E65 B1052 w † 1-800-544-7769 † Fax: (763) 553-0708 † TURCK Inc. Minneapolis, MN 55441 WHAT ARE ROD LEVEL SENSORS AND CONTROLLERS? TURCK liquid level probes may be

Discover the best professional documents and content resources in AnyFlip Document Base.
Search
Published by , 2016-08-24 03:12:02

TURCK Conductive Rod Level Sensors - clrwtr.com

E65 B1052 w † 1-800-544-7769 † Fax: (763) 553-0708 † TURCK Inc. Minneapolis, MN 55441 WHAT ARE ROD LEVEL SENSORS AND CONTROLLERS? TURCK liquid level probes may be

CONDUCTIVE ROD LEVEL SENSORS
PRODUCT OVERVIEW

WHAT ARE ROD LEVEL SENSORS WHY CHOOSE ROD LEVEL
AND CONTROLLERS? SENSORS AND CONTROLLERS?

TURCK liquid level probes may be ■ Adjustable sensitivity
used in conjunction with TURCK level ■ Single set-points
control monitors, to provide a simple ■ Multiple inputs
solution for liquid level applications. ■ On/off delay
The resistance between the terminals is ■ Programmable outputs
measured to determine the level of the
medium in the tank. WHERE CAN I USE ROD LEVEL
SENSORS AND CONTROLLERS?
TURCK also offers stainless steel probes
and stainless steel holders with ceramic ■ To control the filling and draining of a
insulators. The probes are used to
provide single-point level control, tank, or as high and low level alarms.
while the holders are sealed to
withstand applications up to 2500 psi ■ To differentiate between a variety
at 70° F (21°C).
of liquids, as well as distinguishing
between liquid and foam.

■ To set an adjustable on and

off-delay for use in turbulent
liquid level applications.

■ To control overflow monitoring.

Level Detection Application Examples MAX Time
MIN On On Off Off On
Control for Pump-in
“Filling” a Tank Example Application using MK91-12-R/...

The MK91-12-R will start a pump or
open a fill valve when the liquid drops
below the MIN level probe and will
remain on until the MAX level probe is
reached. The relay then de-energizes
and stays off until the MIN level is
reached. The pump or valve does not
cycle constantly, as would be the case if
only one sensor were used.

Control for Pump-out
“Draining” a Tank

The MK91-12-R will start a pump when MAX Time
the liquid reaches the MAX level probe MIN On On Off Off On
and remain on until the MIN level probe
is reached. The relay then de-energizes Example Application using MK91-12-R/...
and stays off until the MAX level is
reached. The pump or valve does not
cycle constantly, as would be the case if
only one sensor were used.

E65 B1052 w • 1-800-544-7769 • Fax: (763) 553-0708 • TURCK Inc. Minneapolis, MN 55441

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

MK91-121-R.. and MK91-12-R..

Galvanic Isolation between input, output and supply circuits, test voltage 2.5 kVrms

Probe Voltage 0.02-5 VPP/150 Hz (delta)

Sensitivity Ranges (Switching Thresholds)

- Range 1 0.2-1 kΩ

- Range 2 0.8-4 kΩ

- Range 3 2.5-15 kΩ

- Range 4 10-100 kΩ

Hysteresis approx. 10%

Switch-on Delay 0-20 s (adj.)

Switch-off Delay 0-20 s (adj.)

Contact Material silver alloy + 3 µ Au

Switching Capacity ≤500 VA / 60 W

Protection IP20

Mounting DIN 50022 or pull-out tabs

Operating Temperature -25°C to +60°C (-13°F to +140°F)

Line Frequency (AC) 48-62 Hz

Ripple (DC) ≤10%

MS91-12-R..

Galvanic Isolation between input, output and supply circuits

Probe Voltage typ. 5 VPP/100 Hz (delta)

Sensitivity Ranges (Switching Thresholds)

- Range 1 0.1-1 kΩ

- Range 2 0.5-5 kΩ

- Range 3 2-20 kΩ CONDUCTIVE RODS

- Range 4 10-100 kΩ

Hysteresis 10%

Switch-on /Switch-off Delay 0.1-15 s (adj.

Contact Material AgCdO

Switching Capacity ≤500 Va/60 W

Protection IP20

Mounting DIN 50022 or pull-out tabs

Operating Temperature -25°C to +60°C (-13°F to +140°F)

Line Frequency (AC) 48-62 Hz

Ripple (DC) ≤10%

MK91-R11.. between input and output circuit, insulation test voltage 4 kV/8 mm
input circuit and supply voltage galvanically connected
Galvanic Isolation ≤1%

Switching Point Deviation in Supply V = 24 V, RM = 40 k
Voltage Range f = 1 Hz
Operating Characteristics at: ±2 V
±50 µA
- Rectangular Signal silver alloy + 3µ Au
- Amplitude of Electrode Voltage ≤500 VA / 60 W
- Amplitude of electrode current IP20
Contact Material DIN 50022 or pull-out tabs
Switching Capacity -25°C to +60°C (-13°F to +140°F)
Protection 48-62 Hz
Mounting ≤10%
Operating Temperature
Line Frequency (AC)
Ripple (DC)

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Housing Style Part Number ID Number PNruombebser of
Probe Holder WCC-1138 (PMprsaeixs)isumruem
FClouindnection
Probe Holder
A3365 1 2500 Dryseal
3/8-18UNC
PTF-SAE
Short thread

WCT-2 A3375 2 2500 Dryseal
1-11 1/2 UNC
PTF-SAE
Short thread

Material 303/304 Stainless Steel
Ceramic
Probe Holders 304 Stainless Steel
Insulators
Probes

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Housing Style Part Number ID Number Material
Stainless Steel Probes 91-SSP 01 Ft A3000 304 Stainless Steel
91-SSP 02 Ft A3002 304 Stainless Steel
1/ 4 -20 THD 91-SSP 03 Ft A3004 304 Stainless Steel
91-SSP 04 Ft A3006 304 Stainless Steel
LENGTH 91-SSP 05 Ft A3008 304 Stainless Steel
(See Part Number) 91-SSP 06 Ft A3010 304 Stainless Steel
91-SSP 07 Ft A3014 304 Stainless Steel
91-SSP 08 Ft A3016 304 Stainless Steel
91-SSP 09 Ft A3018 304 Stainless Steel
91-SSP 10 Ft A3020 304 Stainless Steel

For use with Amplifiers on pages D55.

CONDUCTIVE RODS

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]