The words you are searching are inside this book. To get more targeted content, please make full-text search by clicking here.

In an effort to offer world-class product solutions in all of its categories, Schier announced the spin-off of its Oil Separator, Solids Interceptor, and Chemical Waste Tank products to a separate and wholly-owned brand, Striem.

Discover the best professional documents and content resources in AnyFlip Document Base.
Search
Published by Indicia Design, 2016-08-08 09:21:53

2016 Striem Catalog

In an effort to offer world-class product solutions in all of its categories, Schier announced the spin-off of its Oil Separator, Solids Interceptor, and Chemical Waste Tank products to a separate and wholly-owned brand, Striem.

Keywords: Striem

A New Look

It’s becoming increasingly rare to buy a product that is 100% made in America. At Striem, we’re
proud to make products smack dab in the heart of our great country. Born and raised in Missouri,
we are used to calling our home state the “heart” of America, given its central geographic
location. The true meaning of “Missouri” comes from the Sioux Indians, translated as “town of
the large canoes.” As we began work on a new logo, we knew we wanted the canoe to be the
centerpiece, as it became synonymous with our home.
Now, take a second to just stare at the logo. Pictures have different meanings to different
people. Make it your own.
Here’s what it means to us.
The water makes up nearly half of the logo. We wanted to show its vastness as a resource.
The straight-line waves give the water a clean look. After all, we’re in the business to make water
clean. The mountains depict strength, and their bright color represents the creativity that we
value so highly. The scene is outlined in a bold, dark green shield, which is meant to exude a
premium feeling. We hope our products do the same.
Last but not least: the rower. He not only gives the logo life and vitality, but he also provides
direction, as if to say “we’re moving forward.” And we are.

www.striemco.com | Made in the USA | Striem Catalog

Table of Contents

Oil Separators

Oil Reserve™ oil/sand separators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Oil Reserve™ oil collection tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Solids Interceptors

HLT/B and USI Series under counter solids interceptors . . . . . . . . . . . . . . . . . . . . . . . . . 12
Prospector™ (-B) basket style solids interceptors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Prospector™ (-S) screen style solids interceptors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Settler™ catch basins for sand and sediment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Chemical Waste Tanks

Lab Rat™ under counter neutralization tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Lab Basin™ neutralization tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
NT Series neutralization tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Command Center™ pH monitoring package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Bio Basin™ decontamination tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Appendix

Terms and Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Lifetime Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Thank You for Trusting Us . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Customer Support

8:00 a.m. – 5:00 p.m. CST (Monday through Friday)
Tel: 913-222-1500 | Fax: 913-951-3399
email: [email protected] | [email protected]

www.striemco.com | Made in the USA | Striem Catalog 2

Oil Reserve™ Product Selection

sizing guidelines

Oil Reserve™ Oil/Sand Separators incorporate patented Diffusion Flow™ technology to maximize
oil and sand separation. Petroleum based oils are typically lighter than water and will quickly rise
to the surface by gravity differential separation according to Stokes' Law.

Common Specific Gravities

The following chart is provided for reference only. Specific gravities less than 1 float
while those greater than 1 sink.

substance specific gravity substance specific gravity

Gasoline A 0.74 Chicken Fat 0.924
Petroleum Oil 0.82 Fish Oil 0.928
Hydraulic Fluid 0.86 Water 1
Butter 0.87 Freon 11 1.49
Lard 0.875 Mud 1.73
Olive Oil 0.91 Sand 1.92
Vegetable Oil 0.92

Option 1: size by drainage area for service facilities

When allowed, use the following sizing chart where motor vehicles are serviced and/or stored. For parking-only areas, consider option 2.

Oil Separator Sizing Chart

square feet of drainage area required capacity: cubic feet required capacity: gallons recommended model

Up to 200 Up to 7 52 OS-50
>200 – 1,100 Up to 16 120 OS-75
>1,100 – 3,100 Up to 36 269 OS-100
>3,100 – 6,700 Up to 72 539 OS-100 (2 in series)
>6,700 – 10,400 Up to 109 815 OS-100 (3 in series)
>10,400 – 14,200 Up to 147 1,100 OS-100 (4 in series)

Review plumbing code and locally adopted ordinances for specific requirements.

Option 2: size by flow rate for parking only facilities

Consider drain / hose bib flow rates when sizing for applications where motor vehicles are neither serviced nor stored (parking-only areas).

Drain Line Flow Rates (GPM) by Pipe Size* Hose Bib Flow Rates

pipe size (nominal) half pipe flow (design flow) maximum full pipe flow velocity ½ ¾
6.64 GPM
2 9.67 19.44 4 Ft./sec 3.77 GPM 9.96 GPM
3 29.33 58.67 13.29 GPM
4 62.96 125.77 6 Ft./sec 5.66 GPM 16.61 GPM
6 187.74 375.47
8 Ft./sec 7.54 GPM
preferred flow rate
10 Ft./sec 9.43 GPM

* ¼" pitch slope based on Manning’s Formula with friction factor N=0.012"

3 www.striemco.com | Made in the USA | Striem Catalog

Option 3: size by flow rate for elevator pits

ASME A17.1-2007/CSA B44-07 is the Safety Code for Elevators and Escalators.
It intended to serve as the basis for the design construction, installation,
operation, testing, inspection, maintenance, alteration and repair of elevators,
dumbwaiters, escalators, moving walks and material lifts. Section 2.2 details
the requirements for pits for all elevators governed by the code. 2.2.2.3
mandates that permanent provision be made to prevent accumulation of ground
water in the pit, while 2.2.2.4 requires the necessary floor drain or sump pump
meet the applicable plumbing code for the jurisdiction. 2.2.2.5 requires all
elevators with Firefighters’ Emergency Operation to have a drain or sump pump.
A sump pump or drain shall have the capacity to remove 3,000 gallons per hour
(50 gpm) per elevator.

IPC mandates the installation of an oil separator for hydraulic elevator pits,
unless there is an approved alarm system installed. The intent of the code is to
prevent an oil discharge to the sanitary drainage system. Some manufacturers
produce a specially fitted sump pump with an oil sensor and alarm unit which
functions to shut off the pump if oil is detected in the pit. For elevators with
Firefighters’ Emergency Operation the pit must be kept clear of accumulated
water as required in ASME A17.1-2007/CSA B44-07 section 2.2.2.5. However,
it may be possible for a sump pump with an oil sensor to shut off during a fire
allowing the pit to fill with sprinkler water undermining a firefighting operation.
The installation of an oil interceptor downstream of a sump pump satisfies both
the elevator and plumbing codes.

Sizing Guidelines Following an Elevator Sump

First, select an oil separator that meets the pump flow rate. Then, choose an oil separator with an oil capacity that is equal to or greater
than the worst possible discharge of hydraulic fluid.

application pump flow (GPM) OS model OS flow rate (GPM) OS oil capacity (gal.)

Single Elevator A 50 OS-50 50 34.1
Single Elevator B 50 OS-75 75 84.4
Double Elevator 100 OS-100 100 147.5

Review plumbing code and locally adopted ordinances for specific requirements.

Single Elevator A Single Elevator B Double Elevator

VENT VENT VENT

PIT PIT PIT PIT OS-100
OS-50 OS-75 SUMP

SUMP SUMP

NOTE: all pump fed oil separators should be specified with Clean Sweep™ coalescing media (as shown above) due to emulsification of oil.

www.striemco.com | Made in the USA | Striem Catalog 4

Oil Reserve™ OS-100 OS-75
OS-50 OS-35
oil/sand separators
OS-15 OS-25
With a standard lifetime warranty and
several innovative installation features,
the Oil Reserve™ stands alone as the
most versatile oil/sand separator series.

Features: above grade or buried installations
| easy to carry HDPE design | TeleGlide™ field
adjustable risers | models OS-50 through OS-100
suitable for exterior installations

Oil Reserve™ Covers

Covers are provided with water/air tight gasket seal and are designed to fit tightly into a key-fit frame.

indoor covers outdoor cover

16" 24" 24" 24"

BOLTED BOLTED BOLTED PICKABLE CAST
POLYPROPYLENE COMPOSITE COMPOSITE – TRAFFIC IRON – H20 (optional)

OS-15, OS-25 OS-35, OS-50 OS-50 (optional), OS-50, OS-75, OS-100
2,000 lbs. pedestrian load rating 2,000 lbs. pedestrian load rating OS-75, OS-100 16,000 lbs. H20 load rating

16,000 lbs. highway load rating

Clean Sweep™ Coalescing Media (optional)

When oily wastewater is mechanically Clean Sweep™ polypropylene
emulsified (as in pump applications), oils
break into smaller, less buoyant droplets coalescing media has been
and decrease separator efficiency.
Coalescing media provides increased third party tested to
surface area for emulsified oil droplets to
merge into larger, more buoyant droplets, performance standard CEN EN858-1 for
greatly improving separator efficiency.
class 1 coalescing separators. The Clean
Specify Clean Sweep™ coalescing media
with select Oil Reserve™ Series models Sweep™ will render effluent quality to no
(OS-35, OS-50, OS-75, OS-100) to
significantly improve the separation of more than 5 mg/L (parts per million) up
mechanically emulsified oils.
to the following flow rates: Flow Rate:

OS-35 (with single media) 15 GPM
OS-50 (with single media) 15 GPM
OS-75 (with single media) 30 GPM
OS-100 (with single media) 45 GPM
OS-100 (with double media) 90 GPM

Efficiency may decrease at higher flow rates.

5 www.striemco.com | Made in the USA | Striem Catalog

specifications & submittals
formats available online
.pdf .doc .dwg .rfa

Specifications

Capacity Pipe Sizes Rough-in Dimensions (in.) Weight (lbs.)

Striem Flow Oil Sand Liquid Plain End Optional Vent Body Inlet/Outlet Vent optional oil Vent/ Adapter Dry Wet
Model Rate (gal.) (gal.) (gal.) SCH.40 Male WH AB CD draw-off draw-off Adjust-
(GPM) Std. Optional Thread ability
EF (add to
L G B, D & H)

OS-15 15 10.1 3.9 16 2 3 2, 3 3 25 19 14 ¼ 10 4 ¼ 11 ¼ 3 4 10 ¼ 5 ½ n/a 28 160
OS-25 25 10.3 6.4 22 3 2 2, 3 3 27 21 15 10 ¾ 4 ¼ 11 ½ 3 ½ 4 11 6 ¼ n/a 31 215
OS-35 35 19.5 9.5 35 3 2, 4 2, 3, 4 3 33 25 25 15 10 17 8 5 ½ 19 ½ 7 ½ 3 ½ 77 369
OS-50 50 34.1 12.5 52 4 3 3, 4 3 37 28 28 ½ 18 10 ½ 20 8 ½ 6 ½ 22
OS-75 75 84.4 19.2 125 4 6 4, 6 3 46 32 38 ½ 26 12 ½ 28 ½ 10 21 ½ 17 9 3 ½ 92 525
OS-100 100 147.5 105 275 4 6 4, 6 3 68 33 ½ 51 ½ 38 13 ½ 40 11 ½ 31 20 ½ 12 6 130 1,171
16 6 230 2,520

OS-15 OS-25 OS-35 OS-50 OS-75 OS-100

Miscellaneous Options TeleGlide™ Riser Order Guide

Desired Riser Height (in.)

High Water *Upgrade to Highway *Upgrade to H-20 OS-15 OS-35 OS-75 Risers Needed
Striem Anchor Kit Rated Bolted Rated Pickable Cast OS-25 OS-50 OS-100
Model Composite Cover Iron Cover 16 Series
Riser (SR-16)
Part # Part # Part # >2 1 ⁄8 - 16 n/a n/a

OS-15 n/a n/a n/a n/a 0 - 3½ 0-6 24 Series Adapter
OS-25 n/a n/a
OS-35 n/a n/a
OS-50 AK1 n/a
n/a n/a >3½ - 22 >6 - 24 24 Series
OS-75 AK1 C24-H Short Riser (SR24)
OS-100 AK1 n/c C24-HP n/c

included C24-HP n/c n/a >22 - 37 >24 - 39 24 Series
included C24-HP (2) n/c Long Riser (LR24)

Clean Sweep Coalescing Media Part # Compatible with Model(s) n/a n/a >39 - 43 24 Series Short +
CS1 (single media) 0S-35 / 0S-50 Short (SR24 + SR24)
CS2 (single media) 0S-75
CS3 (single media) 0S-100 n/a n/a >43 - 58 24 Series Short +
CS6 (double media) 0S-100 Long (SR24 + LR24)

n/a n/a >58 - 72 24 Series Long +
Long (LR24 + LR24)

DO2: Optional 2" Oil Draw-off Arm required when ordered with
Oil Reserve™ oil collection tank.

* When ordered with oil separator.

NOTE 1: OS-100 has two covers requiring a set of two TeleGlide™ risers when ordered.
NOTE 2: When upgraded covers are purchased separately, the full price will apply.

www.striemco.com | Made in the USA | Striem Catalog 6

specifications & submittals
formats available online
.pdf .doc .dwg .rfa

OS-750 OS-1000

Specifications Specifications

Inlet/Outlet Max Flow Rate Max Operating Inlet/Outlet Max Flow Rate Max Operating
6" 314 GPM Temperature 6" 314 GPM Temperature

Liquid Capacity Oil Capacity 190°F Liquid Capacity Oil Capacity 190°F
750 (gal.) 430 (gal.) 1,000 (gal.) 575 (gal.)
Solids/Sediment Solids/Sediment
Capacity Capacity

75 (gal.) 100 (gal.)

Unit Weight w/Std. Covers Unit Weight w/Std. Covers
1200 (lbs.) 1400 (lbs.)

Highway rated, bolted, gas/water tight composite Highway rated, bolted, gas/water tight composite
covers (16,000 lbs.) covers (16,000 lbs.)

Side View Side View

CL

CL
CL

Options Options

Teleglide field adjustable risers for extending covers to grade Teleglide field adjustable risers for extending covers to grade
H20 rated pickable cast iron covers H20 rated pickable cast iron covers
4" Plain end connections 4" Plain end connections
Male pipe thread connections Male pipe thread connections

7 www.striemco.com | Made in the USA | Striem Catalog

OS-1500

Specifications Notes

Inlet/Outlet Max Flow Rate Max Operating 1. 3/4" thick seamless high density polyethylene walls.
6" 314 GPM Temperature 2. Unit supplied with built-in adapter(s) for up to 6" of adjustability.
190°F
Liquid Capacity Oil Capacity Additional riser(s) available for deeper burial depth.
1500 (gal.) 850 (gal.) Solids/Sediment 3. Cover placement allows full access to tank for proper
Capacity
500 (gal.) maintenance.
4. Engineered inlet and outlet diffusers for ease of inspection and
Unit Weight w/Std. Covers
1700 (lbs.) cleaning of piping.
5. For buried applications
Highway rated, bolted, gas/water tight composite 6. Integral Air Relief/Anti-siphon
covers (16,000 lbs.)

Side View TeleGlide™ Riser Order Guide

CL Desired Riser Height (in.) Risers Needed
CL OS-750, OS-1000, OS-1500
16 Series
n/a Riser (SR-16)
0-6
>6 - 24 24 Series Adapter
>24 - 39
>39 - 43 24 Series
>43 - 58 Short Riser (SR24)
>58 - 72
24 Series
Long Riser (LR24)
24 Series Short +
Short (SR24 + SR24)
24 Series Short +
Long (SR24 + LR24)

24 Series Long +
Long (LR24 + LR24)

Options

Teleglide field adjustable risers for extending covers to grade
H20 rated pickable cast iron covers
4" Plain end connections
Male pipe thread connections

www.striemco.com | Made in the USA | Striem Catalog 8

Oil Reserve™

oil collection tanks

Oil Reserve™ Collection Tanks in OCT-35 OCT-275 OCT-125
conjunction with oil/sand separators OCT-15 OCT-25 OCT-50
maximize oil storage capacity and
minimize pump-out frequency. The Oil/Sand Oil Collection
collection tank also provides more Separator Tank
accurate oil level monitoring.

Features: above grade or buried installations | easy to carry
HDPE design | TeleGlide™ field adjustable risers | models
OCT-50 through OCT-275 suitable for exterior installations |
install with Striem oil separator

Operating Adjustable Oil Venting Maximum
Water Level Draw-off Arm Spill Line Oil Capacity
Slip
Static Nut
Water Level
Oil/Sand
Separator Oil
Collection

Tank

Cutaway View of
Oil Draw-off Arm

Oil Reserve™ Covers

Covers are provided with water/air tight gasket seal and are designed to fit tightly into a key-fit frame.

indoor covers outdoor covers

16" 24" 24" 24"

BOLTED BOLTED BOLTED PICKABLE CAST
POLYPROPYLENE COMPOSITE COMPOSITE – TRAFFIC IRON – H20 (optional)

OCT-15, OCT-25 OCT-35, OCT-50 OCT-50 (optional), OCT-50, OCT-125, OCT-275
2,000 lbs. pedestrian load rating 2,000 lbs. pedestrian load rating OCT-125, OCT-275 16,000 lbs. H20 load rating
16,000 lbs. highway load rating

9 www.striemco.com | Made in the USA | Striem Catalog

specifications & submittals
formats available online
.pdf .doc .dwg .rfa

Specifications

Oil Capacity Pipe Size Rough-in Dimensions (in.) Weight (lbs.)
Cubic Feet Gallons (Plain End SCH.40)
Dry Wet
Striem Inlet Vent Body Vent Inlet Vent/ Adapter Install
Model W AB CD Inlet Adjustability 28 166 with:
31 220
L H E (add to B, D & H) 77 369 0S-15
92 525 0S-25
OCT-15 2.1 16 2 3 25 19 14 ¼ 11 ¼ 3 4 10 ¼ 5½ n/a 130 1,171 0S-35
OCT-25 2.9 22 2 3 27 21 15 11 ½ 3½ 4 11 6¼ n/a 230 2,313 0S-50
OCT-35 4.7 35 2 3 33 25 25 5½ 7½ 3½ 0S-75
OCT-50 7 52 2 3 37 28 17 8 6½ 19 ½ 3½ 0S-100
OCT-125 16.7 125 2 3 46 32 28 ½ 20 8½ 21 ½ 22 9 6
OCT-275 36.8 275 2 3 68 33 ½ 38 ½ 28 ½ 10 31 17 12 6
51 ½ 40 11 ½ 16
20 ½

OCT-15 OCT-25 OCT-35 OCT-50 OCT-125 OCT-275

Miscellaneous Options TeleGlide™ Riser Order Guide

Desired Riser Height (in.)

High Water *Upgrade to Highway *Upgrade to H-20 OCT-15 OCT-35 OCT-125 Risers Needed
Striem Anchor Kit Rated Bolted Rated Pickable Cast OCT-25 OCT-50 OCT-275
Model Composite Cover Iron Cover 16 Series
Riser (SR-16)
OCT-15 Part # Part # Part # >2 1 ⁄8 - 16 n/a n/a
OCT-25 n/a
OCT-35 n/a n/a n/a n/a 0 - 3½ 0-6 24 Series Adapter
OCT-50 n/a
OCT-125 AK1 n/a n/a
OCT-275 AK1
AK1 n/a n/a n/a >3½ - 22 >6 - 24 24 Series
Short Riser (SR24)
C24-H n/c C24-H n/c

included C24-HP n/c n/a >22 - 37 >24 - 39 24 Series
Long Riser (LR24)
included C24-HP (2) n/c
24 Series Short +
Monitoring Packages n/a n/a >39 - 43 Short (SR24 + SR24)

n/a n/a >43 - 58 24 Series Short +
Long (SR24 + LR24)

AVA-3: Single Level AVA-4: Multi-level 80% n/a n/a >58 - 72 24 Series Long +
Monitoring Package Monitoring Package 50% Long (LR24 + LR24)
20%
Remote audio/visual alarm Remote audio/visual alarm
panel and explosion proof panel and explosion proof
stainless steel float switch. multi-level float switch.

NOTE 1: When ordered with float switch, add 2" measuring finished cover to centerline of all connections and subtract 2" from available riser height.
NOTE 2: OCT-275 has two covers requiring a set of two risers when ordered.
NOTE 3: When upgraded covers are purchased separately, the full price will apply.

www.striemco.com | Made in the USA | Striem Catalog 10

Solids Interceptors Product Selection

sizing guidelines

For General Applications

Striem recommends that solids interceptors first be sized by pipe size, then by selecting the unit with the
appropriate sediment capacity to provide an acceptable cleaning frequency.

Flow Rates (GPM) by Pipe Size

pipe size per Manning’s Formula*
(nominal)
half pipe flow (design flow) maximum full pipe flow

2 9.67 19.44

3 29.33 58.67

4 62.96 125.77

6 187.74 375.47

preferred flow rate

* ¼" pitch slope based on Manning’s Formula with friction factor N=0.012"

For Lint Applications

Striem recommends the following sizing guidelines.

Step 1 of 2: Select interceptor with appropriate drain line pipe size.

For example, if your primary drain line is 4", choose models with standard 4" connections (models PS-50 and up).

Step 2 of 2: Complete formula, then select interceptor with appropriate
lint capacity based on maintenance interval.

30-Day Professional Maintenance Interval Weekly Do-It-Yourself Maintenance Interval

Gallons Number 30 Gallons Recommended Gallons Number 7 Gallons Recommended
of Lint of Days of Lint Prospector (-S) of Lint of Days of Lint Prospector (-B)
Per Day Machines Per Per Day Machines Per
Month Model Week Model

0.0495 5 30 7.4 PS-15-S 0.0495 6 7 2 PS-15-B
30 10.4 PS-25-S 7 3 PS-25-B
0.0495 7 30 17.8 PS-35-S 0.0495 9 7 5 PS-35-B
30 26.7 PS-50-S 7 8 PS-50-B
0.0495 12 30 62.4 PS-125-S 0.0495 14 7 10 PS-125-B
30 209.4 PS-275-S 7 13 PS-275-B
0.0495 18 0.0495 23

0.0495 42 0.0495 29

0.0495 141 0.0495 38

NOTE 1: Average wash cycle time of a commercial laundr y machine = 42 minutes. Average business hours of a commercial laundr y facility = 16
hours. Average lint output per wash of 20-60 lb. commercial laundr y machine = 0.009 gallons (1.14 oz.). Average wash cycles per day of a commercial
laundr y machine = 5.5 cycles. Lint output may var y based on clothes type. For example, towels and linens yield high lint levels while clothing will
yield lower lint levels. Data developed by Striem with assistance from Alliance Laundr y Systems (www.unimac.com) and the Coin Operated Laundr y
Association (www.coinlaundr y.org)

NOTE 2: Periodic maintenance by professional may be required to fully pump down the interceptor.

11 www.striemco.com | Made in the USA | Striem Catalog

HLT/B Series specifications & submittals
formats available online
under counter solids interceptors .pdf .doc .dwg .rfa

Features: lightweight HDPE body | handles temperatures up to 190º F | 4" threaded and gasket-sealed port | removable type 304
stainless steel basket with 3/32" perforations | for hair and lint applications

Specifications

Striem Model Liquid Access Plain End Body Rough-in Dimensions (in.) Outlet Weight
Capacity Location Connections Inlet (lbs.)
HLT-1176-1
HLT-1176-2 (gal.) Top 1 ½ OD H A B C D Dry Wet
HLB-1176-1 Top 2
HLB-1176-2 0.5 Bottom 8 ½ 8 ¾ 1 5 ⁄8 7 1 ⁄8 5 3 ⁄8 3 3 ⁄8 5 9
0.5 Bottom 1 ½ 1 5 ⁄8 7 1 ⁄8 5 3 ⁄8 3 3 ⁄8 5 9
0.5 2 8 ½ 8 ¾ 3 3 ⁄8 5 3 ⁄8 7 1 ⁄8 1 5 ⁄8 5 9
0.5 3 3 ⁄8 5 3 ⁄8 7 1 ⁄8 1 5 ⁄8 5 9
8 ½ 8 ¾

8 ½ 8 ¾

HLT-1176 HLB-1176 HLT-1176 Installation HLB-1176 Installation

D D 7" Min.
B B
HLT-1176-1 Shown 7" Min.
H H
C C
A A
OD
OD

USI Series

under counter solids interceptors

Features: lightweight HDPE body | handles temperatures up to 190º F | gasket-sealed cover with hand threaded clamps | removable
HDPE bucket with 3/16" filter screen | for plaster, clay and heavy solids

Specifications

Striem Model Liquid Access Plain End Body Rough-in Dimensions (in.) Outlet Weight
Capacity Location Connections Inlet (lbs.)
USI-1180-1
USI-1180-2 (gal.) Top 1 ½ OD CD H A B C D Dry Wet
USI-1184-1 Top 2
USI-1184-2 1.2 Bottom 7 11 11 ¾ 4 3 ⁄8 7 3 ⁄8 8 3 ⁄8 3 3 ⁄8 8 18
1.2 Bottom 1 ½
1.2 2 7 11 11 ¾ 4 3 ⁄8 7 3 ⁄8 8 3 ⁄8 3 3 ⁄8 8 18
1.2
7 11 11 ¾ 3 3 ⁄8 8 3 ⁄8 7 3 ⁄8 4 3 ⁄8 8 18

7 11 11 ¾ 3 3 ⁄8 8 3 ⁄8 7 3 ⁄8 4 3 ⁄8 8 18

USI-1180 USI-1184 USI-1180 Installation USI-1184 Installation

CD OD

B D D 11" Min.
B
A H
OD C H
C
A 11" Min.
DRAIN PLUG
CD USI-1180-1 Shown

www.striemco.com | Made in the USA | Striem Catalog 12

Prospector™ (-B) Series

basket style solids interceptors

Prospector™ Basket-Style Solids PS-35-B PS-275-B PS-125-B
Interceptors provide a removable PS-15-B PS-25-B PS-50-B
filter basket to allow for DIY
(do-it-yourself) maintenance and
to catch valuables that need
to be retrieved. Intermittent
professional maintenance may
be required.

Features: above grade or buried PS-125-B Shown
installations | non-corrosive polypropylene
filter | easy to carry HDPE design | 6
models with sediment capacities from
2 gallons up to 197 gallons | removable
filter basket | TeleGlide™ field adjustable
risers | models PS-50-B through PS-
275-B suitable for exterior installations

Prospector™(-B) Covers

Covers are provided with water/air tight gasket seal and are designed to fit tightly into a key-fit frame.

indoor covers outdoor covers

16" 24" 24" 24"

BOLTED BOLTED BOLTED PICKABLE CAST
POLYPROPYLENE COMPOSITE COMPOSITE – TRAFFIC IRON – H20 (optional)

PS-15-B, PS-25-B PS-35-B, PS-50-B PS-50-B (optional), PS-50-B, PS-125-B, PS-275-B
2,000 lbs. pedestrian load rating 2,000 lbs. pedestrian load rating PS-125-B, PS-275-B 16,000 lbs. H20 load rating
16,000 lbs. highway load rating

13 www.striemco.com | Made in the USA | Striem Catalog

specifications & submittals
formats available online
.pdf .doc .dwg .rfa

Specifications

Capacity and Rating Pipe Sizes Rough-in Dimensions (in.) Weight (lbs.)

Striem Total *No. of Plain End SCH.40 Optional Body Inlet/Outlet
Model Liquid Washing Male W Adapter
(gal.) Basket Thread Adjustability Dry Wet
Capacity (gal.) Machines Standard Optional (no A B (add to B & H)
Plain
charge) L H

PS-15-B 16 2 6 2 3 2, 3 25 19 14 ¼ 10 4 ¼ n/a 32 165
39 223
PS-25-B 22 3 9 3 2 2, 3 27 21 15 10 ¾ 4 ¼ n/a 86 378
109 543
PS-35-B 35 5 14 3 2, 4 2, 3, 4 33 25 25 15 10 3 ½ 148 1,191
259 2,553
PS-50-B 52 8 23 4 2, 3 2, 3, 4 37 28 28 ½ 18 10 ½ 3 ½

PS-125-B 125 10 29 4 6 4 46 32 38 ½ 26 12 ½ 6

PS-275-B 275 13 basket/197 screen 38 4 6 4 68 33 ½ 51 ½ 38 13 ½ 6

* Based on 7 day maintenance interval.

PS-15-B PS-25-B PS-35-B PS-50-B PS-125-B PS-275-B

Miscellaneous Options *Basket and screen combo
configurations for PS-275-B

TeleGlide™ Riser Order Guide

High Water *Upgrade to *Upgrade to Desired Riser Height (in.)
Anchor Kit Highway H-20 Rated
Striem Pickable Cast PS-15-B PS-35-B PS-125-B Risers Needed
Model Rated Bolted Iron Cover PS-25-B PS-50-B PS-275-B
Composite Cover 16 Series
Riser (SR-16)
Part # Part # Price Part # Price >2 1 ⁄8 - 16 n/a n/a 24 Series Adapter
n/a 0 - 3½ 0-6
PS-15-B n/a n/a n/a 24 Series
PS-25-B Short Riser (SR24)
PS-35-B n/a n/a n/a n/a >3½ - 22 >6 - 24
PS-50-B 24 Series
PS-125-B n/a n/a n/a Long Riser (LR24)
PS-275-B 24 Series Short +
AK1 C24-H n/c C24-HP n/c n/a >22 - 37 >24 - 39 Short (SR24 + SR24)
24 Series Short +
AK1 included C24-HP n/c n/a n/a >39 - 43 Long (SR24 + LR24)
24 Series Long +
AK1 included C24-HP(2) n/c Long (LR24 + LR24)

* When ordered with solids interceptor. n/a n/a >43 - 58

n/a n/a >58 - 72

Polypropylene Basket Filter Options (actual sizes shown)

Buttons, Change, Gravel Lint and Hair, Fish Scales, Gravel and Sand Precious Metals, Sand
Coarse – 0.3" x 0.27" opening Medium – 0.1" x 0.08" opening Fine – 0.03" x 0.025" opening

–C –M –F
14
NOTE 1: Select appropriate basket filter suffix in step 3 to complete model number.
NOTE 2: Subtract 1" from adapter and riser range when PS-35-B is ordered with 4" connections.
NOTE 3: PS-275-B has two covers requiring a set of two risers when ordered.

www.striemco.com | Made in the USA | Striem Catalog

Prospector™ (-S) Series

screen style solids interceptors

Prospector™ Screen-Style PS-35-S PS-275-S PS-125-S
Solids Interceptors provide PS-15-S PS-25-S PS-50-S
a removable filter screen to
allow for professional pumping
maintenance.

Features: above grade or buried PS-125-S Shown
installations | non-corrosive polypropylene
filter | easy to carry HDPE design | 6
models with sediment capacities from
8 gallons up to 210 gallons | removable
filter screen | TeleGlide™ field adjustable
risers | models PS-50-S through PS-275-S
suitable for exterior installations

Prospector™(-S) Covers

Covers are provided with water/air tight gasket seal and are designed to fit tightly into a key-fit frame.

indoor covers outdoor covers

16" 24" 24" 24"

BOLTED BOLTED BOLTED PICKABLE CAST
POLYPROPYLENE COMPOSITE COMPOSITE – TRAFFIC IRON – H20 (optional)

PS-15-S, PS-25-S PS-35-S, PS-50-S PS-50-S (optional), PS-50-S, PS-125-S, PS-275-S
2,000 lbs. pedestrian load rating 2,000 lbs. pedestrian load rating PS-125-S, PS-275-S 16,000 lbs. H20 load rating
16,000 lbs. highway load rating

15 www.striemco.com | Made in the USA | Striem Catalog

specifications & submittals
formats available online
.pdf .doc .dwg .rfa

Specifications

Capacity and Rating Pipe Sizes Rough-in Dimensions (in.) Weight (lbs.)

Striem Total Plain End SCH.40 Optional Body Inlet/Outlet Adapter
Model Liquid Solids *No. of Male W AB Adjustability
(gal.) Thread (add to B & H)
Capacity Washing Optional (no Dry Wet
(gal.) Machines Standard Plain
charge) L H

PS-15-S 16 8 5 2 3 2, 3 25 19 14 ¼ 10 4 ¼ n/a 29 162
35 219
PS-25-S 22 11 7 3 2 2, 3 27 21 15 10 ¾ 4 ¼ n/a 83 375
106 550
PS-35-S 35 17.5 12 3 2, 4 2, 3, 4 33 25 25 15 10 3 ½ 140 1,183
270 2,564
PS-50-S 52 26 18 4 2, 3 2, 3, 4 37 28 28 ½ 18 10 ½ 3 ½

PS-125-S 125 62.5 42 4 6 4 46 32 38 ½ 26 12 ½ 6

PS-275-S 275 210 141 4 6 4 68 33 ½ 51 ½ 38 13 ½ 6

* Based on 30-day maintenance interval.

PS-15-S PS-25-S PS-35-S PS-50-S PS-125-S PS-275-S

Miscellaneous Options TeleGlide™ Riser Order Guide

High Water *Upgrade to *Upgrade to Desired Riser Height (in.)
Anchor Kit Highway H-20 Rated
Striem Pickable Cast PS-15-S PS-35-S PS-125-S Risers Needed
Model Part # Rated Bolted Iron Cover PS-25-S PS-50-S PS-275-S
n/a Composite Cover 16 Series
PS-15-S n/a Riser (SR-16)
PS-25-S n/a Part # Price Part # Price >2 1 ⁄8 - 16 n/a n/a 24 Series Adapter
PS-35-S AK1 n/a 0 - 3½ 0-6
PS-50-S AK1 n/a n/a 24 Series
PS-125-S AK1 Short Riser (SR24)
PS-275-S n/a n/a n/a >3½ - 22 >6 - 24
24 Series
n/a n/a Long Riser (LR24)
24 Series Short +
C24-H n/c C24-HP n/c n/a >22 - 37 >24 - 39 Short (SR24 + SR24)
24 Series Short +
included C24-HP n/c n/a n/a >39 - 43 Long (SR24 + LR24)
24 Series Long +
included C24-HP(2) n/c Long (LR24 + LR24)

* When ordered with solids interceptor. n/a n/a >43 - 58

n/a n/a >58 - 72

Polypropylene Screen Filter Options (actual sizes shown)

Buttons, Change, Gravel Lint and Hair, Fish Scales, Gravel and Sand Precious Metals, Fine Sand
Coarse – 0.3" x 0.27" opening Medium – 0.1" x 0.08" opening Fine – 0.03" x 0.025" opening

–C –M –F
16
NOTE 1: Select appropriate screen filter suffix in step 3 to complete model number.
NOTE 2: Subtract 1" from adapter and riser range when PS-35-S is ordered with 4" connections.
NOTE 3: PS-275-S has two covers requiring a set of two risers when ordered.

www.striemco.com | Made in the USA | Striem Catalog

Settler™ Series CB-275-G CB-275-S
CB-125-G CB-125-S
catch basins
CB-50-G CB-50-S
Settler™ Catch Basins allow sand and
sediment to collect from the bottom up and
may drain either through a drain line (-S
models) or directly through a top inlet grate (-G
models). An optional removable filter basket
may be ordered with –G models to allow for
intermittent DIY (do-it-yourself) maintenance
and to catch valuables that need to
be retrieved.

Features: for buried installations | easy to carry HDPE
design | 6 models from 50 to 275 gallons | TeleGlide™
field adjustable riser system | suitable for exterior
installations

Cutaway of CB-275-G Shown

Settler™ Covers

Covers are provided with water/air tight gasket seal and are designed to fit tightly into a key-fit frame.

outdoor covers and grate

24" 24" 28"

BOLTED PICKABLE CAST IRON PICKABLE
COMPOSITE – TRAFFIC – H20 (optional) GRATE – H20

CB-50-S, CB-125-S, CB-275-S CB-50-S, CB-125-S, CB-275-S CB-50-G, CB-125-G, CB-275-G
16,000 lbs. highway load rating 16,000 lbs. H20 load rating 16,000 lbs. H20 load rating

17 www.striemco.com | Made in the USA | Striem Catalog

specifications & submittals
formats available online
.pdf .doc .dwg .rfa

Specifications

Capacity Pipe Sizes Rough-in Dimensions (in.) Weight (lbs.)

Striem Total Optional Plain End SCH.40 Optional Body Inlet/Outlet Adapter Dry Wet
Model Liquid Basket Standard Optional Male Thread W AB Adjustability
(gal.) Capacity (no charge) (add to B & H)
(gal.) L H

CB-50-S 52 n/a 4 2, 3 2, 3, 4 37 28 28 ½ 18 10 ½ 3 ½ 86 520
CB-50-G 4 2, 3 2, 3, 4 37 28
CB-125-S 52 7 4 46 32 30 1 ⁄8 18 12 1 ⁄8 3 ½ 187 621
CB-125-G 4 6 4 46 32
CB-275-S 125 n/a 4 6 4 68 33 ½ 38 ½ 26 12 ½ 6 123 1,166
CB-275-G 4 6 4 68 33 ½
125 7 6 4 40 1 ⁄8 26 14 1 ⁄8 6 213 1,256

275 n/a 51 ½ 38 13 ½ 6 218 2,532

275 7 ea. (includes 2) 53 1 ⁄8 38 15 1 ⁄8 6 398 2,692

* Smaller sizes available upon request.

CB-50-S CB-50-G CB-125-S CB-125-G CB-275-S CB-275-G

Miscellaneous Options TeleGlide™ Riser Order Guide

Optional High Water *Upgrade to Desired Riser Height (in.)
Basket Anchor Kit H-20 Rated
Striem Pickable Cast CB-50-S CB-125-S, CB-125-G Risers Needed
Model Part # Part # Iron Cover CB-50-G CB-275-S, CB-275-G
n/a
CB-50-S AK1 Part # 0 - 3½ 0-6 24 Series Adapter
CB-50-G BCB-7 AK1
CB-125-S n/a AK1 C24-HP >3½ - 22 >6 - 24 24 Series
CB-125-G AK1 n/a >22 - 37 >24 - 39 Short Riser (SR24)
CB-275-S BCB-7 AK1 >39 - 43
CB-275-G n/a AK1 C24-HP n/a >43 - 58 24 Series
n/a n/a >58 - 72 Long Riser (LR24)
BCB-7(2) n/a
C24-HP(2) 24 Series Short +
n/a Short (SR24 + SR24)

* When ordered with catch basin. 24 Series Short +
Long (SR24 + LR24)

24 Series Long +
Long (LR24 + LR24)

BCB-7

Optional 7 gal. sediment
basket with coarse filter
(0.3" x 0.27" openings) for
initial separation of large
solids. (weighs 10 lbs.).
Must be ordered with
catch basin.

NOTE: CB-275-S/CB-275-G have two covers requiring a set of two risers when ordered.

www.striemco.com | Made in the USA | Striem Catalog 18

Chemical Waste Tanks Product Selection

sizing guidelines

Did You Know? EPA Guidelines for Acceptable pH Levels
Plumbing and pretreatment codes
require treatment of acidic waste, 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0
but make no mention of caustic waste.
Caustic waste can be just as harmful ACID 7.0 NEUTRAL ALKALINE
and must be considered when choosing
the neutralization approach. Stomach Acid Limes Apples Beer Milk Egg Whites Bleach Drain Cleaner

Step 1 of 6: Determine Characteristics of the Waste Stream

a) If acidic – proceed to step 2. b) If caustic or caustic and acidic, reagent injection system needed.

Step 2 of 6: Choose Neutralization System Type

Continuous (go to step 3) or Batch (contact Striem)

Use • Flow is relatively constant and not characterized by large surges. Use • Flow is discharged in large batches or there are large
When When fluctuations in flow.
• Influent chemistry is relatively constant and not characterized by
large swings in pH. • Influent chemistry is characterized by large swings in pH.

• Effluent chemistry is not critical, such as the first stage in a • Effluent makeup is critical and pH must be kept within
multi-stage process. specific parameters.

Examples High school, college, and professional labs Examples Manufacturing, pharmaceutical, and food processing

Step 3 of 6: Determine Size of Tank

For all labs, use "Sizing by Sinks" table below to determine tank size to provide adequate residence time for acid neutralization via limestone treatment.
Residence times vary significantly based on strength of acid. For more information on required contact time, see "Contact Time" table below.

Sizing by Sinks Contact Time For Limestone Neutralization of Acids*

Per ASPE Plumbing Engineering Design Handbook Volume 3 *Data provided via third party test requested by Striem.

Number of Tank Size Number of Tank Size Number of Tank Size
Lab Sinks (Gal.) Lab Sinks (Gal.) Lab Sinks (Gal.)

2 5 30 108 150 500
4 15 40 150 175 550
8 30 50 175 200 650
16 55 60 200 300 1,200
22 75 75 275 500 2,000
27 90 110 360 600 3,000

NOTE: Table assumes a “worst case scenario” influent pH of 2 and provides
3 hours residence time at a flow rate of 1 GPH per fixture. See "Contact

Time" table for appropriate limestone contact time.

Step 4 of 6: Consider Solids Pretreatment

Most lab waste contains solids that can clog the acid waste drain system. It is recommended that a solids interceptor be installed in front of
centralized neutralization tanks. See the Prospector™ Series on p. 13-16 for more information.

Step 5 of 6: Determine Tank Material

Striem offers neutralization tanks in both polyethylene and polypropylene. While polyethylene is adequate for most projects, it’s important to
consider the chemical resistances of polyethylene and polypropylene.

Step 6 of 6: Consider pH Monitoring

All acid waste streams should be monitored. The monitor acts as both an alarm in the event of system failure and to indicate when the
neutralization media needs to be replaced. See Striem’s Command Center™ on p. 25-26.

19 www.striemco.com | Made in the USA | Striem Catalog

Lab Rat™ Series specifications & submittals
formats available online
under counter neutralization tanks .pdf .doc .dwg .rfa

The Lab Rat™ Series of under-counter neutralization tanks for LB-5 LB-2
school labs is the most versatile design in the industry with 5-Gallon 2-Gallon
standard top or side inlet connections, hand-threaded cover
and adaptability for 1½" or 2" drain lines.

Features: 2 and 5 gallons | for under counter sink installations | gasketed top
with captive hand-thread hardware | easy to carry HDPE design | combination
1½" or 2" FPT connections standard | built-in top and side inlet options |
optional top vent connection (LB-5 only) | internal sewer gas seal

Specifications

Rough-in Dimensions (in.) Pipe Connections Weight (lbs.)

Striem Liquid Sizing By Body Side Inlet/Outlet Top Inlet Standard FPT Outlet Optional Dry Wet
Model Capacity Number Connections Location Top Vent Wet with
Connection 6
(gal.) of Sinks per ANSI 11 Limestone
B1.20.1
L WH A B C D 23 28
LB-2 2 1 1 ½ or 2 Top or Side n/a 58 80
LB-5 5.3 2 9 9 10 1 ⁄8 7 2 7 2
14 14 12 5 ⁄8 9 2 ½ 11 ½ 2 ½ 1 ½ or 2 Top or Side included

LB-2 LB-5

Side View Top View Side View Top View

Limestone Application Specific Details

Striem Model Load (lbs.) Part # LB-2 Elevated LB-5 Elevated
LB-2 25 LS-25
LB-5 50 LS-50

Optional
Vent

When loading Lab 4" Plain End 4" Plain End
Rat™ Series tanks with Pipe by Others Pipe by Others
limestone, use Striem Cut to Size Cut to Size
limestone chips 2 - 3"
in size with a calcium LB-2 with Limestone Serving LB-5 with Limestone Serving
carbonate content (CACO3) Condensate Line Condensate Line
of 90% or greater. When
limestone is depleted High Efficiency High Efficiency
contact a waste specialist Water Heater or Water Heater or
to evacuate basins. Condensing Boiler Condensing Boiler

Condensate Line Condensate Line
Up to 2 GPH Up to 6 GPH

www.striemco.com | Made in the USA | Striem Catalog 20

Lab Basin™ Series

neutralization tanks

Lab Basin™ Neutralization Tanks LB-35 LB-275 LB-125
are designed for above or below LB-15 LB-25 LB-50
grade installation, providing an
excellent value for the most
common industry neutralization
tanks sizes from 15 gallons to
275 gallons.

Features: 15 through 275 gal. | easy to Cutaway of LB-275 Shown
carry HDPE design | above or below grade
installations | TeleGlide™ field adjustable
riser system | models LB-50 through LB-
275 suitable for exterior installations

Lab Basin™ Covers

Covers are provided with water/air tight gasket seal and are designed to fit tightly into a key-fit frame.

indoor covers outdoor covers

16" 24" 24"

BOLTED BOLTED BOLTED
POLYPROPYLENE COMPOSITE COMPOSITE – TRAFFIC

LB-15, LB-25 LB-35, LB-50 LB-50, LB-125, LB-275
2,000 lbs. pedestrian load rating 2,000 lbs. pedestrian load rating 16,000 lbs. highway load rating

21 www.striemco.com | Made in the USA | Striem Catalog

specifications & submittals
formats available online
.pdf .doc .dwg .rfa

Made To Order – Submittal Required

Specifications

Recommended Rough-in Dimensions (in.) Weight (lbs.)
Pipe Size
Sizing By Limestone Liquid
Striem Number Required Holding Inlet & Body Inlet/Outlet Vent Adapter
Model of Sinks (lbs.) Gallons Outlet W AB CD Adjustability
Vent (add to Dry Wet

L H E H & B)

LB-15 4 200 15 2 2 25 19 14 ¼ 10 4 ¼ 11 ½ 2 ¼ 5 ½ n/a 28 166
LB-25 3 n/a 31 220
LB-35 6 275 22 3 2 27 21 15 10 ¾ 4 ¼ 11 ½ 3 ½ 6 ¼ 3 ½ 77 369
LB-50 4 3 ½ 92 525
LB-125 9 450 35 4 2 33 25 25 15 10 17 8 7 ½ 6 130 1,171
LB-275 4 6 230 2,313
15 650 52 2 37 28 28 ½ 18 10 ½ 20 8 ½ 9

35 1,550 125 2 46 32 38 ½ 26 12 ½ 28 10 ½ 12

75 3,150 275 2 68 33 ½ 51 ½ 38 13 ½ 40 11 ½ 16

LB-15 LB-25 LB-35 LB-50 LB-125 LB-275

Product Selection: Add For Tank And Options TeleGlide™ Riser Order Guide

Miscellaneous Options Desired Riser Height (in.)

Striem High Water Limestone *Upgrade to LB-15 LB-35 LB-125 Risers Needed
Model Anchor Kit Highway Rated Bolted LB-25 LB-50 LB-275
Part # 16 Series
LB-15 Part # LS-50 (4) Composite Cover Riser (SR-16)
LB-25 n/a LS-50 (6)
LB-35 n/a LS-50 (9) Part # Price >2 1 ⁄8 - 16 n/a n/a
LB-50 n/a LS-50 (13)
LB-125 AK1 LS-50 (31) n/a n/a 0 - 3½ 0-6 24 Series Adapter
LB-275 AK1 LS-50 (63)
AK1 n/a

n/a n/a >3½ - 22 >6 - 24 24 Series
Short Riser (SR24)
C24-H n/c

included n/a >22 - 37 >24 - 39 24 Series
Long Riser (LR24)
included
24 Series Short +
* When ordered with neutralization tank. n/a n/a >39 - 43 Short (SR24 + SR24)

n/a n/a >43 - 58 24 Series Short +
Long (SR24 + LR24)

n/a n/a >58 - 72 24 Series Long +
Long (LR24 + LR24)
For monitoring package see Command
Center™ on pages 22-23

NOTE 1: Subtract 1" from adapter and riser range when LB-35 is ordered with 4" connections. 22
NOTE 2: LB-275 has two covers requiring a set of two TeleGlide™ risers when ordered.

www.striemco.com | Made in the USA | Striem Catalog

NT Series Better Below
Grade Value
neutralization tanks See Lab Basin™
Models on

p. 18-19

Specifications

Capacity (gal.) Recommended Rough-in Dimensions (in.) Adapter Weight (lbs.)

Sizing Pipe Size In/Out Vent In/Out Adjust-
C/L to C/L to C/L to ability
Striem by Body Bottom Bottom Cover (add to Above Grade Below Grade Lab Basin™
Model of Tank of Tank HB & B) Equivalent
No. of Total Liquid Inlet /
Sinks Tank Holding Outlet Vent

ID OD HA HB A B C* Dry Wet Dry Wet

NT-30H 8 40 30.4 3 2 22 28 24 ½ 33 20 21 13 3 ½" 40 294 27 281 LB-35
NT-55 12 55 41.1 3 2
NT-55H 16 70 55 3 2 22 28 36 ½ 43 27 29 16 6" 50 393 67 410 LB-50
NT-100 27 100 90.6 4 2
NT-100H 32 150 117.6 4 2 24 30 36 ½ 43 ¾ 30 32 13 ¾ 6" 70 529 105 564 LB-50
NT-150 32 150 117.6 4 2
NT-150H 41 200 154.2 4 2 28 34 42 ½ 49 ¾ 36 38 13 ¾ 6" 85 841 119 875 LB-125
NT-200 41 200 154.2 4 2
NT-200H 63 275 209.9 4 2 31 37 48 5 ⁄8 56 ½ 38 40 17 ¾ 6" 100 1,081 134 1,115 LB-125
NT-275 63 275 209.9 4 2 31 37 48 5 ⁄8 56 ½ 38 40 17 ¾ 6" 100 1,081 134 1,115 LB-125
NT-275H 75 350 275 4 2 36 40 48 ½ 55 ¾ 38 40 17 ¾ 6" 125 1,411 214 1,500 LB-275
NT-350 75 350 275 4 2
NT-350H 107 440 350 4 2 36 40 48 ½ 56 ½ 38 40 17 ¾ 6" 125 1,411 214 1,500 LB-275
NT-500 135 500 450.5 4 2
NT-500H 150 650 501.1 4 2 42 48 48 ½ 56 ½ 38 40 17 ¾ 6" 160 1,911 253 2,004 LB-275
NT-1200 291 1,360 1,200 4 2
NT-1500 326 1,500 1,304 4 2 42 48 48 ½ 56 ½ 38 40 17 ¾ 6" 160 1,911 253 2,004 LB-275

48 52 48 ½ 56 ½ 38 40 17 ¾ 6" 200 2,494 329 2,623 LB-275

48 52 48 ½ 56 ½ 38 40 17 ¾ 6" 200 2,494 329 2,623 LB-275

52 58 48 ½ 56 ½ 41 43 14 ¾ 6" 210 3,129 310 3,229 LB-275 (2 in series)

52 58 60 ½ 68 ½ 52 54 15 ¾ 6" 225 3,982 506 4,263 LB-275 (2 in series)

48 54 84 ½ 92 ½ 70 76 21 ¾ 6" 300 4,479 455 4,634 LB-275 (3 in series)

69 75 87 94 ¾ 76 78 18 6" 500 10,216 1,004 10,720 LB-275 (4 in series)

73 77 ¾ 85 ½  93 ¼ 74 76 18 ½ 6" 650 11,400 1,040 11,789 LB-275 (5 in series)

* Inlet/outlet centerline to cover dimensions listed are for below grade (-B) models only.

Above Grade Below Grade

NT Tank Covers

Covers are provided with water/air tight gasket seal and are designed to fit tightly into a key-fit frame.

indoor covers outdoor covers

8" 15" 24"

BOLTED BOLTED BOLTED
POLYPROPYLENE POLYPROPYLENE COMPOSITE – TRAFFIC

NT-30H, NT-55 NT-55H through NT-2000 All -B Models
non-load manway with non-load manway with 16,000 lbs. highway load rating
8" threaded access 15" threaded access

NOTE: Add ¾" measurement to A, C, and HB dimensions when models NT-30H through NT-150 are ordered with anchor flange.

23 www.striemco.com | Made in the USA | Striem Catalog

specifications & submittals
formats available online
.pdf .doc .dwg .rfa

Made To Order – Submittal Required

Tank And Limestone

Polyethylene Polypropylene Add for Limestone

Above Grade Below Grade Above Grade Below Grade Part # Load
(lbs.)
Striem Model Striem Model Striem Model Striem Model

NT-30H-A-PE NT-30H-B-PE NT-30H-A-PP NT-30H-B-PP LS-50 (8) 400
NT-55-A-PE NT-55-B-PE NT-55-A-PP NT-55-B-PP LS-50 (10) 500
NT-55H-A-PE NT-55H-B-PE NT-55H-A-PP NT-55H-B-PP LS-50 (14) 700
NT-100-A-PE NT-100-B-PE NT-100-A-PP NT-100-B-PP LS-50 (22) 1,100
NT-100H-A-PE NT-100H-B-PE NT-100H-A-PP NT-100H-B-PP LS-50 (29) 1,450
NT-150-A-PE NT-150-B-PE NT-150-A-PP NT-150-B-PP LS-50 (29) 1,450
NT-150H-A-PE NT-150H-B-PE NT-150H-A-PP NT-150H-B-PP LS-50 (38) 1,900
NT-200-A-PE NT-200-B-PE NT-200-A-PP NT-200-B-PP LS-50 (38) 1,900
NT-200H-A-PE NT-200H-B-PE NT-200H-A-PP NT-200H-B-PP LS-50 (52) 2,600
NT-275-A-PE NT-275-B-PE NT-275-A-PP NT-275-B-PP LS-50 (52) 2,600
NT-275H-A-PE NT-275H-B-PE NT-275H-A-PP NT-275H-B-PP LS-50 (66) 3,300
NT-350-A-PE NT-350-B-PE NT-350-A-PP NT-350-B-PP LS-50 (68) 3,400
NT-350H-A-PE NT-350H-B-PE NT-350H-A-PP NT-350H-B-PP LS-50 (86) 4,300
NT-500-A-PE NT-500-B-PE NT-500-A-PP NT-500-B-PP LS-50 (110) 5,500
NT-500H-A-PE NT-500H-B-PE NT-500H-A-PP NT-500H-B-PP LS-50 (130) 6,500
NT-1200-A-PE NT-1200-B-PE LS-50 (258) 12,900
NT-1500-A-PE NT-1500-B-PE n/a n/a LS-50 (310) 15,500
NT-2000-A-PE NT-2000-B-PE n/a n/a LS-50 (444) 22,200
n/a n/a

TeleGlide™ Riser Order Guide

Desired Riser Height (in.)

NT-30H all other Risers Needed For monitoring package see Command
NT models Center™ on pages 25-26

0 - 3½ 0-6 24 Series Adapter
>3½ - 22 >6 - 24
>22 - 37 >24 - 39 24 Series
>39 - 43 Short Riser (SR24)
n/a >43 - 58
n/a >58 - 72 24 Series
n/a Long Riser (LR24)

24 Series Short +
Short (SR24 + SR24)

24 Series Short +
Long (SR24 + LR24)

24 Series Long +
Long (LR24 + LR24)

NOTE 1: 6" connections are not available with NT-30H through NT-100. 24
NOTE 2: NT-1200, NT-1500 and NT-2000 have two covers requiring a set of two risers when ordered.

www.striemco.com | Made in the USA | Striem Catalog

Command Center™

pH monitoring package

The Command Center™ is the industry's only ”ready-to-use” Touchscreen Interface
pH monitoring package. Simply install the pH sensor and supply
power — that's it. The system is pre-programmed to alarm at low
and high pH values (6-9 pH) and can be adjusted as required. Up to
1 year of recorded data can be stored to the micro SD card (included) for
easy data transfer. Customizations are simple using the easy-to-navigate
menus on the color touchscreen display.

Features: ready-to-use: pre-programmed audio/visual alarm set points | touchscreen:
bright, easy-to-navigate 3.5" color touch-screen display | large memory storage: includes
two formatted micro SD cards – each card stores approximately 1 year of history | exports
to Excel: recorded data logs, alarm history, and trend data export to Excel for easy data
management | remote access: use ethernet connection to remotely manage the Command
Center™ through your company’s building management system | fresh water flush: pre-
programmed with digital output to power solenoid valve for fresh water flush if pH approaches
high/low limits | NEMA 4X lockable weather proof enclosure – temperature resistant from
32º F to 122º F | sensor maintenance and calibration kit included (CC-K) | 120 V AC power
supply required | all components are UL listed | sensor can be mounted up to 3,000 feet from
Command Center™

Command Center™
with SPK-A above grade sen-

sor placement kit

Solenoid Valve
(by others)

Cutaway of Lab Basin™
LB-275 installed above grade
with Command Center™ and
optional limestone

25 www.striemco.com | Made in the USA | Striem Catalog

specifications & submittals
formats available online
.pdf .doc .dwg .rfa

Step 1 of 3: Select Your System

Command Center™ with 1 Sensor Command Center™ with 2 Sensors

CC-1 (10 ft. of cable) CC-2 (10 ft. of cable)

includes includes CC-K Sensor Maintenance and
CC-K (qty. 1) CC-K (qty. 1) Calibration Kit (see step 3 below) is
included with order of CC-1 or CC-2.

Step 2 of 3: Select Sensor Placement Kit

Above Grade Below Grade

SPK-A SPK-B

For installation of sensor in For installation of sensor in below grade outlet
above grade outlet drainage line drainage line. Exclusive quick disconnect feature
allows for easy cleaning or replacement of probe
Kit Contents (depicted below) from finished grade Quick
Disconnect
9" x 9" sensor port with threaded Kit Contents (depicted below)
Cable Grip
and gasketed cover access. Top assembly with dual quick-disconnect
4" plain end connections and adapter components for 2" and
4" PVC connection
Above Grade with Effluent Sensor
pH sensor port with 4" plain end connections
Flow Command 50 ft. of sensor wire with single quick
Center™ disconnect clip

Lab Basin™ Heavy duty cleanout with sidewall Sensor
1½" and 4" PVC pipe cut to length (by others) And Cable
Come with
Below Grade with Effluent Sensor Command
Center™
Flow Command
Center™

Lab Basin™

Stabilizing
Mount for pH

Probe

Step 3 of 3: Select Accessories and Replacement Components (Optional)

Replacement Sensor with Additional Sensor Cable Quick Disconnect Clip Sensor Maintenance and Calibration Kit
10 ft. of Cable and Quick (for use with below grade (required when ordering
Disconnect Clip SPK-B, quick disconnect above grade CC-PHW for 500 mL 7 pH buffer solution, 500 mL 10 pH buffer solution,
clip not required) SPK-A) 500 mL cleaning solution, sensor brush, gloves, salt bridge,
standard cell solution

CC-K (qty. 1) included
standard with order of
Command Center
(CC-1 or CC-2)

CC-PH CC-PHW CC-PHWC CC-K

www.striemco.com | Made in the USA | Striem Catalog 26

Bio Basin™ Series

decontamination tanks

Chapter 8 of the UPC and IPC require the pretreatment of
liquid wastes likely to damage the building’s drain, waste
and vent system, public sewer or ground/surface waters.
According to the American Institute of Architects (AIA)
“water drainage must be contained and disposed of safely
to ensure that it does not enter hospital or community
drainage systems.” The American National
Standards Institute Standard (ANSI Z538.1)
says “consideration should be given to the
proper disposal of waste
flushing fluids from operating
emergency eye wash and
shower equipment.” Other
local codes may apply.

Striem recommends the following steps for sizing a decontamination tank:

Number of Supply Line Rinse Time Size of Supply Line Flow Rates
Fixtures (showers Flow Rate of (15-20 Tank in
Each Fixture minutes Gallons velocity ½ ¾
or eyewash (see table right) typical) 6.64 GPM
stations) 4 Ft./sec 3.77 GPM 9.96 GPM
13.29 GPM
Sizing Sample: 6 Ft./sec 5.66 GPM 16.61 GPM
1. A hospital with two emergency showers, each with a ¾" supply line carrying a
8 Ft./sec 7.54 GPM
flow rate of 9.96 GPM. 2 fixtures x 9.96 GPM = 19.92 GPM
2. 19.92 GPM x 15 minutes = 298.8 gallons 10 Ft./sec 9.43 GPM
3. Select Bio Basin™ model BB-500 (500 liquid holding gallons)

Bio Basin™ Covers

Covers are provided with water/air tight gasket seal and are designed to fit tightly into a key-fit frame.

indoor covers outdoor covers

15" 24" 24"

BOLTED BOLTED PICKABLE CAST IRON
POLYPROPYLENE COMPOSITE – TRAFFIC – H20 (optional)

BB-500-A, BB-1200-A BB-50, BB-125, BB-275 BB-500-B, BB-1200-B
non-load manway with BB-500-B, BB-1200-B 16,000 lbs. H20 load rating
15" threaded access 16,000 lbs. highway load rating

27 www.striemco.com | Made in the USA | Striem Catalog

specifications & submittals
formats available online
.pdf .doc .dwg .rfa

Made To Order – Submittal Required

Specifications

Capacity (gal.) Recommended Rough-In Dimensions (in.) Adapter Weight (lbs.)
Pipe Size Adjustability
Striem Inlet and Optional Optional 4" Dry Wet
Model Total Liquid Body Pump-out Outlet Outlet Valve Vent (add to Weight Weight
W ID (High Connection) (Low Connection) B, D, F & H)
Tank Holding Inlet / Vent
Outlet L OD H A B C D EF

BB-50 — 52 4 2 37 28 — — 28 ½ 18 10 ½ 6 22 ½ 20 8 ½ 3 ½" 92 527

BB-125 — 125 4 2 46 32 — — 38 ½ 26 12 ½ 8 30 ½ 28 ½ 10 6" 127 1,168

BB-275 — 275 4 2 68 33 ½ — — 51 ½ 38 13 ½ 9 42 ½ 40 11 ½ 6" 223 2,306

BB-500-A 650 501.1 4 2 — — 48 54 84 ½ 70 14 ½ 6 77 ¾ 76 7 ¾ n/a 300 4,479

BB-500-B 650 501.1 4 2 — — 48 54 91 ¾ 70 21 ¾ 6 85 ¾ 76 15 ¾ 6" 455 4,634

BB-1200-A 1,360 1,200 4 2 — — 69 75 87 76 10 ¼ 6 80 ¼ 78 8 ¼ n/a 500 10,216

BB-1200-B 1,360 1,200 4 2 — — 69 75 94 76 18 6 88 78 16 6" 1,004 10,720

BB-50 BB-125 BB-275 BB-500/BB-1200

Above Grade (-A) Below Grade (-B)

Product Selection TeleGlide™ Riser Order Guide

Miscellaneous Options Desired Riser Height (in.)
High Water
Striem Anchor Kit BB-50 BB-125, BB-275, Risers Needed
Model Part # BB-500, BB-1200

Part # AK1 0 - 3½ 0-6 24 Series Adapter
AK1
BB-50 AK1 >3½ - 22 >6 - 24 24 Series
BB-125 >22 - 37 >24 - 39 Short Riser (SR24)
BB-275 >39 - 43
n/a >43 - 58 24 Series
Striem Model *Upgrade to H-20 n/a >58 - 72 Long Riser (LR24)
Rated Pickable n/a
Cast Iron Cover 24 Series Short +
(-B Style only) Short (SR24 + SR24)

Part # 24 Series Short +
Long (SR24 + LR24)
BB-500 C24-HP
BB-1200 C24-HP (2) 24 Series Long +
Long (LR24 + LR24)

Monitoring Packages

AVA-3: Single Level AVA-4: Multi-level 80%
Monitoring Package Monitoring Package 50%
20%
Remote audio/visual Remote audio/visual alarm
alarm panel and explosion panel and explosion proof
proof stainless steel float multi-level float switch.
switch.

* When ordered with decontamination tank.

NOTE 1: When ordered with float switch, add 2" measuring finished cover to centerline of all connections and subtract 2" from available riser height.
NOTE 2: BB-275/BB-1200 have two covers requiring a set of two risers when ordered.

www.striemco.com | Made in the USA | Striem Catalog 28

Appendix

100% American Made

All products manufactured by Striem are 100% American Made and meet requirements for the Buy American Act and
the “Buy American” provision of the American Recovery and Reinvestment Act of 2009 (ARRA).

Terms and Conditions

All Customers: The following terms and conditions pertain to qualified customers only.
Striem, at its option, may qualify or disqualify any customer. All prices are subject to change without notice.

International Customers: All border crossing fees are paid by the importing customer. Contact Striem for further information on NAFTA and HTS
numbers.

Credit Terms: 2% 10 days, net 30.
A 2% discount may be taken if payment is received on or before the 10th day from date of invoice. Full payment is required on or before the
30th day from date of invoice. A 2% service charge will be applied to all overdue accounts. Accounts that regularly pay beyond net terms will
be denied open account status. All prices are subject to change without notice. Invoices may be sent via email upon request.

Freight Terms: Shipments are F.O.B. Edwardsville, KS. Freight charges are pre-paid and billed with product invoice.

Returned Goods: Effective March 2nd, 2015, standard catalog products may be returned with no restock charge if returned in saleable
condition within 6 months of purchase date. The customer is responsible for return freight. A Striem-issued RGA is required before return. If
product is damaged or incomplete, additional charges may apply. Made-to-order products are non-returnable.

Lifetime Warranty

Effective March 2nd, 2015 Striem represents and warrants that HDPE and PP products (“Products”) will be free
from any and all defects in material and workmanship, including corrosion, during the lifetime of the plumbing
system in which the Products were originally installed and will, at its option, agree to repair, replace, or supply
credit to the original purchaser.

This warranty does not cover damage caused by the Products’ normal usage, or wear and tear, nor does it cover
damage from naturally occurring phenomenon, including, but not limited to UV, freeze-related damage, or natural
disasters. This warranty does not cover the purchaser’s cost of routine maintenance including replacement of parts required in routine
maintenance. This warranty does not cover fabricated steel products, or any monitoring equipment. This warranty shall be effective if, and
only if, the Products were:

• installed in accordance with Striem’s notes, specifications and instructions, for installation, operation, and maintenance;
• installed in conformance with all applicable building and plumbing codes, and passed all applicable testing methods immediately

following installation;
• not subjected to misuse or abuse, whether negligent or intentional;
• never modified, repaired, or altered by any individual(s) not authorized by Striem;
• sold through a Striem qualified wholesale distributor.
This warranty is the purchaser’s sole and exclusive remedy, and acceptance of this exclusive remedy is a condition of the contract for the
purchase of these Products.

In no event shall Striem be liable for any incidental, special, consequential or punitive damages, or for any costs, attorney fees, expenses, losses
or delays claimed to be as a consequence of any damage to, failure of, or defect in any products including, but not limited to, any claims for loss of
profits, transportation, removal and installation charges. This warranty is exclusive and in lieu of all other warranties or conditions, written or oral,
expressed or implied.

29 www.striemco.com | Made in the USA | Striem Catalog

Thank You for Trusting Us

At Striem, we make three things: oil separators, solids interceptors, and chemical waste tanks. If we don’t make them right, we have nothing
to fall back on. This tends to keep us very sharp.

Whether you’re specifying, buying, installing, or maintaining one of our products, we thank you for trusting us.

We want to make a promise. If you call us, we will provide best-in-class customer service. If you interact with our product, it will be easy.

If you think we didn’t hold up our end of the bargain, call us and we’ll make it right. It’s that simple.

Vince Ismert Gabe Ismert

Direct: 816-591-9765 Direct: 816-820-5454

www.striemco.com | Made in the USA | Striem Catalog 30

v2.0

[email protected]


Click to View FlipBook Version