EALTH FACILITIES GUIDEBOOK - COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS (EDITION 2023)

COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS INTERIOR DESIGN Nurse Counter Hospital Pengajar Unisza DOCUMENTS SUBMISSION C SAMPLES OF DRAWINGS SPECIFICATION D SAMPLES OF SCHEDULES Disclaimer: Images/samples are subjected to project basis. 301


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS INTERIOR DESIGN 3D Presentation Drawings (A2 size) DRAWINGS & SCHEDULES ▪ The successful tenderer is required to produce exterior and interiors views : A B Animations C Specifications D Samples of the Fittings & Accessories ▪ ….of the proposal of duration to the Government's approval and: The selected material for fittings and accessories shall suit the required location and position. The successful tenderer shall submit specifications and samples of the fittings and accessories Registration Counter, Hospital Tanjung Karang DOCUMENTS SUBMISSION 2. DESIGN & BUILD (SUCCESSFUL TENDERER) Disclaimer: Images/samples are subjected to project basis. 302


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS INTERIOR DESIGN FLOOR PLAN OF PROPOSED ID WORKS BLOW UP FLOOR PLAN / PATTERN DETAILS DOCUMENTS SUBMISSION SAMPLES OF DRAWINGS & SCHEDULES Disclaimer: Images/samples are subjected to project basis. 303


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS INTERIOR DESIGN Main Lobby Hospital Rompin, Kuala Rompin 3D ANIMATIONS/PERSPECTIVE ACTUAL VIEW Main Lobby Hospital Rompin, Kuala Rompin DOCUMENTS SUBMISSION SAMPLES OF 3D DRAWINGS / ANIMATION Disclaimer: Images/samples are subjected to project basis. 304


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS INTERIOR DESIGN Registration Counter ,Hospital Tanjung Karang SPECIFICATIONS DOCUMENTS SUBMISSION SAMPLES OF SPECIFICATIONS Disclaimer: Images/samples are subjected to project basis. 305


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS DOCUMENTS SAMPLES OF FITTINGS & ACCESSORIES SUBMISSION INTERIOR DESIGN Disclaimer: Images/samples are subjected to project basis. 306


5.10 ACCESSORIES 307


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS INTRODUCTION TYPE OF ACCESSORIES IN HEALTH FACILITY ACCESSORIES PROJECTS TRACKS BLINDS WALL, COLUMN & DOOR PROTECTION A B C 308


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS A TRACKS ACCESSORIES 1. MEDICAL CUBICLE TRACK ▪ All medical cubicle tracks shall be anodised aluminium alloy, rigidly fixed and suspended from the soffit slab. ▪ It shall be fixed onto slab and shall not be fixed off the suspended ceiling T-bars nor ceiling board ▪ The cubicle track needs to be U-shaped track and not the fused type and shall connected to the adjacent cubicle track. ▪ The installation position shall not clash with built-ins /furniture and away from windows ▪ The height of the cubicle track shall be 2100mm from finished floor level. ▪ The size of the installed heavy-duty curtains shall follow the size of each bay and the height shall be off 250mm from the finished floor level SPECIFICATIONS TYPE OF TRACKS IN HEALTH FACILITY PROJECTS 1) MEDICAL CUBICLE TRACK 2) INTRAVENOUS (IV) TRACK 3) CURTAIN TRACK / CUBICLE CHANGING TRACK 309


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS ACCESSORIES TYPE OF MEDICAL CUBICLE TRACK DESIGN 250mm FFL Disclaimer : Images are for reference purpose only. The installation shall depend on design proposal TECHNICAL DESIGN INSTALLATION OF MEDICAL CUBICLE TRACK 310


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS ACCESSORIES ▪ All intravenous tracks shall be anodised aluminium alloy, rigidly fixed and suspended from the soffit slab. ▪ It shall be fixed onto slab and shall not be fixed off the suspended ceiling T-bars nor ceiling board ▪ The IV track shall be installed in: - resus bays - recovery bays (OT) - Intensive Care Area ▪ ICU/CCU/HDW ▪ The height of the IV track shall be below ceiling boards / 20mm from ceiling level. ▪ It shall be installed in the center of patient bed that size 1000mm (W) x 1500mm (L) 2. INTRAVENOUS (IV) TRACK SPECIFICATIONS 311


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS ACCESSORIES TECHNICAL DESIGN INSTALLATION OF INTRAVENOUS (IV) TRACK TYPE OF INTRAVENOUS (IV) TRACK DESIGN Disclaimer : Images are for reference purpose only. The installation shall depend on design proposal 312


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS ACCESSORIES ▪ All curtain track or cubicle changing track shall be anodised aluminium alloy, rigidly fixed and suspended from the soffit slab. ▪ It shall be fixed onto slab and shall not be fixed off the suspended ceiling T-bars nor ceiling board ▪ The curtain track shall be installed in all windows in clinical areas except DCE, laboratory and in quarters ▪ The cubicle changing track shall be installed in all staff / patient changing areas follow the size of each changing bay ▪ The height of the cubicle curtain track shall be 2100mm from finish floor level 3. CURTAIN TRACK / CUBICLE CHANGING TRACK SPECIFICATIONS 313


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS ACCESSORIES Wall Mounted curtain track Recessed Mounted curtain track Cubicle changing track TECHNICAL DESIGN INSTALLATION OF CURTAIN TRACK / CUBICLE CHANGING TRACK Disclaimer : Images are for reference purpose only. The installation shall depend on design proposal CURTAIN TRACK / CUBICLE CHANGING TRACK 314


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS B BLINDS ACCESSORIES VERTICAL BLINDS / BLACK OUT BLINDS / INTEGRATED GLAZING BLINDS ▪ Consists mainly of a headrail and vertical strips of fabric called louvres. ▪ The head rail stretches the length of the window and the louvres hang from it. It drawn across the window by cords, which also allows them to be tilted too. ▪ Vertical blinds shall be provided in all windows in non-clinical areas (external windows and internal glazing) SPECIFICATIONS ▪ Blackout blinds shall be provided normally in seminar / education rooms and dark rooms ▪ Integral blinds shall be provided between ICU bed bays and ISO Isolation Rooms. ▪ Motorised blinds shall be installed for curtain wall / high windows with double volume space unless otherwise stated. TYPE OF BLINDS IN HEALTH FACILITY PROJECTS ▪ Vertical Blinds ▪ Blackout Blinds ▪ Integral Blinds ▪ Motorised Blinds 315


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS ACCESSORIES Vertical blinds Black out blinds Integral blinds Motorised curtain/blinds TYPE OF DESIGN TECHNICAL DESIGN INSTALLATION 316


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS ACCESSORIES Wall and column corners along traffic routes in health facilities shall be protected with high impact extrusion guard protection system. The guard protection system consist of : - Seamless high impact vinyl / acrylic extrusions guards - Continuous gaskets - Aluminium retainers - Mounting brackets GENERAL WALL, COLUMN AND DOOR PROTECTION C TYPE OF ‘GUARD PROTECTION’ IN HEALTH FACILITES PROJECTS ▪ Wall Guard / Crash rail ▪ Wall Guard with handrail ▪ Corner Guard ▪ Bumper Guard 317


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS ACCESSORIES TROLLEY PARK ▪ Crash rail 2 layers ▪ Wall guard : 900mm FFL ▪ Crash rail : 250mm FFL TROLLEY ROUTE (CORRIDOR) ▪ Crash rail 1 layers ▪ Wall guard : 900mm FFL PATIENT ROUTE (CORRIDOR) ▪ Handrail / Grab rail cum wall protection CORNER / SHARP EDGES ▪ Corner guard ▪ Height : 900mm FFL BUMPER GUARD ▪ Surface mounted ▪ Loading and Unloading area GUARD PROTECTION INSTALLATION ROUTES 318


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS ACCESSORIES WALL GUARD WITH HANDRAIL TECHNICAL DESIGN WALL GUARD / CRASH RAIL 319


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS ACCESSORIES BUMPER GUARD TECHNICAL DESIGN CORNER GUARD 320


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS SUBMISSION OF ACCESSORIES DOCUMENTATION The ACCESSORIES Proposal Document that needs to be interacted with and approved by JKR includes : ▪ Floor Plan Drawing – indicating the location of the accessories, track placement of the medical cubicle track/curtain track, blinds and wall, column and door protection; ▪ Details of each accessories code; ▪ Working Drawing of the accessories based on approved measurement on site. 321


5.11 FLOOR FINISH 322


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH FLOOR FINISHES Generally, floors shall be of concrete slab, unless otherwise specified. Workstation and computer rooms shall have antistatic vinyl floor. Raised floor for IT rooms shall flush with the surrounding floor finishes. All sports activities shall be finished with approved sports standards – rubber paint, epoxy, EPDM etc. All floor skirtings shall not be less than 100mm high unless otherwise specified Types of floor finishes : 1 Vinyl 2 Tiles 3 Seamless flooring system – i.e.: selflevelling epoxy, PU resin, polished concrete, stencilled concrete, floor hardener 4 Pavers 5 Timber floor finished 6 Carpets INTRODUCTION Disclaimer: Images/samples are subjected to project basis. 323


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH All joints shall be welded with matching colours Skirting shall be bent up of the same vinyl at 100mm high with uPVC capping strips and approved acrylic adhesive Stainless steel traps and/or gratings for vinyl floor shall be of approved for suitable vinyl flooring To apply approved moisture barrier vinyl sheet underlay for the floor with rising dampness moisture content of 75% relative humidity – usually on ground floor Warranty : Minimum 10 years 5 types of Vinyl : V1 Vinyl Type 1 heavy duty to withstand heavy traffic of trolleys V2 Vinyl Type 2 Anti-Static Conductive to cater for aseptic and dust-free environment (OT Rooms, Server Room, Imaging Room or other rooms depending on the equipments) V3 Vinyl Type 3 Anti Slip to cater for wet/slippery areas V4 Vinyl Type 4 Heavy duty, fully flexible, cushioned/ padded and sports-friendly (Gymnasium and Playground) duty, fully flexible and sports-friendly V5 Vinyl Type 5 High resistant to chemical 1. VINYL SPECIFICATIONS Disclaimer: Images/samples are subjected to project basis. 324


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS TECHNICAL DESIGN FLOOR FINISH Disclaimer: Images/diagrams are for reference/guideline only and subject to project basis. 325


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH Disclaimer: Images/diagrams are for reference/guideline only and subject to project basis. TECHNICAL DESIGN 326


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH ▪ Ceramic tiles – To provide tiles with water absorption rate according to MS 1294 ▪ Tile size shall be minimum 300mm x 300mm unless otherwise specified ▪ Internal and external floor heavy duty tiles – fully vitrified with water absorption less than 0.5%, of vitreous hard wearing non-slip glazed tiles min size 300mm x 300mm ▪ Internal floor areas under normal conditions shall be fully vitrified with water absorption more than 0.5% less than 10%, of vitreous hard wearing non-slip glazed tiles min size 300mm x 300mm ▪ All accessories such as skirting, step tiles, step nosing, edging strips, angle tiles of approved same type to match flooring. All skirting shall be 100mm high, step nosing min 20mm wide laid at full length treads and bullnose profile and 25mm wide edging strips 2. TILES SPECIFICATIONS ▪ Minimum 600mm x 600mm full body porcelain tiles/granite tiles – the main entrance, lobby, waiting area, lift lobby, hospital streets, corridors (heavy traffic) and revenue collection. Special floor patterns shall be integrated with the ID ▪ Toilet, pantry, kitchen, ablution and other wet areas – non-slip tiles (min 300mm x 300mm) ▪ All tile joints shall be filled with approved epoxy grout 327


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH Disclaimer: Images/diagrams are for reference/guideline only and subject to project basis. TECHNICAL DESIGN 328


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH Disclaimer: Images/diagrams are for reference/guideline only and subject to project basis. TECHNICAL DESIGN 329


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH Disclaimer: Images/diagrams are for reference/guideline only and subject to project basis. TECHNICAL DESIGN 330


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH Disclaimer: Images/diagrams are for reference/guideline only and subject to project basis. TECHNICAL DESIGN 331


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH Disclaimer: Images/diagrams are for reference/guideline only and subject to project basis. TECHNICAL DESIGN 332


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH ▪ Method of application – all concrete floor slabs shall be applied with waterproofing and floor hardener before receiving the seamless flooring ▪ Epoxy coating vs epoxy paint – epoxy coats shall be of highperformance epoxy resin sealer ▪ High performance, self-levelling epoxy or PU resin for heavy duty machinery and high traffic – such as medical store ▪ Laboratories – chemical resistant epoxy resin or any approved equivalent ▪ Food prep area/kitchen/cold storage or freezer in kitchens - PU resin (for hygienic and clean floors) ▪ Polished concrete – super flat concrete slab, grinded to either 800, 1500 or 3000 grit level; low maintenance, waterproof, chemical resistance etc ▪ Driveways / car porches – heavy duty coloured stamped or stenciled concrete ▪ Coloured concrete floor hardener – areas for heavy machinery works, proprietary floor hardener. FH of high quality materials, 5mm thick above 150mm thick concrete floor slab 3. SEAMLESS FLOORING SPECIFICATIONS Disclaimer: Images/diagrams are for reference/guideline only and subject to project basis. 333


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH ▪ Shall be provided to areas needed as per functional requirement ▪ Shall be minimum of 60mm thick for medium traffic (e.g.: footpaths, jogging tracks and etc.) ▪ Shall be minimum of 80mm thick for heavy duty application (e.g.: driveway, drop off and parking) ▪ Interlocking pavers shall be laid on sand bedding and lean concrete 4. PAVERS SPECIFICATIONS Disclaimer: Images/samples are subjected to project basis. 334


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH ▪ Shall Comply with the latest JKR Standard Specification for Building Works ▪ Timber flooring shall be high quality timber / laminated timber to be laid on rubberised cushioning pad of 30 mm thick cement screed on concrete slab with an approved waterproof ▪ Shall Timber skirting of 100mm x 12mm thick, chamfered at the top ▪ The proprietary timber flooring system shall be following the manufacturer’s specifications : surface of antiabrasive protective overlay a) Solid timber – hardwood timber strips of not less than 1200mm x 18mm thk; b) Natural timber laminated – 14.5mm thk of 3 ply engineered solid timber; c) Laminated composite flooring – 8mm thk prefinished 5. TIMBER FLOOR FINISHES SPECIFICATIONS Disclaimer: Images/diagrams are for reference/guideline only and subject to project basis. 335


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH ▪ Carpet tiles or broadloom carpet shall be appropriate to the function of areas and shall comply to the latest PK WP 2.1 – Peraturan Had Harga Perabut/Kelengkapan Bagi Pejabat Anggota Perkhidmatan Awam Persekutuan ▪ Not encourage to be used in Clinical Area. If need be, it must be hygienic type medical carpet, for example Audiometry Acoustic Attenuation Booth/ Room ▪ Timber skirting of 100mm (height) x 12mm (thick) ▪ Pattern/ design shall match with ID proposal ▪ Of good quality, wear and stain resistant, easy to clean and low VOC ▪ At ground level – the receiving floor slabs must be damp-proof floor slabs with underlay with 100mm timber skirting ▪ Aluminium dividing strips to divide between materials/finishes ▪ Method of installation – shall be laid with close butt joints with the underlay, sketched and balanced so all seams are parallel with min bows and rust-proof metal gripper strips. To be installed in largest practical pieces and salvage to be trimmed 6. CARPET SPECIFICATIONS Disclaimer: Images/diagrams are for reference/guideline only and subject to project basis. 336


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS FLOOR FINISH ▪ The tenderer shall submit a summary of architecture components and materials range of series shall be provided to support the specifications for all building materials. A minimum of three (3) equivalent alternatives shall be submitted for every specification proposed on materials. ▪ For successful tenderer, The Room Data Documents shall consist of every individual room, the list, descriptions, and specification such as Floor, wall, and ceiling finishes. (Refer to Room Data Sheet) DOCUMENTS SUBMISSION FOR DESIGN AND BUILD ARCHITECTURAL COMPONENTS/SCHEDULES Disclaimer: Images/samples are subjected to project basis. 337


COMPONENTS OF CLINICAL AND NON-CLINICAL MATERIALS DOCUMENTS SAMPLE OF ROOM DATA SHEET SUBMISSION FLOOR FINISH Disclaimer: Images/samples are subjected to project basis. 338


5.12 CCTV & ACCESS CARD 339


COMPONENTS OF NON-CLINICAL MATERIALS INTRODUCTION CCTV & ACCESS CARD SCOPE (ELV SYSTEM) 1. Closed Circuit Television (CCTV) System 2. Access Control System 340


COMPONENTS OF NON-CLINICAL MATERIALS CCTV & ACCESS CARD Requirement Varifocal (Dome/Bullet) Pan, Tilt & Zoom (PTZ) Panaromic Resolution 2688 x 1520 pixels (5MP) 2688 x 1521 pixels (5MP) 4 x 1920 x 1080 (8MP) Frame Rate 25 fps at full resolution 25 fps at full resolution 25 fps at full resolution Compression H.265 H.265 H.264 Vandal Resistant IK10 IK09 IK09 IR View Distance 30 Metre 150 Metre - Application Dome : Indoor (wide area) Bullet : Mostly outdoor Outdoor Outdoor CCTV MAIN EQUIPMENT a. Cameras - Type of camera : IR Dome, IR Bullet, PTZ, Panaromic - Minimum technical specification: SPECIFICATIONS 1. CLOSED CIRCUIT TELEVESION (CCTV) SYSTEM 341


COMPONENTS OF NON-CLINICAL MATERIALS CCTV & ACCESS CARD b. Network Video Recorder The NVR and its associated software shall be fully compatible with all the installed cameras. It shall perform the managing and setting up of cameras, day to day recording operation, live viewing, playback of recorded video and other configuration necessary for the successful operation of the CCTV system. The NVR shall be preloaded with CCTV management software and cameralicenses. Minimum technical specification: • Number of camera channel : 16, 32, 64 or 128 • Camera licenses : Built-in for all connected cameras • Video storage capacity : In terabytes (TB) as specified in bill of quantities or drawings (e.g.450 TB for 1 month) • Redundant array of independent disks (RAID) : RAID-5 • Recording & playback resolution : 2MP to 8MP SPECIFICATIONS 342


COMPONENTS OF NON-CLINICAL MATERIALS CCTV & ACCESS CARD c. Storage Array The storage array shall be provided as a whole solution satisfying the total storage required. It shall complete with processor, operating system, memory, controllers and fully compatible with the video management software. Minimum specifications: Type : Rack mount Video storage capacity : In TB as specified in bill of quantities ordrawings RAID : RAID-5 Power Supply : Redundant power supply unit d. Management And Video Recording Server The management server shall provide management, monitoring and control of the entire CCTV system. The server together with the video management software shall perform the managing and setting up of cameras, day to day recording operation, live viewing, playback of recorded video and other configuration necessary for the successful operation of the CCTV system. SPECIFICATIONS 343


COMPONENTS OF NON-CLINICAL MATERIALS CCTV & ACCESS CARD e. Central Processing Unit (CPU) Minimum specifications: • Processors : Intel Xeon E5-2600 v4 or equivalent; 3.0 GHz, 4 core, 10MB L3cache • Operating System : Microsoft Windows 11, 64-bit orlatest version • Memory : 16 GB DDR4 • Network Interface : 1GbE RJ-45 • Graphic Card Resolution : 3840 x 2160 pixels per display • SSD : 1 TB • Included software : Antivirus f. LED Monitor The LED monitor shall comply with the following minimum technical specifications: • Type : Industrial type suitable for 24/7 operation • Screen size : 42” (diagonal) • Panel type : LED • Aspect ratio : 16:9 • Number of pixels (H x V) : 3840 x 2160 pixels • Brightness : 500 cd/m2 • Display connector : Compatible with the display CPU graphic card SPECIFICATIONS 344


COMPONENTS OF NON-CLINICAL MATERIALS CCTV & ACCESS CARD g. Other Equipment: • Surge Protective Device For Data • DC Power Supply • Backup Battery • Power over Ethernet (PoE) Media Converter • Media Converter • PoE Injector • PoE Extender • Equipment Rack ❖ CCTV system shall have backup power supply SPECIFICATIONS 345


COMPONENTS OF NON-CLINICAL MATERIALS CCTV & ACCESS CARD Location Areas/ Rooms Type of Camera EXTERNAL • Multi-storey / basement carpark • All hospital building entrances and exits • Loading /unloading area – e.g. medical store, mortuary, catering • Fire exit door at ground floor • Main lobby and all patient drop off areas • Primary Triage ED and all ED entrance and exit points • Others Outdoor Type Camera (Bullet, PTZ, Panaromic) - With pole (e.g. 5m pole) - Wall Mounted (Bullet, PTZ) INTERNAL • All lift lobbies ( service & public) • Entrance and exit of link bridge • Pharmacy – drug store and DD room, all entrance band exit points • All revenue collection counters • All of PAC, LDR, Obstetric & Paed wards, NICU, SCN • Main Server Room • Medical record –Medicolegal file • Admin – Strong room • Others Indoor Type Camera (Dome, Bullet) - Ceiling mounted - Surface mounted - Wall mounted Hospital guideline for CCTV location SPECIFICATIONS 346


COMPONENTS OF NON-CLINICAL MATERIALS CCTV & ACCESS CARD Example of CCTV setup in the 'Waiting Area' - DOME CAMERA - DOME CAMERA TECHNICAL DESIGN 347


COMPONENTS OF NON-CLINICAL MATERIALS CCTV & ACCESS CARD DOOR ACCESS Example of Door Access System Layout in 'Body Freezer Room' TECHNICAL DESIGN 348


COMPONENTS OF NON-CLINICAL MATERIALS CCTV & ACCESS CARD Example of CCTV Layout in 'Emergency Area' - PTZ CAMERA - PTZ CAMERA - PTZ CAMERA TECHNICAL DESIGN 349


COMPONENTS OF NON-CLINICAL MATERIALS CCTV & ACCESS CARD Brief description : • Access card system shall be applied at entrance to staff/zone areas where public is restricted. e.g. all staff entrance • Console to be located at admin/security office • Access card system shall have backup power supply • For upgrading work project, the new access card system shall be integrated with existing access card system • All automatic door shall be able to be locked manually wheneverrequired • Location : - All changing room, all staff entrances - Wards main/public entrance SPECIFICATIONS 2. ACCESS CARD SYSTEM 350