Eaton FAZ-NA miniature circuit breakers • Dual rated for AC or DC applications Feeder and Branch Circuit Protection Cable Ties
offer optimum and efficient protection • C omplete range of UL 489 listed DIN rail • C onvenience receptacle circuits
for branch and control circuits up to 40 mounted miniature circuit breakers up to (internal / external) Wire
amps. The FAZ-NA series is available 40 ampere current rating • M otor control circuits
with C or D trip characteristics in • S ingle-pole, two-pole and three-pole • L oad circuits leaving the equipment Bulk
accordance with UL 489. These circuit models (external) Multi-conductor
breakers are current limiting, which • C urrent limiting design provides fast • HACR Equipment (Heating Air Cables
means they interrupt fault currents within short circuit interruption that reduces the Conditioning, Refrigeration)
one half cycle of the fault. The FAZ-NA let-through energy, which can damage • P LC I/O points Wire
series is DIN-rail mountable and can the circuit • C omputers Management
be used in feeder and branch circuit • Suitable for branch circuit device • Power supplies Products
applications. protection • Control instrumentation
• Thermal-magnetic overcurrent • Relays Power Supplies
Listings protection • UPS
— two levels of short circuit protection, • Power conditioners DC Converters
• U L Listed under UL 489 categorized by C and D curves
Category DIVQ File E235139 C curve magnetic trip point: Transformers
Busbar Accessory 5 to 10 times the rated current, and Filters
Category NMTR2.E257181 typically used for small
Category DIHS E257181 transformers, pilot devices, etc. Circuit Protection
• CSA 22.2, No. 5 File 204453 D curve magnetic trip point:
• CE LVD 2006/95/EC 10 to 20 times the rated current, Tools
• IEC/EN 60947-2 typically used for transformers or very
high inductive loads. Test
R • T rip-free design — breaker cannot be Equipment
defeated by holding the handle in the
“ON” position Enclosures
• Captive screws cannot be lost
• SWD (switching duty) rated circuit Enclosure
breaker — suitable for switching Climate Control
fluorescent lighting loads (In m 20A)
• Fulfills UL 489, CSA C22.2 No.5 and also Safety: Electrical
IEC 60947-2 Standard Components
• Can also be used in applications for
which UL 1077 or CSA C22.2 No.235 Safety: Protective
are also allowed Wear
• F ield installable shunt trip and auxiliary
switch subsequent mounting Terms and
• Module width of only 17.7 mm (per pole) Conditions
• Contact position indicator (red / green)
• 3 5mm DIN-rail mountable, utilizing
spring clip
• S uitable for reverse feed applications
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n Circuit Protection Book 3 (14.3)
eCP-69
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Miniature Circuit Breakers
Tripping Characteristics Labeling
Eaton FAZ-NA miniature circuit breakers are available with “C” The front of each Eaton FAZ-NA miniature circuit
and “D” tripping characteristics. breaker is labeled for positive identification.
Type C trip curve: 5 to10 In IP20
Finger and Hand
C-curve devices are suitable for applications where medium
levels of inrush current are expected. Applications include small Touch Safe
transformers, lighting, pilot devices, control circuits and coils.
C-curve devices provide a medium magnetic trip point.
Type D trip curve: 10 to 20 In Conductor Type DIN Rail
Mounting
D-curve devices are suitable for applications where high levels Color Coded
of inrush current are expected. The high magnetic trip point Breaker Status
prevents nuisance tripping in high inductive applications such as Indicator
motors, transformers and power supplies.
Eaton FAZ-NA devices are current limiting, which means they
interrupt fault currents within one half cycle of the fault. Current
limiting devices offer superior protection by reducing peak
let-through current and energy.
7200 2 tripping characteristic Operating Calibration
3600 1 3 acc. to UL 489 / CSA 22.2 No. 235 Handle Temperature
1200 1 conventional non-tripping current
3 Int= 1.0 IN (T=40 °C ) with Trip Free UL / CSA
600 2 conventional tripping current Design Rated
300 It = 1.35 IN: t < 1 h (T=25 °C ) Current
Rated Voltage
120 3 2.0 IN: t = 12 - 120 s (T=25 °C ) UL / CSA Captive Terminal
60 Screws
30 instantaneous tripping Part Number
acc. to IEC 60898-1
10
Tr ipping time t [sec] 5 4 type C: 5I Nt:<t > 0.1 s
10 IN: 0.1 s
2
1 6 type D: 10 I N: t > 0.1 s
0.5 20 IN: t < 0.1 s
0.2 4 5
0.1
0.05 4 C5 D
0.02 2 3 4 5 6 7 8 9 10 15 20 30 40 50
0.01
0.005
0.002
0.001
0.0005
1
Multiples of In
Book 3 (14.3) 1 - 8 0 0 - 633 - 0 4 05
eCP-70 Circuit Protection
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Selection Guide Company
Information
Terminal Blocks
FAZ-NA – Single-Pole Selection Guide Power
Distribution
Ampere C Curve Price D Curve Price Blocks
Rating Part Number Part Number
FAZ-C0P5-1-NA-SP FAZ-D0P5-1-NA-SP $18.00 Wiring
0.5 FAZ-C1-1-NA-SP FAZ-D1-1-NA-SP Accessories
1 FAZ-C1P5-1-NA-SP FAZ-D1P5-1-NA-SP
1.5 FAZ-C2-1-NA-SP FAZ-D2-1-NA-SP ZIPLink
2 FAZ-C3-1-NA-SP FAZ-D3-1-NA-SP Connection
3 FAZ-C4-1-NA-SP FAZ-D4-1-NA-SP System
4 FAZ-C5-1-NA-SP FAZ-D5-1-NA-SP
5 Multi-wire
Connectors
6 FAZ-C6-1-NA-SP FAZ-D6-1-NA-SP
Sensor Cables
7 FAZ-C7-1-NA-SP FAZ-D7-1-NA-SP and Connectors
8 FAZ-C8-1-NA-SP $18.00 FAZ-D8-1-NA-SP M12 Junction
10 FAZ-C10-1-NA-SP FAZ-D10-1-NA-SP Blocks
13 FAZ-C13-1-NA-SP FAZ-D13-1-NA-SP Panel Interface
Connectors
Single-Pole 15 FAZ-C15-1-NA-SP FAZ-D15-1-NA-SP
Wiring Duct
Note: Eaton product part numbers will 16 FAZ-C16-1-NA-SP FAZ-D16-1-NA-SP
contain a [.] instead of [ P ] and Cable Ties
a [ / ] instead of a [ - ]. 20 FAZ-C20-1-NA-SP FAZ-D20-1-NA-SP
Example: FAZ-C0P5-1-NA-SP = Wire
FAZ-C0.5/1-NA-SP 25 FAZ-C25-1-NA-SP FAZ-D25-1-NA-SP
Bulk
30 FAZ-C30-1-NA-SP FAZ-D30-1-NA-SP Multi-conductor
32 FAZ-C32-1-NA-SP FAZ-D32-1-NA-SP Cables
*35 FAZ-C35-1-NA-SP FAZ-D35-1-NA-SP
Wire
*40 FAZ-C40-1-NA-SP FAZ-D40-1-NA-SP Management
Products
* Rated 240VAC
Power Supplies
DC Converters
FAZ-NA – Two-Pole Selection Guide Transformers
and Filters
Ampere C Curve Price D Curve Price
Rating Part Number Part Number Circuit Protection
FAZ-C0P5-2-NA FAZ-D0P5-2-NA $35.00
0.5 FAZ-C1-2-NA FAZ-D1-2-NA Tools
1 Book 3 (14.3)
1.5 FAZ-C1P5-2-NA FAZ-D1P5-2-NA Test
2 FAZ-C2-2-NA FAZ-D2-2-NA eCP-71 Equipment
3
4 FAZ-C3-2-NA $35.00 FAZ-D3-2-NA Enclosures
5 FAZ-C4-2-NA FAZ-D4-2-NA
6 FAZ-C5-2-NA FAZ-D5-2-NA Enclosure
7 FAZ-C6-2-NA FAZ-D6-2-NA Climate Control
8 FAZ-C7-2-NA FAZ-D7-2-NA
10 FAZ-C8-2-NA FAZ-D8-2-NA Safety: Electrical
13 FAZ-C10-2-NA FAZ-D10-2-NA Components
15
16 Safety: Protective
20 Wear
25
30 Terms and
32 Conditions
*35
Two-Pole *40 FAZ-C13-2-NA FAZ-D13-2-NA
FAZ-C15-2-NA FAZ-D15-2-NA
Note: Eaton parts available for * Rated 240VAC
sale to North America FAZ-C16-2-NA FAZ-D16-2-NA
locations only. FAZ-C20-2-NA FAZ-D20-2-NA
FAZ-C25-2-NA FAZ-D25-2-NA
FAZ-C30-2-NA FAZ-D30-2-NA
FAZ-C32-2-NA FAZ-D32-2-NA
FAZ-C35-2-NA FAZ-D35-2-NA
FAZ-C40-2-NA FAZ-D40-2-NA
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n Circuit Protection
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Selection Guide
FAZ-NA – Three-Pole Selection Guide
Ampere C Curve Price D Curve Price
Rating Part Number Part Number
FAZ-C0P5-3-NA $54.50 FAZ-D0P5-3-NA $54.50
0.5 FAZ-C1-3-NA FAZ-D1-3-NA
1 FAZ-C1P5-3-NA FAZ-D1P5-3-NA Three-Pole
1.5 FAZ-C2-3-NA FAZ-D2-3-NA
2 FAZ-C3-3-NA FAZ-D3-3-NA Note: Eaton product part numbers will
3 FAZ-C4-3-NA FAZ-D4-3-NA contain a [.] instead of [ P ] and
4 FAZ-C5-3-NA FAZ-D5-3-NA a [ / ] instead of a [ - ].
5 FAZ-C6-3-NA FAZ-D6-3-NA Example: FAZ-C0P5-3-NA =
6 FAZ-C7-3-NA FAZ-D7-3-NA FAZ-C0.5/3-NA
7 FAZ-C8-3-NA FAZ-D8-3-NA
8 FAZ-C10-3-NA FAZ-D10-3-NA
10 FAZ-C13-3-NA FAZ-D13-3-NA
13 FAZ-C15-3-NA FAZ-D15-3-NA
15 FAZ-C16-3-NA FAZ-D16-3-NA
16 FAZ-C20-3-NA FAZ-D20-3-NA
20 FAZ-C25-3-NA FAZ-D25-3-NA
25 FAZ-C30-3-NA FAZ-D30-3-NA
30 FAZ-C32-3-NA FAZ-D32-3-NA
32 FAZ-C35-3-NA FAZ-D35-3-NA
*35 FAZ-C40-3-NA FAZ-D40-3-NA
*40
* Rated 240VAC
Book 3 (14.3) 1 - 8 0 0 - 633 - 0 4 05
eCP-72 Circuit Protection
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Company
Technical Specifications Information
Terminal Blocks
Power
Distribution
Blocks
FAZ-NA Miniature Circuit Breakers – UL/CSA Wiring
Accessories
C Curve D Curve
ZIPLink
Short Circuit Trip Response 5 - 10 In 10 - 20 I n Connection
Current Range System
0.5 - 40 A
Multi-wire
0.5 - 32 A 277 / 480Y Connectors
Maximum Voltage Ratings 35 - 40 A 240VAC Sensor Cables
UL / CSA Per pole 48VDC and Connectors
2 poles in series 96VDC Max M12 Junction
Blocks
Thermal Tripping Single pole 40°C
Characteristics Multi-pole Panel Interface
Connectors
Short Circuit 1 pole 10kA
Ratings 2 pole Note: 14 kAIC at select amperages Wiring Duct
(@ maximum voltage) 3 pole
B and C curves (15-25 A) Cable Ties
Rated Frequency D curve (13-20 A)
Agency Approvals 50/60 Hz Wire
UL File #E235139, CSA #204453 Bulk
Multi-conductor
Note: To obtain the most current agency approval information, see the Agency Approval Checklist section Cables
on the specific part number's web page.
Wire
FAZ-NA Miniature Circuit Breaker - IEC Management
Products
C Curve D Curve
Power Supplies
Short Circuit Trip Response 5 - 10 In 10 - 20 I n
Current Range DC Converters
0.5 - 40 A
Transformers
Maximum Voltage 1 pole 240/415 VAC and Filters
Ratings - 2 pole / 3 pole
IEC/EN 60947-2 2 poles in series Circuit Protection
Thermal Tripping Single pole 30°C Tools
Characteristics Multi-pole
Test
Interrupt Ratings (At Max Voltage) 15kA Equipment
Rated Frequency 50/60 Hz Enclosures
General Specifications Enclosure
Climate Control
Lifespan / Endurance M20,000 (1 operation = ON/OFF)
Operating Temperature UL 489, CSA C22.2 No.5 = 40°C Safety: Electrical
Shock (UL 489) Components
IEC 60947-2 = 30°C
10g 20-25 ms Safety: Protective
Wear
Housing Material Nylon
Terms and
Mounting Position Vertical Conditions
1 pole 0.3 lb (136g)
Weight 2 pole 0.6 lb (272g)
3 pole 0.9 lb (408g)
Wire Size
Ampere Rating Conductor Size
0.5 - 40 One wire 18 to 6 AWG (0.75 to 13mm²)
Two wires 18 to 10 AWG (0.75 to 5mm²)
Note: Eaton does not recommend the use of wire ferrules or crimping terminals. The wire gauges are
specified above and in the installation instructions included with each circuit breaker.
Tightening Torque
Conductor Size Tightening Torque
18 - 12 AWG 21 lb·in (2.4 N·m)
10 - 8 AWG 25 lb·in (2.8 N·m)
6AWG 36 lb·in (4.1 N·m)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n Circuit Protection Book 3 (14.3)
eCP-73
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Technical Data
Let-Through Energy • The X axis shows the prospective short-circuit current levels.
• The Y axis indicates the actual let-through values at those prospective fault ratings
Characteristic C (0.5-20A), 277V for each FAZ-NA device plotted.
As can be interpreted from the bend in the plotted curves, each device acts to limit the damaging let-through
energy at those values of short-circuit current.
Characteristic C (25-40A), 240V
80000 C 20 C 16 80000
70000 C 15, 70000
60000 60000 C40
50000 CCCC681130, C7 50000 C35
40000 40000 CC3320
30000 30000 C25
20000 C5 20000
C4
15000 C3 15000
10000 C2 10000
9000 C 1,5 9000
8000 8000
7000 C1 7000
6000 C 0.5 6000
5000 5000
4000 4000
3000 3000
2000 2000
1500 1500
1000 1000
900 900
800 800
700 700
600 600
500 500
400 400
300 300
500
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
500
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
Prospective short-circuit current [A] D20 Prospective short-circuit current [A] D40
D15, D16
Characteristic D (0.5-20A), 277V DD1103 Characteristic D (25-40A), 240V DDD333052
DD68,D7 D25
80000 D5 80000
70000 D4 70000
60000 D3 60000
50000 D2 50000
40000 D 1 .5 40000
30000 D1 30000
20000 D0.5 20000
15000 15000
10000 10000
9000 9000
8000 8000
7000 7000
6000 6000
5000 5000
4000 4000
3000 3000
2000 2000
1500 1500
1000 1000
900 900
800 800
700 700
600 600
500 500
400 400
300 300
500
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
500
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
Book 3 (14.3) Prospective short-circuit current [A] Prospective short-circuit current [A]
eCP-74 Circuit Protection 1 - 8 0 0 - 633 - 0 4 05
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Technical Data Company
Information
Power Loss at In Tripping Curves Terminal Blocks
Characteristic C
1p 2p 3p Power
In [A] P[W] P[W] P[W] Distribution
Blocks
0.5 1.6 3.2 4.7 7200 2
1 1.1 2.2 3.4 3600 1 3 Wiring
1.5 1.3 2.6 3.9 1200 tripping characteristic Accessories
2 1.4 2.8 4.3 3 acc. to UL 489 / CSA 22.2 No. 235
3 1.2 2.4 3.6 600 1 conventional non-tripping current ZIPLink
4 1.4 2.9 4.3 300 Int= 1.0 IN (T=40 °C ) Connection
5 1.9 3.7 5.6 2 conventional tripping current System
6 1.2 2.3 3.5 120 It = 1.35 IN: t < 1 h (T=25 °C )
7 1.4 2.8 4.3 60 Multi-wire
8 1.4 2.8 4.2 30 3 2.0 IN: t = 12 - 120 s (T=25 °C ) Connectors
10 1.8 3.6 5.3
13 2.4 4.7 7.1 10 Sensor Cables
15 1.9 3.8 5.6 5 and Connectors
16 2.1 4.3 6.4 instantaneous tripping
2 acc. to IEC 60898-1 M12 Junction
Blocks
20 2.9 5.8 8.7 Tr ipping time t [sec] 4 type C: 5I Nt:<t > 0.1 s
25 3.1 6.2 9.3 10 IN: 0.1 s Panel Interface
30 3.0 6.0 9.0 Connectors
32 3.4 6.8 10.2 6 type D: 10 I N: t > 0.1 s
35 3.7 7.4 11.0 20 IN: t < 0.1 s Wiring Duct
40 4.0 8.1 12.1 Cable Ties
Power Loss at In 1 Wire
Characteristic D 0.5
1p 2p 3p Bulk
In [A] P[W] P[W] P[W] 0.2 Multi-conductor
0.1 Cables
0.5 1.6 3.2 4.8 0.05 4 5
1 0.8 1.5 2.3 Wire
1.5 1.0 2.1 3.1 0.02 4 C5 D Management
2 1.0 2.1 3.1 0.01 Products
3 1.2 2.4 3.6 0.005
4 1.4 2.9 4.3 Power Supplies
5 1.5 2.9 4.4 0.002
6 1.2 2.3 3.5 0.001 DC Converters
7 1.4 2.8 4.3 0.0005
8 1.2 2.4 3.7 Transformers
10 1.5 3.0 4.5 1 and Filters
13 2.0 4.1 6.1
15 1.5 3.1 4.6 Circuit Protection
16 1.7 3.5 5.2
20 1.8 3.7 5.5 Tools
25 2.6 5.1 7.7
30 2.7 5.4 8.1 2 3 4 5 6 7 8 9 10 15 20 30 40 50 Test
Equipment
32 3.1 6.2 9.3 Multiples of In
35 3.8 7.6 11.3 Enclosures
40 3.9 7.8 11.6 Enclosure
Climate Control
FAZ-NA Miniature Circuit Breakers Dimensions
Safety: Electrical
Components
Safety: Protective
Wear
Terms and
Conditions
Please see our website www.AutomationDirect.com for complete engineering drawings. Circuit Protection Book 3 (14.3)
Dimensions are approximate. Not for construction purposes.
eCP-75
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Technical Data
Device Market Influence of Ambient Temperature T on Load Carrying Capacity
Current Rating In (A) at Higher Ambient Temperature
In (A) at 40°C 15°C 20°C 25°C 30°C 40°C 50°C 55°C 60°C
0.5 0.6 0.5 0.5 0.5 0.5 0.5 0.5 0.5
1.0 1.1 1.1 1.1 1.0 1.0 1.0 0.9 0.9
1.5 1.7 1.6 1.6 1.6 1.5 1.4 1.4 1.4
2.0 2.2 2.2 2.1 2.1 2.0 1.9 1.9 1.8
3.0 3.3 3.2 3.2 3.1 3.0 2.9 2.9 2.8
4.0 4.4 4.3 4.2 4.2 4.0 3.8 3.8 3.7
5.0 5.5 5.4 5.3 5.2 5.0 4.8 4.7 4.6
6.0 6.6 6.5 6.4 6.2 6.0 5.8 5.6 5.5
7.0 7.7 7.6 7.4 7.3 7.0 6.7 6.6 6.4
8.0 8.8 8.6 8.5 8.3 8.0 7.7 7.5 7.4
10.0 11.0 10.8 10.6 10.4 10.0 9.6 9.4 9.2
13.0 14.3 14.0 13.8 13.5 13.0 12.5 12.5 12.0
15.0 16.5 16.2 15.9 15.6 15.0 14.4 14.1 13.8
16.0 17.6 17.3 17.0 16.6 16.0 15.4 15.0 14.7
20.0 22.0 21.6 21.2 20.8 20.0 19.2 18.8 18.4
25.0 27.5 27.0 26.5 26.0 25.0 24.0 23.3 23.0
30.0 33.0 32.4 31.8 31.2 30.0 28.8 28.2 27.6
32.0 35.2 34.6 33.9 33.3 32.0 30.7 30.1 29.4
35.0 38.5 37.8 37.1 36.4 35.0 33.6 32.9 32.2
40.0 44.0 37.6 36.8
43.2 42.4 41.6 40.0 38.4
1.40
Load factor KT [I/In] 1.30
1.20
1.10
1.00
0.90
-20 -10 0 10 20 30 40 50
Ambient temperature T [°C ]
Maximum load IL at ambient temperature T:
IL (T) = In KT (T)
IL = Maximum Load
T = Ambient Temperature
IN = Rated Current in Amps
KT = Load Factor
Book 3 (14.3) 1 - 8 0 0 - 633 - 0 4 05
eCP-76 Circuit Protection
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Accessories Company
Information
Terminal Blocks
Field Mountable Accessories Power
Distribution
Blocks
• Auxiliary switch Wiring
• Alarm switch Accessories
• Shunt trip
• No tools required for mounting ZIPLink
Connection
System
Multi-wire
Connectors
Sensor Cables
and Connectors
ZNHK ZIHK-NA M12 Junction
Blocks
Alarm/Aux Contact Auxiliary Contact
Panel Interface
ZNHK* ZIHK-NA Connectors
Price $20.75 $16.00 Wiring Duct
Electrical Data Cable Ties
Contact function 2 Form C (one set changeover) (SPDT) 1 N.O. + 1 N.C. (DPST) Wire
Rated voltage 230VAC / 110V AC/DC 600VAC / 230VAC / 120VAC Bulk
Multi-conductor
Frequency 50/60 Hz Cables
Rated current 2A / 0.5 A 1.2 A / 2A / 6A Wire
Management
Rated thermal current Ith 60947-5-1 2A / 250VAC 6A / 250VAC Products
60947-5-1 Utilization category AC13 3A / 250VAC 0.5 A / 110VDC Power Supplies
2A / 250VAC 0.25 A / 220VDC
Rated Utilization category AC15 DC Converters
operational 250VAC 10 mA AC/DC
current Ie Utilization category DC12 0.5 A / 110VDC 5VDC 4kV Transformers
1kA and Filters
Rated insulation voltage UI
Minimal operational voltage per Contact Umin Circuit Protection
Minimum operational current Imin
10mA DC Tools
Rated peak withstand voltage Uimp (1.2/50µ) 2.5 kV Test
Equipment
Conditional short-circuit current Ik w/ backup fuse 6A 1kA
Enclosures
Mechanical Data
Enclosure
Tripping indicator "electrical tripping" Blue/white – Climate Control
Frame size 45mm Safety: Electrical
Components
Mounting Onto FAZ-NA
Safety: Protective
Degree of protection, built-in IP40 Wear
Terminal protection Finger and hand touch safe according to BGV A3, OVE-EN 6 Terms and
Conditions
Terminals Lift terminals
Terminal capacity 20-18 AWG (0.75 - 2.5 mm²) 20-14 AWG (0.5 - 2.5 mm²)
Terminal screws M3 (Posidrive Z0 - Phillips)
Fastening torque of terminal screws 7 lb·in (0.79 N·m) Max. 10.6 lb·in (1.2 N·m)
*Voltage of the FAZ-NA circuit breaker is limited to 300V with contact installed.
Allowable Combinations of Accessories
or or
Z-IHK-NA Z-NHK FAZ-NA Z-IHK-NA Z-NHK FAZ-XAA-NAxxx FAZ-NA
Standard Auxilary / Miniature Standard Auxilary / Shunt Miniature
Auxilary Auxilary Trip
Alarm Circuit Alarm Circuit
Switch Breaker Switch Breaker
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n Circuit Protection Book 3 (14.3)
eCP-77
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Accessories
Shunt Trip Release C1
• Remote release for subsequent mounting onto
FAZ-NA
• Additional installation of standard auxiliary
switch is possible
• Position indicator red-green
C2
FAZ-XAA-NA Series Circuit Diagram
FAZ-XAA-NA12-110V FAZ-XAA-NA110-415V
Price $29.00 $29.00
Can be mounted onto Electrical Data
Operational voltage range
Maximum inrush current FAZ-NA
Frequency
12-110 VAC 110-415 VAC
Frame size 12-60 VDC 110-230 VDC
Height
Width 15A 2.1 A
Weight
Mounting 50/60 Hz
Degree of protection, built-in
Terminal protection Mechanical Data
Terminals
Terminal capacity, one and two wires 45mm
Agency Approval
4.13 in (105mm)
0.69 in (17.5 mm)
0.28 lb (127g)
Quick fastening with two lock-in positions on EN 50022
IP40
Finger and hand touch safe according to BGV A3, OVE-EN 6
Open mouthed/lift
18-10 AWG (0.8 - 5.3 mm²)
UL File # E257181, CSA 204453
Note: To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number's web page.
Lockout Attachment
Lockout Attachment
Part Number Description Weight Qty Price
ZIS-SPE-1TE-3 Lockout attachment for Eaton FAZ-NA series supplementary protectors and 0.10 lb 3 $25.50
FAZ-NA mini circuit breakers, suitable to prevent unauthorized activation of a (45g)
de-energized circuit, accepts lock shackles up to 9/32 in. (7.1 mm) in diameter
ZIS-SPE-1TE-3 Installation ZIS-SPE-1TE-3
2 Lockout Attachment
1 3
ZIS-SPE-1TE-3
Book 3 (14.3) FAZ or FAZ-NA Series 1 - 8 0 0 - 633 - 0 4 05
eCP-78 Circuit Protection
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Accessories Company
Information
Busbar System Terminal Blocks
(Without auxiliary contacts) Power
Distribution
Busbar System for FAZ-NA Series Miniature Circuit Breakers Blocks
Part Number Description Price Wiring
ZSVUL16-1P-1TE6SP Accessories
Busbar for connecting up to six (6) 1-pole FAZ-NA series circuit breakers $8.50
$15.50 ZIPLink
ZSVUL16-1P-1TE12SP Busbar for connecting up to twelve (12) 1-pole FAZ-NA series circuit breakers $23.25 Connection
$9.50 System
ZSVUL16-1P-1TE18SP Busbar for connecting up to eighteen (18) 1-pole FAZ-NA series circuit breakers $19.00
$28.00 Multi-wire
ZSVUL16-2P-2TE6SP Busbar for connecting up to three (3) 2-pole FAZ-NA series circuit breakers $10.00 Connectors
$20.00
ZSVUL16-2P-2TE12SP Busbar for connecting up to six (6) 2-pole FAZ-NA series circuit breakers $29.50 Sensor Cables
and Connectors
ZSVUL16-2P-2TE18SP Busbar for connecting up to nine (9) 2-pole FAZ-NA series circuit breakers
M12 Junction
ZSVUL16-3P-3TE6SP Busbar for connecting up to two (2) 3-pole FAZ-NA series circuit breakers Blocks
ZSVUL16-3P-3TE12SP Busbar for connecting up to four (4) 3-pole FAZ-NA series circuit breakers Panel Interface
Connectors
ZSVUL16-3P-3TE18SP Busbar for connecting up to six (6) 3-pole FAZ-NA series circuit breakers
Note: FAZ-NA Busbar is not for use with FAZ supplementary protectors.
Busbar Specifications Wiring Duct
Description UL489 IEC/EN60947-2 Cable Ties
Operating Voltage
480VAC 96VDC 240/415 VAC Wire
50/60 Hz
Frequency 50/60 Hz n/a 9.5 kV Bulk
Multi-conductor
Rated impulse withstand Uimp n/a 80A @ 30°C Cables
Max Current - Ie Fed from End 16 mm2
Cross Section 80A @ 40°C Wire
Management
n/a Products
Busbar Connection Diagrams Power Supplies
ZSVUL16-xP-xTExSP Three-Pole Busbar Two-Pole Busbar Single Pole Busbar DC Converters
L
L1 L1 Transformers
L2 L2 and Filters
L3
Circuit Protection
ZEK35-UL Tools
Test
Equipment
Note: Do not cut Enclosures
Enclosure
Climate Control
ZSVUL16-3P-3TE12SP ZVBS-UL Safety: Electrical
Components
Top
Side Safety: Protective
Wear
Terms and
Conditions
Bottom
Side
FAZ-NA Series
May feed from Top or Bottom side
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n Circuit Protection Book 3 (14.3)
eCP-79
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Accessories
Busbar Accessories
Busbar Accessories for FAZ-NA Series Miniature Circuit Breakers
Part Number Description Price
ZVBS-UL Busbar Shroud - covers for unused bus bar terminals, (10) 3-terminal covers per package $21.75
ZVBS-UL-5 Busbar Shroud - covers for unused bus bar terminals, (5) 3-terminal covers per package $11.75
ZEK35-UL Wiring Lug, 2 - 14 AWG (35mm), 3 lugs per package $31.50 ZVBS-UL
ZEK35-UL-1 Wiring Lug, 2 - 14 AWG (35mm), 1 lug per package $11.25
ZEK35-UL – Specifications
Description UL489 IEC/EN60947-2 ZEK35-UL
Operating Voltage
Frequency 480VAC 96VDC 240/415 VAC
50/60 Hz n/a 50/60 Hz
9.5 kV
Rated impulse withstand - Uimp n/a ZEK35-UL – Tightening Torque
Max Current - Ie 80A @ 40°C 80A @ 30°C Tested Tightening
#2 - 14 AWG 2.5 - 35 mm2 Acc. To Cable Size Torque
UL 486A #14 AWG M 20 lb·in (2.3 N·m)
0.56 in 14mm UL 486B #8 - 12 AWG M 25 lb·in (2.8 N·m)
Agency Approval UL File # E257182, E257181 UL 486E #6 - 1 AWG 35 lb·in (4 N·m)
Note: To obtain the most current agency approval information, see the Agency
Approval Checklist section on the specific part number's web page.
Book 3 (14.3) 1 - 8 0 0 - 633 - 0 4 05
eCP-80 Circuit Protection
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Accessories Company
Information
Accessories Dimensions in [mm] Terminal Blocks
contact 4.xx in Auxilary mode SEL TRIP Manual or Power
contact 1.xx in Auxilary mode Electrical Trip Distribution
OFF Blocks
OFF ON 1.11 4.11
4.11 1 N Wiring
1 N 1.11 4.11 1 N 1.11 Accessories
1.14 4.12 1.14 4.12 1.14 4.12 ZIPLink
2 N 1.12 4.14 2 N 1.12 4.14 2 N 1.12 4.14 Connection
System
contact 4.xx in Alarm mode SEL TRIP 4.11
contact 1.xx in Auxilary mode Multi-wire
OFF Manual Trip Connectors
OFF ON
4.11 1 N 4.14 Sensor Cables
1 N 1.11 4.11 1 N 1.11 1.11 4.12 and Connectors
M12 Junction
Blocks
1.14 4.14 1.14 4.14 1.14 4.11 Panel Interface
2 N 1.12 4.12 2 N 1.12 4.12 2 N 1.12 Connectors
ZNHK 4.14 Wiring Duct
Diagrams
Electrical Trip Cable Ties
4.12 Wire
ZNHK
Bulk
Multi-conductor
Cables
21 Wire
13 Management
Products
Power Supplies
DC Converters
Transformers
and Filters
22 14 Circuit Protection
Tools
ZIHK-NA ZIHK-NA Test
Diagram Equipment
FAZ-NA Series Enclosures
Miniature Circuit Breakers
Enclosure
Connection Diagrams Climate Control
Safety: Electrical
Components
Safety: Protective
Wear
Single Pole Two-Pole Three-Pole Terms and
1 13 13 5 Conditions
2 24 24 6
FAZ-XAA-NA-xxx
Please see our website www.AutomationDirect.com for complete engineering drawings.
Dimensions are approximate. Not for construction purposes.
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n Circuit Protection Book 3 (14.3)
eCP-81
Prices as of April 27, 2016. Check Web site for most current prices.
FAZ-NA Series Accessories
Accessories Dimensions in [mm]
ZSVUL16-xP-xTExSP
FAZ-NA Busbar Length – in [mm]
Part Number AB
ZSVUL16-xP-xTE6SP 3.90 [99.0] 3.46 [88.0]
ZSVUL16-xP-xTE12SP 8.06 [204.6] 7.62 [193.6]
ZSVUL16-xP-xTE18SP 12.21 [310.2] 11.78 [299.2]
ZVBS-UL ZEK35-UL
Book 3 (14.3) Please see our website www.AutomationDirect.com
for complete engineering drawings.Dimensions are
eCP-82 Circuit Protection approximate. Not for construction purposes.
1 - 8 0 0 - 633 - 0 4 05
Prices as of April 27, 2016. Check Web site for most current prices. Company
Information
UL489 or UL1077?
What are your Circuit Protection Requirements? Terminal Blocks
An understanding of circuit types and circuit protection products is critical to ensure their proper application. Power
See NEC Sections 100, 430 and 409 for definitions. Distribution
Blocks
The proper sizing of an overcurrent protection device is the responsibility of the customer and should be determined using the
application standards of the NEC (National Electric Code), CEC (Canadian Electrical Code) or other Wiring
applicable standards. Per fine print note of 2008 NEC Section 100 “A current in excess of rating may be Accessories
accommodated by certain equipment and conductors for a given set of conditions. Therefore, the rules for
overcurrent protection are specific for particular situations.” ZIPLink
UL1077 Connection
UL489 Supplementary Protection System
Branch Protection Multi-wire
Connectors
Sensor Cables
and Connectors
M12 Junction
Blocks
Panel Interface
Connectors
Wiring Duct
Cable Ties
Wire
Bulk
Multi-conductor
Cables
Wire
Management
Products
Power Supplies
DC Converters
What You Need to Know and Look For In Specifications Transformers
Certifications – Standards – Acceptance and Filters
UL489 UL1077
Circuit Protection
Branch Protection Supplementary Protection
Tools
••• CIUnSLte4Ar8nC9a2tLi2ois.n2taelNdroao.tri5nRgescoavganiilzaebdle depending on breaker type ••• ICUESLCAR6e20c29o.42g7nN-i2zoe.od2r8uIE5nCde8r9U8L1077
Test
Function Equipment
• O pens automatically on Overload and Short Circuit when properly •• pNOP rropooettvensicudstieiatosaunbatoldiesmdfaioatlitrroiectnhaaaedlllyyperpoqornutoeiOvpcimvtdieoeerndnlotooapfrdrbnoarotnaetndcrcteiShoqhnucoiiwrrretchduCeiirtreccuobinrtadnucchtocrisrcuit Enclosures
• aPproptleiecdtswwitihreinaintsd rcaatbinlegsagainst Overload and Short Circuit •
Enclosure
Applications Climate Control
• B ranch circuit protection in control panels, panelboards, switchboards • cplUIidigrsreohceatutdeliincrtwsetgi,piotcclhnaioircncneutamripotseplnlpitaofnwocreerfsutsroaernsosttfhhoaertmraeerleresca,tprreipcllaaieyl dse,qaPusLipsCumpIe/pOnltepmsoueicnnhttsaarasyncdontrol Safety: Electrical
• maM noodttoomrrocotivorcerurcliootanpdtrrooatnledccteomnrtose)trosfrorshcoornttrcoirlcpuaitnpelrsotaencdtiomno(tUorL4co8n9trRoelccoegnnteizresd • Components
Safety: Protective
Wear
Terms and
Conditions
Features
• Bolted down or DIN-rail mounted • DIN-Rail mounted
••••• VHFESxiatieagtrlenihdordnuvmaasollololthueanavngeneteeldbsdalrenaoandfmccpciehnercotscehtsierarorccnurtuiiipesoittsmniops(nrcoaultveeravvcieetlilaostbyn(lpeuep) to 100 kAIC @ 480V) ••••• 1VF1100i0aerlkkkidoAAAumIIICCCsol@@@uevnet422el748sdV07oaDfVVcCpcAAerCCostsaeoncrtdiieo5snk(AcuICrv@e ty4p8e0)VAC
kAIC = thousands of Amps interrupt capacity
Summary
A Supplementary Protector can’t be used for Branch Circuit Protection.
Understanding the difference between Branch Circuit Protection and Supplementary Protection helps to ensure their proper use.
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n Circuit Protection Book 3 (14.3)
eCP-5
Prices as of April 27, 2016. Check Web site for most current prices.
UL 1077 Supplementary Protectors and
UL 489 Circuit Breakers Application
Guidelines
UL 489
Breaker
UL1077 UL 489 External
Branch Receptacle
Electronics
Internal Receptacle External
UL1077 Motor
Other UL 489 M
Sensitive Branch
Devices External
UL 489 Motor
UL 489 Branch M
Branch
UL1077 Motor
HACR Controller
(Circuits)
Example of UL 489 and UL 1077 Application
UL489 circuit breakers
Used for branch circuit protection, internal/external receptacles, external motors and HACR equipment (heating, air conditioning
and refrigeration).
UL1077 supplementary protectors
Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection is already provided or
not required.
Note: UL489 devices can be used in place of UL1077; UL1077 devices cannot be used in place of UL489.
Book 3 (14.3) 1 - 8 0 0 - 633 - 0 4 05