The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The device shows 59 energy closes for each display period. The energy close values are reset when the device is disconnected from the auxiliary power supply. 5.1.1.1.3.- Demand parameters. On this screen, Figure 55, you can view all the maximum demand parameters indicated in Table 11. Figure 55: Demand parameters (display 1 parameter). > > > < < < varh 8 1 VA A Back Main menu Display parameters Figure 56: Demand parameters menu. Use the keys and to browse the various parameters. The menu in the lower area disappears after 3 seconds. The and keys remain active to browse the parameters, even though the menu has disappeared. Press the key to display the lower area again. If you press the key while selecting a display parameter, you will enter the parameter display menu. Instruction Manual 51 CVM-B100 - CVM-B150


For each of the demand parameters you can view: The maximum and minimum value, with the date and time of the event. A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4.4.3. CENTRAL AREA”. Table 11:Demand parameters (displays 1 parameter). Icon Display 1 parameter Demand parameters. Current Active power Apparent power The following icons appear for all these parameters on the screen: Indicating that the parameter refers to consumed or generated energy. If the 2 icons light up at the same time, it means the installation is not properly connected. If there is an alarm associated with the variable being displayed, the following will be shown: The module with which the alarm is associated. The associated output in the module. The alarm status: not activated, pre-alarm activated, alarm activated. The icon flashes during the delay time in the alarm connection (ON) and disconnection (OFF). 52 CVM-B100 - CVM-B150 Instruction Manual


5.1.1.1.3.1.- Demand parameters display menu. For each demand parameter, this menu enables (Figure 57): Graphical representation of the parameter. The analogue representation of the parameter. The value for each tariff, T1, T2 and T3. Figure 57:Demand parameters display menu (display 1 parameter). > > > > > < < < < < VA A ... Main menu Back Graphic view Analog view Tarifi selection Figure 58: Demand parameters display menu. Use the keys and to browse the different options. To access the option selected press the key . Instruction Manual 53 CVM-B100 - CVM-B150


5.1.1.1.3.1.1.- Graphic view. Figure 59 shows the graphical display screen. Figure 59:Demand parameters, graphic view (displays 1 parameter). > > > < < < varh 8 1 48h 120m Back Main menu Integration time Figure 60: Graphic view menu. The integration time ( X-axis ) on the graph can be set to 120 minutes or 48 hours. Note: The option selected is not displayed on the menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. 54 CVM-B100 - CVM-B150 Instruction Manual


5.1.1.1.3.1.2.- Analogue view. The analogue display screen is shown in Figure 61. Figure 61:Demand parameters, analog view (display 1 parameter). > > < < Back varh Main menu Figure 62: Analog view menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The second red coloured needle indicates the instantaneous value of the parameter being displayed. If there is an alarm associated with the variable being displayed, the following will be shown: The module with which the alarm is associated. The associated output in the module. The alarm status: not activated, pre-alarm activated, alarm activated. Instruction Manual 55 CVM-B100 - CVM-B150


The icon flashes during the delay time in the alarm connection (ON) and disconnection (OFF). 5.1.1.1.3.1.3.- Tariff selection. The screen for selecting the tariff to be displayed is shown in Figure 63. Figure 63: Demand parameters, tariff selection (display 1 parameter). 2 > > > < < < varh 11 ∑ 1 Back Main menu Tarifi Figure 64: tariff selection menu. Tariff 1, Tariff 2, Tariff 3. Note: The option selected is not displayed on the menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. 56 CVM-B100 - CVM-B150 Instruction Manual


5.1.1.2.- Customise parameters On this screen, Figure 65, you can view the five custom screens with 1 parameter. Figure 65: Custom parameters screen (display 1 parameter). > > > < < < varh 1 5 1 Back Main menu Custom screens Figure 66: Custom parameters menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. The and keys remain active to browse the parameters, even though the menu has disappeared. Press the key to display the lower area again. Instruction Manual 57 CVM-B100 - CVM-B150


5.1.1.2.1.- , ... Customisation screens Figure 67 shows the screen used to customise 1 parameter. These screens can also be configured for communications. See “6.- INTEGRATED COMMUNICATIONS”. Figure 67: Custom parameters screen (displays 1 parameter). > > > < < < varh 1 5 Main Back 1 menu Parameter 1 Figure 68: Custom screen menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. 58 CVM-B100 - CVM-B150 Instruction Manual


5.1.1.2.1.1.- Parameter selection Figure 69 shows the screen for selecting the parameter for display. Figure 69: Custom parameters screen, parameter selection (displays 1 parameter). > > > > > < < < < < 1 1 > < Instantaneous parameters Incremental parameters Demand parameters Delete parameter Back Main menu Figure 70: parameter selection menu. Delete parameter, deletes the parameter displayed on the screen. When this option is selected the icon appears with the option to save the deleted parameter. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. Instruction Manual 59 CVM-B100 - CVM-B150


5.1.1.2.1.1.1.- Selecting an instantaneous parameter. Figure 71 shows the screen for selecting the Instantaneous parameters. Figure 71: Custom parameters screen, selecting an instantaneous parameter (displays 1 parameter). > > > < < < varh 8 1 THD AV ph-n Back Main menu Instantaneous parameters Figure 72: Selecting an instantaneous parameter menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The menu at the bottom displays all the available instantaneous parameters (Table 12). 60 CVM-B100 - CVM-B150 Instruction Manual


Table 12: Instantaneous parameters that can be selected on the customisation screens. Customisation screen Icon Instantaneous parameter Icon Instantaneous parameter Phase-Neutral Voltage Total reactive power Phase-Phase Voltage Apparent power Current Power factor Frequency Cosine phi Active power Voltage THD Inductive reactive power Current THD Capacitive reactive power To select a parameter, press the button to open the menu at the bottom for selecting the phase: ● For the Neutral-Phase and Voltage parameters: Phase L1, Phase L2, Phase L3, Three-phase, Neutral. ● For the Phase-Phase Voltage parameter: Phase L1-L2, Phase L2-L3, Phase L1-L3, Phase L1-L2-L3. ● For the Frequency parameter: Phase L1. ● For the Active power, Inductive reactive power, Capacitive reactive power, Total reactive power, Apparent power, Power factor and Cosine phi parameters: Phase L1, Phase L2, Phase L3, Three-phase. ● For the Voltage THD and Current THD parameters: Phase L1, Phase L2, Phase L3, Neutral. The option appears after selecting the phase to save the selection. Instruction Manual 61 CVM-B100 - CVM-B150


5.1.1.2.1.1.2.- Selecting an incremental parameter. Figure 73 shows the screen for selecting an incremental parameter. Figure 73: Custom parameters screen, selecting an incremental parameter (displays 1 parameter). > > > < < < varh 8 Wh1 Back Main menu Incremental parameters Figure 74: Selecting an incremental parameter menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The menu at the bottom displays all the available instantaneous parameters (Table 13). 62 CVM-B100 - CVM-B150 Instruction Manual


Table 13: Incremental parameters that can be selected on the customisation screens. Customisation screen Icon Incremental parameter Icon Incremental parameter Active energy Apparent energy Inductive reactive energy Active tariff hours Capacitive reactive energy CO2 Emissions Total reactive energy Cost To select a parameter, press the button to open the menu at the bottom for selecting the phase: ● For the Active energy, Inductive reactive energy, Capacitive reactive energy, Total reactive energy and Apparent energy parameters: Phase L1, Phase L2, Phase L3, Three-phase. ● For the Active tariff time, CO2 Emissions and Cost parameters: Phase L1. The tariff must be selected after selecting the phase: Tariff 1, Tariff 2, Tariff 3, Total tariff. And to select the consumption or generation value: Consumption, Generation. Finally, the option appears for saving the selection. Instruction Manual 63 CVM-B100 - CVM-B150


5.1.1.2.1.1.3.- Selecting a demand parameter. Figure 75 shows the screen for selecting a demand parameter. Figure 75: Custom parameters screen, selecting a demand parameter (displays 1 parameter). > > > < < < varh 1 VA A Back Main menu Demand parameters Figure 76: selecting a demand parameter menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The menu at the bottom displays all the available demand parameters (Table 14). 64 CVM-B100 - CVM-B150 Instruction Manual


Table 14: Demand parameters that can be selected on the customisation screens. Customisation screen Icon Demand parameter Current Active power Apparent power To select a parameter, press the button to open the menu at the bottom for selecting the phase: Phase L1, Phase L2, Phase L3, Three-phase. The tariff must be selected after selecting the phase: Tariff 1, Tariff 2, Tariff 3. Finally, the option appears for saving the selection. Instruction Manual 65 CVM-B100 - CVM-B150


5.1.2.- DISPLAY 3 PARAMETERS. By selecting this option, you can view the three parameters at the same time on the display. Figure 77: 3 parameter display screen. The following options appear in the lower area: > > < < > < > < Default parameters Customize parameters Main menu Back Figure 78: 3 parameter display menu. Use the keys and to browse the various menus. To access the selected menu press the key . If no key is pressed for 5 minutes, the display screen changes automatically to the default screen. 66 CVM-B100 - CVM-B150 Instruction Manual


5.1.2.1.- Default parameters. This menu allows you to view the following types of parameters: Figure 79:Default parameters display screen (display 3 parameters). > > > > > < < < < < Instantaneous parameters Incremental parameters Demand parameters Main menu Back Figure 80: Default parameters menu. Use the keys and to browse the various menus. To access the selected menu press the key . If no key is pressed for 5 minutes, the display screen changes automatically to the default screen. Instruction Manual 67 CVM-B100 - CVM-B150


5.1.2.1.1.- Instantaneous parameters. On this screen, Figure 81, you can view all the parameters indicated in Table 15. Figure 81: Instantaneous parameters (display 3 parameters). > > > < < < varh 8 1 THD AV ph-n Back Main menu Display parameters Figure 82: Instantaneous parameters menu. Use the keys and to browse the various parameters. The menu in the lower area disappears after 3 seconds. The and keys remain active to browse the parameters, even though the menu has disappeared. Press the key to display the lower area. If you press the key while selecting a display parameter, you will enter the parameter display menu. 68 CVM-B100 - CVM-B150 Instruction Manual


For each of the instantaneous parameters you can view: The maximum and minimum value, with the date and time when it occurred. A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4.4.3. CENTRAL AREA”. Table 15:Instantaneous parameters (display 3 parameters). Icon Display 3 parameters Instantaneous parameters Icon Display 3 parameters Instantaneous parameters Phase-Neutral Voltage L1 Phase-Neutral Voltage L2 Phase-Neutral Voltage L3 Capacitive reactive power L1 (5) Capacitive reactive power L2 (5) Capacitive reactive power L3 (5) Neutral voltage Total reactive power L1 (5) Total reactive power L2 (5) Total reactive power L3 (5) Phase-Phase Voltage L1-L2 Phase-Phase Voltage L2-L3 Phase-Phase Voltage L3-L1 Apparent power L1 (5) Apparent power L2 (5) Apparent power L3 (5) Current L1 Current L2 Current L3 Power Factor L1 (5) Power Factor L2 (5) Power Factor L3 (5) Neutral current Cosine phi L1 (5) Cosine phi L2 (5) Cosine phi L3 (5) Frequency Voltage THD L1 (5) Voltage THD L2 (5) Voltage THD L3 (5) Active power L1 (5) Active power L2 (5) Active power L3 (5) Current THD L1 (5) Current THD L2 (5) Current THD L3 (5) Inductive reactive power L1 (5) Inductive reactive power L2 (5) Inductive reactive power L3 (5) (5) The following icons appear for all these parameters on the screen: Indicating that the parameter refers to inductive or capacitive energy. Indicating that the parameter refers to consumed or generated energy. If the 2 icons light up at the same time, it means the installation is not properly connected. If there is an alarm associated with the variable being displayed, the following will be shown: The module with which the alarm is associated. The associated output in the module. The alarm status: not activated, pre-alarm activated, alarm activated. The icon flashes during the delay time in the alarm connection (ON) and disconnection (OFF). Instruction Manual 69 CVM-B100 - CVM-B150


5.1.2.1.1.1.- Instantaneous parameters display menu. For each instantaneous parameter, this menu allows (Figure 83): Figure 83: Instantaneous parameters, display menu (displays 3 parameters). > > > < < < Wh varh THD A VPh-n ... Graphic view Back Main menu Figure 84: Instantaneous parameters menu. The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. 70 CVM-B100 - CVM-B150 Instruction Manual


5.1.2.1.1.1.1.- Graphic view. Figure 85 shows the graphical display screen. Figure 85: Instantaneous parameters, graphical representation (displays 3 parameters). The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The lower area menu options are: 300s > > > < < < varh 8 1 60s 20s Back Main menu Display time Figure 86: Graphic view menu. The graph display time (X-axis) can be set to 20, 60 or 300 seconds Note: The option selected is not displayed on the menu. Use the keys and to browse the different options. To access the option selected press the key . Instruction Manual 71 CVM-B100 - CVM-B150


5.1.2.1.2.- Incremental parameters. On this screen, Figure 87, you can view all the parameters indicated in Table 16. Figure 87: Incremental parameters (display 3 parameters). > > > < < < varh Wh1 Back Main menu Display parameters Figure 88: Incremental parameters menu. Use the keys and to browse the various parameters. The menu in the lower area disappears after 3 seconds. The and keys remain active to browse the parameters, even though the menu has disappeared. Press the key to display the lower area again. If you press the key while selecting a display parameter, you will enter the parameter display menu. 72 CVM-B100 - CVM-B150 Instruction Manual


Table 16: Instantaneous parameters (display 3 parameters). Icon Display 3 parameters Incremental parameters Active energy L1(6) (7) Active energy L2 (6) (7) Active energy L3 (6) (7) Inductive reactive energy L1 (6) (7) Inductive reactive energy L2 (6) (7) Inductive reactive energy L3 (6) (7) Capacitive reactive energy L1 (6) (7) Capacitive reactive energy L2 (6) (7) Capacitive reactive energy L3 (6) (7) Total reactive energy L1 (6) (7) Total reactive energy L2 (6) (7) Total reactive energy L3 (6) (7) Apparent energy L1 (6) (7) Apparent energy L2 (6) (7) Apparent energy L3 (6) (7) Active tariff hours Active tariff CO2 emissions Cost of active tariff (6) The following icons appear for all these parameters on the screen: Indicating that the parameter refers to consumed or generated energy. If the 2 icons light up at the same time, it means the installation is not properly connected. (7) The value of the energy parameters is saved in the non-volatile memory every minute. If there is a transistor digital output or input, programmed in impulse mode, associated with the variable being displayed, the following will appear: The icon that indicates that an impulse input or output has been programmed The module with which the alarm is associated. The associated output in the module. Instruction Manual 73 CVM-B100 - CVM-B150


5.1.2.1.2.1.- Incremental parameters display menu. For each incremental parameter (Figure 89), you can view: The value generated and consumed, The value for each tariff, T1, T2 and T3 and the total value of the 3 tariffs. Graphical representation of the energy closes. Figure 89: Incremental parameters, display menu (display 3 parameters). > > > > > < < < < < ... Wh Consumption / Generation Tarifi selection Graphic view Main menu Back Figure 90: Incremental parameters menu. Display the generation or consumption value of the selected parameter. Note: The option selected is not displayed on the menu. 74 CVM-B100 - CVM-B150 Instruction Manual


5.1.2.1.2.1.1.- Tariff selection. The screen for selecting the tariff to be displayed is shown in Figure 91. Figure 91:Incremental parameters, tariff selection (display 3 parameters). > > > < < < varh 8 11 ∑ 1 Back Main menu Tarifi Figure 92: Tariff selection menu. Tariff 1, Tariff 2, Tariff 3, the total value of the three tariffs. Note: The option selected is not displayed on the menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. Instruction Manual 75 CVM-B100 - CVM-B150


5.1.2.1.2.1.2.- Graphic view. The graphical representation of the energy closes is shown for all the incremental energy parameters, Figure 93 Figure 93:Incremental parameters, graphic view (displays 3 parameters). > > > > > < < < < < 1 2 30d 1h Main menu Closes Previous Next Back Figure 94: graphic view menu. Closes of 1 hour, 12 hours, 24 hours, 30 days. Note: The option selected is not displayed on the menu. scrolls through the energy closes in ascending order, in descending order. Use the keys and to browse the different options. To access the option selected press the key . 76 CVM-B100 - CVM-B150 Instruction Manual


The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The device shows 59 energy closes for each display period. The energy close values are reset when the device is disconnected from the auxiliary power supply. 5.1.2.1.3.- Demand parameters. On this screen, Figure 95, you can view all the maximum demand parameters indicated in Table 17. Figure 95: Demand parameters (display 3 parameters). > > > < < < varh 8 1 VA A Back Main menu Display parameters Figure 96: Demand parameters menu. Use the keys and to browse the various parameters. The menu in the lower area disappears after 3 seconds. The and keys remain active to browse the parameters, even though the menu has disappeared. Press the key to display the lower area again. For each of the demand parameters you can view: The maximum value, with the date and time when it occurred. Instruction Manual 77 CVM-B100 - CVM-B150


A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4.4.3. CENTRAL AREA”. Table 17:Demand parameters (display 3 parameters). Icon Display 3 parameters Demand parameters. Current L1 Current L2 Current L3 Active power L1 Active power L2 Active power L3 Apparent power L1 Apparent power L2 Apparent power L3 The following icons appear for all these parameters on the screen: Indicating that the parameter refers to consumed or generated energy. If the 2 icons light up at the same time, it means the installation is not properly connected. The following icons also appear in the active power maximum demand parameters: Indicating that the parameter refers to inductive or capacitive energy. If there is an alarm associated with the variable being displayed, the following will be shown: The module with which the alarm is associated. The associated output in the module. The alarm status: not activated, pre-alarm activated, alarm activated. The icon flashes during the delay time in the alarm connection (ON) and disconnection (OFF). 78 CVM-B100 - CVM-B150 Instruction Manual


5.1.2.1.3.1.- Demand parameters display menu. For each demand parameter, you can view: The graphic view. The value for each tariff, T1, T2 and T3. Figure 97:Demand parameters, display menu (display 3 parameters). > > < < > < > < VA A ... Main menu Back Graphic view Tarifi selection Figure 98: Demand parameters menu Use the keys and to browse the different options. To access the option selected press the key . Instruction Manual 79 CVM-B100 - CVM-B150


5.1.2.1.3.1.1.- Graphic view. Figure 99 shows the graphical display screen. Figure 99: Demand parameters, graphical representation (displays 3 parameters). > > > < < < varh 8 1 48h 120m Back Main menu Integration time Figure 100: Graphic view menu. The integration time (X-axis) on the graph can be set to 120 minutes or 48 hours. Note: The option selected is not displayed on the menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after a few seconds. Press the key to display the lower area again. 80 CVM-B100 - CVM-B150 Instruction Manual


5.1.2.1.3.1.2.- Tariff selection. The screen for selecting the tariff to be displayed is shown in Figure 101. Figure 101:Demand parameters, tariff selection (display 3 parameters). 2 > > > < < < varh 11 ∑ 1 Back Main menu Tarifi Figure 102: tariff selection menu. Tariff 1, Tariff 2, Tariff 3. Note: The option selected is not displayed on the menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after a few seconds. Press the key to display the lower area again. Instruction Manual 81 CVM-B100 - CVM-B150


5.1.2.2.- Customise parameters On this screen, Figure 103, you can view the five custom screens with 3 parameters. Figure 103: Custom parameters screen (display 3 parameter). > > > < < < varh 1 5 1 Back Main menu Custom screens Figure 104: Custom parameters menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. The and keys remain active to browse the parameters, even though the menu has disappeared. Press the key to display the lower area again. 82 CVM-B100 - CVM-B150 Instruction Manual


5.1.2.2.1.- , ... Customisation screens Figure 107 shows the screen used to customise 3 parameters. These screens can also be configured for communications. See “6.- INTEGRATED COMMUNICATIONS” Figure 105: Custom parameters screen (displays 3 parameter). > > > < < < varh 1 5 Main Back 1 menu Parameter selection Figure 106: Custom parameters screen menu. , Select the parameter 1 that you wish to display on the customisation screen. , Select the parameter 2 that you wish to display on the customisation screen. , Select the parameter 3 that you wish to display on the customisation screen. Note: See “5.1.1.2.1.1. Parameter selection” Use the keys and to browse the different options. To access the option selected press the key . Instruction Manual 83 CVM-B100 - CVM-B150


5.1.3.- DISPLAY 4 PARAMETERS. By selecting this option, you can view the four parameters at the same time on the display. Figure 107: 4 parameter display screen. The following options appear in the lower area: > > < < > < > < Default parameters Customize parameters Main menu Back Figure 108: 4 parameter display menu. Use the keys and to browse the various menus. To access the selected menu press the key . If no key is pressed for 5 minutes, the display screen changes automatically to the default screen. 84 CVM-B100 - CVM-B150 Instruction Manual


5.1.3.1.- Default parameters. This menu allows you to view the following types of parameters: Figure 109:Default parameters display screen (display 4 parameters). > > > > > < < < < < Instantaneous parameters Incremental parameters Demand parameters Main menu Back Figure 110: Default parameters menu. Use the keys and to browse the various menus. To access the selected menu press the key . If no key is pressed for 5 minutes, the display screen changes automatically to the default screen. Instruction Manual 85 CVM-B100 - CVM-B150


5.1.3.1.1.- Instantaneous parameters. On this screen, Figure 111, you can view all the parameters indicated in Table 18. Figure 111: Instantaneous parameters (display 4 parameters). > > > < < < varh 8 1 THD AV ph-n Back Main menu Display parameters Figure 112: Instantaneous parameters menu. Use the keys and to browse the various parameters. The menu in the lower area disappears after 3 seconds. The and keys remain active to browse the parameters, even though the menu has disappeared. Press the key to display the lower area. If you press the key while selecting a display parameter, you will enter the parameter display menu. For each of the instantaneous parameters you can view: The maximum and minimum value, with the date and time when it occurred. 86 CVM-B100 - CVM-B150 Instruction Manual


A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4.4.3. CENTRAL AREA”. Table 18:Instantaneous parameters (display 4 parameters). Icon Display 4 parameters Instantaneous parameters Icon Display 4 parameters Instantaneous parameters Phase-Neutral Voltage L1 Phase-Neutral Voltage L2 Phase-Neutral Voltage L3 Phase-Neutral Voltage III Capacitive reactive power L1 (9) Capacitive reactive power L2 (9) Capacitive reactive power L3 (9) Capacitive reactive power III (2) Neutral voltage Total reactive power L1 (8) (9) Total reactive power L2 (8)(9) Total reactive power L3 (8)(9) Total reactive power III (8) (9) Phase-Phase Voltage L1-L2 Phase-Phase Voltage L2-L3 Phase-Phase Voltage L3-L1 Phase-Phase Voltage III Apparent power L1 (9) Apparent power L2 (9) Apparent power L3 (9) Apparent power III (9) Current L1 Current L2 Current L3 Current III Power Factor L1 (8) (9) Power Factor L2 (8) (9) Power Factor L3 (8) (9) Power Factor III (8) (9) Neutral current Cosine phi L1 (8) (9) Cosine phi L2 (8) (9) Cosine phi L3 (8) (9) Cosine phi III (8) (9) Frequency Voltage THD L1 (9) Voltage THD L2 (9) Voltage THD L3 (9) Voltage THD LN (9) Active power L1 (9) Active power L2 (9) Active power L3 (9) Active power III (9) Current THD L1 (9) Current THD L2 (9) Current THD L3 (9) Current THD LN (9) Inductive reactive power L1 (9) Inductive reactive power L2 (9) Inductive reactive power L3 (9) Inductive reactive power III (9) (8) The following icons appear for all these parameters on the screen: Indicating that the parameter refers to inductive or capacitive energy. (9) The following icons appear for all these parameters on the screen: Indicating that the parameter refers to consumed or generated energy. If the 2 icons light up at the same time, it means the installation is not properly connected. If there is an alarm associated with the variable being displayed, the following will be shown: The module with which the alarm is associated. The associated output in the module. The alarm status: not activated, pre-alarm activated, alarm activated. Instruction Manual 87 CVM-B100 - CVM-B150


The icon flashes during the delay time in the alarm connection (ON) and disconnection (OFF). 5.1.3.1.1.1.- Instantaneous parameters display menu. For each instantaneous parameter, this menu allows (Figure 113): Figure 113: Instantaneous parameters, display menu (display 4 parameters). > > > < < < varh THD A VPh-n ... Graphic view Back Main menu Figure 114: Instantaneous parameters menu. The menu in the lower area disappears after a few seconds. Press the key to display the lower area again. 88 CVM-B100 - CVM-B150 Instruction Manual


5.1.3.1.1.1.1.- Graphic view. Figure 115 shows the graphical display screen . Figure 115: Instantaneous parameters, graphical representation (displays 4 parameters). The menu in the lower area disappears after a few seconds. Press the key to display the lower area again. The lower area menu options are: 300s > > > < < < varh 8 1 60s 20s Back Main menu Display time Figure 116: Graphic view menu. The graph display time (X-axis) can be set to 20, 60 or 300 seconds Note: The option selected is not displayed on the menu. Use the keys and to browse the various parameters. Press the key to display the lower area. Instruction Manual 89 CVM-B100 - CVM-B150


5.1.3.1.2.- Incremental parameters. On this screen, Figure 117, you can view all the parameters indicated in Table 19. Figure 117: Incremental parameters (display 4 parameters). > > > < < < varh Wh1 Back Main menu Display parameters Figure 118: Incremental parameters menu. Use the keys and to browse the various parameters. The lower area menu disappears when selecting the parameter to display. The and keys remain active to browse the parameters, even though the menu has disappeared. Press the key to display the lower area again. If you press the key while selecting a display parameter, you will enter the parameter display menu. 90 CVM-B100 - CVM-B150 Instruction Manual


Table 19:Incremental parameters (display 4 parameters). Icon Display 4 parameters Incremental parameters Active energy L1 (10) (11) Active energy L2 (10) (11) Active energy L3 (10) (11) Active energy III (10) (11) Inductive reactive energy L1 (10) (11) Inductive reactive energy L2 (10) (11) Inductive reactive energy L3 (10) (11) Inductive reactive energy III (10) (11) Capacitive reactive energy L1 (10) (11) Capacitive reactive energy L2 ((10) (11) Capacitive reactive energy L3 (10) (11) Capacitive reactive energy III (10) (11) Total reactive energy L1 (10) (11) Total reactive energy L2 (10) (11) Total reactive energy L3(10) (11) Total reactive energy III (10) (11) Apparent energy L1 (10) (11) Apparent energy L2 (10) (11) Apparent energy L3 (10) (11) Apparent energy III (10) (11) Active tariff hours Active tariff CO2 emissions Cost of active tariff (10) The following icons appear for all these parameters on the screen: Indicating that the parameter refers to consumed or generated energy. If the 2 icons light up at the same time, it means the installation is not properly connected. (11) The value of the energy parameters is saved in the non-volatile memory every minute. If there is a transistor digital output or input, programmed in impulse mode, associated with the variable being displayed, the following will appear: The icon that indicates that an impulse input or output has been programmed The module with which the alarm is associated. The associated output in the module. Instruction Manual 91 CVM-B100 - CVM-B150


5.1.3.1.2.1.- Incremental parameters display menu. For each incremental parameter, this menu enables the following (Figure 119): The value generated and consumed. The value for each tariff, T1, T2 and T3 and the total value of the 3 tariffs. Graphical representation of the energy closes. Figure 119: Incremental parameters, display menu (display 4 parameters). > > > > > < < < < < ... Wh Consumption / Generation Tarifi selection Graphic view Main menu Back Figure 120: Incremental parameters menu. Display the generation or consumption value of the selected parameter. Note: The option selected is not displayed on the menu. 92 CVM-B100 - CVM-B150 Instruction Manual


5.1.3.1.2.1.1.- Tariff selection. The screen for selecting the tariff to be displayed is shown in Figure 121. Figure 121:Incremental parameters, tariff selection (display 4 parameters). > > > < < < varh 8 11 ∑ 1 Back Main menu Tarifi Figure 122: Tariff selection menu. Tariff 1, Tariff 2, Tariff 3, the total value of the three tariffs. Note: The option selected is not displayed on the menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after a few seconds. Press the key to display the lower area again. Instruction Manual 93 CVM-B100 - CVM-B150


5.1.3.1.2.1.2.- Graphic view. The graphical representation of the energy closes is shown for all the incremental energy parameters, Figure 123. Figure 123: Incremental parameters, graphic view (displays 4 parameters). > > > > > < < < < < 1 2 30d 1h Main menu Closes Previous Next Back Figure 124: Graphic view menu. Closes of 1 hour, 12 hours, 24 hours, 30 days. Note: The option selected is not displayed on the menu. scrolls through the energy closes in ascending order in descending order. Use the keys and to browse the different options. To access the option selected press the key . The device shows 59 energy closes for each display period. 94 CVM-B100 - CVM-B150 Instruction Manual


The energy close values are reset when the device is disconnected from the auxiliary power supply. 5.1.3.1.3.- Demand parameters. On this screen, Figure 125, you can view all the maximum demand parameters indicated in Table 20. Figure 125:Demand parameters (display 4 parameters). > > > < < < varh 8 1 VA A Back Main menu Display parameters Figure 126: Demand parameters menu. Use the keys and to browse the various parameters. The menu in the lower area disappears after a few seconds. The and keys remain active to browse the parameters, even though the menu has disappeared. Press the key to display the lower area again. For each of the demand parameters you can view: The maximum value, with the date and time when it occurred. A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4.4.3. CENTRAL AREA”. Instruction Manual 95 CVM-B100 - CVM-B150


Table 20:Demand parameters (display 4 parameters). Icon Display 4 parameters Demand parameters Current L1 Current L2 Current L3 Current III Active power L1 Active power L2 Active power L3 Active power III Apparent power L1 Apparent power L2 Apparent power L3 Apparent power III The following icons appear for all these parameters on the screen: Indicating that the parameter refers to consumed or generated energy. If the 2 icons light up at the same time, it means the installation is not properly connected. If there is an alarm associated with the variable being displayed, the following will be shown: The module with which the alarm is associated. The associated output in the module. The alarm status: not activated, pre-alarm activated, alarm activated. The icon flashes during the delay time in the alarm connection (ON) and disconnection (OFF). 96 CVM-B100 - CVM-B150 Instruction Manual


5.1.3.1.3.1.- Demand parameters display menu. For each demand parameter, you can view: The graphic view. The value for each tariff, T1, T2 and T3. Figure 127: Demand parameters, display menu (display 4 parameters). > > < < > < > < VA A ... Main menu Back Graphic view Tarifi selection Figure 128: Demand parameters, display menu Use the keys and to browse the different options. To access the option selected press the key . Instruction Manual 97 CVM-B100 - CVM-B150


5.1.3.1.3.1.1.- Graphic view. Figure 129 shows the graphical display screen. Figure 129: Demand parameters, graphic view (displays 4 parameters). > > > < < < varh 8 1 48h 120m Back Main menu Integration time Figure 130:Graphic view menu. The integration time (X-axis) on the graph, can be set to 120 minutes or 48 hours. Note: The option selected is not displayed on the menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after a few seconds. Press the key to display the lower area again. 98 CVM-B100 - CVM-B150 Instruction Manual


5.1.3.1.3.1.2.- Tariff selection. The screen for selecting the tariff to be displayed is shown in Figure 131. Figure 131:Demand parameters, tariff selection (display 4 parameters). 2 > > > < < < varh 11 ∑ 1 Back Main menu Tarifi Figure 132: tariff selection menu. Tariff 1, Tariff 2, Tariff 3. Note: The option selected is not displayed on the menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after a few seconds. Press the key to display the lower area again. Instruction Manual 99 CVM-B100 - CVM-B150


5.1.3.2.- Customise parameters On this screen, Figure 133, you can view the five custom screens with 4 parameters. Figure 133: Custom parameters screen (display 4 parameter). > > > < < < varh 1 5 1 Back Main menu Custom screens Figure 134: Custom parameters menu. Use the keys and to browse the different options. To access the option selected press the key . The menu in the lower area disappears after 3 seconds. The and keys remain active to browse the parameters, even though the menu has disappeared. Press the key to display the lower area again. 100 CVM-B100 - CVM-B150 Instruction Manual