

+U1.06 -KF1 -X81 1 -X81 3 -X81 5 -X81 7 -X81 9 -X81 11 -X81 13 -X81 15 E

E Merging Unit - 1 + + + + + + + +

SAM600 IO P8#BI.01 P8#BI.02 P8#BI.03 P8#BI.04 P8#BI.05 P8#BI.06 P8#BI.07 P8#BI.08
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

/Z59.B3 - /Z59.B3 - /Z59.B3 - /Z59.C3 - /Z59.C3 - /Z59.C3 - /Z59.D3 - /Z59.D3 -

2 4 6 8 10 12 14 16

/Y46.F8 -DCF102
+U1.06-KF1:16 (-X72)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 SAM600 IO - 1 INPUTS Y47
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y51
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 6 7 8
A
© Copyright 2020 Hitachi Power Grids. MK DC-1 FAIL EXTERNAL RESET SPARE LA Counter S LA Counter T

SAM600 IO-1 FAIL SPARE LA Counter R +F10.S +F10.T A

+F10.R LIGHTINING LIGHTINING
ARRESTOR ARRESTOR
LIGHTINING PH. S PH.T
ARRESTOR
PH. R

BB

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1 EXTERNAL RESET 2 4 6
#35
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK +DCF202
BANGIL #
LA Counter R
1 13 14 #2 15 31
+DCF202
-XKF2 #+DCF202 -XFA
LA Counter S
#/L20.C6+A2.20-XDCF202:105
+DCF202
C /L20.C6 +DCF202 # +DCF202 /Y52.C1 C
+A2.20-XDCF202:104 LA Counter T +A1.30-XKF2:4

/L20.C6 +DCF202
+A2.20-XDCF202:103

+U1.06 -KF1

Merging Unit - 1 -X11 3 1

D 12 14 12 14 12 14 12 14 12 14 SAM600 IO D

-F101 -F102 -F103 -F104 -K101 Internal fail 22 24

/L12.C2 11 /L12.C4 11 /L12.C6 11 /L12.C7 11 /Z66.C3 11 #IRF -KRST1

/Z57.B3 /Z66.B4 21

2

+U1.14 -KF2 -X31 3 -X31 5 -X31 7 -X31 9 -X31 11 -X31 13 -X31 15 E

E Merging Unit - 2 -X31 1 + + + + + + +

SAM600 IO P3#BI.02 P3#BI.03 P3#BI.04 P3#BI.05 P3#BI.06 P3#BI.07 P3#BI.08
+ 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

P3#BI.01 /Z61.B6 - /Z61.B6 - /Z61.C6 - /Z61.C6 - /Z61.C6 - /Z61.D6 - /Z61.D6 -
110-125VDC
4 6 8 10 12 14 16
/Z61.B6 -

2

/L20.C7 -DCF202 -DCF202 /Y52.F1
+A2.20-XDCF202:503 +U1.14-KF2:2 (-X32)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 KD Project PT. PLN PERSERO DCC EFS en
22-09-2021 MR SAM600 IO - 2 INPUTS Y51
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y52
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 5 6 7 8
A
© Copyright 2020 Hitachi Power Grids. TCS 1 PHASE R TCS 1 PHASE S TCS 1 PHASE T SPARE SPARE SPARE

SPARE SPARE A

27 27 27 B
C
-P11 -P21 -P31

/Z66.B5 28 /Z66.B5 28 /Z66.B6 28

B 20 21 5 22

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK
BANGIL

4 19 23 6 24 25 26

-XKF2

C /Y51.C8 +DCF202
+A1.30-XKF2:3

DD

+U1.14 -KF2 -X32 1 -X32 3 -X32 5 -X32 7 -X32 9 -X32 11 -X32 13 -X32 15 E

E Merging Unit - 2 + + + + + + + +

SAM600 IO P3#BI.09 P3#BI.10 P3#BI.11 P3#BI.12 P3#BI.13 P3#BI.14 P3#BI.15 P3#BI.16
110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC 110-125VDC

/Z61.B8 - /Z61.B8 - /Z61.B8 - /Z61.C8 - /Z61.C8 - /Z61.C8 - /Z61.D8 - /Z61.D8 -

2 4 6 8 10 12 14 16

/Y51.F8 -DCF202
+U1.14-KF2:16 (-X31)

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 SAM600 IO - 2 INPUTS Y52
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y61
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 56 78
A
© Copyright 2020 Hitachi Power Grids. A QA1 - OPEN QA1- CLOSE QB1 - OPEN QB1 - CLOSE QB2 - OPEN QB2 - CLOSE
B
+QA1 +QB1 +QB2

CIRCUIT BREAKER DISCONNECTOR DISCONNECTOR
BUS 1 BUS 2
-X-A -X-C -X2 -X-A -X-C REF DWG: FU10.61YMM400.LV07 REF DWG: FU10.61YMM400.LV07
44 43 -X2 :11 -X2 :9SH: 006/010 SH: 006/010 -X2 :11 -X2 :9
55 45 45
61 62 63-X2 -X2 61 62 63
B REF DWG NO: 2GSF000065-002 -X-A -X-C
-X2 -X-ASH: 07 OF 13 46 46 -XQB1 11 11 -XQB2
54 43 +DCF204 +DCF204
-X1
-X2 -X2
53
+DCF204 12 12
QB1_OPEN -QB2 OPEN
-X1
-X2 -X2
44
QA1 OPEN 10 10
QB1_CLOSE -QB2 CLOSE
-X1

56
QA1 _CLOSED

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK
BANGIL

61 62 63

-XQA1

C /L20.E5 +DCF204 +DCF204 /Y62.C1 C
+A2.20-XDCF204:105 +C1.20-XQB8:61

D D
E
A1 A1 A1 A1 A1 A1

-KQA1OP -KQA1CL -KQB1OP -KQB1CL -KQB2OP -KQB2CL

/Z66.E2 A2 /Z66.E1 A2 /Z66.E4 A2 /Z66.E3 A2 /Z66.E5 A2 /Z66.E5 A2

A1

-KQA1OP1

/Z66.E3 A2

E

/L20.E7 +A2.20-XDCF204:506 +A1.10-KQB8OP:A2 /Y62.E1

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 BAY CONTACT MULTIPLIER Y61
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y62
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 12 3 4 5 67 8
A
© Copyright 2020 Hitachi Power Grids. QB8 - OPEN QB8 - CLOSE QC9 - OPEN QC9 - CLOSE B

A +QC9 C

+QB8 EARTH SWITCH

DISCONNECTOR
LINE

REF DWG: FU10.61YMM400.LV07-X2 :11 -X2 :9 -XT2 :11 -XT2 :9
SH: 006/010
B REF DWG: SH-SIG-06160
-X2 SH: 1/1

11 -XT2
+DCF204
11
-X2 +DCF204
12
12 QC9_OPEN
QB8_OPEN 10
QC9_CLOSE
-X2

10
QB8_CLOSE

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +C1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MARSHALING KIOSK
BANGIL

61 62 63 61 62 63

+DCF204 -XQB8 -XQC9
+C1.30-XQB2:61
C /Y61.C7

D D
E
A1 A1 A1 A1

-KQB8OP -KQB8CL -KQC9OP -KQC9CL

/Z66.E7 A2 /Z66.E6 A2 /Z66.E8 A2 /Z66.E7 A2

E

/Y61.E7 +A1.10-KQB2CL:A2

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 BAY CONTACT MULTIPLIER Y62
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y63
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 12 34 5 6 7 8

© Copyright 2020 Hitachi Power Grids. DISCREPANCY INDICATOR QB8 - CLOSE QC9 - OPEN QC9 - CLOSE

A QA1 - CLOSE QA1 - OPEN QB1 - CLOSE QB1 - OPEN QB2 - CLOSE QB2 - OPEN QB8 - OPEN A
B
+C1

MARSHALING KIOSK
BANGIL

/L20.E4 +DCF204
+A2.20-XDCF204:102

-X51 32 34 42 44 42 44 32 34 32 34

B 56 -KQB1CL -KQB2CL -KQB8CL -KQC9OP

-KQA1CL /Z66.E3 41 /Z66.E5 41 /Z66.E6 31 /Z66.E8 31

-S30 /Z66.E1 31 12 14 12 14 12 14 32 34 32 34

TEST LAMP -KQB1OP -KQB2OP -KQB8OP -KQC9CL

-KQA1OP1 /Z66.E4 11 /Z66.E6 11 /Z66.E7 31 /Z66.E8 31

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s 4
/Z66.E3 11
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
/Y63.D1 3 -SQA1 16 QA1 OPEN/CLOSE SWITCH -SQB1 12 QB1 OPEN/CLOSE SWITCH -SQB2 12 QB2 OPEN/CLOSE SWITCH 11 12
/Z65.D5 /Z65.D6 /Z65.D7 QB8 OPEN/CLOSE CMD
13 9 9 -SQB8
14 15 10 11 10 11
/Z65.D5 /Z65.D6 /Z65.D7 9
10

C C

1 1 1 1 1 1 1 1

-DQA.1 -DQA.3 -DQB1.1 -DQB1.3 -DQB2.1 -DQB2.3 -DQB8.1 -DQB8.2

1 11 11 1 1 1

D -S30 1 1 1 1 +U2.06 -QC9 1 2 D
3 E
14 13 -D01 -D02 -D03 -D04 ES-QC9
/Y63.E7
1 1 1 1 LED INDICATOR
43 QA1 OPEN/CLOSE SWITCH
/Y63.C1 L1 QB1 OPEN/CLOSE SWITCHL1 L1 -SQB8 L1
QB2 OPEN/CLOSE SWITCH L2
LAMP TEST PUSHBUTTON -SQA1 QB8 OPEN/CLOSE CMD-SQB1-SQB2

-K74T /Z65.B5 L2 OPEN/Z65.B6 L2/Z65.B7 L2
CLOSED
/Y63.E2 1 1 1 1
31 /Y63.E2
-DQA.2 -DQB1.2 -DQB2.2 -DQB8.3
4
1 1 1 1
68

E5

FLICKER RELAY

/Y63.E1 7 34 14
1 /Y63.E1
-K74T -S30

2 /Y63.D1 13

4

-X51

/L20.E6 +A2.20-XDCF204:502 Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
F Based on 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
A AS MANUFACTURED 22-09-2021 BAY MIMIC INDICATOR Y63
B AS BUILT DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y70
Date Name ACP20051 HITACHI Sheet
Rev. Revision note Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
1 7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 4 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A KC1_DEVICE IS OK B

+CP1 C

CONTROL AND PROTECTION PANEL
BANGIL

B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +U.01 -KC1 -R1 1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. AFS670 ETHERNET
SWITCH

/Z41.C3

2

C

D D

-X811 2

1

>=E04 +CP1

CONTROL AND PROTECTION PANEL
KTT BAY
-XKF1

1
+DCF101

6
E02_PORONG ESW OK
E E

REF DWG: JBTB1.056-KIS-EM-E-003
SHT:Y11

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 COMMON ALARM CIRCUIT Y70
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y71
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 45 6 78
A
© Copyright 2020 Hitachi Power Grids. A >=E04 +CP1

>=E02 +CP1 CONTROL AND PROTECTION PANEL
KTT BAY
CONTROL AND PROTECTION PANEL
PORONG OHL

REF DWG: JBTB1.056-KIS-EM-E-002, SH Y71 REF DWG: JBTB1.056-KIS-EM-E-003, SH Y71

B B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -KC1 Tx
#
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. P2 Rx
Rx P2
#
Tx -KC1

+CP1 C

CONTROL AND PROTECTION PANEL
BANGIL

C

+U.07 -KF1 +U.15 -FN1 +U.22 -FN2

REC650 BCU RED670 MPU REQ650 BPU

100FX /Z11.C4 100FX /Z21.B6 100FX /Z31.C4
Ethernet port Ethernet port Ethernet port

D LC LC LC LC LC LC D

-X301 TX RX -X301 TX RX -X301 TX RX

SPARE SPARE SPARE SPARE SPARE

+U.01 -KC1 Rx Tx -P3 Rx Tx -P4 Rx Tx -P5 Rx Tx -P6 Rx Tx -P7 Rx Tx -P8 -P2 Tx Rx E
AFS670 ETHERNET SWITCH-P1 Tx Rx ST ST
/Z41.C4 -P9 RJ45
E /Z41.B4

ST ST ST ST ST ST ST ST ST ST ST ST ST /Z41.B6 ST
/Z41.B4
ETHERNET PORT ETHERNET PORT ETHERNET PORT ETHERNET PORT ETHERNET PORT 10/100Tx
#FO1 /Z41.C4 /Z41.D4 /Z41.D4 /Z41.E4 ETHERNET PORT ETHERNET PORT #LAN9 ETHERNET PORT
#FO2
100FX 100FX 100FX 100FX 100FX #FO7 /Z41.E4 #FO8 ETHERNET PORT
-P10 RJ45 100FX
100FX 100FX

/Z41.B6
10/100Tx
#LAN10
ETHERNET PORT

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 COMMUNICATION CIRCUIT Y71
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y72
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 45 6 78
A
© Copyright 2020 Hitachi Power Grids. A >=E04 +CP1

>=E02 +CP1 CONTROL AND PROTECTION PANEL
KTT BAY
CONTROL AND PROTECTION PANEL
PORONG OHL

REF DWG: JBTB1.056-KIS-EM-E-002, SH Y72 REF DWG: JBTB1.056-KIS-EM-E-003, SH Y72

B B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -KC101 -KC101

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. P2 P1
Rx Rx

-KC101 -KC101

# #
Tx Tx

+CP1 C

CONTROL AND PROTECTION PANEL
BANGIL

C

+U.07 -KF1 +U.15 -FN1 +U.22 -FN2

REC650 BCU RED670 MPU REQ650 BPU

100FX /Z11.B4 100FX /Z21.B6 100FX /Z31.B4
Ethernet port Ethernet port Ethernet port

D LC LC LC LC LC LC D

-X302 TX RX -X302 TX RX -X302 TX RX

+U.03 -KC101 Rx Tx -P3 Rx Tx -P4 Rx Tx -P5 Rx Tx -P6 Rx Tx -P7 -P1 Tx Rx E
AFS677 ETHERNET SWITCH -P1 Tx Rx

E

LC LC LC LC LC LC LC LC LC LC LC LC LC LC
Ethernet port /Z43.B3 /Z43.C3 /Z43.D3 /Z43.E3 /Z43.E3 /Z43.B4 Ethernet port /Z43.B3
Ethernet port Ethernet port Ethernet port Ethernet port Ethernet port
1000LX #LAN3 #LAN4 #LAN5 #LAN6 #LAN7 1000LX
100FX 100FX 100FX 100FX 100FX

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 COMMUNICATION CIRCUIT Y72
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y73
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A B

+C1 C

MARSHALING KIOSK D
BANGIL

+V1.10 -TS1 +U1.06 -KF1 +U1.14 -KF2

B SAM 600 -TS Merging Unit - 1 Merging Unit - 2
SAM600 IO SAM600 IO

#ETH3 /Z56.D3 100FX /Z57.B5 100FX /Z61.B5
Ethernet port Ethernet port

SFP SFP LC LC LC LC

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -X101 Tx Rx -X301 TX RX -X301 TX RX

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. +U1.22 -TJ1 IEC 61850
-FO1
ODF -FO2 -FO3 -FO4 -FO5
ST 1
C ST 2 ST 3 ST 4 ST 5

-FO1 -FO2 -FO3 -FO4 -FO5

1 ST 2 ST 3 ST 4 ST 5 ST

+CP1

CONTROL AND PROTECTION PANEL

BANGIL +U.13 -TJ1

D ODF -FO1 -FO2 -FO3 -FO4 -FO5

ST 1 ST 2 ST 3 ST 4 ST 5

-FO1 -FO2 -FO3 -FO4 -FO5

1 ST 2 ST 3 ST 4 ST 5 ST

+U.03 -KC101 Rx Tx -P8 Rx Tx -P9 Rx Tx -P10 E

AFS677 ETHERNET SWITCH

E

LC LC LC LC LC LC
/Z43.B4 /Z43.C4 /Z43.D4
Ethernet port Ethernet port Ethernet port
#LAN8 #LAN9 #LAN10
100FX 100FX 100FX

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 COMMUNICATION CIRCUIT Y73
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y74
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 3 45 6 78
A
© Copyright 2020 Hitachi Power Grids. A >=E04 +CP1

>=E02 +CP1 CONTROL AND PROTECTION PANEL
KTT BAY
CONTROL AND PROTECTION PANEL
PORONG OHL

REF DWG: JBTB1.056-KIS-EM-E-002, SH Y74 REF DWG: JBTB1.056-KIS-EM-E-003, SH Y74

B B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -KC201 -KC201

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. P2 P1
Rx Rx

-KC201 -KC201

# #
Tx Tx

+CP1 C

CONTROL AND PROTECTION PANEL
BANGIL

C

+U.07 -KF1 +U.15 -FN1 +U.22 -FN2

REC650 BCU RED670 MPU REQ650 BPU

100FX /Z11.B4 100FX /Z21.C6 100FX /Z31.B4
Ethernet port Ethernet port Ethernet port

D LC LC LC LC LC LC D

-X303 TX RX -P1 TX RX -X303 TX RX

+U.05 -KC201 Rx Tx -P3 Rx Tx -P4 Rx Tx -P5 Rx Tx -P6 Rx Tx -P7 -P1 Tx Rx E
AFS677 ETHERNET SWITCH -P1 Tx Rx

E

LC LC LC LC LC LC LC LC LC LC LC LC LC LC
Ethernet port /Z45.B3 /Z45.C3 /Z45.D3 /Z45.E3 /Z45.E3 /Z45.B4 Ethernet port /Z45.B3
Ethernet port Ethernet port Ethernet port Ethernet port Ethernet port
1000LX #LAN3 #LAN4 #LAN5 #LAN6 #LAN7 1000LX
100FX 100FX 100FX 100FX 100FX

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 COMMUNICATION CIRCUIT Y74
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y75
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A B

+C1 C

MARSHALING KIOSK D
BANGIL

+V1.10 -TS1 +U1.06 -KF1 +U1.14 -KF2

B SAM 600 -TS Merging Unit - 1 Merging Unit - 2
SAM600 IO SAM600 IO

/Z56.D3 #ETH4 /Z57.B5 100FX /Z61.B5 100FX
Ethernet port Ethernet port

SFP SFP LC LC LC LC

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s Rx Tx -X102 RX TX -X302 RX TX -X302

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. +U1.22 -TJ1 IEC 61850

ODF -FO13 -FO14 -FO15 -FO16 -FO17

C ST 13 ST 14 ST 15 ST 16 ST 17

-FO13 -FO14 -FO15 -FO16 -FO17

13 ST 14 ST 15 ST 16 ST 17 ST

+CP1

CONTROL AND PROTECTION PANEL

BANGIL +U.13 -TJ1

D ODF -FO13 -FO14 -FO15 -FO16 -FO17

ST 13 ST 14 ST 15 ST 16 ST 17

-FO13 -FO14 -FO15 -FO16 -FO17

13 ST 14 ST 15 ST 16 ST 17 ST

+U.05 -KC201 -P8 Tx Rx -P9 Tx Rx -P10 Tx Rx E

AFS677 ETHERNET SWITCH

E

LC LC LC LC LC LC
/Z45.B4 /Z45.C4 /Z45.D4
Ethernet port Ethernet port Ethernet port
#LAN8 #LAN9 #LAN10
100FX 100FX 100FX

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 COMMUNICATION CIRCUIT Y75
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y76
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A A
© Copyright 2020 Hitachi Power Grids.

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s B B
C
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. +C1 D
E
MARSHALING KIOSK
BANGIL

C

IEC 61850 IEC 61850-9-2 IEC 61850-9-2 IEC 61850-9-2 IEC 61850-9-2

+V1.10 -TS1 +C2.30 -CM1 +C2.30 -CM2 +C2.30 -CM3 +C2.20 -CM4

D SAM 600 -TS -X106 Tx Rx SAM CT - 1 -X101 Tx Rx SAM CT - 2 -X101 Tx Rx SAM CT -X3101 Tx Rx SAM VT - 1 -X101 Tx Rx

SAM600 SAM600 SAM600 SAM600

SFP SFP LC LC LC LC LC LC SFP SFP

#ETH5 /Z56.E3 #ETH3 /Z51.D3 #ETH3 /Z52.D3 #ETH3 /Z53.D3 #ETH3 /Z54.D3
100Base-FX 100Base-FX 100Base-FX 100Base-FX

#ETH6 /Z56.E3 100Base-FX /Z51.A1 100Base-FX /Z52.A1 100Base-FX /Z53.A1 100Base-FX /Z54.A1
#ETH4 #ETH4 #ETH4 #ETH4

SFP SFP LC LC LC LC LC LC SFP SFP

E -X107 Tx Rx -X102 Tx Rx -X102 Tx Rx -X102 Tx Rx -X102 Tx Rx

IEC 61850 IEC 61850-9-2 IEC 61850-9-2 IEC 61850-9-2 IEC 61850-9-2

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 COMMUNICATION CIRCUIT Y76
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y81
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8

© Copyright 2020 Hitachi Power Grids. A A
B
+CP1 C
D
CONTROL AND PROTECTION PANEL
BANGIL

+U.07 -KF1 -X41 5 -X41 8 -X41 11 -X41 14 -X41 17 -X42 2 -X42 5

REC650 BCU

B #BO.03 #BO.04 #BO.05 #BO.06 #BO.07 #BO.08 #BO.09 #BO.10 #BO.11 #BO.12 #BO.13 #BO.14 #BO.15 #BO.16
/Z12.C6 /Z12.C6 /Z12.B8 /Z12.B8
/Z12.B6 /Z12.C6 7 9 /Z12.D6 /Z12.D6 /Z12.D6 /Z12.E6 /Z12.E6 /Z12.E6 1 3 /Z12.B8 /Z12.C8

46 10 12 13 15 16 18 46

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -XKF1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. 14 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

C

+U.07 -KF1 -X42 8 -X42 11 -X42 17

REC650 BCU

#BO.17 #BO.18 #BO.19 #BO.20 #BO.23 #BO.24
/Z12.C8 /Z12.C8
7 9 /Z12.D8 /Z12.D8 /Z12.E8 /Z12.E8

10 12 16 18

D

-XKF1

38 39 40 41 42 43 44 45 46

EE

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 BCU BINARY OUTPUT SPARE Y81
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y82
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A B

+CP1 C

CONTROL AND PROTECTION PANEL
BANGIL

+U.15 -FN1 -X41 2 -X41 5 -X41 8 -X41 11

RED670
MPU

B P4#BO.01 P4#BO.02 P4#BO.03 P4#BO.04 P4#BO.05 P4#BO.06 P4#BO.07 P4#BO.08

/Z22.B6 /Z22.B6 /Z22.B6 /Z22.C6 /Z22.C6 /Z22.C6 /Z22.D6 /Z22.D6

13 46 79 10 12

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -XFN1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. 21 22 23 24 25 26 27 28 29 30 31 32

C

DD

EE

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 MPU BINARY OUTPUT SPARE Y82
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y83
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 56 7 8
A
© Copyright 2020 Hitachi Power Grids. A B

+CP1 C

CONTROL AND PROTECTION PANEL
BANGIL

+U.22 -FN2 -X41 5 -X41 8 -X41 11 -X41 14 -X41 17

REQ650 BPU

B #BO.03 #BO.04 #BO.05 #BO.06 #BO.07 #BO.08 #BO.09 #BO.10 #BO.11 #BO.12
/Z32.C6 /Z32.C6
/Z32.B6 /Z32.C6 7 9 /Z32.D6 /Z32.D6 /Z32.D6 /Z32.E6 /Z32.E6 /Z32.E6

46 10 12 13 15 16 18

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -XFN2

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

C

DD

EE

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 BPU BINARY OUTPUT SPARE Y83
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y84
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 56 7 8
A
© Copyright 2020 Hitachi Power Grids. A B

+C1 C

MARSHALING KIOSK
BANGIL

+U1.06 -KF1 -X61 11 -X61 14 -X61 17 -X62 2 -X62 5

Merging Unit - 1
SAM600 IO

B P6#BO.07 P6#BO.08 P6#BO.09 P6#BO.10 P6#BO.11 P6#BO.12 P6#BO.13 P6#BO.14 P6#BO.15 P6#BO.16

/Z60.D3 /Z60.D3 /Z60.D3 /Z60.E3 /Z60.E3 /Z60.E3 /Z60.B5 /Z60.B5 /Z60.B5 /Z60.C5

10 12 13 15 16 18 13 46

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -XKF1

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

C

DD

EE

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 SAM IO-1 BINARY OUTPUT SPARE Y84
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y85
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 56 7 8
A
© Copyright 2020 Hitachi Power Grids. A B

+C1 C

MARSHALING KIOSK D
BANGIL

+U1.14 -KF2 -X41 17 -X42 8 -X42 11 -X42 14 -X42 17

Merging Unit - 2
SAM600 IO

B P4#BO.11 P4#BO.12 P4#BO.17 P4#BO.18 P4#BO.19 P4#BO.20 P4#BO.21 P4#BO.22 P4#BO.23 P4#BO.24

/Z63.E6 /Z63.E6 /Z63.C8 /Z63.C8 /Z63.D8 /Z63.D8 /Z63.D8 /Z63.E8 /Z63.E8 /Z63.E8

16 18 79 10 12 13 15 16 18

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s -XKF2

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

C

+U1.14 -KF2 -X61 8 -X61 11 -X61 14 -X61 17

Merging Unit - 2
SAM600 IO

P6#BO.05 P6#BO.06 P6#BO.07 P6#BO.08 P6#BO.09 P6#BO.10 P6#BO.11 P6#BO.12

/Z64.C3 /Z64.C3 /Z64.D3 /Z64.D3 /Z64.D3 /Z64.E3 /Z64.E3 /Z64.E3

79 10 12 13 15 16 18

D

-XKF2

49 50 51 52 53 54 55 56 57 58 59 60

+U1.14 -KF2 -X62 2 -X62 5 -X62 8 -X62 11 -X62 14 -X62 17

Merging Unit - 2
SAM600 IO

E P6#BO.13 P6#BO.14 P6#BO.15 P6#BO.16 P6#BO.17 P6#BO.18 P6#BO.19 P6#BO.20 P6#BO.21 P6#BO.22 P6#BO.23 P6#BO.24 E

/Z64.B5 /Z64.B5 /Z64.B5 /Z64.C5 /Z64.C5 /Z64.C5 /Z64.D5 /Z64.D5 /Z64.D5 /Z64.E5 /Z64.E5 /Z64.E5

13 46 79 10 12 13 15 16 18

-XKF2

61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 SAM IO-2 BINARY OUTPUT SPARE Y85
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y91
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 23 4 5 67 8
A A
© Copyright 2020 Hitachi Power Grids. BPU TRIP TO DFR BCU TO DFR(SF6 LCK) DIST OPTD DIST CS DEF CS DTT REC
SPARE SPARE
DIFF OPTD DIST CR DEF CR DTT SEND AR IN PROGRESS

B B
C
Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s +CP1 -X42 17 +U.07 -KF1 -X41 2 +U.15 -FN1 -X42 11 -X42 14 -X42 17 -X41 17 D
RED670 MPU-X42 8 E
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. CONTROL AND PROTECTION PANEL REC650 BCU
BANGIL
#BO.23 #BO.24 #BO.01 #BO.02 P4#BO.17 P4#BO.18 P4#BO.19 P4#BO.20 P4#BO.21 P4#BO.22 P4#BO.23 P4#BO.24 P4#BO.11 P4#BO.12
C /Z12.B6 /Z12.B6
/Z32.E8 /Z32.E8 1 3 /Z22.C8 /Z22.C8 /Z22.D8 /Z22.D8 /Z22.D8 /Z22.E8 /Z22.E8 /Z22.E8 /Z22.E6 /Z22.E6
+U.22 -FN2
16 18 7 9 10 12 13 15 16 18 16 18
REQ650 BPU

D

-XDFR 2 4 5 6 7 8 9 10 11 12 13 14

1

>=E00 +DFR2 -TP21

DIGITAL FAULT RECORDER PANEL2 49
+DFR
E
-TP21

41
E02_BPU TRIP

-TP21

42
E02_QA1 - SF6 ST2 LOCKOUT

-TP21

43
E02_DIFF OPTD

-TP21

44
E02_DIST ZONE OPTD

-TP21

45
E02_DIST CR

-TP21

46
E02_DIST CS

-TP21

47
E02_DEF CR

-TP21

48
E02_DEF CS

-TP21

51
E02_DTT SEND

-TP21

52
E02_DTT REC

-TP21

53
E02_AR in progress

REF DWG: JBTB1.056-KIS-EM-F-001
SHT:09 OF 15

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 DFR INTERFACE CIRCUIT Y91
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Y92
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 23 4 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A QA1 - OPEN QA1 - CLOSE
B
+C1

MARSHALING KIOSK
BANGIL

B

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s C C

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. 42 44 42 44

-KQA1OP -KQA1CL

/Z66.E2 41 /Z66.E1 41

D D

-XDFR 2 3

1

>=E00 +DFR2

DIGITAL FAULT RECORDER PANEL2

-TP21

48
+DFR

-TP21

54
E02_CB OPEN

-TP21

55
E02_CB CLOSE

E E

REF DWG: JBTB1.056-KIS-EM-F-001
SHT:09 OF 15

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 DFR INTERFACE CIRCUIT Y92
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Z11
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 12 34 5 67 8

© Copyright 2020 Hitachi Power Grids. A REC650*2.2-A02X00-P23-P31-B1-X0-AA-CB-B-X0-CD1AX-KKKXXXXXXXXX A

+CP1.U.07 -KF1 Indication HMI
LED
REC650 BCU

Power supply module Communication interface module -X301
PSM SFP
24-60VDC/90-250VDC LC RX
Ethernet port
-X11 + 100FX /Y74.D3
LC TX
4 Communication interface module
SFP
/L21.C1 -
5 Ethernet port
100FX
B 24-60VDC/90-250VDC -X11 B

50W 1 1
2
Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s Relay ready 2 -X302 /Y72.D3 3
/Y31.D4 4
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. LC RX 5
3 6
LC TX 7

C Communication interface module -X303 C
SFP
LC RX /Y71.D3 8
Ethernet port 9
100FX LC TX 10
11
D 12
13
14
15

D

EE

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 DEVICE OVERVIEW - BCU Z11
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Z12
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A

+CP1.U.07 -KF1

REC650 BCU

Binary input module Binary input module Binary output module Binary output module
BIM BIM BOM BOM
110-125VDC 110-125VDC
BCU TO DFR(SF6 LCK) SPARE
SOFTWARE INTERLOCK -X31 SPARE -X32 #BO.01 -X41 #BO.13 -X42
SPARE SPARE
BYPASS SWITCH +1 +1 #BO.02 2 #BO.14 2 /Y81.B6
/Y11.E2 /Y12.E2 SPARE /Y91.D4 SPARE
P3#BI.01 110-125VDC P3#BI.09 110-125VDC #BO.03 #BO.15 1
-2 -2 SPARE 1 SPARE
B CONTROL - BCU SYNC ON #BO.04 #BO.16 B
+3 +3 SPARE 3 SPARE C
P3#BI.02 110-125VDC /Y11.E3 P3#BI.10 110-125VDC /Y12.E2 #BO.05 /Y91.D4 #BO.17 3 D
SPARE SPARE /Y81.B7 E
CONTROL - REMOTE -4 SYNC OFF -4 #BO.06 5 #BO.18
SPARE /Y81.B2 SPARE 5
Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s P3#BI.03 110-125VDC +5 P3#BI.11 110-125VDC +5 #BO.07 #BO.19 /Y81.B7
/Y11.E4 /Y12.E3 SPARE 4 SPARE
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. #BO.08 #BO.20 4
-6 -6 SPARE 6 ALARM RESET
CRP AC MCB HEALTHY SPARE #BO.09 /Y81.B2 #BO.21
+7 +7 SPARE GENERAL ALARM
P3#BI.04 110-125VDC /Y11.E4 P3#BI.12 110-125VDC /Y12.E4 #BO.10 8 #BO.22 6
SPARE /Y81.B2 SPARE /Y81.B8
C FN1 BPU FAULTY -8 SPARE -8 #BO.11 #BO.23
SPARE 7 SPARE 8
P3#BI.05 110-125VDC +9 P3#BI.13 110-125VDC +9 #BO.12 #BO.24 /Y81.D2
/Y11.E5 /Y12.E5 9
/Y81.B3 7
- 10 - 10
DC2 - MCB TRIP SPARE 11
+ 11 + 11 /Y81.B3
P3#BI.06 110-125VDC /Y11.E5 P3#BI.14 110-125VDC /Y12.E5 9
10 /Y81.D2
EXTERNAL RESET - 12 SPARE - 12
12 11
P3#BI.07 110-125VDC + 13 P3#BI.15 110-125VDC + 13 /Y81.B4 /Y81.D2
/Y11.E7 /Y12.E6
14 10
- 14 - 14 /Y81.B4
E05 KC1 ESW OK SPARE
+ 15 + 15 13
D /Y11.E8 /Y12.E7 12
15 /Y81.D3
P3#BI.08 110-125VDC - 16 P3#BI.16 110-125VDC - 16 /Y81.B5
14
17 /M51.B2
/Y81.B5
13
16
E 15
18 /M51.B2
/Y81.B6
17
/Y81.D3

16

18
/Y81.D4

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 DEVICE OVERVIEW - BCU Z12
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Z21
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 123 4 56 78

© Copyright 2020 Hitachi Power Grids. A A

+CP1.U.15 -FN1 RED670*2.2-C42X00-F01P23P30-B1X0-AA-CB-B-X0-CD1AX-KKKXABXXXXXY

MPU POWER SUPPLY MODULE 1MRK002239-BB Communication interface module HMI
RED670 PSM SFP 1/2x19" REx670 HMI
90-250VDC -X11 IEC keypad symbols
Ethernet port -X301
-X11 2 100FX
3 LC RX
4+
/Y31.D5 /Y71.D3
1 LC TX

5 -
/L21.E1

B 90-250VDC B

PE 1
2
Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s RELAY READY Communication interface module -X302 /Y72.D3 3
SFP 4
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. LC RX 5
Ethernet port 6
100FX LC TX 7

C Communication interface module -X303 C
SFP
LC RX /Y74.D3 8
Ethernet port 9
100FX LC TX 10
11
1MRK002311-AA Communication interface module 12
IEC61850 LDCM 13
14
Optical budget 23dB, 1310nm 15

-X305 D

D FC(Rx) A
E
FC(Tx) B /Y23.E6

1MRK002122-AB Communication interface module

LDCM

Optical budget 7/11dB, 850nm, ST connectors

-X306

ST(Rx) A

IEC61850 ST(Tx) B /Y23.E7

E

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 DEVICE OVERVIEW - MPU Z21
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Z22
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 12 34 5 67 8

© Copyright 2020 Hitachi Power Grids. A A
B
+CP1.U.15 -FN1 C
D
MPU BINARY INPUT MODULE 1MRK000508-BD BINARY INPUT MODULE 1MRK000508-BD BINARY OUTPUT MODULE 1MRK000614-AB BINARY OUTPUT MODULE 1MRK000614-AB E
RED670 BIM BIM BOM BOM
110-125VDC, 50mA -X31 110-125VDC, 50mA -X32 -X41
SPARE DISTANCE SEND
AR ON +1 TELE COMM GUARD OK +1 P4#BO.01 2 P4#BO.13 -X42
/Y21.E2 /Y22.E2 SPARE /Y82.B2 DEF SEND
P4#BO.02 P4#BO.14 2 /Y23.E2
-2 -2 SPARE 1 DTT SEND
P3#BI.01 110-125VDC P3#BI.09 110-125VDC P4#BO.03 P4#BO.15 1
+3 +3 3
B AR OFF /Y21.E2 EXT RESET /Y22.E3 P4#BO.04 /Y82.B2 P4#BO.16
SPARE DIFF OPTD
P3#BI.02 110-125VDC -4 P3#BI.10 110-125VDC -4 P4#BO.05 5 P4#BO.17 3
SPARE /Y82.B2 DIST OPTD /Y23.E2
SPAR +5 SPARE +5 P4#BO.06 P4#BO.18
/Y21.E3 /Y22.E3 SPARE 4 DIST CR 5
Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s P3#BI.03 110-125VDC P3#BI.11 110-125VDC P4#BO.07 P4#BO.19 /Y23.E2
-6 -6 6 DIST CS
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. P4#BO.08 /Y82.B3 P4#BO.20 4
+7 +7 GENERAL ALARM DEF CR
TPAR /Y21.E3 SPARE /Y22.E4 P4#BO.09 8 P4#BO.21
/Y82.B3 DEF CS
P3#BI.04 110-125VDC -8 P3#BI.12 110-125VDC -8 P4#BO.10 P4#BO.22 6
AR IN PROGRESS 7 DTT SEND /Y23.E3
C TRAP/SPAR +9 SPARE +9 P4#BO.11 P4#BO.23
/Y21.E4 /Y22.E5 9 DTT REC 8
P3#BI.05 110-125VDC P3#BI.13 110-125VDC P4#BO.12 /Y82.B4 P4#BO.24 /Y91.D5
- 10 - 10
11 7
+ 11 + 11 /Y82.B4
DISTANCE RECEIVE /Y21.E4 SPARE /Y22.E6
10
P3#BI.06 110-125VDC - 12 P3#BI.14 110-125VDC - 12 9
12 /Y91.D5
DEF RECEIVE + 13 SPARE + 13 /Y82.B5
/Y21.E5 /Y22.E7 11
P3#BI.07 110-125VDC P3#BI.15 110-125VDC 14 /Y91.D5
- 14 - 14 /M51.B3
10
+ 15 + 15 13
DTT RECEIVE /Y21.E6 SPARE /Y22.E7
15
D - 16 - 16 /M51.B3 12
/Y91.D5
P3#BI.08 110-125VDC P3#BI.16 110-125VDC 17
/Y91.D7 14
/Y91.D6
16
13
18
E /Y91.D7 15
/Y91.D6

17
/Y91.D6

16

18
/Y91.D6

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 DEVICE OVERVIEW - MPU Z22
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Z31
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 12 34 5 67 8

© Copyright 2020 Hitachi Power Grids. A REQ650*2.2-B11X00-P23-P31-B1-X0-AA-CB-B-X0-CD1AX-KKKXXXXXXXXX A

+CP1.U.22 -FN2 Indication HMI
LED
REQ650 BPU

Power supply module Communication interface module -X301
PSM SFP
24-60VDC/90-250VDC LC RX
Ethernet port
-X11 + 100FX /Y74.D4
LC TX
4 Communication interface module
SFP
/L21.C3 -
5 Ethernet port
100FX
B 24-60VDC/90-250VDC -X11 B

50W 1 1
2
Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s Relay ready 2 -X302 /Y72.D4 3
/Y11.D5 4
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. LC RX 5
3 6
LC TX 7

C Communication interface module -X303 C
SFP
LC RX /Y71.D4 8
Ethernet port 9
100FX LC TX 10
11
D 12
13
14
15

D

EE

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 DEVICE OVERVIEW - BPU Z31
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Z32
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 1 2 34 5 67 8
A
© Copyright 2020 Hitachi Power Grids. A

+CP1.U.22 -FN2

REQ650 BPU

Binary input module Binary input module Binary output module Binary output module
BIM BIM BOM BOM
110-125VDC 110-125VDC
SPARE SPARE
CRP DC1 FAIL -X31 SPARE -X32 #BO.01 -X41 #BO.13 -X42
SPARE
P3#BI.01 110-125VDC +1 P3#BI.09 110-125VDC +1 #BO.02 2 #BO.14 2
/Y31.E2 /Y32.E2 SPARE 1 SPARE 1
B PROTN RESET SPARE #BO.03 #BO.15 B
-2 -2 SPARE 3 SPARE 3 C
P3#BI.02 110-125VDC P3#BI.10 110-125VDC #BO.04 5 #BO.16 5 D
+3 +3 SPARE SPARE 4 E
-KF1 BCU IED FAIL /Y31.E3 SPARE /Y32.E2 #BO.05 /Y83.B2 #BO.17
SPARE 4 SPARE 6
Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s P3#BI.03 110-125VDC -4 P3#BI.11 110-125VDC -4 #BO.06 #BO.18 8
SPARE 6 SPARE 7
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. MPU DC1 MCB FAIL +5 SPARE +5 #BO.07 /Y83.B2 #BO.19
/Y31.E4 /Y32.E3 SPARE SPARE 9
P3#BI.04 110-125VDC P3#BI.12 110-125VDC #BO.08 8 #BO.20 11
-6 -6 SPARE /Y83.B2 GENERAL ALARM 10
C -FN1 MPU IED FAULTY SPARE #BO.09 #BO.21
+7 +7 SPARE 7 SPARE 12
P3#BI.05 110-125VDC /Y31.E5 P3#BI.13 110-125VDC /Y32.E4 #BO.10 #BO.22 14
SPARE 9 BPU TRIP TO DFR
SPARE -8 SPARE -8 #BO.11 /Y83.B3 #BO.23 /M51.B4
SPARE SPARE 13
P3#BI.06 110-125VDC +9 P3#BI.14 110-125VDC +9 #BO.12 11 #BO.24
/Y31.E5 /Y32.E5 /Y83.B3 15
SPARE SPARE /M51.B4
- 10 - 10 10
P3#BI.07 110-125VDC P3#BI.15 110-125VDC 17
+ 11 + 11 12 /Y91.D2
SPARE /Y31.E6 SPARE /Y32.E5 /Y83.B4
16
D - 12 - 12 14
/Y83.B4 18
P3#BI.08 110-125VDC + 13 P3#BI.16 110-125VDC + 13 /Y91.D3
/Y31.E6 /Y32.E6 13

- 14 - 14 15
/Y83.B5
+ 15 + 15
/Y31.E7 /Y32.E7 17
/Y83.B5
- 16 - 16
16
E
18
/Y83.B6

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 DEVICE OVERVIEW - BPU Z32
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Z41
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56
7 8

ID HitachiABB Frame A3 - Version 01 12 34 56 7 8

© Copyright 2020 Hitachi Power Grids. A A

+CP1.U.01 -KC1 AFS670-EREEAAAATEEEEEEENZEX08.0

AFS670 ETHERNET SWITCH COMMUNICATION INTERFACE MODULE -P1 COMMUNICATION INTERFACE MODULE
ETHERNET SWITCH A T
AFS670 Rx
Single PS 77-300VDC/90-265VAC ST -P9
/Y71.E2
-P1 ETHERNET PORT ST Tx ETHERNET PORT RJ45
/Y71.E7
L+ -P2
#FO1 100FX #LAN9 10/100Tx
Rx
N- ST -P10
/Y71.E8
B /L21.C4 77-300VDC ETHERNET PORT Tx ETHERNET PORT RJ45 /Y71.E8 B

GND 90-265VAC #FO2 100FX ST #LAN10 10/100Tx

PE

Print: 3/25/2022 D:\OneDrive - PG\PROJECT\KIS\51 latest as built\150kV=E03+CP1-BANGIL OHL-JBTB.056-KIS-EM-E-001-Rev-B_AS BUILT.e3s ETHERNET PORT RJ45 COMMUNICATION INTERFACE MODULE -P3
#Diagnosis A
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. KC1_DEVICE IS OK -R1 Rx
ST
C 1 /Y71.E2
/Y70.C2 ETHERNET PORT ST Tx

2 #FO3 100FX -P4

ST Rx

ETHERNET PORT /Y71.E3 C
Tx
#FO4 100FX ST

COMMUNICATION INTERFACE MODULE -P5
A
Rx
ST
/Y71.E4
ETHERNET PORT ST Tx

#FO5 100FX -P6

D ST Rx D
E E
ETHERNET PORT ST /Y71.E5
Tx
#FO6 100FX

COMMUNICATION INTERFACE MODULE -P7
A
Rx
ST
/Y71.E6
ETHERNET PORT ST Tx

#FO7 100FX -P8

ST Rx

ETHERNET PORT ST /Y71.E6
Tx
#FO8 100FX

F Based on Prepared 22-09-2021 MR Title CONTROL & PROTECTION PANEL Doc. kind. Circuit diagram Ref.Des. =E03 F
A AS MANUFACTURED KD Approved 22-09-2021 MA SCHEMATIC DIAGRAM
B AS BUILT 25-03-2021 MR Project PT. PLN PERSERO DCC EFS en
22-09-2021 DEVICE OVERVIEW - KC1 Z41
Rev. Revision note DSS 150KV KIS Resp. dept. PGGA Rev. ind. B Language Z42
Date Name ACP20051 HITACHI Sheet
1 Doc. no. JBTB.056-KIS-EM-E-001 n. sheet
2 34 56