Eaton_Product Overall

Eaton_Product Overall

© 2019 Eaton. All rights reserved.. Eaton’s electrical business Power distribution products


2 © 2018 Eaton. All rights reserved.. Comprehensive range of power distribution and control products, services & solutions


3 © 2018 Eaton. All rights reserved.. Leverage global innovation to develop a right product for you Type tested panel Non-type tested panel Right protection device for right markets Power Secure series


© 2018 Eaton. All rights reserved.. ACB


5 © 2018 Eaton. All rights reserved.. Eaton Low Voltage Air Circuit Breaker Technology Evolution 1930 1967 1976 1980 1999 2009 Performance & Features World’s first ACB in 1930! DA • ANSI C37.13 • Open Frame • De-Ion Arc Chutes • Solenoid Operated • Low Ratings • Electro-Mech Trip DS • ANSI (UL 1066) • Metal Frame • Stored Energy Spring Mechanism • Solid State Peak Trip Unit • Medium Ratings •200kA Interruption with Limiters • Up to 4000A Rating SPB • UL 489 • Insulated Case Circuit Breaker • Stored Energy Spring Mechanism • Solid State Peak Trip Unit • Medium Ratings • 150kA w/o Limiters • IEC Ratings DigiTrip Trip Unit • True RMS sensing • Provides ability to coordinate with time delay. • Provides metering capability. • Provides communication capability. • Programmable IZM97/99(MWI) Magnum • Global Product Offering - KEMA KEUR Mark • Smaller Size • High Ratings - 100kA w/o Limiters - Up to 6300A Rating • Magnetic Blow-On Contacts • Field Installable Accessories • Dual Micro Processor Trip Unit • Zone interlocking •200 ka current limiting & Selective Frames •Arc reduction maintenance system IZM91(NES) Series NRX • Small size • 65ka interrupting • 42ka withstand • Plug & play Accessories • High performance Trip units • Communication modules • Maintenance free • Rogowski sensors


6 © 2018 Eaton. All rights reserved.. Value line (IZM6) IZM6(55 / 66kA) IZMX Series IZMX16 IZMX40 IZMX63 Breaking Capacity 100/105kA(H) 100kA(H) 85kA(N) 85kA(N) 66kA(H) 65/66kA(B) 50kA(N) 42kA(B) Frame Current(In) 630A~1600A (Narrow Frame) 800A~4000A (Regular Frame) 4000A~6300A (Double Frame) Overview of Range (ACB) IZM6 (1140 Vac, 50 kA, 65 kA, 85 kA) Solar Application


7 © 2018 Eaton. All rights reserved.. Series IZMX(NRX) /Magnum Competition Size Comparison 15.79” 18.54” 18.54” 15.79” 15.63” 20.43” 18.35” 17.28” 18.15” 17.64” 17.72” 18.11” 17.36” 23.38” 16.69” 4000A RF Frame Siemens 3WL Schneider NW ABB Emax 4000A IEC normal Depth Width Height Volume Cu inches Vol var vs NRX 4649 6712 6161 4737 6632 > 44% > 33% > 2% > 43%


8 © 2018 Eaton. All rights reserved.. Frame size-related accessory „Common Frame size-related accessory IZMX - Options and Accessories


9 © 2018 Eaton. All rights reserved.. Horizontal 3200A and below IZMX - Flexible Connection Vertical 3200A and below Horizontal 4000A Vertical 4000A Plant change Customer change Plant change only


10 © 2018 Eaton. All rights reserved.. IZMX - Performance Ratings Thermal 60947-2 Rated Current 630A 800A 1000A 1250A 1600A 40o C [A] 630 800 1000 1250 1600 50o C [A] 630 800 1000 1250 1500 60o C [A] 630 800 1000 1250 1400 70o C [A] 630 800 1000 1250 1350 Rated Current 800A 1000A 1250A 1600A 2000A 2500A 3200A 4000A 40o C [A] 800 1000 1250 1600 2000 2500 3200 4000 50o C [A] 800 1000 1250 1600 2000 2500 3200 4000 2) 60o C [A] 800 1000 1250 1600 2000 2500 3200 3650 2) 70o C [A] 800 1000 1250 1600 2000 2280 3200 3500 2) 1) No derating for the full range to work under +40o C and below 2) Rated continuous current stated applies only with 4 x 120 x 100 mm vertical terminal rails painted black. The values are reduced by 100A each with 4 x 100 x 10mm


11 © 2018 Eaton. All rights reserved.. IZMX - New PXR Trip Unit Platform Exclusively available on IZMX series Breakers LCD and current measurement as standard on all models A V U P IZMX PXR Platform PXR10 PXR20 PXR25 PXR35(l2019) Std.:Basic LSI/LSIG protection Std.: LCD, current Opt.: Communication, Arcflash Reduction Maintenance System Std.: PXR20+voltage, power, communication, waveform Opt.: Arcflash Reduction Maintenance System Std.: PXR25+Color LCD, touch screen, harmonics, programmable digital relay output, etc. Opt.: Arcflash Reduction Maintenance System


12 © 2018 Eaton. All rights reserved.. IZMX - Flexible and cost effective communication Increased operating safety and flexibility based on communication PXR20(V type) PXR25 (U type) USB Standard Standard Embedded Modbus Optional Standard External CAM module Optional Optional USB: Test, diagnostics, parameter setting Onboard Modbus: Monitoring External CAM: Monitoring, remote control , Time-adjustment, event record, waveform record Embedded Modbus: monitoring only


13 © 2018 Eaton. All rights reserved.. IZMX - Power Xpert Release Configuration Tool Through the micro-USB connector, the PXR trip unit can be connected to the PC and configured via the Power Xpert Release tool: • Trip test • Waveform capture • Diagnostics • Long trip curve setting • ZSI/Thermal Memory on/off


14 © 2018 Eaton. All rights reserved.. ARMS Technology TM Overview Arc Flash Reduction Maintenance System ARMS is a separate integral analog circuit that when enabled in the Maintenance Mode, ARMS TechnologiesTM provides an accelerated instantaneous trip to reduce arc flash (system can trip within 40ms!) The operator can pre-select from 5 levels of protection to facilitate the maximum arc flash reduction while avoiding nuisance tripping during planned start-up and maintenance operations without disturbing the normal operational trip unit settings Local and remote enabling and indication capabilities are provided as well as consideration for Lock-out/Tag-out procedures


17 © 2018 Eaton. All rights reserved.. • Thermal Memory electronically simulates the thermal condition of the electrical distribution system to prevent overheating caused by repeated overload conditions. • Thermal Memory function will cause faster trip times in sequential testing of breaker poles! • The electronic trip unit Thermal Memory function replicates the bimetal function of a mechanical trip unit. • Will be inactive after ~ 10min Thermal Memory


18 © 2018 Eaton. All rights reserved.. Ground Fault Protection • Three types of Ground Fault Protection • Residual – Vector sum of currents with individual current sensors(11,12) • Source – Monitors actual current from a ground electrode or bonding jumper.(17,18) • Zero-Sequence – Also a vector sum, monitors 3-4 wire with a single sensor.(17,18) • Ground alarm is available without protection if desired.


19 © 2018 Eaton. All rights reserved.. Neutral Sensor Wiring RF Sensor NF Sensor


20 © 2018 Eaton. All rights reserved.. Source Ground / Zero Sequence


28 © 2018 Eaton. All rights reserved.. Power Safe Line (PSL) ACB


29 © 2018 Eaton. All rights reserved.. Performance without compromise Unbeatable value throughout its lifecycle No deratings under 40C Fully protected neutral line on 4P type4 pole breakers IEC/EN 60947 Power Safe Line (PSL): More flexible…more value 2 Frame size: • 2000A frame: 800 – 2000 A • 4000A frame: 2500 – 4000 A • 100% In in N-pole 2 Breaking capability: • PSL5: Icu = Ics = Icw = 55kA • PSL6: Icu = Ics = Icw = 66kA Breaking and closing time: • Breaking: ≤30ms • Closing: ≤70ms


30 © 2018 Eaton. All rights reserved.. PVR21: • LED digital with current measurement • LSI and LSIG protection Flexible trip unit for right application PVR21V: • LED digital with current + voltage measurement • LSI, LSIG protection


31 © 2018 Eaton. All rights reserved.. 1 2 3 4 5 6 7 9 8 10 11 12 1. PSL circuit breaker PSL5: 55kA PSL6: 66kA 800~4000A, 3P/4P, drawout/fixed type 2. Control terminal block 3. Auxiliary switch None/4a4b/6a6b 4. Phase barrier Default assembled on 2500~4000A optional for 800~2000A 5. Under voltage release R: 220Vac / 110Vdc C: 24Vdc 6. Shunt trip / Spring release R: 220Vac / 110Vdc C: 24Vdc 7. Motor operator R: 220Vac / 110Vdc C: 24Vdc 8. Mechanical interlock 9. Door frame 10. Keylock 11. Operation counter Full of accessories to match with your application


32 © 2018 Eaton. All rights reserved.. Benchmark with others… Eaton vs Schneider 42 kA 50 kA 65 kA 85 kA 630 A >105 kA 800 - 2000 A 2500 - 4000 A 4000b - 6300A MVS MasterPact NW/MTZ MasterPact NW/MTZ IZMX PSL IZMX


33 © 2018 Eaton. All rights reserved.. Benchmark with others… Eaton vs ABB 42 kA 50 kA 65 kA 85 kA 630 A >105 kA 800 - 2000 A 2500 - 4000 A 4000b - 6300A Formula Air EMax2 EMax2 IZMX IZMX PSL


36 © 2018 Eaton. All rights reserved.. Update Price positioning: Eaton vs competitors 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 55kA LSI Fix 55kA LSI Withdraw 55kA LSIG Fix 55kA LSIG Withdraw 65kA LSI Fix 65kA LSI Withdraw 65kA LSIG Fix 65kA LSIG Withdraw Value Line ACB price index Eaton Schneider ABB


© 2018 Eaton. All rights reserved.. MCCB


38 © 2018 Eaton. All rights reserved.. Current (In) PDC H 100/150kA NZM/LZM 16-1000A 20-1600A N 50kA S 75kA Overview of Range (MCCB) 16—400A BZM Interrupting Capacities Icu N 50kA C 36kA B 25kA C 36kA B 25kA N 50kA C 36kA B 25kA E 18kA D 15kA


39 © 2018 Eaton. All rights reserved.. NZM/LZM Product Overview • Global Tier 1 Product • Wide Range of Current Ratings and Interruption Capacities • System and Cable, Motor and Generator Protection • Thermal Magnetic/ Electronic Trip Units • Complete Accessories Family NZM1, N1,PN1 Iu ~ 160A NZM2, N2,PN2 In ~ 300A NZM3, N3,PN3 Iu ~ 630A NZM4, N4,PN4 Iu ~ 1600A


40 © 2018 Eaton. All rights reserved.. Technical Overview Icm @400/415V 50/60Hz Up to 220kA Up to 330kA Up to 330kA Up to 220kA Icu @400/415V 50/60Hz Up to 100kA Up to 150kA Up to 150kA Up to 85kA Ics @400/415V 50/60Hz Up to 50kA Up to 150kA Up to 150kA Up to 43kA Mechanical endurance 20000 20000 15000 10000 Electrical endurance 10000 10000 5000 3000 Max. operating frequency Ops/h 120 120 60 60 Utilization category IEC/EN60947-2 A A A B NZM1 NZM2 NZM3 NZM4 Standards IEC/EN 60947 Rated impulse withstand voltage, Uimp 8000Vac Rated operating voltage Ue 690Vac Reated insulation voltage Ui 1000V Ambient Temp °C (Operation) -25~70 Direction of incoming supply Any Buit-in position Vertical and 90°in all directions (Plug-in,Withdrawable and with remote operator, reference to catalog)


41 © 2018 Eaton. All rights reserved.. NZM Global Certification


42 © 2018 Eaton. All rights reserved.. No Derating! Iu = 100%In max 50°C Good Performance in Harsh Environment Derating form– see catalog


43 © 2018 Eaton. All rights reserved.. Trip Units Contents -S -A,-M -AE -ME -VE Long Delay Protection Ir Adj. Adj. Adj. Adj. Adj. Long Delay tr Adj. Adj. Short Delay Protection Isd Adj. Short Delay tsd Adj. Instantaneous Ii Adj. Adj. Adj. Adj. TMTU ETU -M, -ME, for Motor Protection


49 © 2018 Eaton. All rights reserved.. Circuit Breakers with Residual Circuit Protection IΔn= 0,03A – 3A IΔn= 0,03A – 1A I NZM1-XFI… Δn= 0,03A – 3A NZM2-4-XFI… XFI… PFR-003-I∆n=30mA PFR-03- I∆n=300mA PFR-5- I∆n=30mA – 5A Tr=0.02~5A PFR… • External residual current replay up to 1800A. • External auxiliary voltage supply required; • For circuit breakers/ switch disconnector series; • Up to 250A, no external auxiliary voltage supply;


50 © 2018 Eaton. All rights reserved.. Flexible mounting and connection Connection preparation Control circuit terminal for multiple conductors Back of hand or finger-proof Box terminal for copper cable Rear connection


51 © 2018 Eaton. All rights reserved.. Parallel drive for PN1~ 3 enable simultaneous switching with just a single action – e.g. with main or auxiliary circuits. Mechanical interlock components of NZM1~4 enable the interlocking of two or three switches, equipped with rotary handles or door coupling rotary handles. Easy to handle, safe to operate


52 © 2018 Eaton. All rights reserved.. Wide range of diagnostics and communication features 1 Direct signaling 2 Checked on-site 3 Fieldbus control 4 Remote monitoring


53 © 2018 Eaton. All rights reserved.. BZM Series MCCB Compact Smallest Design, saving space Easy Fixed trip units, easier and quick installation Reliable First-class quality Economic Cost saving for simple applications Comply with IEC60947 and CCC Bonn/Pittsburg/Suzhou R&D support Germany/Romania/China manufacturing, with Germany technology and standards.


54 © 2018 Eaton. All rights reserved.. BZM Series MCCB BZM1 -1p, -2p, -3p Rated current:20-125A Breaking capacity:18/25/36kA Rated voltage:440/415Vac Width per pole:25mm次 Mechanical endurance:10000 BZM2 -3p Rated current:125A-250A Breaking capacity: 25﹑36kA Rated voltage:440/415Vac Mechanical endurance:8000 BZM3 -3p Rated current:250A-400A Breaking capacity: 25/36/50kA Rated voltage:440/415Vac 25mm 50mm


55 © 2018 Eaton. All rights reserved.. 55 Box Terminal Cabling up to 50mm² Screw Terminal Screw M6 (BZM1) Screw Terminal v.s Box Terminal BZM provide both terminals: BZM1… BZM1…-BT


56 © 2018 Eaton. All rights reserved.. Power Defense Product Line at a Glance PDC1 16-160A PDC2 16-250A PDC3 200-630A PDC4 320-1000A Poles 3,4 3,4 3,4 3,4 T/M TU Adj/Adj Adj/Adj Adj/Adj Adj/Adj PXR ETU* 10/20/25 10/20/25 10/20/25 Icu (@415Vac) 25,36,50 kA 25,36,50 kA 25,36,50 kA 36,50 kA Ics (@415 Vac) 25,36,50 kA 25,36,50 kA 25,36,50 kA 36,50 kA Accessories • Aux, Shunt trip, UVR, Bell Alarm Switches, Interlock • Plug-in Adapters • Rotary handles, RCD, Remote operators etc • Keylocks, IP protection * - PXR availability is in year 2020


57 © 2018 Eaton. All rights reserved.. Thermal Magnetic Offering PDC1 • Current Rating 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160A • Interrupting current 25kA, 36kA, 50kA @ 415VAC • Maximum rated voltage 690VAC • Terminal type Box terminal • Shunt trip 1 connection • Undervoltage release 1 connection • Long delay setting 0.8 – 1.0In • Short delay setting< 32A (fixed), 8 – 1.0In • Phase-to-phase splitter Optional • Terminal cover Optional • Finger protection Optional (IP20) • DIN Rail Optional • Rotary handle Direct/extension shaft • Remote operator Optional • RCD Optional • Unique Product Feature • Adjustable/Adjustable • 100% neutral protection


58 © 2018 Eaton. All rights reserved.. • Current Rating • PDC2 : 125, 160, 200, 250A • PDC3 : 250, 320, 400, 500, 630A • Interrupting current 25kA, 36kA, 50kA @ 415VAC • Maximum rated voltage 690VAC • Terminal type Screw terminal • Shunt trip 1 connection • Undervoltage release 1 connection • Long delay setting 0.8 – 1.0In • Short delay setting< 5 – 1.0In • Phase-to-phase splitter Standard • Terminal cover Optional • Rotary handle Direct/extension shaft • Remote operator Optional • RCD Optional • Unique Product Feature • Adjustable/Adjustable • 60%/100% neutral protection • Ics = 100% Icu Thermal Magnetic Offering PDC2&3


59 © 2018 Eaton. All rights reserved.. • Current Rating 800, 1000A • Interrupting current 36kA, 50kA @ 415VAC • Maximum rated voltage 690VAC • Aux Contacts 4 (3P), 7 (4P) • Alarm contacts 2 (3P/4P) • Terminal type Screw terminal • Shunt trip 1 connection • Undervoltage release 1 connection • Long delay setting 0.8 – 1.0In • Short delay setting< 5 – 1.0In • Phase-to-phase splitter Standard • Terminal cover Optional • Rotary handle Direct/extension shaft • Remote operator Optional • RCD Optional • Unique Product Feature • Adjustable/Adjustable • 60%/100% neutral protection • Ics = 100% Icu Thermal Magnetic Offering PDC4


62 © 2018 Eaton. All rights reserved.. Update Price positioning: Eaton vs competitors 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 25kA 160AF 36kA 160AF 50kA 160AF 36kA 250AF 50kA 250AF 36kA 400AF 50kA 400AF 36kA 630AF 50kA 630AF Value Line MCCB price index Eaton Schneider ABB


© 2018 Eaton. All rights reserved.. MCB & RCCB & RCBo


64 © 2018 Eaton. All rights reserved.. Overview of Range (MCB) PLHT Series E6X series E4X series 1A----------------6A-------------------------------63A----------------------80A-------------------125A FAZ Xpole: PLS6/PLSM Residential Commercial Residential Industrial


65 © 2018 Eaton. All rights reserved.. Overview of Range ---- MCB Ratings Product type Curves Pole Config. Current Breaking Capability FAZ B,C,D K,S,Z 1,2,3,4,1P+N 3P+N 0~63A 15kA FAZ-NA(RT) B,C,D 1,2,3 1-40A 15kA FAZ-DC C 1,2 2-50A 10kA PLSM B,C,D 1,2,3,4,1P+N 3P+N 1~63A 10kA PLS6 B,C,D 1,2,3,4,1P+N 3P+N 1~63A 10kA PLN6 B,C 1P+N (18mm width) 6-40A(B) 2-40A(C ) 6kA PLS6-DC B,C 1,2 1-50A 10kA PLHT C,D 1,2,3,4,3P+N 63-125A(C ) 50-100A(D) 15-25kA E4X &E6X B,C,D 1,2,3,4,1P+N 3P+N 6~63A 4.5KA & 6kA


66 © 2018 Eaton. All rights reserved.. Indication window Guide for secure terminal connection Prevents missing the terminal when introducing the wire Colored toggles per different current rating 8 A 1 0 A 1 3 A 2 0 A 1 6 A < 2 A N 4 A 2 A 6 3 A 5 0 A 4 0 A 3 2 A 6 A 2 5 A Only X-pole possess PLS Commercial Series Unique Features


67 © 2018 Eaton. All rights reserved.. End Distribution- MCB’s, RCD’s, Commercial, Industrial & Shipboard applications RCCB / RCBo PKNM : Combine MCB and RCCB = RCBo eRBM : Combine MCB and RCCB = RCBo PFIM : RCCB 2P PFIM : RCCB 4P RCBo : มอก. 909-2548 RCCB : มอก. 2425-2552


68 © 2018 Eaton. All rights reserved.. Overview of Range ---- RCD Ratings Product Series Type Feature Curves Pole Config. Current RCD Sensitivity (mA) RCD Type PFIM RCCB ELM -- 2,4P 25-100A 30,100,300,500 AC A G S S/A PFDM RCCB ELM -- 2,4P 125A 30,100,300,500 AC A S/A FRCMx RCCB ELM -- 2,4P 10-125A 10, 30, 100, 300,500 PBSM RCD Add-on ELM -- 2,3,4P 40-63A 30,100,300,500, 1000 AC A G S S/A PBHT RCD Add-on ELM -- 2,4P 80-125A 30, 300, 500, 1000 AC A S/A PKNM RCBO 2 Mod, ELM B, C 1P+N 2-40A 10, 30, 100, 300 AC A G eRB6 RCBO 6kA,ELN 1 Mod B, C 1P+N 6-45A 10, 30, 100, 300 AC A eRBM RCBO 10kA, ELN 1 Mod B, C, D 1P+N 6-45A 10, 30, 100, 300 AC A PFL10 RCBO 10kA 2 Mod C 1P+N 6-40A 10, 30, 300 AC A PFL9 RCBO 6kA 2 Mod C 1P+N 6-40A 10, 30, 300 AC A FRBxxRCBO6KA/10K A10, 30, 100, 300500ACAGSS/Aoth ers


Click to View FlipBook Version