Reporte Mant. Miraflores 2017

Incluye mantenimiento y termografía

Tablero Principal TD

Flipon Principal / Princemart Miraflores

21.0° C 26.2° C 06/01/17 ­ 12:37 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno Ninguna
s1 22.4° C
s2 23.8° C

22.6° C
s3 24.6° C
s4 22.2° C
s5 23.9° C

s6

P: 1
F:

July 19, 2017

Tablero Reg EDP3

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION o. 17897

P:
F:

July 19, 2017

P:
F:

July 19, 2017

Tablero Reg EDP3

Flipones Varios / Pricemart Miraflores

23.2° C 29.3° C 06/01/17 ­ 01:35 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Cable caliente
a1 24.0° C Prom. Temperatura moderada pero
recomendable revisar carga y calibre del
Máx: 29.3° C Min: 22.8° C mismo

P: 1
F:

July 19, 2017

Tablero Reg EDP3

Flipones Varios / Pricemart Miraflores

22.4° C 27.7° C 06/01/17 ­ 01:35 PM

PROBLEM DESCRIPTION RECOMMENDATION
Ninguno Ninguna

P: 2
F:

July 19, 2017

Tablero Rostizador

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Tablero Rostizador

Flipones Varios / Pricemart Miraflores

F1
F2

20.3° C 29.9° C 06/01/17 ­ 12:00 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Registro moderado de temperatura
a1 25.0° C Prom. Medir carga de cada circuito y revisar
conexiones en F1 y F2
Máx: 33.1° C Min: 21.3° C

P: 1
F:

July 18, 2017

Tablero T 0 2

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Tablero T 0 2

Flipones Varios / Pricemart Miraflores

25.0° C 32.1° C 06/01/17 ­ 10:39 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno En rango
a1 27.7° C Prom.

Máx: 31.2° C Min: 25.2° C

P: 1
F:

July 18, 2017

Tablero T EMA

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Tablero T EMA

Flipones Varios / Pricemart Miraflores

19.4° C 24.8° C 06/01/17 ­ 12:34 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno Ninguna
a1 20.3° C Prom.

Máx: 22.5° C Min: 19.0° C

P: 1
F:

July 18, 2017

Tablero TB

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Tablero TB

Flipones Varios / Pricemart Miraflores

F1 F2

20.6° C 26.6° C 06/01/17 ­ 12:42 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION

a1 22.7° C Prom. Registro moderado Revisar carga de circuito, cables y flipones
de temperatura para verificar adecuada ampacidad
Máx: 27.1° C Min: 20.0° C

P: 1
F:

July 18, 2017

Tablero TC

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION o. 17897

P:
F:

July 19, 2017

Tablero TC

Flipones Varios / Pricemart Miraflores

F1

26.0° C 36.8° C 06/01/17 ­ 01:07 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Registro de temperatura incrementada Revisar carga, flipon y conexiones
a1 29.9° C Prom.

Máx: 39.7° C Min: 26.9° C

P: 1
F:

July 19, 2017

Tablero TCA

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 19, 2017

Tablero TCA

Flipones Varios / Pricemart Miraflores

F1

26.5° C 35.3° C 06/01/17 ­ 01:07 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Revisar la carga del circuito y conexiones
a1 29.5° C Prom. Registra leve incremento de
temperatura
Máx: 35.5° C Min: 26.7° C

P: 1
F:

July 19, 2017

Tablero TD

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Tablero TD

Flipones Varios / Pricemart Miraflores

F1

F2

19.7° C 30.4° C 06/01/17 ­ 12:39 PM

PROBLEM DESCRIPTION RECOMMENDATION
Ninguno Revisar carga de circuitos y flipones

P: 1
F:

July 18, 2017

Tablero TDP

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BORNER LADO FUENTE Y LADO CARGA

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Tablero TDP

Borner Lado Fuente / Pricemart Miraflores

26.2° C 33.1° C 06/01/17 ­ 10:31 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION

s1 27.8° C Calentamiento de Verificar la corriente de carga en conductores
s2 28.5° C conductores de salida del flipon

29.1° C

s3

P: 1
F:

July 18, 2017

Tablero TDP

Borner Lado Carga / Pricemart Miraflores

L3

25.8° C 34.6° C 06/01/17 ­ 10:31 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Calentamiento en conductores de una fase
s1 29.0° C Verificar la
s2 29.1° C corriente de carga y
caliber de
28.5° C conductores de
salida Fase 3
s3

P: 2
F:

July 18, 2017

Tablero TDP 2

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Tablero TDP 2

Flipones Varios / Pricemart Miraflores

CABLES

25.3° C 36.3° C 06/01/17 ­ 10:37 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION

a1 29.0° C Prom. Calentamiento de Medir corriente de carga y calibre del
conductores conductores
Máx: 37.6° C Min: 25.1° C

P: 1
F:

July 18, 2017

Tablero TDP 2

Flipones Varios / Pricemart Miraflores

F1

27.1° C 37.4° C 06/01/17 ­ 10:37 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Calentamiento de cables
a1 29.5° C Prom. Posible desbalance de una fase, verificar
corrientes de cada línea de F1
Máx: 41.0° C Min: 26.3° C

P: 2
F:

July 18, 2017

Tablero TDP 2

Flipones Varios / Pricemart Miraflores

CABLES

26.1° C 34.5° C 06/01/17 ­ 10:38 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Calentamiento en cables
a1 28.3° C Prom. Se hace necesario verifica corriente de
alimentadores y ampacidad del cable
Máx: 34.7° C Min: 26.0° C

P: 3
F:

July 18, 2017

Tablero TEDP2

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION o. 17897

P:
F:

July 19, 2017

Tablero TEDP2

Flipones Varios / Pricemart Miraflores

B3

23.2° C 29.7° C 06/01/17 ­ 01:29 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno
a1 25.3° C Prom. Revisar conexión
borne 3
Máx: 31.1° C Min: 23.6° C

P: 1
F:

July 19, 2017

Tablero TEDP2

Flipones Varios / Pricemart Miraflores

F1

22.6° C 28.6° C 06/01/17 ­ 01:29 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno Revisar conexión del flipon indicado
a1 24.8° C Prom.

Máx: 28.8° C Min: 22.4° C

P: 2
F:

July 19, 2017

Tablero TK

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Tablero TK

Flipones Varios / Pricemart Miraflores

F1

22.3° C 32.7° C 06/01/17 ­ 12:21 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno
a1 26.4° C Prom. Revisar conexiones
del flipon
Máx: 33.9° C Min: 21.7° C

P: 1
F:

July 18, 2017

Tablero TUP

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Tablero TUP

Flipones Varios / Pricemart Miraflores

F

25.5° C 32.3° C 06/01/17 ­ 10:40 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Verificar la carga del circuito
a1 27.4° C Prom. Calentamiento en
cables y flipon
Máx: 33.1° C Min: 25.2° C

P: 1
F:

July 18, 2017

Tablero TUP

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
FLIPONES VARIOS

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Tablero TUP

Flipones Varios / Pricemart Miraflores

F1

25.5° C 32.3° C 06/01/17 ­ 10:40 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION

a1 27.4° C Prom. Incremento de Medir carga del
temperatura circuito indicado y
Máx: 33.1° C Min: 25.2° C revisar flipon

P: 1
F:

July 18, 2017

Trafo PM 100kva

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE ALTA Y BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES
FECHA: 01 DE JUNIO 2017
PUNTO DE TERMOGRAFIA:
BUSHING DE ALTA Y BAJA TENSION
TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Trafo PM 100kva

Bushing de Alta Tension / Pricemart Miraflores

30.2° C 40.7° C 06/01/17 ­ 10:24 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno EN RANGO
s1 32.7° C
s2 32.8° C

32.9° C

s3

P: 1
F:

July 18, 2017

Trafo PM 100kva

Bushing de Baja Tension / Pricemart Miraflores

30.6° C 42.7° C 06/01/17 ­ 10:25 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno EN RANGO
s1 31.1° C
s2 33.8° C

33.1° C
s3 33.3° C

s4

P: 2
F:

July 18, 2017

Trafo Seco 1

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BOBINAS Y PUNTOS DE CONEXION

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Trafo Seco 1

Bobinas y Puntos de Conexión / Pricemart Miraflores

B2

26.0° C 102.3° C 06/01/17 ­ 10:45 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Calentamiento terminales
a1 54.9° C Prom. Verificar la carga en cada fase, la alta
temperatura se concentra en una placa
Máx: 102.3° C Min: 29.6° C metálica de aluminio adherida al nucleo

P: 1
F:

July 18, 2017

Trafo Seco Area Comp

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BORNER LADO FUENTE Y LADO CARGA

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION o. 17897

P:
F:

July 19, 2017

Trafo Seco Area Comp

Borner Lado Fuente / Pricemart Miraflores

22.2° C 27.4° C 06/01/17 ­ 11:04 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno Ninguna
s1 25.0° C
s2 24.9° C

24.6° C

s3

P: 1
F:

July 19, 2017

Trafo Seco Area Comp

Borner Lado Carga / Pricemart Miraflores

21.9° C 27.1° C 06/01/17 ­ 11:04 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno Ninguna
s1 24.2° C
s2 24.7° C

24.7° C

s3

P: 2
F:

July 19, 2017

Trafo Seco DM

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BOBINAS Y PUNTOS DE CONEXIÓN

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Trafo Seco DM

Bobinas y Puntos de Conexión / Pricemart Miraflores

B2

29.5° C 101.3° C 06/01/17 ­ 10:43 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION

a1 60.8° C Prom. Calentamiento en Verificar la carga del transformador, revisar
Bobina 2 las conexiones superiores y considerar
Máx: 106.9° C Min: 30.3° C ventilación forzada

P: 1
F:

July 18, 2017

Trafo Seco K1A

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BOBINAS Y PUNTOS DE CONEXION

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Trafo Seco K1A

Bobinas y Puntos de Conexion / Pricemart Miraflores

33.3° C 88.1° C 06/01/17 ­ 12:23 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION

a1 60.8° C Prom. Calentamiento de Verificar la carga del trafo y considerar
transformador ventilarlo
Máx: 88.1° C Min: 26.7° C

P: 1
F:

July 18, 2017

Trafo Seco T EMA

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BOBINAS Y PUNTOS DE CONEXION

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Trafo Seco T EMA

Bobinas y Puntos de Conexion / Pricemart Miraflores

F1

28.8° C 109.6° C 06/01/17 ­ 12:33 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION

a1 59.7° C Prom. Desbalance de carga Verificar la carga de la Fase 1 respecto de las
en el transformador demás y balancearlas. El punto de mayor
Máx: 111.8° C Min: 30.1° C temperatura corresponde a una placa metálica
adherida al nuecleo.

P: 1
F:

July 18, 2017

Trafo Seco TB

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BOBINAS Y PUNTOS DE CONEXION

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017