Fire Alarm System “AVENGER”
Submittal
TEBA UNUTED GROUP
Address: 98 Hassan Al-Maamoun St., Nasr city, Cairo, Egypt
Telephone: 02-26774254/9 – 2677445/1
Fax: 02-26774256
E-mail: [email protected]
Introduction
TEBA UNUTED GROUP
Address: 98 Hassan Al-Maamoun St., Nasr city, Cairo, Egypt
Telephone: 02-26774254/9 – 2677445/1
Fax: 02-26774256
E-mail: [email protected]
ةسدنهلاو تاديروتلل ةبيط
ﺔﯾﻔﯾرﻌﺗ ﺔﻟﺎﺳر
ةكرش نع ةرصتخم ةذبن ميدقت انرسي
ةسدنهلاو تاديروتلل ةبيط
) ةدحتملا ةبيط ةعومجم تاكرش ىدحإ(
ذنم ةيرصملا ق وسلا يف نودجاوتم نحن ،ةيبرهكلا عيزوتلا تامهمل ةلماكتملا لولحلا مدقت يتلا ةيرصملا تاكرشلا قرعأ نم نحن
ةصصختملا تلاباكلل ةعنصملا تاكرشلا ىدحإ يهو ةيلاطيلإا ITALCOND دنوكلاتيإ ةكرشل ديحولا ليكولا نحن ،اماع نوثلاث
،ملاعلا ىوتسم ىلع ةدوجلا ةيلاع
ﻲﺿرﻷا ﺔﻣظﻧأ ﻰﻓ ﺔﺻﺻﺧﺗﻣﻟاو ﺔﯾﻛﯾرﻣﻷا HARGER ﺔﻛرﺷﻟ يرﺻﺣﻟا عزوﻣﻟا ﺎﻧﻧا ﺎﻣﻛ
نوﺻﺻﺧﺗﻣ ﺎﻧﻧا ﺎﻣﻛ ﻖﻋاوﺻﻟا تﺎﻌﻧﺎﻣو ﻲﺿرﻷا ﺔﻣظﻧأ ﻰﻓ ﺔﺻﺻﺧﺗﻣﻟاو ﺔﯾﻛرﺗﻟا رﯾﺑﻣأ ﺔﻛرﺷﻟ دﯾﺣو لﯾﻛوو ﻖﻋاوﺻﻟا تﺎﻌﻧﺎﻣو
ةصاخلاو ةيموكحلا تاعاطقلا ىربك ىدل نودمتعم اضيأ نحنو AVENGER ﺔﻛرﺎﻣ ﻖﯾرﺣﻟا ﺔﺣﻓﺎﻛﻣ ﺔﻣظﻧأ لﺎﺟﻣ ﻰﻓ
اهريغو ةيلخادلا ةرازو عاطق يف ىلولأا ةجردلا نم زيمتملا لواقملا ةجرد ىلع نولصاح اننأ امك ، ةماعلا ت لاواقملا لامعأ يف
.انلامعأ ةقباس يف ةحضاولا تاعاطقلا نم
:ةيتلآا تلااجملا يف ةرقوملا مكتئيه نيبو اننيب ءانبلا نواعتلا تايوتسم ىقرأ قيقحت يف نيلمآ
AVENGER - USA ﺔﻛرﺎﻣ ﻖﯾرﺣﻟا ﺔﺣﻓﺎﻛﻣ ﺔﻣطﻧأ دﯾروﺗ -
ITALCOND - ITALY ﺔﻛرﺎﻣ ﺔﺻﺻﺧﺗﻣﻟا تﻼﺑﺎﻛﻟا دﯾروﺗ -
HARGER - USA ﺔﻛرﺎﻣ ﻖﻋاوﺻﻟا تﺎﻌﻧﺎﻣو ﻲﺿرﻷا ﺔﻣظﻧأ بﯾﻛرﺗو دﯾروﺗ -
AMPER - Europe ﺔﻛرﺎﻣ ﻖﻋاوﺻﻟا تﺎﻌﻧﺎﻣو ﻲﺿرﻷا ﺔﻣظﻧأ بﯾﻛرﺗو دﯾروﺗ -
ةدحتملا ةبيط ةعومجم
ةرهاقلا – رصن ةنيدم – ) 13 :رودلا( نومأملا نسح 98 :ناونعلا
02-26774254/9 – 26774450/1 :نوفيلت
02-26774256 :سكاف
[email protected] :ينورتكلا ديرب
TEBA for Trading & Engineering
Armed with 10s of employees working in TEBA for Trading & Engineering We
managed to build our hierarchy in supplying & Contracting as following:
Marketing department responsible for:
The company Technical approvals
Develop long-term relationships with clients (Owners and Consultant)
Identify opportunities that can be transferred to sales leads
Creating all the marketing tools catalogues, brochures, C.D, flyers
organizing seminars & exhibitions
Sales department responsible for:
Searching for new clients who might benefit from company products
Develop a long-term relationships with clients (Owners and Contractors ) in
each & every market segment
- Get Sales leads, Follow up offers, persuade clients that the products satisfies
their needs in terms of quality, price and delivery to achieve orders.
Techno Commercial department responsible for :
- Preparing Technical & commercial offers using high advanced technical
tools.
Design department responsible for:
- Preparing a full set of documents, assembly & shop drawings including all
technical details, bill of material, control diagrams, as built documentation.
Purchasing department responsible for:
- Purchase the material required from the planning department.
- Mechanical department responsible for:
- Formation of the mechanical parts used in our low voltage products as sheet-
metal &copper parts
Project Management department responsible for:
Managing All project phases from Initiation, Implementation, Until Closing.
Financial department:
- Manage the company’s cash in a profitable way, and provide all the activities
with its cash requirements.
- Maximize the company’s wealth via increasing the sales and reducing the
cost
- Ensure the best utilization of the company’s resources.
- Responsible for issuing the monthly, the quarterly, the annual financial
statements.
- Monitoring and controlling the company’performance.
Human Resources department responsible for:
- Put Mission and vision of the company into action this includes the following:
Recruiting & Hiring, Training, salary & Benefits, communication and
performance management.
Service department Responsible for:
- Rehabilitation & Retrofitting
- Erection and installation
- Commissioning and start up
- After sales support and services
Quality Policy
The Policy of TU Company is to provide Products that
conform to our customers' requirements and deliver
them on time and at a competitive price.
Our name must represent quality to our vendors, our
customers, and ourselves.
The top management has established quality
objectives for each department, which are reviewed
periodically to ensure continuous improvement of the
quality management system.
Marketing and Sales Manager General Manager
Head Office:
TEBA for Trading & Engineering
th
Address: 98 Hassan El Ma’amon St., (13 floor), Nasr City, Cairo, Egypt.
Tel: +20 26774256-7-8-9 - 26774450-1
Fax: +20 226774256
TEBA for Developed Industries
nd
Address: 98 Hassan El Ma’amon St., (2 floor), Nasr City, Cairo, Egypt.
Tel: +20 26774256-7-8-9 - 26774450-1
Fax: +20 226774256
TEBA Factory:
th
Address: Plot No. 1 - Industrial Zone (7A) – 10 of Ramadan – Egypt
Tel: +20 55 4334340 / 1 / 2
Fax: +20 226774256-7-8-9 – 26774450 / 1
E-mail: [email protected]
Website: www.tu-egy.com
Working hours: From 09:30 am To 17:30 pm (From Saturday to Thursday)
About AVENGER
TEBA UNUTED GROUP
Address: 98 Hassan Al-Maamoun St., Nasr city, Cairo, Egypt
Telephone: 02-26774254/9 – 2677445/1
Fax: 02-26774256
E-mail: [email protected]
Avenger Systems is an independently owned fire detection and suppression company based in the United
States and operating in most regions around the world. Avenger Systems is committed to providing our
customers with the highest quality, cost-effective products, solutions and excellent customer service,
while focusing on our customers, strategic partners, employees and state of the art technologies.
Avenger Systems is a progressive and reliable organization, providing superior fire detection and
suppression solutions with outstanding customer support.
Our Vision: Avenger Systems was founded with the passion, vision and determination to provide our
customers with superior-quality, cost-effective fire detection and suppression system solutions with
exceptional customer support that exceeds most company's expectations. Our foundation is truly our
people.
Our Culture: Avenger Systems corporate culture fosters creativity, hard work, collaboration and success.
Our Technology: Building on our past success in the fire and suppression markets, Avenger Systems
utilizes state-of-the-art technologies to enable our customers to compete in all type of projects from
small to the very large with software that is simple to use and yet powerful in its abilities.
Autorization Letter
TEBA UNUTED GROUP
Address: 98 Hassan Al-Maamoun St., Nasr city, Cairo, Egypt
Telephone: 02-26774254/9 – 2677445/1
Fax: 02-26774256
E-mail: [email protected]
Products Technical Data
TEBA UNUTED GROUP
Address: 98 Hassan Al-Maamoun St., Nasr city, Cairo, Egypt
Telephone: 02-26774254/9 – 2677445/1
Fax: 02-26774256
E-mail: [email protected]
OASIS
Analog Addressable Fire Alarm Control Panels
Single Aperture Double Aperture
Includes Zone LED Module and Printer
Standard Features
• UL Listed (Tenth Edition) • Hard-wired fire and trouble routing inputs and outputs
• 2 to 8 loop or 2 to 16 loop versions • Modular and expandable electronics
• 400mA loop current • 400 subaddress points per loop (800 per loop module)
• 4 programmable NACs; Class B or 2 Class • Option to “invert” inputs and outputs
A with internal synchronization • 5000 programmable cause and effects;
• 5.25 A or 10.25 A power supply options over 50,000 inputs and outputs
• 3 programmable inputs and 5 • Can be networked with programmable functionality
programmable relay outputs • Programming via USB port to PC or memory stick
• 7 inch, full-color resistive touch screen • Graphical PC User Interface - coming soon!
with intuitive user interface
• Up to 24 programmable soft “function keys”
• Up to 64 user login accounts
2 | Oasis
Product Overview
The all new Oasis product range of fire alarm control equipment
combines the very latest hardware and software to produce a control
and indication system, which is powerful and sophisticated, yet simple
to use and understand. The flexibility of the Oasis platform is such that
it can be re-configured to realize many other control and indication
applications, with direct integration into intelligent buildings.
Moving away from the simple, price driven competitive model used by
most manufacturers today, the Oasis concept is designed to add value
to System Designers, Integrators, Service Providers, and end users.
Developed from the “ground up” and using some of the most advanced
technology available, Oasis is designed as one of the most powerful,
intelligent, and technically robust fire alarm products available.
Not only do the products and services offered under the Oasis brand
provide solutions to the most technically challenging applications in life
safety, Oasis will deliver added value, market advantage, and a
competitive edge to your business.
Optional Panel Peripherals
• Dual Loop Panel Module (S758) • Printer (S768)
The Dual Loop Panel Module monitors loop device The Oasis Printer is an optional feature for printing fire system
status and provides status to the panel processor. events as they occur. The printer is located on the fascia,
It holds device configurations and operates in a below the Zone LEDs (if present). It is a thermal printer and
standalone manner when catastrophic failures occur. never requires replacement ink. Printing
• 16 Channel I/O Interface Card (K6006) is performed on heat-sensitive paper rolls. A trouble message
The 16 Channel I/O Interface enhances the versatility is reported when the paper runs out. The printer includes a
of the alarm system by providing additional input and output front-loading feature for replacing paper rolls.
capabilities to the Oasis Fire Alarm Control Panel. Inputs or • Zone LED Module (S771)
outputs can be selected for up to 16 individual channels, and The Zone LED module contains 48 LEDs and is connected to
are configured in the same the LCD Main Processor Board of the Oasis Fire Alarm
way as devices connected to addressable loops of the panel. Control Panel. A maximum of three Zone LED modules can
The 16 Channel I/O Interface can be configured be connected to provide the fascia with 144 Zone LED
to contribute or act upon cause and effect logic. indicators.
• Media Gateway™ Panel Module (S788) • 4 Channel NAC Panel Module (S793)
The Media Gateway Panel Module provides connectivity FUTURE ENHANCEMENT
to monitoring centers using IP (Sur-Gard), or dial-up Additional NAC output capability can be added to by using 4
connectivity. The Media Gateway may also be used Channel NAC Modules. These boards have 4 supervised
to meet integration application requirements. NAC outputs, each of which can be individually programmed.
• 8 Channel Relay Panel Module (S791) The circuits can be configured for class A or B operation.
The 8 Channel Relay Panel Module has 8 voltage-free These circuits can be configured to act upon cause and effect
changeover relay contacts, each of which can be individually logic.
programmed. All outputs are configurable in the same way • 8 Channel Conventional Zone Panel Module (S792)
as devices connected to the loops and all may be acted upon FUTURE ENHANCEMENT
by cause and effect logic. These boards are typically used in The 8 Channel Conventional Zone Panel Module has 8
applications which require more than the five standard relay supervised detection circuits (Class B). Each circuit can
outputs, such as signaling to other systems or plant control. support up to 20 conventional detectors and approved
devices. Individual circuits may be configured for trigger
• Network Module (S723)
The Oasis Network Module provides enhanced high-speed resistor or short circuit activation. These circuits may
communication for networking fire control panels. The be used for any of the standard input actions and can
be configured to contribute to cause and effect logic.
network provided by this module can support combinations of Each pair of circuits (e.g., 1 and 2, 3 and 4, etc.) can
Oasis Fire Alarm Control Panels and Oasis Vision units. be joined to form a single Class A configuration.
Oasis Fire Alarm Control Panels can receive events from
other panels in the network. The Class X networking used in • 16 Channel I/O Interface Panel Module (S772)
conjunction with the Network Module provides tolerance FUTURE ENHANCEMENT
against open and short circuit trouble conditions. The 16 Channel I/O Interface Panel Module will provide
the same functionality as the 16 Channel I/O Interface
Card, with the convenience of a plug-in-module.
3 | Oasis
T echnical Specifications
2 to 8 LOOP(4 SLOT) ENCLOSURE
Size Standard Cabinet - 420mm (W) x 590mm (H) x 153mm (D), or 16.5in (W) x 23.2in (H) x 6in (D)
Deep Cabinet - 420mm (W) x 590mm (H) x 203mm (D), or 16.5in (W) x 23.2in (H) x 8in (D)
Construction Mild sheet steel enclosure, 1.5 mm
Cable Entry Standard Cabinet - 28 knockouts top, 19 knockouts back, 1 knockout each side, 2 knockouts bottom
Deep - 38 knockouts top, 19 knockouts back, 1 knockout each side, 2 knockouts bottom
Optional Semi-Flush Mounting Kit Semi-Flush Mounting Collar Kit
KM5FCRD - Red
KM5FCGY - Gray
KM5FCBS - Black
Battery Capacity Standard Cabinet - Up to 28 Ah (Power Sonic PS-12280)
Deep Cabinet - Up to 40 Ah (Power Sonic PS-12400)
2 to 16 LOOP (8 SLOT) ENCLOSURE
Size Standard Cabinet - 540mm (W) x 720mm (H) x 160mm (D), or 21.3in (W) x 28.3in (H) x 6.3in (D)
Deep Cabinet - 540mm (W) x 720mm (H) x 212mm (D), or 21.3in (W) x 28.3in (H) x 8.3in (D)
Construction Mild sheet steel enclosure, 1.5 mm
Cable Entry Standard Cabinet - 38 knockouts top, 25 knockouts back, 2 knockouts each side, 2 knockouts bottom
Deep Cabinet - 50 knockouts top, 25 knockouts back, 2 knockouts each side, 2 knockouts bottom
Battery Capacity Standard Cabinet - Up to 28 Ah (Power Sonic PS-12280)
Deep Cabinet - Up to 40 Ah (Power Sonic PS-12400)
ALL MODELS
ALL MODELS
Finish Epoxy powder coated
Color Enclosure
Red (RAL3002)
Gray (BS 00 A 05)
Black (RAL9005)
Fascia
Signal White (RAL9003)
Power supply voltage 120 V AC or 240 V AC
Power supply rating at 24V DC 5.25 A (charges up to 60 Ah)
10.25 A (charges up to 100 Ah)
Display Full-color 800 x 480 LCD with resistive touch screen and automatic backlight dimming
Software zones 2000
Software groups 5000
Cause and Effects 5000
Event log 10,000 events, 1 second resolution. Filterable and printable.
Detection loops 2 to 16 added 2 at a time (S758 dual loop cards)
Detection loop current 400 mA each
AUX 24V Output 2; each rated at 900 mA
NACs 4; each rated at 2.5 A. Class B or 2 Class A.
Programmable Relay Outputs 5; 30 V DC 1 Amp
Programmable Inputs 3; designed to be activated by voltage-free contacts
Network Connection Optional network card provides communication for networking 127 fire control panels
NAC Synchronization Internal Support of System Sensor, Wheelock, Gentex, and Amseco protocols
Printer 40 column, front-loading thermal
(OPTIONAL)
Zone LED Indicators Up to 3 banks of 48 (144) as standard
(OPTIONAL)
4 | Oasis
Panel ModelNumbers
Panel Options Valid Entries Description
OA Oasis Fire Alarm Control Panel
Product Style
OV Oasis Network Vision Annunciator
1 4 Slot Standard Enclosure
2 4 Slot Standard Plex-Door Enclosure
3 4 Slot Deep Enclosure
4 4 Slot Deep Plex-Door Enclosure
5 4 Slot Extra Deep Guard Station Enclosure - FUTURE ENHANCEMENT
Enclosure Style 6 4 Slot 19” Rack Mount Enclosure - FUTURE ENHANCEMENT
7 8 Slot Standard Enclosure - 16 Loop
8 8 Slot Standard Plex-Door Enclosure - 16 Loop
9 8 Slot Deep Enclosure - 16 Loop
A 8 Slot Deep Plex-Door Enclosure - 16 Loop
C Annunciator
0 English
1 Portuguese
Language
2 Spanish
3 Taiwanese
0 None
1 5.25 A 120V
Power Supply
2 5.25 A 240V
3 10.25 A (auto-voltage sensing)
00 Not Fitted
NC Network Module only (Network Vision Annunciator)
Loop Modules & H# 2-Loop Panel Module, Hochiki Protocol
Communication Modules I# 2-Loop Panel Module, Hochiki Protocol, and Media Gateway
J# 2-Loop Panel Module, Hochiki Protocol, and Network Module
K# 2-Loop Panel Module, Hochiki Protocol, Network Module, and Media Gateway
1 Red (RAL3002)
Cabinet Color 4 Gray (BS 00 A 05)
6 Black (RAL9005)
0 No Printer / No Zone LEDs
1 No Printer / No Zone LEDs, Blank 2nd Aperture
3 Printer / No Zone LEDs
Printer, Zone LEDs 4 Printer / 48 Zone LEDs
& Aperture
5 No Printer / 48 Zone LEDs
6 No Printer / 96 Zone LEDs
7 No Printer / 144 Zone LEDs
a 16 Channel I/O Panel Module (S772) - FUTURE ENHANCEMENT
b 8 Channel Relay Panel Module (S791)
Optional Peripheral Cards
c 8 Channel Conventional Zone Module (S792) - FUTURE ENHANCEMENT
d 4 Channel NAC Module (S793) - FUTURE ENHANCEMENT
Supreme RS AS0810-xx (1 Loops)
Analog Addressable Fire Alarm
AS0820-xx (2 Loops)
Control Panels (1 or 2 Loops)
Standard Features Product Overview
• One full SLC circuit expandable to two Supreme RS is a versatile range of open
• 3 programmable relays protocol fire alarm control panels
compatible with existing Supreme fire
• 5.25A integrated power supply alarm panel technology.
• Large graphic display Available with one or two detection loops
for a total of 254 primary SLC points or up
• Real time clock
to 800 points using addresses and sub-
• Compatible with eMATRIX graphics addresses. Supreme RS uses leading edge
annunciator microprocessor based electronics to
provide a flexible control system with
• Powerful, network wide cause and high reliability and integrity.
effects (500 total). Fully user
programmable by point or zone. Suitable for all small to medium sized fire
detection systems, Supreme RS control
• Can be networked with additional RS panels can be expanded and networked
and/ or Supreme control panels.
to become part of much larger systems if
• Compatible with eVIEW Annunciator the need arises, therefore providing a
Programmable through a PC future proof solution for any installation.
connection to the panel With its large graphical display and
• Same look and feel as Supreme range. ergonomic button and indicator layout,
the Supreme RS control panel is simple
• Stores 1000 last events in history log.
and straightforward to understand for
• Model ranges include with or without installers, commissioning engineers and
a Dual-Line internal DACT end users alike.
• Compact, stylish enclosure
• Available in Red or Gray
• 2 Programmable NAC circuits with
internal synchronization support.
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Added Features: Technical Specifications
Construction: 16AWG sheet steel
Supreme RS with Internal Dimensions: 14.5”W x 18.9”H x 4.25” D
Modem/DACT (AS0816-xx/AS0826-xx) Weight (without batteries): 20lb
• Dual line digital communicator and modem Finish (lid & box): RAL3002 (Red) or BS 00 A 05 (Gray)
• Central Station reporting; SIA and Contact ID Secure Finish (product labels): BS 00 A 05 (Gray)
• On-board loop starts terminal connections for both Mains voltage supply: 115 or 230V AC 50 or 60 Hz. (specify
primary and secondary Telco lines
when ordering, default is 115V)
Mains supply fuse: 1.6A 250V
Power supply DC rating: 24V 5.25 Amps
Supreme RS with Internal Modem/DACT Charger Current: 1.25 Amps max
& eNet (AS0817-xx/ AS0827-xx) Battery (24 hour standby): 9Ah 12V (2 per panel)
(non-networked)
• Dual line digital communicator and modem SLC loops: 1 or 2 (class A, “style 6 or 7” or class B, “style 4”)
• Central Station reporting; SIA and Contact ID
• On board loop start terminal connections for both primary Devices per loop: 127 Sensors or Modules
and secondary Telco lines NAC Outputs: 2 x 1.6 Amps Regulated (continuous)
• eNet networking card pre-installed (one required per Relay Outputs: 3 x Form C rated 1 Amp @ 30VDC
node).
Aux. Power: 2 outputs, 360mA @ 24VDC each fused at 500
milliamps
Supreme RS & eNet (AS0815-xx/AS0825-xx) Fault contact rating: 30V DC 1 Amp
Alarm contact rating: 30V DC 1 Amp
• eNet networking card pre-installed (one required per node).
Detection loop: 250 milliamp output
Display: 8 line x 40 character LCD (320 character total)
Serial expansion port: Serial RS485
PC port: Serial RS232
Panel peripherals available: Network connection: Optional network Cards allow the use
of e-Net networking
• eNET Networking Card: AS1170-00 NAC Synchronization: Internal Support
• 1 Loop expansion board: AS1054-00 NAC Protocols: System Sensor, Wheelock, Gentex, Amsec
• Trim ring: AS1071-xx
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Supreme AS1420-xx (2 Loops)
Analog Addressable Fire Alarm
AS1440-xx (4 Loops)
Control Panels (2 or 4 Loops)
Standard Features Product Overview
• UL 864 9th Edition listed The Supreme AS1420 and AS1440 analog
• Multi-Loop 2 Analog Addressable Loops addressable FACPs support 2 or 4 SLC
Field upgradable to 4 loops for a total of 500 primary points and
• 127 primary points per loop up to 800 points using sub-points.
• Powerful, network wide cause and effects
(500 total). Fully user programmable by
point or zone. SLC loop communications uses standard
• Up to 800 points per panel when using twisted pair cabling, shielded cable is not
devices and sub-points necessary.
• Up to 10,000 ft. wiring length on SLC loop
• 64 Panels on a network The panel may be configured with various
• Programmable through a PC connection communication cards; Communications
to the panel, or through keypad options support remote programming,
• Programmable on-board relays: 5
• Supervised Powered Outputs: 3 central station monitoring, Virtual Panel
• Programmable Notification Appliance and networking.
Circuits: 4
• Power per NAC: 1.6 Amps Max The Panel can be configured as a stand-
• Programmable outputs on SLC loop alone panel with just a few devices for a
• Programmable Function button on front small building; it can also operate as the
display building system and can be part of a
• Fire Drill button on front display network with a total of 64 nodes serving a
• Day and night sensitivity settings (user multiple building campus or a very large
programmable)
• Power Supply: 5.25 Amp, regulated & facility.
integrated
• LCD Display: 8x40 Auto Learn capability provides a
• Zonal Mode: Annunciation by zone w/o convenient method to troubleshoot new
individual relationships installations before final programming is
• Panel Ring Modes: Common, Zonal, Stage loaded.
2
• NAC Outputs programmable as:
Continuous, March or Temporal
• Program Cause and Effects: AND, OR, or
Any Two (Cross Zone)
• Battery size: Up to 17 Ah in standard
enclosure; up to 52 Ah with external
cabinet
• Access levels: 3
• Access key switch: Yes
• Recognized for use in High Rise
• One man walk test – Fire Test Mode
• Available with semi-flush trim ring
• Available in Red or Gray
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Added Features: Technical Specifications
Supreme with eNET(AS1425- Primary AC: 120VAC @ 2 Amps 60hz (Optional 240 VAC 50hz)
xx / AS1445-xx) Output DC: 24VDC @ 4 Amps
Power Supply: 5.25 Amp regulated and integrated
Charger Current: 1.25 Amps max.
• Network uses standard RS485 cabling
• Up to 2,000 ft. between adjacent panels 115 Kbps Dimensions: 14.5” W x 24” H x 5” D
constant network speed Weight: 25lbs. (without batteries)
• Secure, fault tolerant communication Color: Red (optional gray)
• Up to 64 nodes
Display: 8 line x 40 character LCD (320 characters total)
Supreme with DACT Zones: 500 Zones per network
SLC loops: 2 or 4 (class A or B)
(AS1424-xx/ AS1444-xx Devices per loop: 127 sensors & modules (800 addresses +
sub-addresses max. per panel)
• Dual line digital communicator and modem
• Contact ID and SIA reporting NAC Outputs: (4) 1.6 Amp @ 24VDC (class B)
• UL 864 9th edition listed Relay Outputs: (5) Form C 1 Amp @ 30VDC
• Zone or point reporting
• Backup and duplicate reporting Voltage Outputs: (3) 500mA @ 24VDC, reverse polarity
supervised
Also available: Aux. Power: 500mA @ 24VDC
Aux Inputs: (3) digital pull downs
• 2 loop expansion board: AS1053-00
• Trim ring: AS1070-xx Current Consumption:
AS1420: 355 mA Standby
650 mA Alarm
AS1440: 455 mA Standby
Supreme Panel with internal 765 mA Alarm
printer
All Parts Number Available in Red or Gray with or without an
internal printer
When ordering specify -CP
where c = 1 for Red or 4 for Gray
where p = 0 for No internal printer or 3
for Internal printer
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
AS2010-00
Fixed Temp / Rate of Rise Heat Detector
Standard Features Operation
• Low Profile - Only 2.0” high, including The AS2010 incorporates a highly linear
base thermistor circuit. The specially designed
cover protects the thermistor while allowing
• Simple and reliable device addressing maximum air flow. The thermistor circuit
method produces a voltage proportional to the
temperature; this information is transmitted
• Uses the noise Immune Digital to the control panel as a digital value. When
Communication Protocol (DCP), the ambient temperature exceeds a
which utilizes interrupts for fast preprogrammed threshold (fixed temp or
response to fires. rate of rise), the sensor transmits an interrupt
• Rate of Rise temperature threshold = to the control panel indicating a fire alarm.
15°F/Min (determined by panel) The fire alarm control panel can adjust the
sensor’s fixed temperature threshold for
• Adjustable threshold temperature= different installation requirements.
135°F -190°F (determined by panel)
Up to 127 devices may be installed on each
Application SLC loop. The sensor address may be set by a
hand-held programming unit. The sensor
mounts to an electronics-free base and
The AS2010 Fixed Temperature / Rate of incorporates a locking mechanism for
Rise sensors provide accurate temperature security. The base provides mounting slots,
measurement data to the fire alarm control terminals for field wiring and a third terminal
panel. These sensors are well-suited for for a remote indicator/ LED. The sensor has
environments where dust, cooking fumes dual LEDs for easy viewing of the sensor
or other factors make the use of smoke status.
sensors Impractical.
Note:
Bases are not included
with detectors, please
order separately.
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Engineering Specification Technical Specifications
Heat sensors are installed in accordance with NFPA (National
Fire Protection Association) 72, the UL Listed Spacing Operating Voltage: 17-41 VDC
Requirements and the rules and regulations set forth by the Standby Current: 350μA
local authorities having jurisdiction.
Alarm Current: 500μA
The contractor shall furnish and install, where indicated on the Transmission Method: DCP—Digital Communication Protocol
plans, Fixed Temp / Rate of Rise Automatic heat sensors.
Maximum Humidity: 95% RH Non-Condensing
The Sensor and Base shall be UL listed as compatible with the UL Temperature Range: 135º F to 190º F
fire alarm control panel (FACP). The base shall permit direct
interchange with the Avenger AS2011 photoelectric smoke Operating Temperature Range: 32º F to 190º F
sensor, AS2010 heat sensor, and the AS2012 Multi-Criteria Rate of Rise: 15º F/ Min
sensor. Color & Case Material: Bone/ White - ABS Blend
The vandal-resistant, security locking feature shall be used in Weight: 3.2 oz, (4.9 oz with 4” base)
those areas as indicated on the drawing. The locking feature
shall be optional and can be implemented when required.
It shall be possible for the control panel to perform a functional Ordering Codes
test of the sensor without heat. The test method shall simulate
the effects of heat on the device to insure testing of internal Part Number Description
circuitry.
AS2010-00 Fixed Temp/Rate of Rise Heat Sensor
Bases AS7001-00 4” Mounting Base
AS7002-00 6” Mounting Base
The AS7001 and the AS7002 mounting bases are electronics AS7008-00 6” Sounder Base
free and are a simple rugged design with screw terminals for
wiring connections. A common mounting base allows sensor
interchange and maintains loop continuity when sensors are
removed. A simple anti-tamper head locking system is
provided which is enabled by removing a small plastic tab on
the back of the sensor. Once locked, the head can be removed
using a small diameter screw driver.
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
AS2011-00
Photoelectric Smoke Sensor
Standard Features Operation
• Low Profile - Only 2.0” high, including The detection chamber consists of a light-
base emitting diode (LED) and photodiode
arrangement. The chamber is designed such
• Simple and reliable device addressing
that light emitted by the LED cannot
• Automatic compensation for sensor normally reach the photodiode. In the event
contamination of fire, particles of smoke enter the chamber
and scatter the light. As the smoke level
• Built-in fire test feature increases, the scattering effect increases,
• Uses the noise-immune Digital causing more light to hit the photodiode.
Communication Protocol (DCP), which The chamber contains a unique baffle design
utilizes interrupts for fast response to which allows smoke to enter the chamber
fires while preventing external light from
affecting the photodiode. The photodiode
• Two built-in power/alarm LEDs input level is sampled to sense smoke
density.
• Programmable non-polling LEDs
When the smoke density exceeds a preset
• Non-directional smoke chamber
threshold the sensor transmits an interrupt
• Vandal resistant security locking feature to the fire control panel indicating a fire
condition. The fire alarm control panel can
• Removable smoke labyrinth for cleaning adjust the sensor threshold to compensate
or replacement for contamination.
Note: Up to 127 devices are permitted on each SLC
Bases are not included Application loop. A sensor address is set by a hand-held
programming unit. The sensor mounts to an
with detectors, please The AS2011 Photoelectric Smoke Sensor is electronics-free base and incorporates a
locking mechanism for secure installation.
order separately. particularly suited to detecting optically dense The base provides mounting slots, terminals
smoke typical of fires involving materials such
for field wiring and a third contact for a
as soft furnishings, plastic, foam or other remote indicator / LED. The sensor
similar materials which tend to smolder and incorporates dual LEDs for easy viewing of
produce large visible smoke particles. sensor status
Avenger’s unique design allows fast response
to flaming fires as well as smoldering fires
while preventing false alarms.
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Engineering Specification Technical Specifications
The contractor shall furnish and install where indicated on
the plans, photoelectric sensors AS2011 The combination Operating Voltage: 17-41 VDC
sensor head and twist lock base shall be UL listed compatible Standby Current: 450μA
with a UL listed fire alarm control panel. Alarm Current: 540μA
The Sensor and Base shall be UL listed as compatible with the Transmission Method: DCP—Digital Communication Protocol
fire alarm control panel (FACP). The base shall permit direct Maximum Humidity: 95% RH Non-Condensing
interchange with the Avenger AS2011 photoelectric smoke
sensor, AS2010 heat sensor, and the AS2012 Multi-Criteria UL Temperature Range: 32º F to 115º F
sensor. Operating Temperature Range: 14º F to 122º F
The sensitivity of the sensor shall be capable of being Sensitivity Range: 0.7 - 4.0%/ FT @ 300 FPM
measured by the control panel. 0.7 - 3.86%/ FT @ 2000 FPM 0.7
2.65%/ FT @ 4000 FPM
The vandal-resistant, security locking feature shall be used in
those areas as indicated on the drawing. The locking feature Air Velocity Range: 0-4000 fpm
shall be optional and can be implemented when required. Color & Case Material: Bone/ White - ABS Blend
Weight: 3.4 oz, (5.1 oz with 4” base)
Bases
The AS7001 and the AS7002 mounting bases are electronics Ordering Codes
free and are a simple rugged design with screw terminals for
wiring connections. A common mounting base allows sensor Part Number Description
interchange and maintains loop continuity when sensors are AS2011-00 Photoelectric Smoke Detector
removed. A simple anti-tamper head locking system is
provided which is enabled by removing a small plastic tab on AS7001-00 4” Mounting Base
the back of the sensor. Once locked, the head can be AS7002-00 6” Mounting Base
removed using a small diameter screw driver. AS7008-00 6” Sounder Base
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
AS2012-00
Multi Criteria Sensor
Operation
Standard Features
The AS2012 chamber consists of a light-
• Low Profile - Only 2.0” high, including emitting diode (LED) and photodiode
base arrangement. The chamber is designed such
that light emitted by the LED cannot
• Simple and reliable device addressing normally reach the photodiode. In the event
• Automatic compensation for sensor of fire, particles of smoke enter the chamber
contamination and scatter the light. As the smoke level
increases, the scattering effect increases,
• Built-in fire test feature causing more light to hit the photodiode.
The chamber contains a unique design
• Uses the noise-immune Digital which allows smoke to enter the chamber
Communication Protocol (DCP), which while preventing external light from
utilizes interrupts for fast response to fires affecting the photodiode. The photodiode
• Two built-in power/alarm LEDs input level is sampled to sense smoke
density. When the smoke density exceeds a
• Programmable non-polling LEDs preset threshold the sensor transmits an
• Non-directional smoke chamber interrupt to the fire control panel indicating
a fire condition. The fire alarm control panel
• Vandal resistant security locking feature can adjust the sensor threshold to
compensate for contamination.
• Removable smoke labyrinth for cleaning
or replacement The AS2012 Heat portion incorporates a
highly linear thermistor circuit, with two
Application thermistors mounted externally. The
specially designed cover protects the
The AS2012 Multi-Criteria Sensor is particularly thermistors while allowing maximum air
suited for detecting smoke produced by a wide flow. The thermistor circuit produces a
range of combustibles found in various voltage proportional to temperature which is
applications. Temperature monitoring is scaled, and transmitted as a digitally
achieved by a thermistor placed for optimum encoded value to the control panel. When
sensitivity. Avenger’s unique design allows fast the ambient temperature exceeds a
response to flaming fires as well as smoldering preprogrammed threshold (fixed
fires while minimizing false alarms. temperature), the sensor transmits an
interrupt to the control panel indicating a fire
alarm. The fire alarm control panel can adjust
Note: the sensor threshold for different standard’s
requirements.
Bases are not included Up to 127 devices are permitted on each SLC
with detectors, please loop. A sensor address can be set by a hand-
held programming unit. The sensor mounts
order separately. to an electronics-free base and incorporates
a locking mechanism for secure installation.
The base provides mounting slots, terminals
for field wiring and a third contact for a
remote indicator / LED. The sensor
incorporates dual LEDs for easy viewing of
sensor status.
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Engineering Specification Technical Specifications
The contractor shall furnish and install AS2012 (Multi-Criteria
Sensor) as indicated on the plans. The Multi-Criteria Sensor head Operating Voltage: 17-41 VDC
and twist lock base shall be UL listed and compatible with the UL Standby Current: 450μA
listed fire alarm control panel. Alarm Current: 540μA
The Sensor and Base shall be UL listed as compatible with the fire Transmission Method: DCP—Digital Communication Protocol
alarm control panel (FACP).
Maximum Humidity: 95% RH Non-Condensing
The base shall permit direct interchange with the Avenger UL Temperature Range: 135º F to 150º F
AS2011 photoelectric smoke sensor, AS2010 heat sensor, and Operating Temperature Range: 14º F to 122º F
the AS2012 Multi-Criteria sensor.
Sensitivity Range: 0.7 - 4.0%/ FT @ 300 FPM
The sensitivity of the sensor shall be capable of being measured 0.7 - 3.86%/ FT @ 2000 FPM
by the control panel. 0.7 - 2.65%/ FT @ 4000 FPM
The vandal-resistant, security locking feature shall be used in Air Velocity Range: 0-4000 fpm
those areas as indicated on the drawing. The locking feature shall Color & Case Material: Bone/ White - ABS Blend
be optional and can be implemented when required.
Weight: 4.2 oz, (5.9 oz with 4” base)
Bases
The AS7001 and the AS7002 mounting bases are electronics free
and are a simple rugged design with screw terminals for wiring Ordering Codes
connections. A common mounting base allows sensor
interchange and maintains loop continuity when sensors are Part Number Description
removed. A simple anti-tamper head locking system is provided AS2012-00 Multi Criteria Sensor
which is enabled by removing a small plastic tab on the back of
the sensor. Once locked, the head can be removed using a small AS7001-00 4” Mounting Base
diameter screw driver. AS7002-00 6” Mounting Base
AS7008-00 6” Sounder Base
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
AS6024-00
Fast Response Miniature Contact Module
Standard Features Operation
• Single input contact monitor The AS6024 Fast Response Contact Monitoring
• Fast, reliable contact monitoring Modules are designed to be used with pull
utilizing the DCP (Digital stations, water flow switches, and other
Communications Protocol) applications requiring the monitoring of dry
• 127 devices can be used per DCP loop contact devices. The interrupt driven Digital
Communications Protocol (DCP) combines
• Can be programmed to monitor maximum communication reliability and fast
Normally Open (NO) or Normally response to emergency conditions. The AS6024
Closed (NC) contacts
contact monitoring module does not require a
• Operates on Class A or Class B SLC loop separate 24 VDC power source.
• Accepts up to 14 AWG wire Each addressable contact monitoring module is
programmed with its own unique Signaling Line
Circuit (SLC) loop address. The device address is
electrically programmable and stored in
onboard EEPROM. Up to 127 devices can be
placed on the DCP SLC loop. The module
supervises the wiring to the contact with an End
of Line (EOL) resistor. It can be programmed to
monitor Normally Open (NO) or Normally Closed
(NC) contacts. If a fault condition occurs in the
Technical Specifications wiring, the module sends a trouble status signal
to the fire alarm control panel. When a change of
Supply Voltage (S-SC): 25.3-39 VDC status (contact changes state) is sensed by the
AS6024 it sends an interrupt to the control panel
Average Current Consumption: 339μA (Typical), 358μA (Alarm) indicating that an alarm has occurred.
Programmable Input: 1 Monitoring Input
EOL Device: 10K Ohms Resistor
Max. Quantity per Loop: 127
Dimensions: 1.75” W x 2.37” H x 0.5” D
Maximum Humidity: 90% RH Non-Condensing
UL Ambient Installation Temperature Range: 32º F to 120º F
Mounting: 2” electrical box
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
AS6040-00 & AS6041-00
with Short Circuit Isolator
Supervised Output Modules (Class A Wiring)
Standard Features Operation
• Built-in SCI circuitry (AS6041-00 only) The Class A Supervised Output Modules
• Flexible application (AS6040-00 & AS6041-00) have been designed
to provide application flexibility and quick
• Quick response to emergency
conditions response to emergency conditions.
• Operation parameters are maintained Flexibility is provided by a wide range of
by the module, and individual operating modes, including supporting multi-
communication with the control zone operations, and/ or functions, up to 16
system during emergency conditions different modulation patterns and multi-state
is not required programming. The operating parameters for
• Contacts are rated 2.0 Amps @ 24VDC the AS6040-00 & AS6041-00 are maintained by
the module and do not require individual
• Programming is highly flexible
providing 16 priority states plus communication with the control system during
zoning capability emergency conditions to operate.
AS6040-00 AS6041-00
• Programmed device output is turned The control panel simply broadcasts system
off, silenced, or programmed to conditions on the Signaling Line Circuit (SLC)
output the selected pattern and the AS6040-00 & AS6041-00 modules do
the rest based upon the custom configuration.
Each AS6040-00 & AS6041-00 provides a single
Class B or Class A circuit rated for 2.0 Amps @ 24
VDC. Each AS6040-00 & AS6041-00 also
requires a 24 VDC power source in addition to
the SLC.
Technical Specifications
Supply Voltage Nominal: 25.3-39VDC
Auxiliary Supply Voltage: 24 VDC
Average Current Consumption:
AS6040: 420μA (Typical),
AS6041: 220μA (Typical)
On S-SC Line: Maximum 6mA (Alarm)
Current Consumption on Auxiliary Power Lines: 50μA (Typical)
SCI on Resistance: 40 ohm Mx. (normal condition)
SCI Fault Detection Threshold: 12 Volts (Typical)
SCI Isolation Current (short circuit condition): 10mA (Typical)
Maximum Quantity per Loop: 127
Dimensions: 4.2” W x 4.7” H x 1.4” D
Mounting: 4” square electrical box
Relative Humidity: 90% RH Non-Condensing
Ambient Temperature Range: 32º F to 120º F
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Dual Relay Modules
AS6052-00 AS6053-00
Low Voltage Low Voltage w/Isolator
AS6054-00 AS6055-00
High Voltage High Voltage w/Isolator
Standard Features Operation
• Provides two independently The Dual Relay Modules have been
configurable Form C contacts per designed to provide flexible and quick
address.
response to emergency conditions. The
• Contacts are rated as follow: Avenger Systems Series allows
AS6052/ AS6053: 2A @ 30 VDC / 0.5A @ independent control of two form C
120 VAC contacts for a variety of normally open
AS6054/ AS6055: 8A @ 30VDC / 4.8A @ and normally closed contact applications
250 VAC
such as fan operation, elevator recall, door
• Up to127 devices can be used on each closure, and auxiliary notification.
SLC loop
Each Avenger Systems Series module
• Visible Bi-colored LED is software provides independent control of two
controlled and can be programmed to
blink red or green when polled. The LED Form C contacts while utilizing one SLC
AS6052-00
can be latched on when activated. (For (Signaling Line Circuit) address. The
All Models) modules have a highly configurable
AS6053-00 • Yellow LED indicates a short circuit programming algorithm that allows the
condition (AS6053 & AS6055 only) user to set up groups of devices (zoning)
for simultaneous operation of multiple
• Programming is highly flexible AS6052, AS6053, AS6054, AS6055
providing 16 priority states plus zoning modules. The operating parameters are
capability
maintained by the module and do not
• Operates on Class A or Class B SLC loop require individual communication with
Technical Specifications the control panel during the emergency
condition to operate. The control panel
Supply Voltage Nominal: 25.3-39 VDC broadcasts the control command on the
SLC loop and the Avenger Series modules
Average Current Consumption: 350μA (Typical), 405μA (Alarm) do the rest based on their custom
Contacts: 2 Independently Controlled Form C configuration. Since mechanically
AS6052/VF6053: 2A @ 30 VDC/ 0.5A @ 120 VAC latching relays are used within the
AS6054/VF6055: 8A @ 30 VDC/ 4.8A @ 250 VAC
Avenger Series modules, a separate
SCI on Resistance: 40 ohm Max. (normal condition)
24VDC power source is not required.
SCI Fault Detection Threshold: 12 Volts (Typical)
SCI Isolation Current (short circuit condition): 10mA (Typical)
Maximum Quantity per Loop: 127
Dimensions: 4.2” W x 4.7” H x 1.4” D
Mounting: 4” square electrical box
Relative Humidity: 90% RH Non-Condensing
UL Ambient Installation Temperature Range: 32º F to 120º F
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Wall Mount Horns, AS4000-10 Low Profile Evacuation Horn
Strobes & Horn/Strobes AS4001-10 Low Profile Evacuation Strobe
AS4002-10 Low Profile Evacuation Horn / Strobe
Standard Features Product Overview
• FM Approved, UL 464, UL 1971 Listed. The Avenger System Signal Series is a low
profile strobe and horn/strobe combination
• Nominal voltage 24VDC that offers dependable audible and visual
• Units have field selectable candela alarms and the lowest current available.
options of 15, 30, 60, 75, and 110 candela The Avenger System Series 24VDC offers
• Super –Slide Bracket - Ease of tamperproof field selectable candela options
TM
Supervision Testing of 15, 30, 60, 75, and 110 candelas.
• Checkmate - Instant Voltage The Avenger System Series horn offers a
TM
Verification continuous or synch able temporal three in
2400Hz and mechanical tone, a chime and
• Unit Dimensions: 5” high x 4.5” wide x whoop tone. All tones are easy for the
2.5” deep professional to change in the field by using
switches.
• Synchronize strobe and/or horn with
Avenger Series Control Module The Avenger System Series has a minimal
operation current and has a minimum flash
• Prewire entire system, then install signals
rate of 1Hz regardless of input voltage.
• Lower installation and operating costs
The Avenger System Series is shipped with
• Input terminals 12 to 18 AWG the standard 4” metal mounting plate which
incorporates the popular Super-Slide
TM
• Switch selection for high or low dBA feature that allows the installer to easily test
• Switch for chime, whoop, mechanical and for supervision. The product also features a
2400Hz tone locking mechanism which secures the
product to the bracket without any screws
• Tamperproof re-entrant grill showing.
• Switch for continuous or temporal 3 (not The appliance also features the Checkmate
TM
available on whoop tone) - Instant Voltage Verification feature which
allows the installer to check the voltage drop
• Surface mount with the AS4005 (Avenger draw and match it to the blueprint.
Surface Mount Box)
The Avenger System Series appliances are UL
• Silence horn while strobes remain 464 and UL 1971, listed for use with fire
flashing protective systems and are warranted for
• Wide voltage ranges 16-33VDC or FWR three years from date of purchase.
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Ordering Codes
Reverberant dBA In Anechoic Room
Part Number Description
@ 10ft. Per UL 464 1 dBA @ 10ft.
24V Low Profile Evacuation Horn-
AS4000-10 62-82 100
Red Faceplate
24V Selectable Candela Low Profile
AS4001-10 Evacuation Strobe-Wall Mount, Red 62-82 100
Faceplate
24V Selectable Candela Low Profile
AS4002-10 Evacuation Horn/Strobe-Wall 62-82 100
Mount, Red Faceplate
AS4002 Product Strobe Current Ratings
Candela 15cd 30cd 60cd 75cd 110cd
24 VDC 30mA 35mA 66mA 80mA 103mA
UL MAX 1 42mA 58mA 97mA 116mA 161mA
1 RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current
within the listed voltage range 16-33VDC for 24VDC units. For strobes the UL max current is usually at the
minimum listed voltage 16VDC for 24VDC units. For audible the max current is usually at the maximum listed
voltage. For unfiltered FWR ratings, see installation manual.
Minimum dBA @ Minimum dBA @ Regulated 24VDC
Horn Mode 10ft. per UL464 10ft. Max. Operating
(HIGH) per UL464 (LOW) @ High Setting (mA)
Temp 3 2400Hz 78 71* 28
Temp 3 Mechanical 76 70* 25
Temp 3 Chime 70* 66* 15
Continuous 2400Hz 81 74* 28
Continuous Mechanical 80 72* 25
Continuous Chime 70* 66* 15
Whoop 82 69 56
* Operating the horn in this mode at this voltage will result in not meeting the minimum UL reverberant sound level required for public mode fire
protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not
applicable when using the chime tone. The chime tone is always private mode.
Notes:
• To obtain the horn/strobe current draw, add the strobe current draw and the horn current draw.
• Operating temperature: 32°to 120°F (0° to 49° C). The Avenger AS4000, AS4001 and AS4002 are not listed for outdoor use.
• The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn
is producing a tone in the temporal 3 modes its sound pressure is the same as the continuous mode.
• For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see
installation manual.
• Avenger Systems does not recommend using a coded or pulsing signaling circuit with any Avenger strobes products.
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Weather-proof AS4029-10 24V Low Profile Evacuation Horn
Devices AS4006-10 24V Low Profile Evacuation Outdoor Strobe
AS4007-10 24V Low Profile Evacuation Outdoor Horn/Strobe
Standard Features Product Overview
• UL 464, UL 1638 Listed. The Outdoor Avenger Series offers
dependable visible and/or audible alarms
• Nominal Voltage 24VDC
for all outdoor needs.
• Unit is Shipped with UL1638 listed
AS4006 Candela Strobe or AS4007 Included with the Avenger Series is the
Candela Horn/Strobe AS4008 outdoor enclosure. The enclosure
is made of high quality Lexan material,
• Unit Dimensions: AS4008 - 5.75” High x
4.75” Wide x 4.18” Deep providing protection from weather
related conditions and allowing the
• To Obtain Outdoor Horn, Must Order necessary full candela output. This highly
AS4000 and AS4008 Separately
constructed enclosure meets various
• Super-Slide - Ease of Supervision installation requirements including
TM
Testing deterring moisture from entering the
• Checkmate - Instant Voltage enclosures.
TM
Verification The Outdoor Series is equipped with the
• Lower Installation and Operating Costs 4” mounting plate which incorporates the
Super-Slide™ feature that allows the
• Switch Selection for High dBA
installer to easily test for supervision. The
• Switch for Mechanical and 2400Hz Tone product also features a locking
• Switch for Continuous Tone mechanism which secures the product to
the bracket without any screws showing.
• Tamperproof Re-entrant Grill
The Avenger Series also features the
• Wide Voltage Range 16-33 VDC or FWR
Checkmate™ - Instant Voltage Verification
• Synchronize Strobe and/or Horn by feature which allows the installer to check
Using the voltage without removing the signal.
• Avenger Synchronization Control The Avenger Series strobe has a minimal
Module Listed for UL1638 when used
with the AS4008 enclosure operation current and has a minimum
flash rate of 1Hz and can vary up to 2Hz
• AS4008 Made of Clear Lexan - Provides regardless of input voltage.
Maximum Visibility and Reliability for
effective Visible Signaling - Allowing Full The Avenger Series appliances are UL 464
75cd Output and UL 1638 listed for use with fire
• Input Terminals 12 to 18 AWG protective systems and are warranted for
three years from date of purchase.
• Faceplate available in Red or Off-White
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Ordering Codes
Reverberant In Anechoic
Part Number Description dBA @ 10ft. Room dBA
Per UL 464 1 @ 10ft
AS4029-10 24V Low Profile Evacuation Horn - Red Faceplate 70-82 100
24V Low Profile Evacuation Outdoor Strobe - Wall
AS4006-10 N/A N/A
Mount, Red Faceplate
24V Low Profile Evacuation Outdoor Horn/ Strobe -
AS4007-10 70-82 100
Wall Mount, Red Faceplate
AS4008-10 Outdoor Enclosure N/A N/A
Notes:
• Avenger Outdoor Series is listed for outdoor use.
• Indoor Operating Temperature: 32°to 120°F (0° to 49°C).
• Outdoor Operating Temperature: -31°to 150°F (-35° to 66°C).
• For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR
[Full Wave Rectified]) power, see installation manual.
• Avenger does not recommend using a coded or pulsing signaling circuit with any of our strobe products.
Minimum dBA Minimum dBA Regulated 24VDC
Horn Mode @ 10ft. per @ 10ft. per Max. Operating
UL464 (HIGH) UL464 (LOW) @ High Setting (mA)
Temp 3 2400Hz 78 71* 28
Temp 3 Mechanical 76 70* 25
Temp 3 Chime 70* 66* 15
Continuous 2400Hz 81 74* 28
Continuous Mechanical 80 72* 25
Continuous Chime 70* 66* 15
Whoop 82 69* 56
*Operating the horn in this mode at this voltage will result in not meeting the minimum UL reverberant sound level required for public
mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode
application (not applicable when using the chime tone. The chime tone is always private mode).
Notes:
• The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While
the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.
• To obtain the horn/strobe current draw, add the strobe current draw and the horn current draw.
Outdoor Product Strobe Current Ratings 1 RMS current ratings are per UL average RMS method. UL max
current rating is the maximum RMS current within the listed voltage
Candela 75cd range 16-33VDC for 24VDC units. For strobes the UL max current is
usually at the minimum listed voltage 16VDC for 24VDC units. For
24 VDC 112mA audibles the max current is usually at the maximum listed voltage.
For unfiltered FWR ratings, see installation manual.
UL Max 1 180mA
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
AS7001-00 AS7002-00
4” Sensor Base 6” Sensor Base
Standard Features Operation
• UL Listed The AS7001 4” base and AS7002 6” base is
• Designed for use with all NS analog designed specifically for use with the Avenger
sensors Analog sensors, models AS2010 Heat Sensor,
AS2011 Photoelectric Smoke Sensor and AS2012
• Available in 4 and 6 inch models Multi Criteria Heat Sensor.
• Contains a security locking tab for
tamper protection The AS7001 and AS7002 common mounting
bases allows for complete compatibility for all of
AS7001-00 the Avenger System Analog sensors.
Application The bases are lightweight and very thin, providing
a low profile once installed. The solder-less screw
The AS7001 4” base and AS7002 6” base is terminals enable quick and easy wiring
designed for use with Avenger System style connections.
sensors models AS2010, AS2011 and
AS2012. Engineering
Each base is connected to a Supreme Specifications
Signaling Line Circuit (SLC) and provides
easy replacement of sensors, without The Dealer shall furnish and install where
disturbing the wiring.
indicated on the plans, Avenger System AS2011
The bases are electronics free and contain a photoelectric sensors, AS2010 Heat Sensor or
simple rugged design with screw terminals AS2012 Multi-criteria Sensor part number.
for wiring connections. A common
AS7002-00 mounting base allows sensor interchange The selected sensor shall be attached to the
AS7001 or AS7002 base and permit direct
and maintains loop continuity when interchange between the listed sensors.
sensors are removed. A simple anti-tamper
head Locking system is provided which is The vandal-resistant, security locking feature shall
enabled by removing a small plastic tab on be used in those areas as indicated on the
the back of the sensor. Once locked, the drawing. The locking feature shall be optional and
head can only be removed using a small can be implemented when required.
diameter screw driver.
It shall be possible to perform a functional test of
the sensor without the need of generating smoke.
The test method shall simulate the effects of
products of combustion in the chamber to ensure
Technical Specifications testing of internal circuitry.
NOTE: SLC maximum resistance is 50 ohms.
AS7001: 4” Sensor Base
AS7002: 6” Sensor Base
Security feature: Plastic Tamper-Lock
Color & Case Material: Bone PC / ABS Blend
Compatible Sensors: AS2010, AS2011, AS2012
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
SPC-24 PROJECTED BEAM SMOKE DETECTOR
APPLICATION
The Hochiki SPC-24 Projected Beam Smoke Detector
consists of an emitter and receiver. The SPC-24
detector should be placed so that smoke generated by
a fire will likely rise into the path of the beam. The
receiver is constantly monitoring and measuring the
intensity of the beam transmitted by the emitter. Should
the smoke from a fire cause a decrease in the signal
STANDARD FEATURES strength of a magnitude that exceeds the programmed
• Microprocessor based for reliability obscuration setting, an alarm signal is generated.
• Simple setup and alignment with signal strength The SPC-24 detector can provide vital fire detection in
LEDs applications where other types of detectors may not be
• Provides 60 feet on center linear protection at a able to respond quickly, or at all, to a fire condition.
range of 32.8 feet to 328 feet Examples of some applications where projected beam
• Automatic compensation for signal drift or dirty lens smoke detectors have been successfully used include:
• Three field adjustable sensitivity settings
• Form A alarm and Form B trouble contacts Atriums gymnasiums theaters
• Calibrated filters available to verify sensitivity museums factories tunnels
(purchased separately) churches stables warehouses
• Color-coded emitter (red) and receiver (green) labels anechoic chambers high air velocity areas
for easy recognition The SPC-24 detector may also be used in conjunction
• Adjustable to one of the three obscuration settings of with more traditional spot type smoke detection
25%, 50% or 70% per span devices to provide an even more comprehensive
• Voltage and RF transient protection detection system.
• External red LED when alarm condition is indicated
OPERATION
SPECIFICATIONS
The near infrared pulsed beam generated by the
emitter is sensed by the photodiode of the receiver,
Rated Voltage 24VDC where it is converted into an electrical signal. This
Supply Voltage 19VDC - 33 VDC signal is then amplified and applied, via an analog to
digital converter, to a microprocessor. The normal state
Supervisory Current Emitter 50µA @ 24VDC signal (the initial beam data), once stored in the
Receiver 200µA @ 24VDC microprocessor, is used as reference for comparison
Alarm Current (Receiver) 20mA @ 24DC with subsequent beam signals.
Trouble Current (Receiver) 20mA @ 24VDC
Operating Temperature Range 14° F - 122° F
PRODUCT LISTINGS
UL Installation Temperature 32° F - 100° F
Range California State
Sensitivity Test Failure Hochiki test filters Fire Marshal
(sold separately) 7260 0410:172
-
S1383 3054275
Allowable misalignment angle Emitter +/- 0.5°
(MAX) Receiver +/- 1.0°
Dimensions 3.2”W x 5.5”H x 4.0”D
Mounting Wall mount or Single gang
box .
Maximum Humidity 95% R.H. non-condensing
Specifications subject to change without notice. Continued on back
Hochiki America Corporation Find latest revision at www.hochiki.com
7051 Village Drive, Suite 100, Buena Park, CA 90621 - 2268
Phone: 714/522 - 2246 Fax : 714/522 - 2268
Technical Support: 800 - 845 - 6692 or [email protected] F0072 07/2015
SPC-24 PROJECTED BEAM SMOKE DETECTOR
OPERATION, continued
When there is a difference between actual beam strength and stored reference data that exceeds
the programmed alarm obscuration reference level, a fire signal is produced. A trouble signal is
generated if the beam is more than 90% obstructed (as opposed to partially obscured by smoke) for
more than 9 seconds and automatically resets to normal when the blockage is removed.
The microprocessor also provides compensation for a change in received signal value, with time,
caused by contamination of the optics. Since such a change with time appears as a slow change
in the beam signal, the microprocessor compensates in such a manner that the signal moves closer
to the reference data at a rate approximately +1% per hour. When this compensating capability
reaches a limit (light received has changed by more than 50%), the SPC-24 automatically generates
a trouble signal.
A calibrated test filter is available upon request to test and verify the sensitivity setting of the SPC-24
detector.
INSTALLATION
The Hochiki SPC-24 detector shall be installed in accordance with the installation instruction guide
provided with every unit. Please refer to the applicable NFPA Standards for additional guidance on
spacing, irregular ceiling surfaces and other design considerations.
FOUR WIRE CONNECTION TO THE CONTROL PANEL
NOTE: EOLR - 24 required
NOTE: End of line relay and trouble contacts are closed
for power supervision on
when power is applied. Receiver.
.
Hochiki America Corporation SPC-24 Specifications subject to change without notice
AS3031-10 Single Action w/ Hex Screw (H)
AMS Manual Pull Stations
AS3032-10 Single Action w/ Key Lock (H)
AS3029-10 Dual Action w/ Key Lock (H)
Standard Features Product Overview
• Addressable integrated design • The AMS series of addressable manual
pull stations provide a fast and practical
• All metal construction means of manually initiating a fire alarm
• Single and dual action models signal. Both single action and dual
available Extremely easy to action manual pull stations are
operate available. Resetting of the pull station
requires either a Cat 30 key or a 1 /8" hex
• Bi-colored status LED indicates key (depending upon the model used).
AS3031-10 Standby and Alarm conditions
• An alarm condition is actuated by
• Address is programmable in pulling down on the handle of the
EEPROM AS3031-10 and AS3032-10 single action
• Address can be programmed models. On the dual action model
when installed AS3029-10 the Lift and Pull cover must
be lifted before pulling down on the pull
• Key lock or hex key lock models station handle. Once the pull station is
AS3032-10 available activated, the handle cannot be put
• Enclosed switch with glass rod back into a normal standby condition
without using the key operated reset
(included) Terminals accept up to
14AWG wire • The AMS series is electronically
addressable and includes a bi-colored
• Surface mount back box available
status LED. The LED blinks green
indicating normal communication with
the DCP compatible SLC loop. When an
alarm condition is actuated by pulling
AS3029-10 the handle, the LED will latch Red to
indicate the alarm condition.
Engineering Specification
Manual pull stations shall be Avenger Systems
addressable AMS series single or dual action models,
AS3031-10, AS3032-10 or AS3029-10. Models shall be
made of 14 AWG CRS and painted with Red enamel. The
words Fire Alarm shall be in a contrasting color and be
embossed text 1/2"tall. The electronics shall be fully
integrated into the manual pull station requiring only
connection to the SLC loop of the control panel.
Programming of the manual pull station address must be
possible with the manual pull station fully installed.
Manual pull stations shall be Underwriters Laboratories
Inc. Listed and be installed within the limits defined in
the Americans with Disabilities Act.
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Ordering Codes Technical Specifications
Part Number Description Operating Voltage: 17-41 VDC
AS3031-10 Single Action with Hex Screw Lock Average current consumption:
AS3032-10 Single action with Hex Key Lock • 550μA (typical)
•
660μA (standard)
AS3029-10 Dual action with Key Lock Ambient Temperature: 32°F to 120°F
Maximum humidity: 90% RH non-condensing
Dimensions: 3.4”W x 4.8”H x 2.0”D
Mounting: Single gang or 4” square electrical box
Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
UL Certificates
TEBA UNUTED GROUP
Address: 98 Hassan Al-Maamoun St., Nasr city, Cairo, Egypt
Telephone: 02-26774254/9 – 2677445/1
Fax: 02-26774256
E-mail: [email protected]
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20161201-S35689
Report Reference S35689-20160209
Issue Date 2016-DECEMBER-1
Issued to: AVENGER SYSTEMS LLC
11586 Zagarolo Lane
Las Vegas, NV 89141
This is to certify that CONTROL UNITS, SYSTEM
representative samples of AS1170-00, AS1171-00, AS1420-1 [+], AS1420-4 [+],
AS1423-1 [+], AS1423-4 [+], AS1425-1 [+], AS1425-4 [+],
AS1440-1 [+], AS1440-4 [+], AS1443-1 [+], AS1443-4 [+],
AS1445-1 [+], AS1445-4 [+]
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: UL 864 - Control Units and Accessories for Fire Alarm
Systems
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 1
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20161201-S35689
Report Reference S35689-20160210
Issue Date 2016-DECEMBER-1
Issued to: AVENGER SYSTEMS LLC
11586 Zagarolo Lane
Las Vegas, NV 89141
This is to certify that CONTROL UNIT ACCESSORIES, SYSTEM
representative samples of See Addendum Page
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: UL864 - Control Units and Accessories for Fire Alarm
Systems
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 2
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20161201-S35689
Report Reference S35689-20160210
Issue Date 2016-DECEMBER-1
This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.
AS1172-10, AS1172-40, AS130X-YYY[+], AS132X-YYY[+], AS133X-YYY[+], AS1821-11, AS1821-41,
AS1821-12, AS1821-42, AS1821-13, AS1821-43, AS1821-14, AS1821-44, AS1823-10, AS1823-40,
AS1832-10, AS1832-40, AS1885-12, AS1885-42, AS1885-14, AS1885-44, AS1885-18, AS1885-48,
AS1822-10, AS1822-40
[+] - Where X can be the number 1 or 2 or 4 denotes color of enclosure, and YYY denotes the number
of LED extension boards, which can be either 2, 4, or 5 boards.
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 2 of 2
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20161201-S35689
Report Reference S35689-20160211
Issue Date 2016-DECEMBER-1
Issued to: AVENGER SYSTEMS LLC
11586 Zagarolo Lane
Las Vegas, NV 89141
This is to certify that CONTROL UNITS, SYSTEM
representative samples of AS0810-10, AS0810-40, AS0830-10, AS0830-40, AS0815-
10, AS0815-40, AS0816-10, AS0816-40, AS0836-10,
AS0836-40, AS0817-10, AS0817-40, AS0820-10, AS0820-
40, AS0825-10, AS0825-40, AS0826-10, AS0826-40,
AS0827-10, AS0827-40
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: UL 864 - Control Units and Accessories for Fire Alarm
Systems
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 1
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20161201-S35689
Report Reference S35689-20160602
Issue Date 2016-DECEMBER-1
Issued to: AVENGER SYSTEMS LLC
11586 Zagarolo Lane
Las Vegas, NV 89141
This is to certify that CONTROL UNITS, SYSTEM
representative samples of See Addendum Page
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: UL864 - Control Units and Accessories for Fire Alarm
Systems
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 2
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20161201-S35689
Report Reference S35689-20160602
Issue Date 2016-DECEMBER-1
This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.
AS1810-10, AS1810-11, AS1810-40, AS1810-41, AS1822-00, AS0613-10, AS0613-40, AS0511-10,
AS0511-40, AS0607-10, AS0607-40, AS1842-10, AS1842-11, AS1842-40, AS1842-41, AS1844-10,
AS1844-11, AS1844-40, AS1844-41, AS1848-10, AS1848-11, AS1848-40, AS1848-41, AS1852-10,
AS1852-11, AS1852-40, AS1852-41, AS1854-10, AS1854-11, AS1854-40, AS1854-41, AS1858-10,
AS1858-11, AS1858-40, AS1858-41, AS1850-00
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 2 of 2
CERTIFICATE OF COMPLIANCE
Certificate Number 20190626-S35689
Report Reference S35689-20160210
Issue Date 2019-JUNE-26
Issued to: AVENGER SYSTEMS LLC
11586 Zagarolo Lane
Las Vegas, NV 89141
This is to certify that CONTROL UNIT ACCESSORIES, SYSTEM
representative samples of See Addendum Page
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: UL864 - Control Units and Accessories for Fire Alarm
Systems
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 2
CERTIFICATE OF COMPLIANCE
Certificate Number 20190626-S35689
Report Reference S35689-20160210
Issue Date 2019-JUNE-26
This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.
Remote Annuciators; AS1172-10, AS1172-40
Mimic Displays ; AS130X-YYY[+], AS132X-YYY[+], AS133X-YYY[+]
[+] - Where X can be the number 1 or 2 or 4 denotes color of enclosure, and YYY denotes the number
of LED extension boards, which can be either 2, 4, or 5 boards.
Lamp Status Unit; AS1821-11, AS1821-41, AS1821-12, AS1821-42, AS1821-13, AS1821-43, AS1821-
14, AS1821-44
Abort Switch ; AS1823-10, AS1823-40
Manual Extinguishant Disablement Switch ; AS1832-10, AS1832-40
Annunciator; AS1885-12, AS1885-42, AS1885-14, AS1885-44, AS1885-18, AS1885-48
Ancillary Board with Enclosure; AS1822-10, AS1822-40
Network annunciator; OVC00NC10, OVC00NC40, OVC00NC60, OVC10NC10, OVC10NC40,
OVC10NC60, OVC20NC10, OVC20NC40, OVC20NC60, OVC30NC10, OVC30NC40, OVC30NC60
Subassembly; S787
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 2 of 2
CERTIFICATE OF COMPLIANCE
Certificate Number 20190626-S35689
Report Reference S35689-20190626
Issue Date 2019-JUNE-26
Issued to: AVENGER SYSTEMS LLC
11586 Zagarolo Lane
Las Vegas, NV 89141
This certificate confirms that CONTROL UNITS, SYSTEM
representative samples of See Addendum Page
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: UL864 - Control Units and Accessories for Fire Alarm
Systems
Additional Information: See the UL Online Certifications Directory at
https://iq.ulprospector.com for additional information.
This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.
Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.
Look for the UL Certification Mark on the product.
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 2
CERTIFICATE OF COMPLIANCE
Certificate Number 20190626-S35689
Report Reference S35689-20190626
Issue Date 2019-JUNE-26
This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.
Control Unit; OA followed by 1, 2, 3, 4, 7, 8, 9 or A, followed by 0, 1, 2 or 3, followed by 0, 1, 2 or 3,
followed by 00 or H, I, J, or K, followed by 1 through 8, followed by 1, 4 or 6, followed by 0, 1, 3, 4, 5, 6
or 7, and may be optionally followed by 0 and 1 through 8
Subassembly; S406, S408, S560, S723, S758, S769, S770, S771, S788, S791
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 2 of 2
7/2/2019 AUDIBLE-SIGNAL APPLIANCES | UL Product iQ
ULSZ.S35913 - AUDIBLE-SIGNAL APPLIANCES
Audible-signal Appliances
See General Information for Audible-signal Appliances
AVENGER SYSTEMS LLC S35913
11586 Zagarolo Lane
Las Vegas, NV 89141 USA
Enclosure Ratings
Installation Type Rating IEC "IP"
Device Model Location Per UL 50 Rating
Accessories, Backboxes AS4005-10 Indoor — —
Accessories, Enclosures AS4008-10 Outdoor — —
Horns AS4000-10 Indoor/Outdoor — —
Horn/strobes AS4002-10 Indoor — —
Horn/strobes AS4007-10 Indoor/Outdoor — —
Horn/strobes AS4004-10 Indoor — —
Model AS7005-00 - Low Frequency 520Hz Detector Sounder Base, Listed (UROX, File S35692) as an Audible Signal Appliance.
Last Updated on 2018-01-18
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format: "© 2019 UL LLC"
https://iq.ulprospector.com/en/profile?e=216698 1/1