intelligent GENERATORS

Tests of the spare diesel generator

Revising the documents of the generator and matching them with details that are installed in the
equipment at the site's conditions and also in the tables of guarantee provided by the manufacturer
and certified before the exporting.

Checking the materials components according to the standard specifications

Checking the certificates of the type test reports and the factory tests.

Checking the generators base, the cables paths, the method of installation and the vibration trans-
fer barriers.

Checking the capacity of the main and daily fuel tanks according to the required specifications.

And the tanks should have been checked before they are assembled on the site according to the
instructions of the manufacturer company.

Verifying the assembly of the ground and daily tank in their correct places according to the draw-
ings.

Checking all the connections and the nets of the tanks and making sure they meet the charts.

Checking the diameters of all the holes and the method of protecting them and making sure they
meet the executive certified drawings (the radiator hole- air feed hole- fuel feed hole- water drain
hole- etc…).

Checking the performance of the main and spare fuel pumps of the daily fuel tank.

Making sure that the suitable fire extinguishers are available in the place where the generator
is assembled.

The loading test is carried out for a specific period according to the international standard specifi-
cations ISO with a value of 25 %, 50 %, 75 %, 100 %, and 110 % of the load and the temperatures
are recorded and compared to the tables of guarantee and the factory tests.

A test of adding a sudden load on the unit is carried out by a value of 25 %, 50 %, 75 % and 100 %
of the load and the exclusion of a sudden load from the unit by a value of 25 %, 50 %, 75 % and 100
%. In each case, the frequency, the machine speed, the decrease of the voltage and the frequency,
the period of recovering them (recovery time) are checked and the back time to the main values
of the voltage and frequency is recorded. See the volume number (10) in the Egyptian Code of
Special Systems- Emergency Generators.

46

--5451--

intelligent

ATP Series - 50HZ 1500 rpm
15 KVA – 2500 KVA Power range

ATOS Generators provide tailor-made power solutions according
to customer needs as well as serving with a wide range of ATP
series products starting from 15 kVA to 2500 kVA. Commercial
and industrial diesel generator sets provide Best-in-class reliabil-
ity and availability. Featuring low fuel consumption, long service
intervals and low emissions backed by more than 30 years of ex-
perience, our generator sets are designed to perform.
Once the generator set is assembled, the complete unit is tested
at and above 100% of rated load for operation and safety.

1. ATOS Generators provides one-source responsibility for the generating system and accessories.
2. Industrial diesel engine in gen set version with certi cate of origin
3. Industrial brushless alternator
4. Steel base frame with retention basin , daily fuel tank with level sensor
5. Canopies in galvanized, power coated sheet steel
6. Internal exhaust silencer with insulated manifold
7. Electrical control panel mounted on board the unit with digital Control device installed in metal box
8. Compact for easy handling and use
9. Test report, manuals and electrical drawings supplied
10. After sales service and technical support for generator sets

ATV Series - 50HZ 1500 rpm
135 KVA – 650 KVA Power range

ATOS Generators provide tailor-made power solutions according
to customer needs as well as serving with a wide range of ATV
series products starting from 135 kVA to 650 kVA. Commercial
and industrial diesel generator sets provide Best-in-class reliabil-
ity and availability. Featuring low fuel consumption, long service
intervals and low emissions backed by more than 30 years of ex-
perience, our generator sets are designed to perform.
Once the generator set is assembled, the complete unit is tested
at and above 100% of rated load for operation and safety.

1. ATOS Generators provides one-source responsibility for the generating system and accessories.
2. Industrial diesel engine in gen set version with certi cate of origin
3. Industrial brushless alternator
4. Steel base frame with retention basin , daily fuel tank with level sensor
5. Canopies in galvanized, power coated sheet steel
6. Internal exhaust silencer with insulated manifold
7. Electrical control panel mounted on board the unit with digital Control device installed in metal box
8. Compact for easy handling and use
9. Test report, manuals and electrical drawings supplied
10. After sales service and technical support for generator sets

49

--5462--





intelligent

ATC Series - 50HZ 1500 rpm
100 KVA – 2500 KVA Power range

ATOS Generators provide tailor-made power solutions according
to customer needs as well as serving with a wide range of ATC se-
ries products starting from 100 kVA to 2500 kVA. Commercial and
industrial diesel generator sets provide Best-in-class reliability and
availability. Featuring low fuel consumption, long service intervals
and low emissions backed by more than 30 years of experience,
our generator sets are designed to perform.
Once the generator set is assembled, the complete unit is tested
at and above 100% of rated load for operation and safety.
1. ATOS Generators provide one-source responsibility for the generating system and accessories.
2. Industrial diesel engine in gen set version with certi cate of origin
3. Industrial brushless alternator
4. Steel base frame with retention basin , daily fuel tank with level sensor
5. Canopies in galvanized, power coated sheet steel
6. Internal exhaust silencer with insulated manifold
7. Electrical control panel mounted on board the unit with digital Control device installed in metal box
8. Compact for easy handling and use
9. Test report, manuals and electrical drawings supplied
10. After sales service and technical support for generator sets

ATL Series - 50HZ 1500 rpm
27 KVA – 180 KVA Power range

ATOS Generators provide tailor-made power solutions according
to customer needs as well as serving with a wide range of ATL se-
ries products starting from 27 kVA to 180 kVA. Commercial and in-
dustrial diesel generator sets provide Best-in-class reliability and
availability. Featuring low fuel consumption, long service intervals
and low emissions backed by more than 30 years of experience,
our generator sets are designed to perform.
Once the generator set is assembled, the complete unit is tested
at and above 100% of rated load for operation and safety.

1. ATOS Generators provides one-source responsibility for the generating system and accessories.
2. Industrial diesel engine in gen set version with certi cate of origin
3. Industrial brushless alternator
4. Steel base frame with retention basin , daily fuel tank with level sensor
5. Canopies in galvanized, power coated sheet steel
6. Internal exhaust silencer with insulated manifold
7. Electrical control panel mounted on board the unit with digital Control device installed in metal box
8. Compact for easy handling and use
9. Test report, manuals and electrical drawings supplied
10. After sales service and technical support for generator sets

50

--5475--

intelligent

Canopies

Canopy (Weather Proof) (Sound Proof) / (super sound proof)
The whole sound proof canopy is ATOS manufactured.
The canopy made of steel sheets painted by electrostatic - paints anti-rustiness, with 2 mm thickness according
to manufacturing basics.
The canopy is internally isolated by sound isolation layer to provide sound level
Sound proof: (75 + 5% @7m),Super sound proof: (65 + 5% @3m)
The canopy internally isolated with in ammable covered rock wool of high thickness that isolates temperature
& liquid.
The internally isolation layer is coated by PGF.
There are inlets & outlets for air in going and outgoing that does not e ect on sound level or the unit temperature.
The presence of glass opening in front of the canopy for viewing the control panel.
The canopy wall with the isolation layer thickness is 60 mm.
It is applied by high quality locks for the unit safety; also, there are holders on the canopy surface to make it able
to be elevated.
Special mu er is xed inside the canopy.
Special canopies can be produced upon customer request.
The whole weather proof canopy is ATOS manufactured.

Tank

Made of steel sheets of thickness 2 mm: 10 mm with cylindrical shape of volume
10000 liters, the tank is painted with two epoxy layers and nal colored layer com-
plete with:
• inspection opening (man hole)
• outlet valve and built in connection for piping
• fuel level indication
• button supports for xation

Trailer

ATOS produce several sizes of the trailers which are prepared for in and outdoor usage.

• Speci cation • Custom Tires that will exceed the weight limitations of your
• Torsion Axle Suspension • trailer Optional Features for All Trailer Models
• Two adjustable axe • Hydraulic Brakes
• Teardrop fenders • Steel Decking
• Safety Chains • Storage Box
• License Plate Holders • Low Level Fuel Alarm

Control Panels

The panel is made of steel sheet with electrostatic paint and totally isolated, a selector is used to load the generator
manual or automatic & it consists of

1. ATS unit operate with the main supply and generator and it consists of MCB connected to all safety systems
and also equipped with indicating lamps and all of the panel components are European manufactured.

2. Main supply current.
3. Generator current.
4. Loading and separating of generator.
5. Automatic control for loading time of main supply.
6. Automatic control for loading time of generator.
7. Delay stopping of generator after load separation for cooling.
8. Automatic battery charger for charging the battery from main supply.
9. Push button for manual loading and separating generator and main supply.
10. Relays for control circuits.
11. Sound alarm switch.
12. Copper sheets as the current doesn’t increase than 1.5 amp. In 1 mm.

51

-5486-

intelligent

Services Keeping your generator well maintained and up to date is important for the overall welfare of your
generator. Here at ATOS Generators Maintenance Center, we tailor our required maintenance pro-
You can be grams to ensure high Performance.
con dent we Proper maintenance will not only increase reliability, it will help to extend the life of your engine
will take care of driven generator system. The life of your generator depends directly on the quality maintenance
your generator it receives. Get the required maintenance your generator needs so that it will perform as planned
system and keep during a power outage.
it running at Our Maintenance Center is the most trusted name in Egypt, providing generator maintenance ser-
optimal perfor- vices and support for your emergency generator systems. Since 1986 ATOS Generators is commit-
mance levels. ted to providing superior service throughout the country, our center ts up to 120 repaired units.
A dedicated team that has the quali cations, experience and know-how in designing and deliv-
ering integrated UPS and diesel generator systems, will tailor each project to the unique require-
ments of customer-speci c applications, while managing everything from the design through to
the installation and service requirements of each project.
Our 24/7 technical support services and routine scheduled visits ensure optimum system perfor-
mance and reliability.

Spare Parts

ATOS o ers a large number of maintenance products to help keep your engine in top condition. These include
lters, gaskets, water pumps, consumables, oil pumps and thermostats. Each one has been designed and built to
meet the requirements of your engine.
Why Genuine Engine Parts? Why not? Did we mention that Genuine Parts are tested against the non-genuine
product to great lengths in lab testing and in the actual physical environment? Did we mention engine engineers
strive for product perfection? Test after test indicates that Genuine Parts o er superior durability and quality. We
take great pride in knowing that a replacement part backed with an engine brand name will provide the durability
needed to go beyond getting the job done. We would not chance it, would you?
Using non-genuine parts means that you are putting your engine at risk, we can provide you with all of the com-
ponents that were originally used to build your engine, so should a part fail come to us for a genuine replacement
If you need parts for a speci c engine and alternator please contact our Parts Department at +2 01117441093/4
Please have the Make, Model & Serial No. of your machine ready for faster service.

Turnkey • We will survey the load, taking measurements, appliance information, etc.
• We will propose what we believe is the correct generator size because
We will interview the end result always re ects on our company.
the customer • We do the research to make sure the desired generator is compliant with local air quality
to con rm that
we’re providing and sound ordinances.
exactly what best • We help the customer choose the best site for his generator and transfer switch.
suits his needs, • We will sign a contract with the customer prior to starting any work.
while it helps • We will provide the generator, transfer switch and any other necessary purchases.
when the client • We obtain the necessary permits for the customer, where applicable
already has in • We handle all the plumbing, wiring, electrical, aesthetic, soundproo ng, HVAC, concrete
mind what he
wants. and structural work. Our team has the necessary tools, skills, licenses and experience to
build an entire building from the ground up but we choose to specialize in generators.
• We will either provide or recommend Generators systems as required.
• We will complete the project on time and on budget.
• We will provide training on how to properly use and maintain your new equipment.

Engineering consulting

At ATOS Generators we believe that e ective engineering design must be carefully planned and systematically ex-
ecuted. In particular, engineering design methods must integrate the many di erent aspects of designing and the
priorities of the end-user. At ATOS, our experience in collaborative engineering has allowed us to excel in providing
power solutions which integrate with the needs of the customer. Our broad range of experience allows us to work in
concert with customers at the beginning of the design to ensure that the best system solution can be found.

52

-5497-

intelligent

Aggreko plc. is a supplier of temporary power
generation equipment and of temperature control
equipment. It is headquartered in Glasgow, Scot-
land, United Kingdom. It is listed on the London
Stock Exchange and is a constituent of the FTSE
250 Index.

Aggreko has the power
to make things happen.

The power, heating and cooling ser-
vices, aggreko deliver transform the
lives and livelihoods of individuals,
organisations and communities across
the globe.
In rental solutions and power solu-
tions industrial aggreko work across
12 major sectors including oil & gas,
petrochemical & refining, utilities and
events.In power solutions utility
aggreko bring power to emerging markets
where there is a structural power deficit. Ag-
greko invest in bolt-on acquisitions that offer
opportunities for growth, including adjacent
solutions such as heating and cooling that
drive demand for power.

55

--5508--

intelligent

Aggreko Industry and Markets

Aggreko are positioned to benefit from long- Aggreko address the market through our two
term trends. The global power generation mar- business units which are well positioned to
ket is undergoing substantial change. Whilst provide solutions for customers as energy mar-
demand continues to grow, we are seeing a kets transform.
transformational shift in regulatory, environ- Power Generation, Temperature Control, Cool-
mental and societal expectations. In devel- ing Towers, Power Plants, Loadbanks, Diesel
oping a long-term view on the market, many Generators, Gas Generators, Transformers,
factors need to be considered. Chillers, Industrial Air Conditioners, Rental
These can vary by country and sector, but can Power, Temporary power, Industrial Heaters,
be broadly defined within global megatrends. Spot Coolers, and Industrial Chillers.
These megatrends offer significant opportuni-
ties for our business.

20kVA Canopy
angle

1375 kVA
Gas Angle

Contact:

Address: 47th building, 4th Floor, 90th North Street, Section 1
5th Settlement, New Cairo, Cairo- Egypt
TEL: +20 225032929

56

-519-

intelligent

Canopy Generator 20 kVA

Aggreko can solve your power generation challenges with our 20 kVA generator
rentals - whether you need power for a wedding or for a construction job. If you need to power a
small tent or a major power plant, get the job done with customized Aggreko
solutions, service & support.

KEY DATA RATING VOLTAGE RANGE FUEL TYPE
20 kVA 220 - 240 V Diesel

ELECTRICAL CONTINUOUS POWER PRIME POWER
OUTPUT 16 kVA 20 kVA

FUEL 75% PRIME POWER 50% PRIME POWER
CONSUMPTION 4.3 l/hr 2.9 l/hr

PHYSICAL DATA

LENGTH (M) WIDTH (M) HEIGHT WEIGHT WITHOUT WEIGHT WITH
1.65 0.88 (M) FUEL (KG) FUEL (KG)

1.43 790 900 kVA

FEATURES 57

• Bolted, galvanised, alloy steel canopy with lockable doors
• Control panel mounted inside, viewable through glass door
• Range of warnings and shutdowns on control system
• Low fuel-level warning sensor in fuel tank

BENEFITS

• The alloy steel provides extra strength, durability and protection
• Prevents unauthorized access without loss of monitoring
• Protects generator set from electrical and mechanical damage, helps identify

and rectify faults before they occur
• Reduces noise to operate even in quieter surroundings
• Aids seamless, interruption-free operation of the genset

--6520--

intelligent

Containerised
Generator 1375
KVA

KEY DATA RATING MAX AMBIENT TEMP FUEL TYPE
1375 kVA 39 °C Gas
ELECTRICAL
OUTPUT CONTINUOUS SINGLE STEP LOAD APPLICATION @ 50
POWER HZ
PHYSICAL DATA
1400 kVA 30%

LENGTH (M) WIDTH (M) HEIGHT (M)
6.06 2.44 2.60

FEATURES

• Acoustically designed equipment with baffle plates
• Welded steel construction
• Fire and gas detectors
• Silencer fitted

BENEFITS

• Cost efficient
• Reduced environmental impact
• Safe and reliable operation in rental applications
• Raises alarm in case of gas leakage

58

--6531--

intelligent

ABOUT CATERPILLAR
POWER SYSTEMS

Caterpillar is the world's largest manufacturer of
generator sets, offering the largest range of spec-
ifications available. If you need a diesel genera-
tor set with 6 to 14,040 ekw (7.5 To 17,550 kva)
of power potential, you'll have peace of mind
knowing cat® diesel -fueled generator sets are
built to world-class standards, for high efficien-
cy, low fuel consumption and global emissions
compliance. Cat® diesel generator sets come in
a range of options to match your power needs
- so selecting the right diesel generator set for
your application, and installing it, is simple.

DIESEL GENERATORS - PRIME,

CONTINUOUS OR STANDBY POWER

For prime, continuous or standby power through the life of the diesel genset.

service, cat commercial and industrial die- For more than 85 years caterpillar has

sel generator sets deliver reliable, clean, been providing power to customers

economical power – even in the most like you around the world. From north

demanding conditions. Each cat diesel america to china, europe to india, in

generator set is designed, engineered and remote regions and extreme climates,

manufactured for optimal performance. caterpillar is meeting the most critical

All major components are tested individ- needs and matching the most stringent

ually; and once the generator set is assem- standards. We’re powering the indus-

bled, the complete unit is tested at and tries that drive economy: agriculture,

above 100% of rated load for operation forestry, mining, drilling, construction,

and safety. A cat brand generator set offers production, well servicing, gas com-

a huge advantage over all other brands: pression and power production. We’re

they all come with the expert service and moving the vessels, yachts and ships

comprehen that voyage to the farthest coasts.

Sive support of your nearby cat®dealer. It We’re powering the data centers busi-

begins with prompt delivery and continues nesses count on and hospitals that com-

67

--6542--

intelligent GENERATORS

munities rely on. From 5 to 16,000 kw
cat® power systems are equipped to
do more than just power today; they’re
built to power tomorrow.

Mantrac Power Systems Egypt

As a leading power-systems supplier, Mantrac Pow- you with turnkey service covering all operation-
er Systems Egypt is committed to providing you al stages, from system design, testing and instal-
with electric power solutions to operate your busi- lation to commissioning, training and long-term
ness at maximum efficiency. We offer Olympian maintenance and repair. Generators are available
generators from 10 kVA to 220 kVA and Caterpillar with or without sound-proof enclosures, fixed or
generators from 250 kVA to 7000 kVA, providing mobile. We also offer rental services with reli-
both primary and standby power. Our generators able equipment built exclusively for this purpose.
can be used to power offshore oil rigs, mines in Mantrac Power Systems Egypt has 2 main head
remote areas, communities in areas far from utility offices in Alexandria (Amerya) and Cairo, as
power grids, hospitals, schools, factories, airports well as local branches in Tanta, Mansoura, Suez,
and office buildings. Our engines are also designed Hurghada, Sharm El Sheikh, Sohag, Luxor, Aswan
to power trucks, ships and boats, agricultural equip- and Toshka. We guarantee customers full prod-
ment, construction and mining machines, and more. uct support services, ensuring that their genera-
Unlike most suppliers of engines and genera- tor / engine is kept running at peak performance.
tor sets, Mantrac Power Systems Egypt provides

Contact:

Cairo:
Address: 30, Lebanon St. El Mohandessin
Tel: 002 02 33004000
Fax: 002 02 33039648
Alexandria:
Address: Amreya, Km. 28, Alex-Cairo Desert Road
Tel: 0020 03 4541000
Fax: 0020 03 4481042

Hotline: 19266
www.mantracpowersystems.com

68

--6553--

intelligent

C18 (50 HZ)

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver
unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications Engine Specifications

Minimum Rating 550 kVA Engine Model C18 ATAAC, I-6, 4-Stroke
Water-Cooled Diesel

Bore 145 mm (5.71 in)

Maximum Rating 715 kVA Displacement 18.13 L (1106.36 in<-
sup>3</sup>)

Voltage 208 to 600 Volts Stroke 183 mm (7.2 in)

Frequency 50 Hz Compression Ratio 14.5:1
Aspiration Air to Air Aftercooled
Speed 1500 or 1800 RPM
Governor Type Adem™A4

Fuel System Electronic unit injection

Generator Set Configurations

Low Fuel Consumption, U.S. EPA Certified for Stationary Emergen-
Emissions/Fuel Strategy cy Use Only (Tier 2 Nonroad Equivalent Emission Standards), China

Nonroad III Emission Standards

Benefits & Features

• Cat Diesel Engine • UL 2200 / CSA - Optional

1. Reliable, rugged, durable design 1. UL 2200 listed packages
2. Field-proven in thousands of applications world- 2. CSA Certified
3. Certain restrictions may apply.
wide 4. Consult with Cat® Dealer.
3. Four-stroke-cycle diesel engine combines
4. consistent performance and excellent fuel econo-

my with minimum weight

• Generator

1. Matched to the performance and output charac-
teristics of Cat engines

2. Industry leading mechanical and electrical design
3. Industry leading motor starting capabilities
4. High Efficiency

69

--6564--

intelligent GENERATORS

• Cat EMCP Control Panel

The EMCP controller features the reliability and durability you have come to expect from your Cat
equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation,
providing extensive information about power output and engine operation. EMCP4 systems can be fur-
ther customized to meet your needs through programming and expansion modules.

• Seismic Certification

1. Seismic Certification available.
2. Anchoring details are site specific, and are dependent on many factors such as generator set size,

weight, and concrete strength.
3. IBC Certification requires that the anchoring system used is reviewed and approved by a Profession-

al Engineer
4. Seismic Certification per Applicable Building Codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009,

CBC 2007, CBC 2010
5. Pre-approved by OSHPD and carries an OSP-0321-10 for use in healthcare projects in California

• Design Criteria

The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient
response.

• Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

• World Wide Product Support

Cat dealers provide extensive post-sale support includ-
ing maintenance and repair agreements. Cat dealers
have over 1,800 dealer branch stores operating in 200
countries. The Caterpillar S•O•Sprogram cost effective-
ly detects internal engine component condition, even the
presence of unwanted fluids and combustion by-products

• Standard Equipment

• Air Inlet System

1. Light duty air cleaner
2. After cooler core
3. Turbocharger

• Control System

EMCP4.2

• Cooling

1. Radiator and cooling fan with guard
2. Coolant drain line with valve
3. Fan drive, battery charging alternator drive
4. Caterpillar extended life coolant

70

--6575--

intelligent

Fuel System

Standard 8 hour open set fuel tank

Generator and Attachments

1. Matched to the performance and output characteristics of Cat engines
2. A frame generator - IP21 protection
3. Integrated Voltage Regulator
4. Integrated Voltage Regulator
5. Power center, IP22
6. Segregated low voltage (AC/DC) wiring panel
7. Mandatory Option circuit breaker, IEC, 3 pole, mounted in power centre

Governing System

Cat Electronic Governor (ADEM A4)

Lube System

Lubricating oil
Oil drain valves

Mounting System

Captive linear vibration isolators between base and engine-generator. includes lifting provisions and
termination points for coolant and lube oil drain lines

Starting/Charging

24 Volt battery with rack and cables

General

Engine and alternator pre-paint, Caterpillar yellow

Optional Equipment

• Air Inlet System

1. Single element air cleaner
2. Dual element air cleaner

• Circuit Breakers

1. 3 Pole (IEC-100% rated) circuit breakers - Package mounted
2. 4 Pole (IEC-100% rated) circuit breakers - Package mounted
3. 3 Pole (IEC-100% rated) circuit breakers - Motorised
4. 4 Pole (IEC-100% rated) circuit breakers - Motorised
5. Circuit breaker (IEC) auxiliary contacts
6. Shunt trip for IEC breaker
7. Pad-lockable circuit breaker device
8. Power terminal strip

71

--6586--

intelligent GENERATORS

Control System

1. EMCP4.2
2. Volt free contact
3. Local alarm horn
4. Oil temperature displays
5. Protective devices: Earth fault relay - earth leageage ground fault relay - Overload shutdown via

breaker - Low fuel level alarm - Low fuel level shutdown - high fuel level alarm - Fuel level sensor
6. Local alarm modules

7. Remote annunciator modules

Cooling System

1. Radiator duct flange

2. Low coolant temperature alarm

Enclosures

3. Sound attenuated enclosures

Exhaust System

1. Engine mounted muffler
2. 10, 25 and 35 end in / end out Mufflers
3. 8 and 10 inch GP flanges
4. 8 and 10 inch elbow kits

5. Manifold and Turbocharger guard

Fuel System

1. Integral - Duel wall fuel tank base
2. Manual fuel transfer pump

3. Fuel transfer system

Generator and Attachments

1. Ingress protection
2. Permanent magnet excitation
3. Space heaters
4. A frame oversize generator
5. A frame CIP generator
6. LC frame generator
7. LC frame oversize generators

8. LC frame CIP generator

Lube System

1. Manual sump pump

Starting and Charging

1. 5 Amp battery charger
2. Battery disconnect switch
3. Jacket water heaters

72

--6597--

intelligent

XQ35

Overview With a robust, rental-ready construction, the XQ35 is designed to be easily
transported around project sites safely and efficiently. A smaller footprint
saves space and provides installation versatility on worksites, while a galva-
nized enclosure is resilient to potentially harsh environments.

Generator Dimensions

Rating 27 ekW (35 kVA) Prime Weight 2215 lb

Frequency 60 Hz Height - Without 63.7 in
Trailer 91.3 in
Voltage 208 - 480V 41.4 in
C2.2 Diesel Engine Length - Without
Engine Trailer

Engine Width - Without
Trailer

Benefits & Features
Fuel/Emissions Strategy

Meets U.S. EPA Tier 4 Final emission standards and CARB certified for non-road mobile applica-
tions at all 60 Hz ratings

73

--6608--

intelligent GENERATORS

Cat C2.2T Diesel Engine

Four-stroke diesel engine combines performance and excellent fuel economy with minimum weight

Cat LC Series Generator

Matched to the performance and output characteristics of Cat diesel engines

Cat EMCP 4.2B Control Panel

Electronic control panel provides power metering, protective relaying, engine and generator pa-
rameter viewing, and expanded AC metering.

Environmentally Friendly Design

110% spill containment of all engine fluids

Sound Attenuated Enclosures

Rugged, corrosion-resistant construction

Controls and Power Distribution

Three-position switch for easy selection of desired output (480/277V 3-phase, 208/120V 3-phase, or
240/120V single phase)

Standard Equipment

Generator and Screen protected and drip-proof (IP23), self-
Voltage Regulation regulating,12-lead, 4-pole, brushless generator

Generator Set Packaging Base frame and containment tray <br> – Heavy-
duty, fabricated steel base frame with \specially-
Generator Controls and
Power Distribution designed lifting points

Engine EMCP 4.2B, digital generator set controller,
mounted behind a hinged, lockable door with

viewing window

Cat C2.2T, heavy-duty, EPA Tier 4 Final certi-
fied diesel engine

Quality and Product Sup- Factory load-testing of complete genera-
port tor set

74

--6619--

-7602-





UPS intelligent

An uninterruptible

UPSpower supply

An uninterruptible power supply (UPS) is require-
ment of every office, home, place or system. UPS
is power supply provides counties power and gives
few benefits to both home office and business. Most-
ly required to keeping the PC and other electronic
systems in running mode. It keeps safe from power
surges and fight also against load shedding.
It device that allows a computer to keep running for
at least a short time when the primary power source
is lost. It also provides protection from power It
cable to charge , it save the electrical power to fed
the machine or device the electrical current when the
main power disconnected and it usually used with
small loads which don’t exceed 100 KVA .

Ups consist of:

Rectifier: Convert the AC power to
DC power to charge the
battery.

Used to control in the

Controller: starting and ending the
charging process.

Inverter: Used to convert the DC
power which coming from
Electronic rectifier the battery to AC power to
fed the loads

77

-7-36-3-

intelligent UPS

Comparison between ups line interactive and online
ups

UPS online ups line interactive

The period time to connect the current when the main The period time to connect the current when the main

current disconnected may be nothing 0 sec. power disconnected from 2: 6 msec.

Wave shape: true sine wave. The wave shape: modify sinewave.

Can add external battery because the capacity of inter- Don’t able to add external battery due to that linked to

nal charging circuit is large. internal charging circuit capacity.

The power factor (p.f) is :(0.7, 0.8, and 0.9). The power factor (p.f) is : 0.6

What the importance of the battery:

Being the battery in the circuit power is main thing to provide the
continuous voltage to pass the current in any electrical circuit.
We must know the energy stored in the battery is lost even without
using it, due to the property) Self-discharge property where chemi-
cal processes are doing in it even if not used. Self-discharge.
Voltage and frequency independent (VFI) UPS sys-
tems are called dual or double conversion because incom-
ing AC is rectified to DC to keep batteries charged and
drive the inverter. The inverter re-creates steady AC pow
er to run the IT equipment.

78

-6-47-4-

UPS intelligent

UPS diagram When incoming power fails, or the voltage
goes out of range, the bypass quickly discon-
When power fails the battery drive the nects from the input and the battery drives the
inverter, which continues to run the informa- inverter. When input power is restored, the
tion technology (IT) load. bypass re-engages the input, re-charges the
When power is restored, either from the util- batteries, and keeps output voltage constant.
ity or a generator, the rectifier delivers direct
current (DC) to the inverter and simultane-
ously recharges the batteries, and bypass is
only used for maintenance safety or if there’s
an internal electronics failure .

Advantages of Using Uninterrupted
Power Supply

• Maintenance Cost – Unfortunately, the UPS batteries do not last forever. Depending on the
battery model, the UPS batteries can last about five or ten years, after which the old batter-
ies require proper disposal, so new batteries must be purchased.

• Energy Use – In order to keep the UPS batteries charged all time, the uninterruptible power
supply system should draw more power than the demand of the attached equipment. All this
causes enormous waste of power that is significant additional cost.

• Startup Cost – Installing a UPS power supply requires a huge startup investment. Even one
UPS device for home use can cost you hundreds of dollars, and a corporate startup on a
large scale runs to ten thousands of dollars. All these installations require an infrastructure
setup that can bring the total setup cost of over $ 100 000.

• Infrastructure – The home UPS devices does not require more setup than the standard
surge protector, but the large corporate UPS devices bring more additional considerations.
Attaching numerous UPS batteries to the existing wiring system must be done by a profes-
sional electrician. These UPS systems additionally require special ventilation care.

79

--7655--

Contacts:
Address: Ibrahim Fathi Ghonem St. Nr. 5, Glym, Alexandria

Telephone: +203 58 426 68035850193-
Mobile: 01001495511 - 01222138880

E-mail: [email protected]
Website: www.lectrosys.com

-76-





FEATURES Ege 100KR Series Technical Specifications intelligent

FEATURES 1-10 kVA 1 Phase Input - 1 Phase Output (HF) Rack Type Online UPS 83
• Rack / Tower Convertible Design
FEATURES • Mimic LCD Display May be Rotated by Simply
• Pushing Front Button
• True Online Double Conversion
• High Output Power Factor at 0.9PF
• Comprehensive Display Allows Easy Monitoring and Access of UPS Status
• Smart SNMP works with either USB or RS-232together
• Hot-Swappable Battery
• Effciency up to 90%
• Estimated Remaining Time Displayed on the LCD
• Support Economic (ECO) Operation Mode
• Matching Battery Pack
• Optional Powerful Charger Cold Start
• Power Shedding May Turn off Uncritical Load In
• Battery Backup
• Emergency Power Off
• Frequency Converter Mode Is Settable

Ege 100KR Series Technical Specifications

1-10 kVA 1 Phase Input - 1 Phase Output (HF) Rack Type Online UPS
• Online-Double conversion
• Non Transfer Time of Output PFC Technology
• Full Digital Control (DSP)
• Output Power Factor: 0.9
• Input Current Harmonic<3%
• ECO Function
• Charging/Rectifer/Inverter Fully Digital Control Technology
• Optimization Battery Group, the Quantity of
• Battery: 16/18/20 pieces (optional)
• Wide Input Voltage Range: 120-276Vac
• Wide Input Frequency Range: 45-55Hz/54-66 Hz
• Self-Testing When UPS Startup
• Input Over/Under Voltage Protection
• Automatic Bypass Cold Start
• Communication Port: RS232, USB
• Options: SNMP Card/ Relay Card

Ege 200K Series Technical Specifications

10-20 kVA 3 Phase Input - 1 Phase Output (HF) Online UPS
• N+X Parallel Redundancy
• Online Double Conversion with DSP Control
• Input Current Harmonic: <5%
• Optimization Battery Group, the Quantity of Battery: 16/18/20

pieces (optional)
• Output Power Factor is Changed When Selection Different

Battery Quantity 16 pcs: 0.7PF; 18pcs:0.8PF; 20pcs:0.9PF
• Wide Input Voltage Range: 208-478Vac
• Wide Input Frequency Range(50Hz: 45-55Hz; 60Hz: 54-66Hz)
• Support Generator Input
• Support Economic (ECO) Operation Mode
• Self-Testing When UPS Startup
• Options: SNMP Card / Relay Card / Parallel Board
• Cold start

--7679--

FEATURESintelligent

FEATURESAtlas 600 Series Technical Specifications

FEATURES3 Phase Input - 1 Phase Output (HF) Online UPS
• Wide Power Range (Available 5-100 kVA per request)
FEATURES• IGBT Rectifer and Inverter
• Input Current Harmonic < %5
• DSP Controlled
• Up to 0.99 Input Power Factor Correction
• Static Bypass at UPS Overload or UPS Failure
• Advanced LCD Panel
• Up to 500 Event History
• Optional SNMP

Ege 300K Series Technical Specifications

10-40 kVA 3 Phase Input - 3 Phase Output (HF) Online UPS
• Smallest Footprint Design
• DSP-controlled Technology
• Parallel Redundancy up to 4 units
• Wide Input Voltage and Frequency
• Unity Power Factor and Low Input Distortion
• Output Power Factor at 0.9
• ECO Mode for Energy Saving
• Common Battery
• Programmable Battery Voltage from +/-96Vdc to +/-240Vdc
• Built-in Batteries makes UPS ready to Use
• Matching Battery Packs
• 3-level intelligent Charge Modes with Smart Charge Current Adjustment
• Powerful Charger up to 10A
• Versatile Communication Interfaces Provided for Different Applications
• Superior Overload Capability
• Programmable Control and Monitoring Software via RS232 port
• Emergency Power Off
• Cold Start

Atlas 4000 Series Technical Specifications

10-300 kVA 3 Phase Input - 3 Phase Output (HF) Online UPS with Transformer
• Output Isolation Transformer
• IGBT Rectifer and Inverter
• Input Current Harmonic < %5
• DSP Controlled
• Up to 0.99 Input Power Factor Correction
• Static Bypass at UPS Overload or UPS Failure
• Advanced LCD Panel
• Up to 500 Event History
• Optional SNMP

Atlas 4000 Series Technical Specifications

10-300 kVA 3 Phase Input - 3 Phase Output (HF) Online with Transformer
• Output Isolation Transformer
• IGBT Rectifier and Inverter
• Input Current Harmonic < %5
• DSP Controlled
• Up to 0.99 Input Power Factor Correction
• Static Bypass at UPS Overload or UPS Failure
• Advanced LCD Panel
• Up to 500 Event History
• Optional SNMP
84

-68-
-80-

FEATURES Atlas 5000 Series UPS intelligent

FEATURES 10-800 kVA 3 Phase Input - 3 Phase Output (HF) Online UPS 85
• IGBT Rectifier and Inverter
FEATURES • Input Current Harmonic < %5
• Regenerative Operating
• Re-adjustable Battery Charge Current
• Built-in Self-Test
• Silent Performance
• Up to 6 Unit Parallel Operation
• DSP Controlled
• Up to 0.99 Input Power Factor Correction
• Static Bypass at UPS Overload or UPS Failure
• Advanced LCD Panel
• Up to 500 Event History
• High Performance for Medical Instruments
• Parallel Operating without Communication
• CE Certificate
• Patented Technology

Atlas 5000 Series UPS

10-800 kVA 3 Phase Input - 3 Phase Output (HF) Online UPS
• IGBT Rectifer and Inverter
• Input Current Harmonic < %5 Regenerative Operating
• Re-adjustable Battery Charge Current
• Built-in Self-Test
• Silent Performance
• Up to 6 Parallel Operation
• DSP Controlled
• Up to 0.99 Input Power Factor Correction
• Static Bypass at UPS Overload or UPS Failure
• Advanced LCD Panel
• Up to 500 Event History
• High Performance for Medical Instruments
• Parallel Operating without Communication
• CE Certifcate
• Patented Technology

Atlas 5000PF Series UPS

10-800 kVA 3 Phase Input - 3 Phase Output 0,9 PF Online UPS
• IGBT Rectfer and Inverter
• Input Current Harmonic < %5
• Regenerative Operating
• Re-adjustable Battery Charge Current
• Built-in Self-Test
• Silent Performance
• Up to 6 Parallel Operation
• DSP Controlled
• Up to 0.99 Input Power Factor Correction
• Static Bypass at UPS Overload or UPS Failure
• Advanced LCD Panel
• Up to 500 Event History
• High Performance for Medical Instruments
• Parallel Operating without Communication
• CE Certifcate
• Patented Technology

--8691--

FEATURESintelligent

FEATURESAtlas 5000PF Series UPS

FEATURES10-800 kVA 3 Phase Input - 3 Phase Output 0,9 PF Online UPS
• IGBT Rectifier and Inverter
• Input Current Harmonic < %5
• Regenerative Operating
• Re-adjustable Battery Charge Current
• Built-in Self-Test
• Silent Performance
• Up to 6 Unit Parallel Operation
• DSP Controlled
• Up to 0.99 Input Power Factor Correction
• Static Bypass at UPS Overload or UPS Failure
• Advanced LCD Panel
• Up to 500 Event History
• High Performance for Medical Instruments
• Parallel Operating without Communication
• CE Certificate
• Patented Technology

Atlas 7000 Series Technical Specations

Three Level (3L) High Efficiency 3 Phase Input - 3 Phase Output Online UPS
• 3L UPS Technology
• High Efficiency Up to %96
• IGBT Rectifier and Inverter
• Input Current Harmonic<%5
• Up to 0,999 Input Power Factor
• Very Low Output THDv <%2
• Advanced LCD Panel
• Up to 500 Event Log History

MODULAR UPS Technical Specifications

10-1560 kVA 3 Phase Input - 3 Phase Output Modular UPS
• High Frequency and Double Conversion Online Technology
• Advanced PFC technology
• 3U Frame, Rack-Mounted and Tower Convertible
• EPO Function
• Wide Input Voltage Range
• Fully Digitized Microprocessor Control
• Parallel Redundancy
• Advanced Battery Management
• Lightning and Surge Protection, Short Circuit and Overload Protection
• Multilingual LCD and LED display
• EMI RFI Noise Filter
• Smart RS232 Communication with Monitoring Software
• Optional SNMP Card Slot

86

--8702--





intelligent

E200R Series 1:1 Phase | 6–10 kVA | 0.8PF

An Advanced UPS Technology

Features • High frequency, double conversion on-line technology
• Fully digital DSP control
• Wide input voltage range
• Integral ‘hot-swap’ maintenance bypass module
• Cold start function
• Advanced battery management
• Selectable ECO mode for high efficiency operation
• Automatic battery charge in UPS off mode
• Lightning and surge protection
• Short circuit and overload protection
• Automatic fan speed control with load variation
• Parallel capacity or redundancy (maximum 4 units) requires a parallel card as

factory fitted option
• Smart RS232 communications with monitoring software
• Optional relay or SNMP communications card
• Matching EE2000 battery packs available
• E suffix models have no internal battery and increased charging capacity
• Internal removable bypass switch

E200R Series 3:1 or 1:1 | 6–10 kVA | 0.9PF

An Advanced UPS Technology

Features • High frequency, double conversion on-line technology
• Input can be configured for either 3:1 or 1:1 operation
• Rotatable LCD – suitable for 19” rack or slim tower
• Fully digital DSP control
• Wide input voltage range
• Cold start function
• Advanced battery management
• Selectable ECO mode for high efficiency operation
• Automatic battery charge in UPS off mode
• Lightning and surge protection
• Short circuit and overload protection
• Automatic fan speed control with load variation
• Up to 4 units can be operated in parallel
• Smart RS232 communications with monitoring software
• USB communications port included
• Optional relay or SNMP communications card
• Matching EER2000 battery pack available

89

--8715--

intelligent

E200 Series 3:1 Phase | 10–20 kVA | 0.8PF

An Advanced UPS Technology

Features • High frequency, double conversion on-line technology
• Fully digital DSP control
• Wide input voltage range
• Integral ‘hot-swap’ maintenance bypass module on E2310(E) model
• Cold start function
• Advanced battery management
• Selectable ECO mode for high efficiency operation
• Automatic battery charge in UPS off mode
• Lightning and surge protection
• Short circuit and overload protection
• Automatic fan speed control with load variation
• Parallel capacity or redundancy (maximum 4 units) requires a parallel card

as factory fitted option
• Smart RS232 communications with monitoring software
• Optional relay or SNMP communications card
• Matching EE2000 battery packs available for E2310(E) model

E300R Series 3:3 Phase | 10 – 250kVA | 0.8PF

An Advanced UPS Technology

Features • High frequency double conversion on-line UPS
• Fully digitised microprocessor control
• Parallel capacity or redundancy (maximum 4 units)
• Wide input voltage range from single or dual source
• Open architecture design provides full access for servicing
• Intelligent battery charge management
• RS232/RS485 communication with monitoring software
• Short circuit and overload protection
• Over temperature and over humidity protection
• EMI and RFI noise filtering
• ECO Mode
• User friendly LCD interface
• Cold start and programmable auto re-start functions (optional extra)
• Fan speed auto control with load variation
• Built-in static and maintenance bypass switches
• Back feed protection between UPS output and mains supply
• Emergency Power Off function
• Low THD & high input power factor for diverse generator compatibility
• Soft start with programmable power walk-in
• Optional temperature compensated battery charging
• Optional SNMP, relay card and remote monitoring panel
• Optional galvanic isolation transformer
• Nicad battery option available

90

--8726--

intelligent

E600 Series 1:1, 3:1, 3:3 Phase | 10 – 200kVA | 0.9PF

An Advanced UPS Technology

Features • Hot swappable modular design
• Flexible and expandable UPS power solution
• 19” cabinets available in full and half height format
• Modular design capable of housing either 5× or 10× power modules
• Power modules available in 10 and 20kVA ratings
• Configurable N+1 modular redundancy
• Parallel system capability (maximum 4x cabinets)
• High frequency double conversion on-line technology
• Wide input voltage range
• Intelligent battery charge management
• Programmable battery charge current
• Short circuit and overload protection
• EMI and RFI noise filtering
• Smart RS232 communication with monitoring software
• Fully digitised microprocessor control
• Large touch screen LCD interface
• Built-in maintenance bypass
• Emergency Power Off function
• Optional SNMP card or relay card
• Optional hot plug internal

E700 Series 3:3 Phase | 10 – 40kVA | 0.9PF

An Advanced UPS Technology

Features • High frequency, double conversion on-line technology
• Fully digital microprocessor control
• Parallel capacity or redundancy(maximum 4 units)
• Wide input voltage range
• Intelligent battery charge management
• Automatic battery charge in UPS off mode
• RS232 communication with monitoring software
• Short circuit and overload protection
• Lightning and surge protection
• EMI and RFI noise filtering
• Line interative ECO Mode
• User friendly LCD interface
• Cold start function
• Built-in maintenance bypass switch
• Emergency Power Off function
• Relay alarm card fitted as standard
• Optional SNMP network card available
• Supplied with 36x 38Ah VRLA battery as standard
• Alternative battery capacity / autonomy available

91

--8737--

intelligent

E800 Series 3:3 Phase | 10–600kVA | 0.8PF
An Advanced UPS Technology

Features • Cutting edge technology, high frequency double conversion on-line UPS
• Fully digital microprocessor control
• Parallel capacity or redundancy (maximum 4 units)
• Wide input voltage and frequency range
• Dual input as standard on 80kVA models and above
• Open architecture design provides full access for servicing
• Intelligent battery charge management
• RS232/RS485 communication with monitoring software
• Short circuit and overload protection
• Over temperature and over humidity protection
• EMI and RFI noise filtering
• Line interactive ECO mode
• Large user friendly LCD interface
• Cold start and programmable auto re-start functions
• Fan speed auto control with load variation
• Built-in static and maintenance bypass switches
• Back feed protection between UPS output and mains supply
• Emergency Power Off function
• Low THD and high input power factor for diverse generator compatibility
• Soft start with programmable power walk-in
• Optional temperature compensated battery charging
• Optional SNMP, relay card and remote monitoring panel

E 900 Series 3:3 Phase | 10–200kVA | 0.9PF

An Advanced UPS Technology

Features • Latest technology, high frequency double conversion on-line UPS
• 3 level inverter and rectifier design achieves >96% efficiency
• Fully digitised microprocessor control
• Parallel capacity or redundancy (maximum 4 units)
• Wide input voltage and frequency range switches
• Open architecture design provides full access for servicing
• Intelligent battery charge management
• RS232/RS485 communication with monitoring software
• Short circuit and overload protection
• Over temperature and over humidity protection
• EMI and RFI noise filtering
• Line interactive ECO mode
• Dual input facility for utility and bypass supplies
• Large user friendly LCD interface
• Programmable auto re-start functions
• Fan speed auto control with load variation
• Built-in static and maintenance bypass
• Optional back feed protection between UPS output and mains supply
• Emergency Power Off function
• Low THD and high input power factor for diverse generator compatibility
• Soft start with programmable power walk-in
• Optional temperature compensated battery charging
• Optional SNMP, relay card and remote monitoring
• Optional galvanic isolation transformer

92

--8748--

AEG Power Solutions intelligent

AEG Power Solutions ensures continuous availabil- 93
ity of power and the safe operation of critical ap-
plications in all environments. AEG PS has a prov-
en track record for developing solutions for highly
demanding applications in all types of infrastruc-
tures. Since its creation more than a century ago,
AEG has stood for rugged reliability and world-
class engineering, including 60 years’ experience
in power electronics and UPS. Our customers know
that they can rely fully on AEG PS for innovative
power solutions that protect people, investments,
data and businesses. AEG PS Group provides reli-
able custom and standard power system solutions,
particularly UPS Systems and industrial chargers,
that ensure continuous power for rugged industrial
infrastructure applications, including oil and gas,
transportation, power generation, power transmis-
sion and distribution, and process manufacturing.
AEG Power goal is to secure the power supply
chain all times, in the most reliable way, and to
make it simple for its customers. AEG Power strive
to the deliver outstanding service, innovative prod-
ucts and customizable, robust and reliable solutions
that meet the demands of today’s energy provision
and to prepare for tomorrows challenges. AEG
Power Solutions is uniquely positioned to benefit
long-term from emerging demand for intelligent
micro-energy grids and the increasing demand for
reliable renewable energy sources that will grow
over the coming years. The growing generation and
integration of renewable energy sources create new
challenges for the public grid, especially regarding
grid stabilization and grid leveling. AEG PS Group
provides highly customized power systems to sup-
port integration of the renewable energies into the
grid, solutions for energy storage and solar solutions.

-75-
-89-

intelligent

The values that drive
our business rela-
tionships are

Innovation – Respect – Accountability - Reliability -
Ethical business behavior
AEG Power Solutions Group is the sole subsidiary of
the holding company 3W Power S.A.

GENERAL CONTACT

[email protected]

DIRECT CONTACT

SINA for Engineering Projects
13 Omar Ibn El Khttab, El Sefarat District 11341Nasr City,
Cairo, EGYPT
Phone: + (20 2) 26776376 +20-26776376 / +20-26776343.
Mob: +20-01128007882 / +20-01140084664
Email: [email protected]
[email protected]

94

--9760--

intelligent

PROTECT PLUS M600

MODULAR 3-PHASE UPS, 30 - 600 KVA

Protect Plus M600 is the Modular UPS sys-
tem that combines high AC/AC efficiency
values with a compact footprint and a flexi-
ble and scalable architecture, able to reach
up to 900 kVA. It is designed specifically
for data centers, transportation, retail and
light industrial applications as well as all
other critical applications where power re-
liability is essential and power consumption
is an important variable. For the 180 and the
300kVA models, it is possible to connect in
parallel up to 3 cabinets, ultimately pro-

viding up to 900 kVA. This scalability optimizes your CAPEX and limits your OPEX.
They offer input PF >0.99 and input THDi <3%, even when a low percentage of load is
applied. The Protect Plus M600 from AEG Power Solutions can reach the highest AC/
AC efficiency levels available, of up to 98.5% in ECO mode. The flat efficiency curve
from 35% of load will ensure maximum energy savings at every percentage of loads.

Protect plus Protect plus
30 Kva power modules
m600 - key features
• Isolated airflow with redundant fans
• Double Conversion (VFI-SS-111) • Independent LCD display for each module
• Transformer-less architecture: lower • Autonomous Start-up (independent from

space and weight the central display)
• Excellent power capability, up to • Dismountable front panel
• High power density
900kVA without additional tools • Cold start
• 30kVA hot-swappable power modules for

predictive power management and lowest
MTTR
• AC/AC Efficiency in double conversion
up to 95.5%
• ECO mode, up to 98.5% efficiency
• Idle Mode
• Output PF = 0.9
• 10.4" color Touch Screen
• Double doors for back access and easy
maintenance
• Intelligent and innovative Self Aging
Test
• MoniUPS compatible

95

--9771--

intelligent

PROTECT PLUS M600 - DESCRIPTION

Hot swappable power
modules for predictive power
management and lowest Mean
Time To
Repair rate

MODULARITY: EVOLVE WITH YOUR NEEDS AT
OPTIMIZED COST

Your business is constantly evolving and plete flexibility, n+x inbuilt redundancy as well
so is your data center infrastructure or pro- as automatic and predictive management of
duction line. The Protect Plus M600 is the power. Protect Plus M600 combines the best
right answer to this. It offers a scalable solu- transformer-less IGBT technology with a mod-
tion by providing the ability to add or re- ular architecture to improve the performance
move power modules in the event of growth of the whole system. It reduces power loss-
or decrease of the protected load, com es, energy consumption and operating costs.

SCALABLE ARCHITECTURE FOR OPTIMUM
PERFORMANCE AND EXIBILITY

The placement of power modules into Idle Mode in a ro-
tating fashion as needed.

96

--9782--

intelligent

The modular and scalable architecture of Protect Plus M600 is designed to max-
imize savings in terms of foot print (m2), power installed (kVA), electrical sys-
tem (cabling and protection devices), security (MTTR and MTBF) and most
importantly, energy management (kWh and costs). Moreover, it allows for an in-
crease or decrease in power installed depending upon the needs of the load.
Each power module has independent hardware and controlability, able to oper-
ate and coordinate with other modules within the system. The control of pow-
er modules connected in parallel is decentralized in the single 30 kVA device (no
centralized control system). The omission of the master/ slave architecture, elim-
inates any possibility of a problem due to the failure of a single power module.
The common frames are available in three different dimensions: able to connect up to
6, 10 or 20 power modules (including redundancy). The frames allow for input/output
connections to the electrical system and to the protected load, with centralized static and
manual bypass lines. This infrastructure provides a unique platform for viewing and man-
aging all parameters, as well as historical events as the UPS frame, the single module, the
electrical system and the supplied load are all connected. Information about preventive or
corrective maintenance is then easily accessible through the LCD touch screen display.

THE PREDICTIVE MANAGEMENT
OF INSTALLED POWER

When using redundant systems (n+1 configuration), it
is quite common that a UPS protects light loads, thus
decreasing the overall system’s efficiency; in this case
the ideal solution is that the UPS may maintain “ac-
tive” only the power modules that are strictly neces-
sary for the actual critical load (plus the “+1” redun-
dant power module). The modular Protect Plus M600,
with its Idle Mode, allows for the ability to “freeze”
automatically, and in rotation, the power modules
that are not normally used to protect the critical load.
Therefore, even with “light” loads, the overall AC/
AC efficiency of the UPS system is increased, and
at the same time, its level of reliability optimized.

INTELLIGENT MANAGEMENT
FOR GREATER ENERGY SAVINGS

The modular Protect Plus M600 from AEG PS has the best IGBT technology and scal-
able architecture available. The intelligent management of power
modules allows the system to reach high AC/AC efficiency values, typically up to 95.5%
in double conversion (VFI) and up to 98.5% in ECO mode (VFD), thus ensuring the sys-
tem’s optimization and reduction of energy waste.

97

--9793--

intelligent

EASY INSTALLATION, OPERATION
AND MAINTENANCE

All power modules as well as other critical components can be
removed from the front of the cabinet thereby affording easy
accessibility and smooth maintenance and operation of the
ventilation system. In addition to perfectly matching a solu-
tion to your requirements, our service net- work will guaran-
tee you full assistance from commissioning to maintenance,
to make your power supply as easy and as reliable as possible.

SERVICES: User interface and ac-
INDUSTRIAL cessories
UPS & INVERTERS
• User-friendly interface
98 • Monitoring, managing and shutdown soft-

ware
• RS232 serial port
• USB port
• EPO contact (for remote emergency push

button)
• Diesel Mode contact
• Modbus port available as standard
• SNMP card as option
• Remote Panel (optional)
• Bottom cable entry (for 300 kVA Frame)

• Pro Care Preventive Maintenance Options
• Turnkey solutions
• Installation & commissioning
• Maintenance services
• E-Service / remote monitoring
• 24/7 hotline
• Onsite training
• Hot swapping
• Onsite battery replacement
• Battery monitoring
• Facility and equipment management
• 24/7 global onsite contracts
• Power quality assessment
• Load bank & site capacity analysis
• Trouble shooting and repair

--9804--

intelligent

PROTECT BLUE

HIGH POWER DATA CENTER UPS (250KW-4MW)

Protect Blue offers a highly efficient & reliable UPS
solution for large data centers and IT applications in
power ranges up to 4MW. In times of constantly in-
creasing energy prices, Protect Blue helps reduce the
costs for operation and cooling to a great extent through
high efficiency. Protect Blue is based on a 250kW pow-
er block architecture that can be configured with par-
allel operation to meet high power requirements (up to
4000kW); n+1 redundancy operation is also possible.
All “Power Blocks” are equipped with decentralized
control mechanisms to increase operational safety.
Protect Blue is transformer-less, works with the latest 3
level IGBT technology and therefore typically reaches
an efficiency level of up to 95.5% (in double conver-
sion, VFI). Protect Blue combines all the advantages of
this technology, such as low input THDi <3%, high in-
put power factor >0.99 and output power factor up to 1.

KEY FEATURES

• Flexible power configuration from 250 kW
• Parallel switching up to 4 MW
• Developed for tomorrow’s power supply system: need- and price-oriented
• energy management
• High operating security through a flexible redundancy concept
• Highest possible typical efficiency of up to 95.5 % during genuine “online”
• operation
• Three operating modes available: double conversion (VFI), ECO mode (VFD) and

Idle mode
• Low input THDi <3 %
• Output power factor up to 1
• Intuitive 7" touch screen
• Front access to all important components
• Wall assembly possible» Extensive communication options
• Highest reliability based on quality components and many years of AEG PS indus-

try experience
• Unique AeBM battery management system maintains the battery

99

--9815--

intelligent

100

--9826--





TRANSFORMERS intelligent

Transformers

WHAT
IS A
TRANSFOER?

A transformer is an electri- nated steel core. When volt- ent voltage value at constant
cal device which converts al- age is introduced into one frequency, it has no moving
ternating current from one coil (called the primary), it parts and is a completely
voltage to another. It can be magnetizes the iron core. As static solid state device which
designed to increase or de- a result, a voltage is induced insures, under normal oper-
crease voltages and works into the secondary or output ating conditions, a long and
on the magnetic induction coil. The change of voltage trouble-free life, as used to
principle. A transformer (voltage ratio) between the transmit the electrical power
has no moving parts and is a primary and secondary de- form the generation places
completely static, solid state pends on the turn’s ratio of to consumption places.
device, which insures under the two coils.
normal operating condi- it’s consider electromagnetic
tions, a long and trouble-free machine, used to convert the
life. A transformer consists alternating power with spe-
of two or more coils of insu- cific voltage to alternating
lated wire wound on a lami- power too but with differ-

131

--9839--

intelligent TRANSFORMERS

Consist of:

In the first must know the transformer designed to “step up transformer” or “step down
transformer”.
It’s consisting of simplest form, of two or more coils of insulated wire wound on a laminat-
ed steel core.

Primary coil:

its insulated cupper coil connected to generation source.

Secondary coil:

its insulated copper coil connected to electrical loads

Iron core: Made of silicon wrought iron in the form of thin strips iso-
We can say: lated from each other to reduce the eddy currents.
When voltage is introduced to one coil, called the primary,
it magnetizes the iron core. A voltage is then induced in the
other coil, called the secondary or output coil. The change of
voltage (or voltage ratio) between the primary and secondary
depends on the turns ratio of the two coils.

We Can Say

When voltage is intro-
duced to one coil, called
the primary, it magnetizes
the iron core. A voltage is
then induced in the other
coil, called the secondary
or output coil. The change
of voltage (or voltage ratio)
between the primary and
secondary depends on the
turns ratio of the two coils

132

--18040--