CAUTION 1 COOLING
HIGH VOLTAGE! SEE USER´S MANUAL CHAPTER 1 A =Clearance around the unit BC
B =Distance from the unit to another unit A
VARAUSJÄNNITE! KATSO KÄYTTÖOHJE KOHTA 1 C =Free space above the unit
D =Free space underneath the unit AD
HÖG SPÄNNING! SE ANVÄNDARMANUALEN KAPITEL 1
HOCHSPANNUNG! SIEHE BETRIEBSANLEITUNG KAP. 1 Dimensions (mm)
A B CD
HAUTE TENSION! VOIR MANUEL UTILISATEUR CHAP. 1 NXL 20 20 100 50
0003-0012 5 20 20 120 60
ALTA TENSIONE! VEDI MANUALE BASE CAPITOLO 1 0016-0031 5 30 20 160 80
0038-0061 5
ALTA TENSIÓN! VER EL CAPITULO. 1 DEL MANUAL
2 MOUNTING 3 POWER
CONNECTIONS
Mounting dimensions (mm)
NXL H2 W2 D1 H2 B- B+ R- U/T1V/T2 W/T3
0003-0012 5 313 100 7 W2
0016-0031 5 406 100 7 L1 L2 L3
0038-0061 5 541 148 9
H1
Unit dimensions (mm)
NXL H1 W1 D1
0003-0012 5 327 128 190
0016-0031 5 419 144 214
0038-0061 5 558 195 237
W1 Mains Brake M
resistor
4 CONTROL CONNECTIONS CONTROL I/O standard CONTROL I/O extension (optional)
I/O extension boards
Terminal Signal Default Terminal Signal Default
1 10 Vref Reference voltage 1 +24V 24 V auxiliary voltage
2 AI1+ 2 GND
3 AI1- Analog input, 0-10V 3 DIN1 I/O ground
4 AI2+ 4 DIN2
Fieldbus boards 5 AI2- Analog input common 5 DIN3 Digital input 1 Preset speed 2
6 24 Vout 6 DO1
1...10 kOhm 7 GND Analog input, 0/4-20 mA OPT-AA 24 RO1 Digital input 2 Fault reset
8 DIN1 Analog input common 25 RO1
9 DIN2 26 RO1 Digital input 3 Disable PID
10 DIN3
11 GND 24 V auxiliary voltage Digital output Ready
18 AO1+
19 AO1- Relay output 1
A RS 485
B RS 485 I/O ground RUN
30 +24V
21 RO1 Digital input 1 Start forward
22 RO1
23 RO1 Digital input 2 Start reverse OR
OPT-AI
Digital input 3 Preset speed 1
I/O ground Terminal Signal Default
12 +24 V
mA Analog output Output freq. 13 GND 24 V auxiliary voltage
14 DIN1
Analog output common 15 DIN2 I/O ground
16 DIN3
9 10 11 18 19 A B 30 Serial bus (Modbus RTU) Digital input 1 Preset speed 2
28 TI1+
Serial bus 29 TI1- Digital input 2 Fault reset
External control voltage supply 25 RO1 Digital input 3 Disable PID
21 22 23 Relay output 1 26 RO1 Thermistor input
12345678 FAULT Thermistor input
Relay output 1
RUN
5 START-UP WIZARD =Push the button
START MODE rpmn In (A) DONE
+ +
- rEeNsTeEt R
+ + - rpm A
- ENTER - ENTER
+ +
reset reset - ENTER - ENTER
reset reset
1 Push 5 seconds 2 Select the 3 Accept 4 Tune 5 Accept 6 Tune 7 Accept
to activate (in mode. See n(rpm) I(A)
stop mode) table below!
P2.1.1Min. Freq (Hz) M NOTE! Startup Wizard returns
P2.1..2 Max.Freq (Hz)
P2.1.3 Acc time (s) all other parameters to factory
P2.1.4 Dec time (s) defaults!
P2.1.5 Current limit(A)
P2.1.6 Motor Un (V)*
P2.1.7 Motor fn(Hz)
P2.1.11Start funct.
P2.1.12 Stop funct.
P2.1.13 U/f optimization
P2.1.14 I/0 ref
P2.1.21 Auto restart
P3.1 Control place
0 50 3 3 IH*1,5 400 50 0= 0= 0= 0= 0=
Hz Hz s s V* Hz Ramp Coasting Not Ai1 Not I/O
Standard
used 0-10V used
20 50 20 20 I *1,1 400 50 0= 0= 0= 0= 0=
Hz Hz s s L Ai1 Not I/O
V* Hz Ramp Coasting Not
Fan used 0-10V used
20 50 5 5 IL*1,1 400 50 0= 1= 0= 0= 0= I/O
Hz Hz s s V* Hz Ramp Ramp Not Ai1 Not
Pump used 0-10V used
0 50 1 1 IH*1,8 400 50 0= 0= 1= 0= 0=
Hz s s
High Hz V* Hz Ramp Coasting automatic Ai1 Not I/O
performance torque 0-10V used *In drives of 208V...230V
boost this value is 230V
6 MENU STRUCTURE 9 PARAMETER SETTINGS
Expander board menu SELECTED MODE MOTOR NAME PLATE VALUES
System menu Standard mode P 2.1.8 Nominal motor speed
Fan mode P 2.1.9 Nominal motor current
Fault history menu
Active faults menu Pump mode
Keypad control menu High performance mode
+ Parameter menu BASIC PARAMETERS
- ENTER
reset
Code Parameter Note Code Parameter Note
(Hz)
Navigation and P 2.1.1 Min frequency 0=Not used
selection keys (Hz) 1=Output freq. (0-fmax)
P 2.1.2 Max frequency
NOTE: If fmax > than the 2=Freq. reference (0-fmax)
motor synchronous speed,
Monitoring menu check suitability for motor 3=Motor speed (0-Mot.nom. spd)
and drive system
4=Output current (0-InMotor)
P2.1.16 Analogue 5=Motor torque (0-TnMotor)
6=Motor voltage (0-UnMotor)
output function 7=DC-link volt (0-1000V)
7 MONITORING MENU M1 P 2.1.3 Acceleration time (s) 8=PI controller ref. value
1 9=PI contr. act. value 1
10=PI contr. error value
P 2.1.4 Deceleration time (s) 11=PI controller output
1
0=Not used
Code Signal name Unit P 2.1.5 Current Output current limit (A)
limit of the unit 1=Start Reverse
V1.1 Output frequency Hz 2=Reverse
V1.2 Frequency reference Hz P 2.1.6 Nominal voltage (V) 3=Stop pulse
rpm
V1.3 Motor speed A of the motor Check the rating plate 4=External fault, cc
V1.4 Motor current %
Motor torque % of the motor P2.1.17 DIN2 function 5=External fault, oc
V1.5 Motor power V
V1.6 Motor voltage V P 2.1.7 Nominal frequency Check (Hz) plate 6=Run enable
DC-link voltage ºC 7=Preset speed 2
V1.7 Unit temperature of the motor the rating 8= Motor pot. UP (cc)
V1.8 Analogue input 1 mA
V1.9 Analogue input 2 mA of the motor 9= Disable PID (Direct freq. ref.)
V1.10 Analogue output current mA 10=Interlock 1
V1.11 Analogue output current 1, expander board (rpm)
V1.12 Analogue output current 2, expander board % Nominal speed 0=Not used
V1.13 DIN1, DIN2, DIN3 % of the motor The default applies for a 4-
V1.14 DIE1, DIE2, DIE3 % P 2.1.8 pole motor and a nominal 1=Reverse
V1.15 % size frequency converter.
V1.16 RO1 2=External fault, cc
V1.17 ROE1, ROE2, ROE3
V1.18 P 2.1.9 Nominal current (A) 3=External fault, oc
V1.19 DOE1 4=Fault reset
V1.20 PID Reference Check the rating plate
V1.21 PID Actual value of the motor 5=Run enable
V1.22 PID Error value of the motor
V1.23 6=Preset speed 1
V1.24 PID Output
Autochange 1,2,3 P 2.1.10 Motor cos Check the rating plate P2.1.18 DIN3 function 7=Preset speed 2
V1.25 of the motor 8=DC-braking command
Mode: 0= Not selected (default), 1= Standard,
2= Fan, 3= Pump, 4= High performance 9=Motor pot. UP (cc)
P 2.1.11 0=Ramp 10=Motor pot. DOWN (cc)
1=Flying start
Start function 11=Disable PID (PID ctrl selection)
12=PID Keypad ref. 2 selection
P 2.1.12 Stop function 0=Coasting 13=Interlock 2
1=Ramp
14=Thermistor input (See Ch. 6.2.4)
15=Force control place to I/O
P 2.1.13 U/f optimisation 0=Not used 16=Force ctrl place to fieldbus
1=Automatic torque boost 17=AI1/AI2 selection
0=AI1 P2.1.19 Preset speed 1 (Hz)
1=AI2 P2.1.20 Preset speed 2 (Hz)
2=Keypad reference
P 2.1.14 I/O reference 3=Fieldbus reference P2.1.21 Autom. restart 0=Not used 1=Used
(FBSpeedReference) P2.1.22 Parameter 0=All parameters and
4=Motor potentiometer conceal menus visible
5=AI1/AI2 selection
1=P2.1 and menus
1=0mA - 20mA MI - H5 visible
P2.1.15 AI2 signal range 2=4mA - 20mA
3=0V - 10V
4=2V - 10V
10 FAULT CODES
CODE FAULT CODE FAULT
8 KEYPAD CONTROL MENU K3 1 Overcurrent 29 Thermistor fault
2 Overvoltage 34 Internal bus communication
Parameters Selections 3 Earth fault 35 Application fault
8 System fault 39 Device removed
P3.1 Selection of control place 1= I/O Terminals, 2=Keypad, 3=Fieldbus 9 Undervoltage 40 Device unknown
11 Output phase supervision 41 IGBT temperature
R3.2 Keypad reference (Hz) 13 Frequency converter undertemperature 44 Device change
14 Frequency converter overtemperature 45 Device added
15 Motor stalled 50 Analogue input Iin < 4mA (sel. signal range 4to20 mA)
16 Motor overtemperature 51 External fault
17 Motor underload 52 Keypad communication fault
22 EEPROM checksum fault 53 Fieldbus fault
24 Counter fault 54 Slot fault
25 Microprocessor watchdog fault 55 Actual value supervision
P3.3 Keypad direction 0= Forward, 1= Reverse
+ P3.4 Stop button activation 0= Limited function, 1= Always enabled
- ENTER
P3.5 PID reference 1 (%)
reset
P3.6 PID reference 2 (%)
ud01074
www.vacon.com
vacon nxl
quick guide