The words you are searching are inside this book. To get more targeted content, please make full-text search by clicking here.
Discover the best professional documents and content resources in AnyFlip Document Base.
Search
Published by Constguide, 2020-07-13 16:40:12

PRYSMIAN

A brand of the






















Certificate No 077a*



SEMI FLEXIBLE LOW FIRE HAZZARD CABLE WITH INSUDITE™























Conductor Key Applications

Plain annealed copper stranded circular conductors to meet the > Low voltage
requirements of BS EN 60228 class 2. > Single phase
> Non-essential, non-emergency circuits in the UK
Insulation > Essential or emergency circuits that require only BS6387 CWZ
approval
High performance, damage resistant Insudite™ to meet
BS EN 50363-5, Type EI5. British Standards and Approvals
Sheath > BS 7629-1:1997 Construction of screened fire resistant cables*
> BS 6387 CWZ fire resistance test
Robust thermoplastic low smoke, zero halogen and reduced flame > BS EN 50200 PH60
propagation outer sheath. Standard colours white and red with bespoke > BASEC Approved
colours available to special order. Suitable for outdoor installation with > LPCB Approved*
exposure to normal daylight without shading. > Approved by Local Civil Defence

Overall metallic screen and CPC Core identification
l
Polyester backed laminated aluminium tape bonded to outer sheath to Non harmonised Harmonised
provide overall screen. In contact with full sized, tinned annealed copper o o red-black o o brown-blue
brown-black-grey
o o o
circuit protective conductor and laid-up with the cores to provide o o o red-yellow-blue
automatic screen earthing. o o o o black-red-yellow-blue o o o o blue-brown-black-grey



Ref:FP200Flex/05/19



Fire Resistance
Temperature Bending Radius Mechanical Impact Fire Performance Flexibilty Halogen Free Low Smoke Emissions Fire resistance
Range Fixed r=6D Medium BS EN 60332-1-2 Semi flexible BS EN 50267-2-1 BS EN 61034-2 BS6387 Category CWZ
BS EN 50200 PH60
Rigid
Fixed r=4D
BS EN 50266-2-4
-20 to +70˚C BS EN 60332 - 3 - 24 BS EN 50200 PH30 & PH60 3
BS 6387 CWZ
BS EN 50200 Annex E
BSEN60332-1-2
BSEN61034-2
EN50200 PH30 & PH60

Nominal Conductor Mean Approximate Maximum Current Current Volt drop Recommended accessories
cross Construction overall cable conductor rating DC or rating DC or DC or single White or Red
sectional diameter weight resistance single phase single phase phase
area at 20°C AC AC AC Copper Nylon
®
Enclosed Clipped direct LSOH LSOH ®
mm 2 no/mm mm kg/km Ω/km Amps Amps mV/A/m fixing gland
clips
Two core

1.5 7/0.53 8.2 99 12.1 16.5 19.5 29 AP7 GL2520
2.5 7/0.67 9.6 145 7.4 23 27 18 AP9 GL2520
Three core

1.5 7/0.53 8.7 120 12.1 16.5 19.5 29 AP8 GL2520
2.5 7/0.67 10.2 176 7.4 23 27 18 AP10 GL2520
Four Core


1.5 7/0.53 9.7 149 12.1 16.5 19.5 29 AP9 GL2520
2.5 7/0.67 11.4 218 7.4 23 27 18 AP11 GL2520

Notes to table

> Recommended clip spacing 300 mm horizontal and 400mm vertical.
> Brass glands may be used as an alternative to the nylon glands recommended.
> Minimum recommended installation temperature 0°C. Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations.
> The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature. For other ambient temperatures or where cables are
grouped together, appropriate de-rating factors should be applied.























Overseas sales enquiries Middle East Region
Tel: +44 (0) 23 5029 5481 Prysmian Cables & Systems
Fax: +44 (0) 23 8029 5465 PO Box 643990
Dubai
Overseas technical UAE
Tel: +44 (0) 23 8029 5481 Tel: +971 42428104
[email protected]
Prysmian Cables & Systems Limited
Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU
United Kingdom
www.prysmiangroup.co.uk
Should you have any concerns about
unsafe, non-approved or counterfeit
cable, please contact the ACI


For further information please Tel: 020 8946 6978
see our dedicated FP Cables website: Email: [email protected]
www.fpcables.co.uk Ref: FP200Flex/ 05/19

All sizes and values without tolerances are reference values. Specifications are for A brand of the
products afterwards may give different results. The information contained within this
document must not be copied, reprinted or reproduced in any form, either wholly or in
part without written consent of Prysmian Group. Prysmian Group reserves the right to
amend this specification without prior notice.

A brand of the





















Certificate No 077b*
Certificate No 517b*

FIRE RESISTANT ARMOURED POWER CABLE - BS 7846 F2 600/1000 V

























Conductor Key Applications

Plain annealed copper stranded conductor meets the requirements > Fire resistant, low fire hazard armoured power and control cable
of BS EN 60228 Class 2 > Use for fire performance circuits in public buildings

Insulation British Standards

Mineral ceramic (Mica) fire resistant tape and 90°C cross - linked > BS 6387 CWZ*
insulation > BS 7846 F2
> London Underground S1085 Approved Product Register
Bedding > BASEC approved
> LPCB approved*
Extruded LSOH > BS EN 61034-2*
> BS EN 60754-1*

Armour Core identification
CABLE DESCRIPTION
Single layer of galvanised steel wires HARMONISED CORE IDENTIFICATION: NON HARMONISED CORE IDENTIFICATION:
o o brown-blue o o red-black l
Sheath o o o brown-black-grey o o o red-yellow-blue
o o o o black-red-yellow-blue
o o o o blue-brown-black-grey
o o o o brown-black-grey-blue-green/yellow o o o o red-yellow-blue-black-green/yellow
Extruded LSOH suitable for outdoor installation with exposure to Non harmonised colours to special order.
normal daylight UV



Ref: FP400/05/2019



Halogen Free
Temperature Bending Radius Mechanical Impact Fire Performance Flexibility Halogen Free Low Smoke Emissions Fire Resistant
Fire Performance
Flexibilty
Fire Resistant
Low Smoke Emissions
Mechnical Impact
Bending Radius
Temperature
Range Fixed r=8D Excellent BSEN60332-1-2 Rigid BSEN50267-2-1 BSEN61034-2 BS 6387 Category CWZ
BS7346-6
Rigid
Range
BS EN 61034-2
High
BS EN 60754-1
BS EN 60332-1-2
8D
-25 to +90˚C BS EN 60332-3-24 120min
BSEN50266-2-4
-25 to +90°C
BSEN60332-1-2
BSEN61034-2
EN50200 PH30 & PH60

Nominal Approximate Approximate Nominal Approximate Maximum Short Circuit Current rating Current rating Volt drop
cross overall diameter diameter cable conductor rating (1 sec) Three Three Three
sectional diameter under of armour weight resistance of conductor phase AC phase AC phase AC
area armour wires at 20°C Clipped direct Free Air
mm 2 mm mm mm kg/km ohms/km kA Amps Amps mV/A/m


Three Core
1.5 13.9 9.4 0.9 370 12.1 0.20 23 25 27
2.5 15.5 10.8 0.9 455 7.41 0.35 31 33 16
4 16.4 11.6 0.9 530 4.61 0.57 42 44 10
6 17.9 13.4 0.9 650 3.08 0.86 53 56 6.8
10 22 16.1 1.25 1000 1.83 1.4 73 78 4.0
16 24 17 1.25 1250 1.15 2.2 94 99 2.5
25 28 22 1.6 1800 0.727 3.6 124 131 1.65
35 32 25 1.6 2300 0.524 5.0 154 162 1.15
50 32 25 1.6 2600 0.387 7.1 187 197 0.87
70 35 28 1.6 3300 0.268 10.0 238 251 0.60
95 38 30 2.0 4400 0.193 13.6 289 304 0.45
120 42 34 2.0 5200 0.153 17.2 335 353 0.37
150 47 37 2.5 6600 0.124 21.4 386 406 0.30
185 51 42 2.5 7900 0.0991 26.5 441 463 0.26
240 56 47 2.5 9900 0.0754 34.3 520 546 0.21
300 61 51 2.5 11900 0.0601 42.9 599 628 0.185
400 67 57 2.5 14700 0.0470 57.2 673 728 0.165



Four Core
1.5 14.9 10.3 0.9 415 12.1 0.20 23 25 27
2.5 16.9 12.1 0.9 530 7.41 0.35 31 33 16
4 17.7 13.1 0.9 610 4.61 0.57 42 44 10
6 21 14.7 1.25 880 3.08 0.86 53 56 6.8
10 24 17.7 1.25 1150 1.83 1.4 73 78 4.0
16 25 19.3 1.25 1450 1.15 2.2 94 99 2.5
25 30 24 1.6 2200 0.727 3.6 124 131 1.65
35 34 28 1.6 2800 0.524 5.0 154 162 1.15
50 36 29 1.6 3200 0.387 7.1 187 197 0.87
70 39 31 2.0 4200 0.268 10.0 238 251 0.60
95 43 34 2.0 5300 0.193 13.6 289 304 0.45
120 48 38 2.5 6800 0.153 17.2 335 353 0.37
150 52 42 2.5 8100 0.124 21.4 386 406 0.30
185 57 47 2.5 9900 0.0991 26.5 441 463 0.26
240 63 53 2.5 12400 0.0754 34.3 520 546 0.21
300 68 58 2.5 15000 0.0601 42.9 599 628 0.185
400 77 65 3.15 19400 0.0470 57.2 673 728 0.165

Nominal Approximate Approximate Nominal Approximate Maximum Short Circuit Current rating Current rating Volt drop
cross overall diameter diameter cable conductor rating (1 sec) Three Three Three
sectional diameter under of armour weight resistance of conductor phase AC phase AC phase AC
area armour wires at 20°C Clipped direct Free Air
mm 2 mm mm mm kg/km ohms/km kA Amps Amps mV/A/m
Five Core
1.5 15.6 11.3 0.9 455 12.10 0.2 23 25 27.0
2.5 17.3 13.0 0.9 550 7.41 0.4 31 33 16.0
4 18.8 14.3 0.9 660 4.61 0.6 42 44 10.0
6 23 16.4 1.25 990 3.08 0.9 53 56 6.8
10 25 19.2 1.25 1300 1.83 1.4 73 78 4.0
16 29 22 1.6 1900 1.15 2.2 94 99 2.5
25 34 27 1.6 2600 0.727 3.6 124 131 1.65
35 37 30 1.6 3200 0.524 5.0 154 162 1.15

No LPCB approval for 5 Core, BASEC approval for 1.5-10mm² inclusive





Nominal Approximate Approximate Nominal Approximate Maximum Current rating Current rating Volt drop Volt drop
cross overall diameter diameter cable conductor DC or Single DC or Single DC Single
sectional diameter under of armour weight resistance phase AC phase AC phase AC
area armour wires at 20°C Clipped direct Free Air
mm 2 mm mm mm kg/km ohms/km Amps Amps mV/A/m mV/A/m

Two Core
1.5 13.5 9.1 0.9 345 12.1 27 29 31 31
2.5 14.8 10.3 0.9 415 7.41 36 39 19 19
4 15.8 11.4 0.9 480 4.61 49 52 12 12
6 16.6 12.1 0.9 550 3.08 62 66 7.9 7.9
10 19.9 15.1 0.9 750 1.83 85 90 4.7 4.7
16 22 16.4 1.25 1050 1.15 110 115 2.9 2.9
25 26 19.7 1.25 1400 0.727 146 152 1.85 1.9
35 29 23 1.6 1900 0.524 180 188 1.35 1.35
50 30 23 1.6 2100 0.387 219 228 0.98 1.00
70 33 26 1.6 2600 0.268 279 291 0.67 0.69
95 34 26 2.0 3200 0.193 338 354 0.49 0.52
120 37 29 2.0 3900 0.153 392 410 0.39 0.42
150 40 32 2.0 4600 0.124 451 472 0.31 0.35
185 45 35 2.5 5900 0.0991 515 539 0.25 0.29
240 50 40 2.5 7200 0.0754 607 636 0.195 0.24
300 54 44 2.5 8600 0.0601 698 732 0.155 0.21
400 59 49 2.5 10500 0.0470 787 847 0.120 0.19





2.
Circular conductor 1.5 - 35mm .
Shaped conductor 50mm and above.
2
Current ratings in accordance with BS 7671/IET Wiring Regulations.
The tabulated ratings are based upon a 30°C ambient temperature and 90°C operating temperature.
Installation
Minimum recommended installation temperature 0°C.
Suitable for indoor and outdoor installations. Should be installed in accordance with BS 7671/IET Wiring Regulations or any other appropriate national
regulations. Suitable for direct burial, trough, tray, ladder or other installations requiring a robust armoured cable.

A brand of the

























FIRE RESISTANT ARMOURED POWER CABLE - BS 7846 F2 600/1000 V



































Overseas sales enquiries Middle East Region
Tel: +44 (0) 23 5029 5481 Prysmian Cables & Systems
Fax: +44 (0) 23 8029 5465 PO Box 643990
Dubai
Overseas technical UAE
Tel: +44 (0) 23 8029 5481 Tel: +971 42428104
[email protected]
Prysmian Cables & Systems Limited
Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU
United Kingdom
www.prysmiangroup.co.uk

Should you have any concerns about
unsafe, non-approved or counterfeit
For further information please cable, please contact the ACI
see our dedicated FP Cables website:
www.fpcables.co.uk Tel: 020 8946 6978
Email: [email protected]


All sizes and values without tolerances are reference values. Specifications are for products A brand of the
afterwards may give different results. The information contained within this document must Ref: FP400/05/2019
not be copied, reprinted or reproduced in any form, either wholly or in part without written
consent of Prysmian Group. Prysmian Group reserves the right to amend this specification
without prior notice.

A brand of the





















Certificate No 077f*

THE ORIGINAL ‘STANDARD’ FIRE RESISTANT CABLE (300/500 V)
























Conductor Key Applications


Plain annealed copper. Solid (1.0 - 2.5 mm²) or stranded circular conductors > Fire detection and fire alarm systems for buildings
(4.0 mm²) to meet the requirements of BS EN 60228 class 1 or class 2. > Voice alarm systems and emergency voice communication
> Emergency and escape lighting
Insulation > Control circuits for life safety and fire fighting systems
> Other essential service control circuits for ‘standard’ fire resistance
High performance, damage resistant Insudite™ to meet BS EN 50363-5,
Type EI5. British Standards

> BS7629-1, Standard 60 (1.0mm² Standard 30)*
Overall metallic screen and CPC > BS EN 50200 PH30, PH60, PH120 and ANNEX E*
> BS 5839-1, 6, 8 & 9 ‘standard’ fire resisting cable
Polyester backed laminated aluminium tape bonded to outer sheath to > BS 5266-1 ‘standard’ fire resisting cable
provide overall screen. In contact with full sized, tinned annealed copper > BS 8519 Category 1 control cable
circuit protective conductor and laid-up with the cores to provide automatic > BASEC approved
screen earthing. > London Underground S1085 Approved Product Register
> LPCB approved*
Sheath > BS 6387 CWZ*
l
Robust thermoplastic low smoke, zero halogen and reduced flame Core identification
propagation outer sheath. Standard colours white and red with bespoke
colours available to special order. Suitable for outdoor installation with
exposure to normal daylight UV. Harmonised - standard Non harmonised – to special order
o o brown-blue o o red-black
o o o brown-black-grey o o o red-yellow-blue
o o o o blue-brown-black-grey o o o o black-red-yellow-blue

Ref:FP200Gold/05/19




Fire Resistance
Temperature Bending Radius Mechanical Impact Fire Performance Flexibilty Halogen Free Low Smoke Emissions Fire resistance
BS EN 60332-1-2
BS EN 50200 PH30
Range Fixed r=6D Medium BS EN 60332-1-2 Rigid BS EN 50267-2-1 BS EN 61034-2 BS6387 Category CWZ
BS EN 60754-1
Rigid
r=6D
-20 to +70˚C BS EN 50266-2-4 BS EN 50200 PH30 & PH60 3
PH60 & PH120
BS EN 50200 Annex E
BS EN 50200 ANNEX E
BS 6387 CWZ
BSEN60332-1-2
BSEN61034-2
EN50200 PH30 & PH60

Nominal Conductor Approximate Approximate Maximum Current Current Volt drop Recommended accessories
cross Construction overall cable conductor rating DC or rating DC or DC or single Colour - White or Red
sectional diameter weight resistance single phase single phase phase
area at 20°C AC AC AC LSOH ® Nylon TM
Enclosed Clipped direct fixing LSOH ® FP Firefix
mm 2 no/mm mm kg/km Ω/km Amps Amps mV/A/m clips gland fixing
clips
Two core
1.0 1/1.13 7.8 79 18.1 13 15 44 AP7 251/GL2520 UFPNF02
UFPNF01
1.5 1/1.38 7.9 90 12.1 16.5 19.5 29 AP7 251/GL2520 UFPNF02
2.5 1/1.78 9.5 140 7.41 23 27 18 AP9 251/GL2520 -
4.0 7/0.85 12.0 205 4.6 30 36 11 AP11 252/GL2520 -
Three core
1.5 1/1.38 8.3 115 12.1 16.5 19.5 29 AP8 251/GL2520 UFPNF04
2.5 1/1.78 10.5 180 7.41 23 27 18 AP10 252/GL2520 -
4.0 7/0.85 12.5 255 4.6 30 36 11 AP12 252 -
Four Core
1.5 1/1.38 10.0 150 12.1 16.5 19.5 29 AP9 251/GL2520 -
2.5 1/1.78 12.0 225 7.41 23 27 18 AP11 252/GL2520 -
4.0 7/0.85 13.5 315 4.6 30 36 11 AP13 254 -




Notes to table
> Recommended clip spacing 300 mm horizontal and 400mm vertical using only metallic fixings.
> Minimum recommended installation temperature 0°C. Installation methods for current rating in accordance with BS7671/IET Wiring Regulations.
> The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature. For other ambient temperatures or where cables are
grouped together, appropriate rating factors should be applied.
> De-rate by factor 0.8 when 4 cores are loaded

Correction factors for Ambient temperatures: Table 4B1


Ambient Temperature°C 25 30 35 40 45 50
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71

Correction factors for grouping of cables: Table 4C1


Number of circuits 2 3 4 5 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54
Overseas sales enquiries Middle East Region
Tel: +44 (0) 23 5029 5481 Prysmian Cables & Systems
Fax: +44 (0) 23 8029 5465 PO Box 643990
Dubai
Overseas technical UAE
Tel: +44 (0) 23 8029 5481 Tel: +971 42428104
[email protected]
Prysmian Cables & Systems Limited
Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU
United Kingdom
www.prysmiangroup.co.uk
Should you have any concerns about
unsafe, non-approved or counterfeit
cable, please contact the ACI
For further information please
see our dedicated FP Cables website: Tel: 020 8946 6978
www.fpcables.co.uk Email: [email protected] Ref: FP200Gold/05/19


All sizes and values without tolerances are reference values. Specifications are for products A brand of the
afterwards may give different results. The information contained within this document must
not be copied, reprinted or reproduced in any form, either wholly or in part without written
consent of Prysmian Group. Prysmian Group reserves the right to amend this specification
without prior notice.

A brand of the























Certificate No 077c*
Certificate No 077p*,†
THE FIRE RESISTANT SOLUTION FOR STEEL CONDUIT

























Conductor Performance Standards
CABLE DESCRIPTION Plain annealed copper stranded conductor meets the requirements of
BS EN 60228 Class 2 > 450/750 V and 600/1000 V
> BS 6387 Category CWZ*
> BS EN 60754-1
Insulation > BS EN 61034-2*,†
> IEC 60331-21*
> Use in screwed steel conduit to achieve fire rating
Mineral ceramic (Mica) fire resistant tape and 90°C cross - linked > LPCB Approved*
insulation > Low smoke, zero halogen, flame retardant
> BS EN 502767-2-1*
Key Applications
Core identification
> Consider using FP100 when FP200 Gold, FP PLUS or FP600S are
unsuitable o red o brown o black o yellow o orange
FIRE RESISTANT CABLES o grey o blue green/yellow LOW VOLTAGE
> Emergency lighting, fire alarm or other emergency systems when
installed in screwed steel conduit
Other core colours available on request
600/1000 V *
l


FP100 ®






Ref:FP100/05/2019


Temperature Range Bending Radius Mechanical impact Fire Performance Flexibility Halogen Free Low Smoke Emissions Fire Resistant
Fire Resistant
Bending Radius
Low Smoke Emissions
Halogen Free
Fire performance
Flexibility
Tempreture Range
Mechanical impact
-25 to +90°C
IEC 60331-21
-25 to +90ºC≠ up to 8mm diameter r=4D Requires protection BSEN60332-1-2 Semi-flexible BSEN50267-2-1 BS EN 61034-2 IEC 60331-21
BS EN 60332-1-2
Semi-flexible
Requires protection
up to 8mm diameter r=4D
BS EN 60754-1
BSEN61034-2
above 9mm diameter r=6D BS 6387 Category CWZ
BS6387 Category CW Z*
above 8mm diameter r=6D
EN50200 PH120*
BS8434-2 120min*
*When tested in Steel Conduit

Nominal Approximate Approximate Maximum Short Current Current Volt drop Volt drop Volt drop
cross overall cable conductor circuit rating rating DC Single Three
sectional diameter weight resistance rating DC or single Three phase AC phase AC
area at 20°C (1 sec) phase AC phase AC

mm 2 mm kg/km Ω/km kA Amps Amps mV/A/m mV/A/m mV/A/m

Single Core
1 .5 3.9 27 12.1 0.20 23 20 31 31 27
2.5 4.6 41 7.41 0.35 31 28 19 19 16
4 5.1 55 4.61 0.57 42 37 12 12 10
6 5.6 77 3.08 0.86 54 48 7.9 7.9 6.8
10 7.5 135 1.83 1.4 75 66 4.7 4.7 4
16 8.1 190 1.15 2.2 100 88 2.9 2.9 2.5
25 9.5 280 0.727 3.6 133 117 1.85 1.9 1.65
35 10.6 370 0.524 5.0 164 144 1.35 1.35 1.15
50 12.2 500 0.387 7.1 198 175 0.99 1.05 0.9
70 14.1 710 0.268 10.0 253 222 0.68 0.75 0.65
95 16 965 0.193 13.6 306 269 0.49 0.58 0.5
120 17.4 1200 0.153 17.2 354 312 0.39 0.48 0.42
150 19.3 1500 0.124 21.4 393 342 0.32 0.43 0.37
185 22 1850 0.0991 26.5 449 384 0.25 0.37 0.32
240 25 2400 0.0754 34.3 528 450 0.19 0.33 0.29
300 27 3100 0.0601 42.9 603 514 0.155 0.31 0.27
400 31 3800 0.0470 57.2 683 584 0.120 0.29 0.25
500 35 4900 0.0366 71.5 783 666 0.093 0.28 0.24
630 38 6200 0.0283 90.1 900 764 0.072 0.27 0.23
Notes to table
> Installation methods for current rating “Enclosed in conduit on a wall” in accordance with BS7671/IET Wiring Regulations.
> Minimum recommended installation temperature 0°C.
> The tabulated ratings are based upon a 30°C ambient temperature at 90°C operating temperature.
> For other ambient temperatures or where several circuits are grouped together, the following rating factors should be applied.











Overseas sales enquiries Middle East Region
Tel: +44 (0) 23 5029 5481 Prysmian Cables & Systems
Fax: +44 (0) 23 8029 5465 PO Box 643990
Dubai
Overseas technical UAE
Tel: +44 (0) 23 8029 5481 Tel: +971 42428104
[email protected]


Prysmian Cables & Systems Limited
Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU
United Kingdom
For further information please
see our dedicated FP Cables website:
www.fpcables.co.uk





All sizes and values without tolerances are reference values. Specifications are A brand of the Ref: FP100/05/2019
for products afterwards may give different results. The information contained
within this document must not be copied, reprinted or reproduced in any form,
either wholly or in part without written consent of Prysmian Group. Prysmian
Group reserves the right to amend this specification without prior notice.

A brand of the






















Certificate No 077g*
Certificate No 077h*
‘ENHANCED’ FIRE RESISTANT CABLE 300/500 V

























Conductor Key Applications

Plain annealed copper. Solid (1.5 & 2.5 mm²) or stranded circular > Fire detection and fire alarm systems for buildings
conductors (4.0 mm²) to meet the requirements of BS EN 60228 class 1 > Voice alarm systems and emergency voice communication
or class 2. > Emergency and escape lighting
> Control circuits for fire safety and fire fighting systems
Insulation > Other essential service control circuits for ‘enhanced’ fire resistance
British Standards, Tests & Approvals
High performance, damage resistant enhanced Insudite™ to meet
BS EN 50363-5, Type EI5. Including mica tape for 2c4mm² and all 3 & 4
core. > BS 7629-1 Enhanced 120*
> BS EN 50200 PH30, PH60, PH120*
Overall metallic screen and CPC > BS 8434-2 Flame, impact & water test for ‘enhanced’ cable*
> BS 5839-1, 6, 8 & 9 ‘enhanced’ fire resisting cable*
Polyester backed laminated aluminium or copper tape bonded to outer > BS 5266-1 ‘enhanced’ fire resisting cable
sheath to provide overall screen. In contact with full sized, tinned > BS 8519 catagory 2 contol cable
> BASEC approved
annealed copper circuit protective conductor and laid-up with the cores > LPCB approved*
to provide automatic screen earthing
> BS 6387 CWZ*
Sheath Core identification l

Robust thermoplastic low smoke, zero halogen and reduced flame Harmonised - standard Non harmonised – to special order
propagation outer sheath. Standard colours white and red with bespoke o o brown-blue
colours available to special order. Suitable for outdoor installation with o o o brown-black-grey o o red-black
o o o red-yellow-blue
exposure to normal daylight UV.
o o o o blue-brown-black-grey o o o o black-red-yellow-blue


Ref:FPPLUS/05/19




Halogen Free
Temperature Bending Radius Mechanical Impact Fire Performance Flexibilty Halogen Free Low Smoke Emissions Fire Resistance
Fire resistance
BS EN 61034-2
r=6D
Range Fixed r=6D Medium BS EN 60332-1-2 Rigid BS EN 50267-2-1 BS EN 61034-2 BS6387 Category CWZ
Rigid
BS EN 50200
BS EN 60754-1
BS EN 60332-1-2
-20 to +70˚C BS EN 50266-2-4 BS EN 50200 PH30 & PH60 3
PH30, PH60, PH120
BS EN 50200 Annex E
BS 8434-2
BS 6387 CW2
BSEN60332-1-2
BSEN61034-2
EN50200 PH30 & PH60

Nominal Conductor Approximate Approximate Maximum Current Current Volt drop Recommended accessories
cross Construction overall cable conductor rating DC or rating DC or DC or single Colour - White or Red
sectional diameter weight resistance single phase single phase phase
area at 20°C AC AC AC LSOH ® Nylon
Enclosed Clipped direct fixing LSOH ®
mm 2 no/mm mm kg/km Ω/km Amps Amps mV/A/m
clips gland

Two core
UNEPNF03
1.5 1/1.38 9.2 115 12.1 16.5 19.5 29 AP9 251/GL2520
2.5 1/1.78 11.5 180 7.41 23 27 18 AP11 252/GL2520
4.0* 7/0.85 12.2 235 4.6 30 36 11 AP11 252/GL2520


Three core
1.5 1/1.38 11.7 175 12.2 16.5 19.5 29 AP10 252/GL2520
2.5 1/1.78 12.7 230 7.41 23 27 18 AP11 251/GL2520
4.0* 7/0.85 13.0 290 4.6 30 36 11 AP13 252/GL2520

Four Core
1.5 1/1.38 12.5 210 12.2 16.5 19.5 29 AP9 251/GL2520
2.5 1/1.78 13.5 270 7.41 23 27 18 AP11 252/GL2520
4.0* 7/0.85 14.7 355 4.6 30 36 11 AP15 254
*Product FP PLUS FLEX
Notes to table
> Recommended clip spacing 300 mm horizontal and 400mm vertical.
> Minimum recommended installation temperature 0°C. Installation methods for current rating in accordance with BS7671/IET Wiring Regulations.
> The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature. For other ambient temperatures or where cables are
grouped together, appropriate de-rating factors should be applied.
> De-rate by factor 0.8 when 4 cores are loaded
Correction factors for Ambient temperatures: Table 4B1


Ambient Temperature°C 25 30 35 40 45 50
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71

Correction factors for grouping of cables: Table 4C1


Number of cables 2 3 4 5 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54

Overseas sales enquiries Middle East Region
Tel: +44 (0) 23 5029 5481 Prysmian Cables & Systems
Fax: +44 (0) 23 8029 5465 PO Box 643990
Dubai
Overseas technical UAE
Tel: +44 (0) 23 8029 5481 Tel: +971 42428104
[email protected]
Prysmian Cables & Systems Limited
Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU
United Kingdom
www.prysmiangroup.co.uk Should you have any concerns about
unsafe, non-approved or counterfeit
cable, please contact the ACI

For further information please Tel: 020 8946 6978
see our dedicated FP Cables website: Email: [email protected]
www.fpcables.co.uk
All sizes and values without tolerances are reference values. Specifications are Ref: FPPLUS/05/19
for products afterwards may give different results. The information contained
within this document must not be copied, reprinted or reproduced in any form,
either wholly or in part without written consent of Prysmian Group. Prysmian
Group reserves the right to amend this specification without prior notice.


Click to View FlipBook Version