Reporte Mant. Miraflores 2017

Incluye mantenimiento y termografía

Trafo Seco TB

Bobinas y Puntos de Conexion / Pricemart Miraflores

26.7° C 109.0° C 06/01/17 ­ 12:40 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION

a1 59.0° C Prom. Calentamiento del Verificar carga y
transformador capacidad del trafo,
Máx: 109.0° C Min: 26.3° C

P: 1
F:

July 18, 2017

Trafo Seco TC

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BOBINAS Y PUNTOS DE CONEXION

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION o. 17897

P:
F:

July 19, 2017

Trafo Seco TC

Bobinas y Puntos de Conexión / Pricemart Miraflores

Placa adherida
B1 B2 B3

34.0° C 112.4° C 06/01/17 ­ 01:06 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION

a1 70.1° C Prom. Desbalance de Medir carga de las tres fases, la Bobina 1 y
cargas 2 parecen mar cargadas.
Máx: 112.9° C Min: 37.9° C

P: 1
F:

July 19, 2017

Trafo Seco TD

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BOBINAS Y PUNTOS DE CONEXION

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Trafo Seco TD

Bobinas y Puntos de Conexion / Pricemart Miraflores

B1 B2 B3

29.6° C 78.0° C 06/01/17 ­ 12:35 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION

a1 57.0° C Prom. Desbalance de Bobina 1 y 2 registran mayor carga que la 3,
cargas verificar balance de cargas
Máx: 78.0° C Min: 32.3° C

P: 1
F:

July 18, 2017

Trafo Seco TK1

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BOBINAS Y PUNTOS DE CONEXION

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Trafo Seco TK1

Bobinas y Puntos de Conexion / Pricemart Miraflores

B1 B2 B3

28.8° C 88.6° C 06/01/17 ­ 12:26 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno
a1 52.8° C Prom. Verificar carga de cada fase, ligero
desbalance de B1
Máx: 88.3° C Min: 27.3° C

P: 1
F:

July 18, 2017

Trafo Seco UP

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BOBINAS Y PUNTOS DE CONEXION

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION No. 17897

P:
F:

July 18, 2017

Trafo Seco UP

Bobinas y Puntos de Conexión / Pricemart Miraflores

27.7° C 90.5° C 06/01/17 ­ 10:43 AM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno
a1 49.2° C Prom. Verificar carga de cada fase y Capacidad
del trafo
Máx: 92.6° C Min: 28.8° C

P: 1
F:

July 18, 2017

Trafo Seco UPS

MIRAFLORES

ESTUDIO TERMOGRAFICO REALIZADO A EQUIPO DE BAJA TENSION
CLIENTE: PRICEMART MIRAFLORES

FECHA: 01 DE JUNIO 2017

PUNTO DE TERMOGRAFIA:
BOBINAS Y PUNTOS DE CONEXION

TERMOGRAFO: Saul Antonio Cardona Hernandez
CERTIFICACION o. 17897

P:
F:

July 19, 2017

Trafo Seco UPS

Bobinas y Puntos de Conexion / Pricemart Miraflores

25.5° C 64.2° C 06/01/17 ­ 12:44 PM

NOTES PROBLEM DESCRIPTION RECOMMENDATION
Ninguno Verificar la carga del trafo
a1 45.3° C Prom.

Máx: 66.0° C Min: 25.1° C

P: 1
F:

July 19, 2017