Locator strip fixed at max. 600 vertical Vertical cavity batten 5 mm gap left between end of
centres with 6g x 2" CSK Sq. S/S self (corners only) fixing with 6g weatherboards and corner flashing
tapping screws through batten into x 1 ¼" CSK Sq. S/S pre drill
stud screws through batten into Ulltraclad© Female Corner
stud Flashing
Ulltraclad© UA4529 Male Corner
Wall frame Flashing fixed to wall framing with
Interior lining 30x2.5 mm clouts @ 600 mm ctrs
Or 6g x ¾" CSK Sq. T17 screws
Note: Ensure to alternate spacings of
fixings for battens and locator lengths to Underlay strips to isolate aluminium
from treated battens (for use on
avoid risk of splitting batten vertical corner battens only)
Ulltraclad© UA6975 weatherboard
(vertical) fixed with locator strip
between boards (UA4535)
Building underlay continuous
around corner
Cavity batten fixing as per Cavibat
requirements
Ullrich Aluminium Co. Ltd. 1 : 2 V.01
Ulltraclad© Aluminium Cladding
May 2012 External Corner On Cavity
Ulltraclad© UA6975 weatherboard Cavity batten fixing as per
(vertical) fixed with locator strip Cavibat requirements
between boards (UA4535)
Note: Double studs required at
Locator strip fixed at max. 600 internal corners
vertical centres with 6g x 2" CSK
Sq. S/S self tapping screws through 5 mm gap left between end of
batten into stud weatherboards and corner
flashing
Building underlay continuous
around corner Interior lining
Vertical cavity batten (corners only)
fixing with 6g x 1 ¼" CSK Sq. S/S
pre drill screws through batten into
stud
Ulltraclad© UA4529 Male Corner
Flashing
Ulltraclad© UA4530 Female Corner
Flashing fixed to wall framing with
30x2.5 mm clouts @ 600 mm ctrs
Note: Leave a 10 mm gap between
battens
Ullrich Aluminium Co. Ltd. 1 : 2 V.02
Ulltraclad© Aluminium Cladding
May 2012 Internal Corner On Cavity
V.03a No Soffit Detail on Cavity
Soffit lining
Ulltraclad© UA5833 Clip Top
Cavity batten fixing as per Cavibat
requirements
Ulltraclad© UA5831 Soffit Clip
Base fixed to wall framing with
50x2.5 mm clouts or 6g x 2" CSK
Sq. S/S self tapping screws through
batten into stud
Building Underlay
Ulltraclad© weatherboards
Note: Ensure to alternate spacings of
fixings for battens and locator lengths to
avoid risk of splitting batten
Ullrich Aluminium Co. Ltd. 1 : 2 V.03a
Ulltraclad© Aluminium Cladding
May 2012 Soffit Detail On Cavity
Note: Ensure to alternate spacings of 10
fixings for battens and locator lengths to
avoid risk of splitting batten
Sealant over PEF backing rod
Cavity batten fixing as per Cavibat
requirements
Screw through top board and fix to
top plate with 6g x 2" CSK Sq. S/S
Underlay strips to isolate aluminium
from treated battens (Alternatively
use 'CAVIBAT' system)
Building underlay
Ulltraclad© UA6975 weatherboard
(vertical) fixed with locator strip
between boards (UA4535)
Locator strip fixed at max. 600 vertical
centers with 6g x 2" CSK Sq. S/S self
tapping screws through batten into
stud
Ullrich Aluminium Co. Ltd. 1 : 2 V.03b
Ulltraclad© Aluminium Cladding
May 2012 No Soffit Detail On Cavity
Ulltraclad© UA6975 weatherboard 100mm min to permanent paving or 175mm Interior lining
(vertical) fixed with locator strip to upaved ground to clause 9.1.3 of E2/AS1
between boards (UA4535) Bottom plate over DPC
Locator strip fixed at max. 600 vertical 50
centres with 6g x 2" CSK Sq. S/S self 6 6 mm overhang (optional)
tapping screws through batten into Concrete slab or blockwork
stud
Building Underlay Cavity vent strip with 15mm drip
edge
Note: Ensure to alternate spacings of
fixings for battens and locator lengths to Ulltraclad© UA4563 with 5mm
diameter drainage holes drilled
avoid risk of splitting batten through base of flashing @ 300
mm ctrs.
Ulltraclad© UA4863 Vertical Starter Strip
fixed to bottom plate @ 300 mm ctrs with:
6g x 2" CSK Sq. S/S self tapping screws
(Through Cavibat)
Finished ground level
Ullrich Aluminium Co. Ltd. 1 : 2 V.04
Ulltraclad© Aluminium Cladding
May 2012 Vertical Wall Starter
Ulltraclad© UA6975 weatherboard Interior lining
(vertical) fixed with locator strip Bottom plate
between boards (UA4535)
Locator strip fixed at max. 600 vertical Timber floor structure in
centres with 6g x 2" CSK Sq. S/S self accordance with NZS 3604:2011
tapping screws through batten into
stud Ulltraclad© cavity vent strip
Ulltraclad© UA4563 with 5mm
Building Underlay diameter drainage holes drilled
through base of flashing @ 300
Note: Ensure to alternate spacings of mm ctrs.
fixings for battens and locator lengths to
avoid risk of splitting batten
Ulltraclad© UA4863 Vertical Starter Strip
fixed to bottom plate @ 300 mm ctrs with:
6g x 2" CSK Sq. S/S self tapping screws
(Through Cavibat)
50
Ullrich Aluminium Co. Ltd. 1 : 2 V.05
Ulltraclad© Aluminium Cladding
May 2012 Wall Starter (Timber Floor)
Ulltraclad© UA6975 weatherboard 35 min Note: Ensure to alternate spacings of
(vertical) fixed with locator strip flashing upstand fixings for battens and locator lengths to
between boards (UA4535)
Locator strip fixed at max. 600 10 mm cover avoid risk of splitting batten
vertical centres with 6g x 2" CSK
Sq. S/S self tapping screws Interior lining
through batten into stud
Building underlay continuous
Ulltraclad© UA4533 Head Flashing. behind head flashing and into
5mm diameter drainage holes opening. Flashing tape over top of
drilled through base of flashing @ head flashing
300 mm ctrs.fixed to lintel @ 300
mm ctrs with: Airseal to perimeter of trim cavity
6g x 2" CSK Sq. S/S self tapping with expandable foam or sealant as
screws per section 9.1.6 of E2/AS1
Window head flashing (15° slope) 7.5 mm gap nominal
and stop end.
(Note: Not supplied with Ulltraclad© Window liner
system - contractor to supply as
additional flashing) H3.1 treated packers
Window frame (Note: refer to Flexible flashing tape at corners
window manufacturer for method of
support and fixing)
5 mm gap between head flashings
Ullrich Aluminium Co. Ltd. 1 : 2 V.06
Ulltraclad© Aluminium Cladding
May 2012 Window Head on Cavity
Ulltraclad© UA4532 Window Note: Ensure negative groove is clear of
Flashing fixed to wall framing with jamb flashing cover. Trim w/bd as required
50 x 2.5 mm clouts @ 600 mm ctrs.
leaving rib for support as shown.
Vertical tracking flashing
Locator strip fixed at max. 600 vertical min 10 mm cover
centers with 6g x 2" CSK Sq. S/S self
tapping screws through batten into Inseal 3109 - min 19 mm thick x
stud 10 mm wide
Ulltraclad© Weatherboards
Window frame (Note: refer to
Interior lining window manufacturer for method
of support and fixing)
Building underlay continuous
around opening
Window liner
H3.1 treated packers
Flexible flashing tape 100 mm
minimum up jamb
Airseal to perimeter of trim
cavity with expandable foam or
sealant as per section 9.1.6 of
E2/AS1
7.5 mm gap nominal
Ullrich Aluminium Co. Ltd. 1 : 2 V.07
Ulltraclad© Aluminium Cladding
May 2012 Window Jamb on Cavity
Flexible flashing tape along entire Airseal to perimeter of trim cavity
sill, 100 mm up each jamb and 50 with expandable foam or sealant as
mm onto face of building underlay per section 9.1.6 of E2/AS1
Window liner
Window frame (Note: refer to 10 mm min cover
window manufacturer for method of 7.5mm
support and fixing)
Interior lining
Ulltraclad© UA6975 weatherboard H3.1 treated packers
(vertical) fixed with locator strip
between boards (UA4535) Window support bar for window
Locator strip fixed at max. 600 vertical openings wider than 600mm.
centres with 6g x 2" CSK Sq. S/S self Support bar to comply with E2/AS1
tapping screws through batten into 9.1.10.5(v)
stud
Vertical 'tracking' flashing running
from jamb flashing to vertical
starter.
Flashing to be .25 aluminium min.
to track accidental water'.
See V.09 and isometric head detail
for more info
Building Underlay
Note: Ensure to alternate spacings of
fixings for battens and locator lengths to
avoid risk of splitting batten
Ullrich Aluminium Co. Ltd. 1 : 2 V.08
Ulltraclad© Aluminium Cladding
May 2012 Window Sill on Cavity
Building underlay folded into 40x18 mm cavity battens
opening One vertical at window jamb then
Cavibat used horizontally
Flexible flashing tape along sill to
continue 50 mm onto face of wall Ulltraclad© jamb flashing
and 100 min, up each jamb
Back of flashing bent forward
approximately 10 mm to divert any
water to the back of the Ulltraclad©
weatherboard
Underlay strips to isolate aluminium
from treated battens
Window support bar for window
openings wider than 600mm.
Support bar to comply with E2/AS1
9.1.10.5 (v). Install batten below if
required.
0.25mm Aluminium back flashing
with hems running from under
window jamb to vertical starter strip
Ullrich Aluminium Co. Ltd. V.09N.T.S
Ulltraclad© Aluminium Cladding
May 2012 Window Sill / Jamb Isometric
40x18 mm cavity battens
Ulltraclad© head flashing
Cut channel on both sides to 70
mm. Turn down channel floor 90°
and trim back to 20 mm
Ulltraclad© jamb flashing
Window head flashing cut around
jamb flashing. Seal junction.
Part of board removed as required
Note: Ulltraclad© Head Flashing to extend 80 mm past edge of
window or door joinery. Building underlay and flashing tape
omitted for clarity
Ullrich Aluminium Co. Ltd. 1 : 2 V.10a
Ulltraclad© Aluminium Cladding
May 2012 Head / Jamb On Cavity
Ulltraclad© head flashing
Part of board removed as required
Cut channel on both sides to 70
mm. Turn down channel floor 90°
and trim back to 20 mm
20 mm upstand on jamb flashing to
tuck behind head flashing upstand.
Ulltraclad© jamb flashing
Note: Ulltraclad© Head Flashing to extend 80 mm past edge of
window or door joinery. Building underlay and flashing tape
omitted for clarity
Ullrich Aluminium Co. Ltd. 1 : 2 V.10b
Ulltraclad© Aluminium Cladding
May 2012 Head / Jamb On Cavity
Ulltraclad© UA6975 weatherboard 10 Note: Ensure to alternate spacings of
(vertical) fixed with locator strip 35 min fixings for battens and locator lengths to
between boards (UA4535)
Locator strip fixed at max. 600 flashing upstand avoid risk of splitting batten
vertical centres with 6g x 2" CSK
Sq. S/S self tapping screws Building underlay continuous
through batten into stud behind head flashing and into
opening. Flashing tape over top of
Cavibat cavity battens head flashing
Ulltraclad© UA4533 Head Flashing. Nog as required
5mm diameter drainage holes
drilled through base of flashing @ Airseal over PEF rod around all
300 mm ctrs.fixed to lintel @ 300 sides of meter box
mm ctrs with:
6g x 2" CSK Sq. S/S self tapping 7.5 mm gap nominal
screw
Flexible flashing tape at corners
Meter box flashing 15° slope
(Note: Not supplied with Ulltraclad© Metal meter box
system - contractor to supply as
additional flashing)
20x20 mm metal angle sealed and
riveted to meter box
5 mm gap between head flashings
Ullrich Aluminium Co. Ltd. 1 : 2 V.11
Ulltraclad© Aluminium Cladding
May 2012 Meter Box head on cavity
Ulltraclad© UA4532 Window Note: Ensure negative groove is clear of
Flashing fixed to wall framing with jamb flashing cover. Trim w/bd as required
50 x 2.5 mm clouts @ 600 mm ctrs.
leaving rib for support as shown.
Cavibat cavity battens
Metal meter box
Locator strip fixed at max. 600 vertical Inseal 3259 tape between angle
centers with 6g x 2" CSK Sq. S/S self and jamb flashing
tapping screws through batten into 20x20 mm metal angle sealed and
stud riveted to meter box
Flexible flashing tape 100 mm
Ulltraclad© Weatherboards minimum up jamb
Airseal over PEF rod around all
sides of meter box
7.5 mm gap nominal
Ullrich Aluminium Co. Ltd. 1 : 2 V.12
Ulltraclad© Aluminium Cladding
May 2012 Meter Box Jamb
20x20 mm metal angle sealed and Metal meter box
riveted to meter box Flexible flashing tape to sill and
jambs
Inseal 3259 tape between angle Airseal over PEF rod around all
and jamb flashing and jamb sides of meter box
flashing and meterbox 7.5 mm gap nominal
Ulltraclad© UA4532 Window Note: Ensure to alternate spacings of
Flashing fixed to wall framing with fixings for battens and locator lengths to
50 x 2.5 mm clouts @ 600 mm ctrs.
Alternatively use soffit clip avoid risk of splitting batten
Ulltraclad© UA6975 weatherboard
(vertical) fixed with locator strip
between boards (UA4535)
Locator strip fixed at max. 600
vertical centers with 6g x 2" CSK
Sq. S/S self tapping screws
through batten into stud
Cavibat cavity batten
Building Underlay
Ulltraclad© weatherboards
UA6975
Vertical 'tracking' flashing with
hems running from base of jamb
flashing to vertical starter.
Flashing to be .25 aluminium min.
to track accidental water'.
See V.10 and isometric head detail
for more info
Ullrich Aluminium Co. Ltd. 1 : 2 V.13
Ulltraclad© Aluminium Cladding
May 2012 Meter Box On Cavity
Building underlay carefully cut to Square of flexible flashing tape to a
suit pipe. min. of 100 mm outside of pipe.
Ensure seal with pipe bandage
Cavibat cavity battens Pipe to have min. 5° fall to outside
Ulltraclad© weatherboard over Flexible flashing tape bandage min.
flashing tape, carefully cut to suit 25 mm wide all round pipe
pipe. Seal with PVC flange and
flexible sealant.
Ullrich Aluminium Co. Ltd. 1 : 2 V.14
Ulltraclad© Aluminium Cladding
May 2012 Pipe Penetration On Cavity
Ulltraclad© UA6975 weatherboard 35 mm min
(vertical) fixed with locator strip clear gap
between boards (UA4535)
Locator strip fixed at max. 600 vertical 75 mm min flashing leg
centers with 6g x 2" CSK Sq. S/S self above bottom of weatherboard
tapping screws through batten into Nog as required
stud
Building underlay over Roofing underlay turned up under
flashing upstand flashing
Note: Ensure to alternate spacings of Selected roofing with stop ends
fixings for battens and locator lengths to
avoid risk of splitting batten
Ulltraclad© cavity vent strip with 15mm
drip edge to cladding
Ulltraclad© UA4863 Vertical Starter Strip
fixed to bottom plate @ 300 mm ctrs with:
6g x 2" CSK Sq. S/S self tapping screws
Ulltraclad© UA4563 with 5mm
diameter drainage holes drilled
through base of flashing @ 300
mm ctrs.
Apron flashing with 75 mm upstand
cover behind cladding
Ullrich Aluminium Co. Ltd. 1 : 2 V.15
Ulltraclad© Aluminium Cladding
May 2012 Roof to Wall Junction
Building underlay
Ulltraclad© UA4563
with 5mm diameter Ulltraclad© UA6975 weatherboard
(vertical) fixed with locator strip
drainage holes between boards (UA4535)
Locator strip fixed at max. 600
drilled through base vertical centers with 6g x 2" CSK
Sq. S/S self tapping screws
of flashing @ 300 through batten into stud
mm ctrs.
Cavibat cavity battens
Flashing tape or extra layer of
building underlay over flashing
Selected roofing Flashing upstand behind building
underlay
Soffit
Fascia board F a ll
Apron flashing with tapered
stopend. Weatherboards to be
carefully cut over stopend & sealed
End of spouting must finish 10 mm
min. clear of weatherboards
Selected spouting
Refer to E2/AS1 Table 7 for apron flashing cover requirements
over roof cladding
V.16
Ullrich Aluminium Co. Ltd. 1 : 2 V.16
Ulltraclad© Aluminium Cladding
May 2012 Gutter Wall Junction On Cavity
H3.1 treated timber packer to form 5 ° s l o p e mi n Underlay to provide isolation of
slope metal flashing from treated timber
See table 7 E2/AS1for
45x18 mm cavity battens, underlay flashing depth Metal capping flashing (Note: not
strips to isolate aluminium from supplied with Ulltraclad© system -
treated battens (Alternatively use contractor to supply as additional
'CAVIBAT' system) flashing)
Cavibat fixing as per manufacturers Metal capping to be fixed with rivets
instructions to sides only
Ulltraclad© UA6975 weatherboard
(vertical) fixed with locator strip
between boards (UA4535)
Locator strip fixed at max. 600 vertical
centers with 6g x 2" CSK Sq. S/S self
tapping screws through batten into
stud
Building underlay continuous over
framing
Ullrich Aluminium Co. Ltd. 1 : 2 V.17
Ulltraclad© Aluminium Cladding
May 2012 Parapet On Cavity
12 mm min
Cavibat cavity battens Building Underlay
Cavibat fixing as per
12 mm H3.2 timber packer at fixing manufacturers requirements
locations Bolt fixing in accordance
with NZS3604:2011
Deck joists Ensure solid packer
around bolt
50x50x3 mm thick Solid blocking
EPDM washer to
suit, hole to fit 1 : 2 V.18
tightly around bolt
Deck Junction On Cavity
H3.2 timber
stringer
Ulltraclad© UA6975 weatherboard
(vertical) fixed with locator strip
between boards (UA4535)
Locator strip fixed at max. 600 vertical
centers with 6g x 2" CSK Sq. S/S self
tapping screws through batten into
stud
Ullrich Aluminium Co. Ltd.
Ulltraclad© Aluminium Cladding
May 2012
Ulltraclad© UA6975 weatherboard 100 mm min finished floor level Interior lining
(vertical) fixed with locator strip to finished deck surface Bottom plate over DPC
between boards (UA4535)
Locator strip fixed at max. 600 vertical 35mm min. 50 Ulltraclad© cavity vent strip with
centers with 6g x 2" CSK Sq. S/S self 15mm drip edge to cladding
tapping screws through batten into Floor structure
stud
Building underlay Deck waterproof membrane lapped
up behind building underlay past
Note: Ensure to alternate spacings of over bottom plate (min. 150mm
fixings for battens and locator lengths to upstand)
Ulltraclad© UA4563 with 5mm
avoid risk of splitting batten diameter drainage holes drilled
Ulltraclad© UA4863 Vertical Starter Strip through base of flashing @ 300
fixed to bottom plate @ 300 mm ctrs with: mm ctrs.
6g x 2" CSK Sq. S/S self tapping screws Corner fillet
Waterproof deck structure 1 : 2 V.19
V.19 Waterproof deck base
Ullrich Aluminium Co. Ltd.
Ulltraclad© Aluminium Cladding
May 2012
Ulltraclad© UA6975 weatherboard 35 mm min5 Bottom plate
(vertical) fixed with locator strip cover Flooring to finish 10 mm back from
between boards (UA4535) 35 mm min outside framing
Locator strip fixed at max. 600 vertical cover
centers with 6g x 2" CSK Sq. S/S self Continuous boundary joists
tapping screws through batten into
stud Ulltraclad© cavity vent strip with
Building underlay 15mm drip edge to cladding
Note: Ensure to alternate spacings of Aluminium flashing 15° slope
fixings for battens and locator lengths to (Note: Not supplied with Ulltraclad©
system - contractor to supply as
avoid risk of splitting batten additional flashing)
Building underlay lapped over
Ulltraclad© UA4863 Vertical Starter Strip flashing upstand
fixed to bottom plate @ 300 mm ctrs with:
6g x 2" CSK Sq. S/S self tapping screws Top plate
Ulltraclad© UA4563 with 5mm Interior lining
diameter drainage holes drilled
through base of flashing @ 300
mm ctrs.
Note: Where top of board is cut
down - screw fix though board,
ensure fixing is covered by
flashing
Cavibat cavity battens
Fixed as per manufacturers
instructions
Ullrich Aluminium Co. Ltd. Note: This detail is to limit cavities to 2-
Ulltraclad© Aluminium Cladding stories or 7m max in height. Refer
May 2012 E2/AS1 clause 9.1.9.4
1 : 2 V.20
Inter-Storey Junction