AUL06 – Newest of Ethernet/IP
Discover the Microsecond
Martin Strömberg – Commercial Engineer IA – Sweden
Veysel Saylam – Commercail Engineer Logix and Networks - EMEA
Rev 5058-CO900B Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Agenda
Time Synchronization using CIP Sync
1756 High Performance I/O modules
Lab Overview
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 2
Time Synchronization (CIP Sync/ Motion)
What?
– Gives us System-wide synchronization for CIP-based Networks Time
• CIP Sync™ = CIP Network + IEEE-1588 Sync
• Implementation of IEEE-1588 on EtherNet/IP Networks Object
– IEEE- 1588PTP (Precision Time Protocol) PTP
• “Standard for a Precision Clock Synchronization Clock
Protocol for Networked Measurement and Control Systems”
• “Precision Time Protocol” (PTP) defined by standard.
• Nanosecond resolution
• +/- 100 nanosecond synchronization (Hardware
assist clock)
― Advantages:
• Minimal installation and administration
• Wide spectrum of clock accuracy
• Low cost, high precision
Copyright © 2008 Rockwell Automation, Inc. All rights reserved. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 3
Time Synchronization (CIP Sync/ Motion)
Devices that support CIP Sync/ Motion
– ControlLogix Controllers 1756-L6x and L7x
• Also in redundant systems (V19 or higher)
– 5370 CompactLogix controllers L1, L2 and L3
– ControlLogix™ Ethernet Scanners 1756-EN2T/ EN3T(R)
• Transparent/ Boundary Clock Mode Capabilities
– Sequence of Event CLX I/O 1756-IB/IH16ISOE
– ControLogix High Performance IO modules
– Digital (1756-IB16IF, OB16IEF(S)) and analog (1756-IF8I , 1756-IRT8I, 1756-OF8I)
– ArmorBlock Distributed I/O 1732E-IB8M8SOER / 1732E-IB8M8SOER
• Transparent Clock Mode Capabilities
– Stratix 8000 / 8300 / 5700 Ethernet Switch
• Transparent/ Boundary Clock Mode Capabilities
– EtherNet/IP Tap 1783-ETAP
• Transparent Clock Mode Capabilities
– Kinetix 6500 / 5500 / 350 Drive
• Transparent Clock Mode Capabilities
– PowerFlex 755
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 4
Time Synchronization (CIP Sync/ Motion)
CIP Sync/ Motion Applications
– Synchronize all CLX Controller wall clocks on the network.
Controller Control Logix Controller Control Logix Controller
Clocks Synched Remote Chassis #2 Clocks Synched Remote Chassis #3 Clocks Synched
(B) (C)
Control Logix
Local Chassis #1
(A)
E E E
N
L2 N L N L
7T 2 6 2 7
X T X T X
GM S S S
Stratix 8000 (1588PTP)
Transparent/ Boundary Modes
Control Logix Controller Control Logix Controller
Remote Chassis #3 Clocks Synched Remote Chassis #3 Clocks Synched
(D) (E)
E E
N L N L
2 7 2 7
T X T X
S S
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 5
Time Synchronization (CIP Sync/ Motion)
CIP Sync/ Motion Applications
– Synchronize multiple motion axis ControlLogix
• Combined with DLR, this is a great solution for very
long conveyer line applications or……
• Each Embedded Dual port device is actually a
managed switch with Transparent Mode capabilities
1756-ENxTR EtherNet/IP
Kinetix 6500 Tap
Point I/O ArmorBlock I/O
PowerFlex 755
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 6
Time Synchronization (CIP Sync/ Motion)
CIP Sync/ Motion Applications
– Synchronize multiple motion axis
• Printing applications that require a specific pattern be
printed using multiple drives.
Position n
Time
Position 1 Time 1 5
Position 2 Time 2 4
3
Position ‘n’ Time ‘n’ 2
1
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 7
Time Synchronization (CIP Sync/ Motion)
CIP Sync/ Motion Applications
− Synchronize SOE I/O devices for sub-microsecond time Database
stamping resolution.
• Used extensively in the Power Industry for First Fault Controller Clocks
Detection. Synched
Controller Clocks
Synched
Stratix 8000
ES D ES
NO O NO
L2E U 2E L
6T T T 6
R X
XR
GM S S
CLX CLX
Chassis Chassis
#1 #2
Event TS Stratix 8000 Event TS
done here. done here.
S S
1732E- 1732E-
IB16M12SOEDR IB16M12SOEDR
Armor Block I/O #1 Armor Block I/O #2
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 8
Time Synchronization (CIP Sync)
ControlLogix Redundancy (V19.5x or higher)
• Control of I/0 modules on Primary UTC Secondary UTC
Ethernet Chassis Chassis
• CIP Sync synchronizes time PP2=31 ER PP2=42 ER
of all controllers, network L NM L NM
devices and SOE modules. 72 72
XT XT
• 1756HP-TIME (GPS) module
used as the Real Time S S
Source and Grand Master
(GM) of time on the Network. P F. O. Cable UTC
Synchorizes PTP and NTP T PTP
devices. P E GS SS SS
PTP N P O OO OO
PC PTP 2 S E EE EE
T
NTP Ethernet
NTP Switch S GM
HMI PTP PTP/ NTP Real Time Source
UTC
UTC
E D DD D D E SS SS SS
L NI I I I I N OO OO OO
7 2 O OO O O 2 EE EE EE
XT T
P2=3
S S
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Sequence of Events Module
1756-IH16ISOE /-IB16ISOE (v2.7 or higher)
Integrated support for CIP Sync
Allows high precision timestamping with “Real Time” values that originate
from time source on Standard Ethernet
SOE architectures are simplified with the elimination of SyncLink and GPS
modules which are no longer required in multi-chassis systems
“x10 FIFO Mode”
Allows the retrieval of 10 Event Timestamps per RPI (versus 1 today) to
accommodate high speed applications
Response time improved 10 fold for high speed applications
Provides best of breed technology and cost effectiveness for SOE/first fault
detection systems
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Sequence of Events Module Analog I/O Blocks
Discrete I/O
1732E ArmorBlock IO (IP67) Blocks
CIP Syn – Time- RTD/Thermocouple
Stamping Input & I/O Blocks
Scheduled Output
I/O Blocks
Total IP67 Blocks: 1732 – 44 catalogues
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 11
Sequence of Events Module
1732E – CIP Sync ArmorBlock for Position-Based Control
2 CIP-Sync 1732E Slim ArmorBlock Digital Modules
1732E-IB8M8SOER
8 CIP Sync Sequence-of-Events input module
Inputs are time-stamped
2048 buffer memories per block
Max jitter of 25 microseconds
1732E-OB8M8SR
8 CIP Sync Scheduled Output sourcing module
Outputs are updated at a specific schedule time
High accuracy scheduling increments of 1 microseconds
Ability to fire multiple outputs at high speed interval of 100 microseconds
Support 16 schedules per coarse update period
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 12
World Class DC I/O Solution
Advanced Input / Output functionality built into the Digital modules:
• Inputs: Event Task triggers with Input Pattern Matching / CIPSync Timestamps with 4uS
accuracy
• Outputs: Per-point Pulse Width Modulation / Per-point Scheduling within 10uS of desired time
• Arguably the fastest field-side hardware with symmetrical On/Off performance in the industry
More capable solution for multiple Counter applications
Chassis Peer-Peer solution featuring screw to screw throughput of <100uS
1756-OB16IEF 1756-LSC8xIB8I 1756-IB16IF 1756-OB16IEFS
Fast Peer Output 8 Chnl Peer Counter Fast Peer Input Scheduled Output
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
What is Peer-to-Peer I/O Control?
Peer-to-Peer I/O Control is output actuation based on input data,
independent of the programmable automation controller (PAC).
Throughput speeds are drastically reduced as outputs are turned on and off without
intervention from the PAC.
Here’s how it works:
1. the input module is configured to “produce” data
2. the output module establishes a connection to the input module
3. the output module “listens” for the data the input module is producing
4. the output module energizes outputs when it “hears” the required parameters
Configuration Input Module
produces data
Controller Info Output
Configuration
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 14
Example Use Cases
Peer-to-Peer I/O Control
Peer control allows outputs on the 1756-OB16IEF module to energize within
50µS of input peer pre-conditions being met.
Max # of Pulses
Per Cycle Limit
Glue
Trigger an Event Based Task Apply Glue Now
Single Input OR a Combination of Inputs Sensor
* S S Glue Gun Control
* S S* S Variable Pulse train to Heating
* Element from PID Calculation
* *S S
* *S Temp Feedback to Analog Input
Simple Flowmeter / Solenoid Valve Control Heated Vessel
Time-Proportioned Control Applications
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 15
Lab Agenda
Lab 1 – Time Synchronization using CIP Sync
Synchronizing controllers WCT
Sequence of Events
Lab 2 – In-Cabinet High-Speed I/O Control: 1756 Fast I/O
Modules
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 16
Thank you for participating!
Please remember to tidy up your work area for the next session.
We want your feedback! Please complete the session survey!
Follow ROKAutomation on Facebook & Twitter. Copyright © 2012 Rockwell A1ut7omation, Inc. All rights reserved.
Connect with us on LinkedIn.
www.rockwellautomation.com