BFeivguerleba1.c3k4 Dwireeactthfiexerbdo–aarpdro-ndfliareshcitngfix–esdtop- aenpdron flashing - stop end
Jenkin A-lign® bevelback
weatherboard
Wall underlay
Spouting to stop 10mm Apron flashing
min from finished wall Apron flashing upstand
cladding behind cladding and
building underlay
50 x 50mm transition tray
behind fascia or seal Tapered stop-end to divert
between fascia and apron flashing water into
coated cladding Fall gutter
Roofing
Gutter
Note: Refer to NZBC Acceptable Solution E2/AS1 Table 7 for apron flashing cover over roofing
Figure 1.38 Direct fixed – internal corner – 135 degrees – scribed
Jenkin Align® Details Version 2.0 All Dimensions are to
be site checked
fig1-34_df_apron_stop.dwg Scale at A4 1:10 before construction
4 October 2012 and installation
© JenkinTimber Ltd. 2012 49
Figure 1.39 Direct fixed – internal corner – 135 degrees – flashed
Figure 1.40 Direct fixed – external corner – 135 degrees – mitred
50 © JenkinTimber Ltd. 2012
Figure 1.41 Direct fixed – nailing
)L[HDFKERDUGZLWKRQHQDLOSHU )L[HDFKERDUGZLWKRQH
ERDUGDWHYHU\VWXGRUEDWWHQ QDLOSHUERDUGDWHYHU\VWXG
ORFDWHIL[LQJPPDERYHWKH
ERWWRPHGJHRIWKHRYHUODS RUEDWWHQORFDWHIL[LQJ
ERDUGWRDOORZIRUH[SDQVLRQ PPDERYHWKHERWWRP
DQGFRQWUDFWLRQ HGJHRIWKHRYHUODSERDUG
WRDOORZIRUH[SDQVLRQDQG
FRQWUDFWLRQ
PP
PP
-HQNLQ$OLJQ'HWDLOV 9HUVLRQ $OO'LPHQVLRQVDUHWR
EHVLWHFKHFNHG
ILJBGIBQDLOLQJBEHYGZJ 6FDOHDW$ EHIRUHFRQVWUXFWLRQ
'HFHPEHU DQGLQVWDOODWLRQ
© JenkinTimber Ltd. 2012 51
CAD Drawings – cavity fixed
Note: The 3-Dimensional diagrams and CAD drawings in this
manual are current at the date of this manual (November 2012).
For any amendments or updates to these diagrams or drawings,
please refer to our website: jenkin.co.nz/products/a-lign/cad-details
52 © JenkinTimber Ltd. 2012
)LJ
Figu%rHeY2H.0OE1DCFaNviZtyHfDixWeKdH–UEbRaDsUeGofwFDaYllLW–\conEcDrVeHteRflIoZorDOOFRQFUHWHIORRU
-HQNLQ$OLJQFDYLW\EDWWHQ PP -HQNLQ$OLJQEHYHOEDFN
,QWHUQDOOLQLQJ ZHDWKHUERDUG
'3& :DOOXQGHUOD\
:DOOSODWHWRRYHUKDQJVODEHGJHE\
&RQFUHWHIORRUVODE PPPLQLPXPRSWLRQDO
-HQNLQ$OLJQEHYHOEDFNEDVHERDUG
4XLFNIODVK&RGHFDYLW\FORVHU
%DVHERDUGWRILQLVKPPPLQ
EHORZIORRUOHYHODQGPPDERYH
ILQLVKHGJURXQGOHYHORUPP
DERYHSDYLQJ
PPIURPVODEVXUIDFHWRQDWXUDO
JURXQGPPWRSDYLQJ
)LJ
Figu%reH2Y.H0O2EDCFavNitZy HfiDxeWKdH–UEbRasDeUGofwFaDlYl L–W\timEbDerVHfloRoIrZDOOWLPEHUIORRU
-HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUG
-HQNLQ$OLJQFDYLW\EDWWHQ
:DOOXQGHUOD\
'3& :DOOSODWHWRRYHUKDQJVODEHGJHE\
PPPLQLPXPRSWLRQDO
-HQNLQ$)ORLJXQQGD'WLHRQWDZLOVDOO
4XLFNIODVKFDYLW\FORVXUHZLWKPP
ILJBFYBEBZDOBFRQBIOUGZJ GULSHGJHWRZHDWKHUERDUG
9HUVLRQ $OO'LPHQVLRQVDUHWR -HQNLQ$OLJQEHYHOEDFNEDVHERDUG
EHVLWHFKHFNHG
6FDOHDW$ EHIRUHFRQVWUXFWLRQ %DVHERDUGWRILQLVKPPPLQ
'HFHPEHU DQGLQVWDOODWLRQ EHORZIORRUOHYHODQGPPDERYH
ILQLVKHGJURXQGOHYHORUPP
DERYHSDYLQJ
© JenkinTimber Ltd. 2012 53
Figure 2.03 Cavity fixed – eaves – angled soffit Recommended eaves widths:
>100mm for l and m wind zones
Continuous horizontal >450mm for h wind zones
batten to close off cavity >600mm for vh wind zones and
above
from roof space
Roof cladding and
underlay to designers
specification
Internal lining Soffit lining
Jenkin A-lign® cavity
Jenkin A-lign® 42 x 18mm eaves
batten mould with weathergroove - fit
tight to soffit lining
)LJ
Wall underlay
Figure 2.04 Cavity fixed – eaves – flat soffit Jenkin A-lign® bevelback
weatherboard
%HYHOEDFNZHDWKHUERDUGFDYLW\HDYHVIODWVRIILW
5RRIFODGGLQJDQGXQGHUOD\ Version 2.0 All Dimensions are to
WRGHVLJQHUVVSHFLILFDWLRQ be site checked
Scale at A4 1:5 before construction
Jenkin Align® Details 4 October 2012 and installation
fig2-03_cv_eav_ang_sof.dwg 6RIILWEHDUHU 6RIILWOLQLQJ
-HQNLQ$OLJQFDYLW\EDWWHQ
FORVHRIIWRSRIFDYLW\IURP -HQNLQ$OLJQ[PPHDYHV
VRIILWVSDFH PRXOG ZLWKZHDWKHUJURRYHILW
,QWHUQDOOLQLQJ WLJKWWRVRIILWOLQLQJ
:DOOXQGHUOD\ -HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUG
54 © JenkinTimber Ltd. 2012
Bevelback weatherboard - cavity - eaves - no soffit
Figure 2.05 Cavity fixed – eaves – no soffit
Roofing underlay draining into
spouting Min. overhang of roofing beyond
fascia
50mm Eaves flashing where roof
pitch less than 10° and fascia
is less than 100mm from
cladding flashing by roofer
Ensure that weatherboard Ensure that
project above top of fascia weatherboard
projects above top
Solid blocking of fascia
Internal lining
Jenkin A-lign® cavity batten Spouting
Jenkin A-lign® tilting
fillet
Jenkin A-lign® facing (fascia) of
width to suit spouting brackets and
falls
Jenkin A-lign® bevelback
weatherboard
Wall underlay
)LJ +WUHDWHGSDFNLQJWRVXLW
Figure 2.06 Cavity fixed – parapet – cap LVRODWHGIURPPHWDOIODVKLQJ
%HYHOEDFNZHDWKHUERDUGFDYLW\SDUDSHWFDS
-HQNLQ$OLJQ[PP
0HWDOFDSIODVKLQJZLWKPLQ HDYHVPRXOG
IDOOIL[WKURXJKGRZQWXUQ
VXSSOLHGE\URRILQJ
PDQXIDFWXUHU
,VRODWLQJOD\HU
PPPLQ %LUGVEHDNGULSHGJHVHH
FRYHU OHIWKDQGGRZQWXUQIRU
PPPLQRXWWXUQGULSHGJH
FRYHU
:DOOXQGHUOD\FRQWLQXRXV
2XWWXUQWRIODVKLQJWR Version 2.0 All Dimensions are to RYHUWRSRIZDOOIUDPH
IRUPGULSVHHULJKWVLGH be site checked
Scale at A4 1:5 before construction -HQNLQ$OLJQFDYLW\
IRUELUGVEHDNRSWLRQ 4 October 2012 and installation EDWWHQ
Jenkin A-lHigQnNL®QD$eOLtJaQilsEHYHOEDFN
ZHDWKHUERDUG
fig2-05_cv_eav_no_sof.dwg
1RWH,QVWDOOIOH[LEOHIODVKLQJWDSHDQGVDGGOHIODVKLQJDWMXQFWLRQZLWKIXOOKHLJKWZDOO
© JenkinTimber Ltd. 2012 55
Figure 2.07 Cavity fixed – external corner – prefabricated box
)LJFigure 2.08 Cavity fixed – external corner – mitred
%HYHOEDFNZHDWKHUERDUGFDYLW\H[WHUQDOFRUQHUPLWUHG
-HQNLQ$OLJQFDYLW\EDWWHQ 2SWLRQDOVRDNHUGDVKHGRU
EDFNIODVKLQJWRPLWUHZLWKWLJKW
56 © JenkinTimber Ltd. 2012 PLWUHGFRUQHU
-HQNLQ$OLJQEHYHOEDFNZHDWKHUERDUG
4XLFNIODVK&RGH[PP
4XLFNIODVKIODVKLQJZLWKPP
UHWXUQVWRERWKHGJHVRUVRDNHUWR
IURQWIDFH
:DOOXQGHUOD\FRQWLQXRXVDURXQG
FRUQHU
)LJ
%FHiYgHuOrEeD2F.0N9ZCHaDviWtKyHfUixEeRdD–UGinteFrDnYaLlW\cornLQeWrH–UQpDreO-FcuRtUQscHrUiberSUHFXWVFULEHU
4XLFNIODVK&RGHRIIVHW :DOOXQGHUOD\FRQWLQXRXV
FRUQHUEDFNIODVKLQJPP DURXQGFRUQHU
PLQFODGGLQJFRYHU -HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUG
-HQNLQ$OLJQFDYLW\ -HQNLQ$OLJQSUHFXW
EDWWHQ [PPLQWHUQDO VFULEHU
-HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUG
)LJ
Figu%reHY2H.1O0EDCFaNvitZyHfiDxWeKdH–UEinRtDeUrGnalcFoDrYnLeW\r–sLQcWrHibUeQdDOFRUQHUVFULEHG
:DOOXQGHUOD\FRQWLQXRXVDURXQG -HQNLQ$OLJQEHYHOEDFN
FRUQHU ZHDWKHUERDUGVFULEHGWRHDFK
RWKHU
-HQNLQ$OLJQFDYLW\EDWWHQ
4XLFNIODVK&RGHFRUQHU
-HQNLQ$OLJQ'HWDLOV 9HUVLRQ EDFNIODVKLQJPPFODGGLQJ
FRYHUWRIODVKLQJUHIHU1=%&
ILJBFYBLQWBFQUBVFULEHUGZJ 6FDOHDW$ ($67DEOHIRUH[WUDKLJK
0DUFK ZLQG]RQHV
$OO'LPHQVLRQVDUHWR
EHVLWHFKHFNHG
EHIRUHFRQVWUXFWLRQ
DQGLQVWDOODWLRQ
© JenkinTimber Ltd. 2012 57
)LJ
Figure 2.11 Cavity fixed – aluminium window – head
%HYHOEDFNZHDWKHUERDUGFDYLW\DOXPLQLXPZLQGRZKHDG
-HQNLQ$OLJQFDYLW\EDWWHQ PP :DOOXQGHUOD\WXUQHGLQWRIUDPLQJ
PPPLQFODGGLQJFRYHUWR PLQ UHYHDOIOH[LEOHIODVKLQJWDSHDW
FRUQHUV
IODVKLQJXSVWDQG
4XLFNIODVKFDYLW\FORVXUH :DOOXQGHUOD\IODSODSSHGRYHU
IODVKLQJ
,QWHUQDOOLQLQJ
$LUVHDORYHUEDFNLQJ -HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUGPPFODGGLQJ
PP FRYHUWRKHDGIODVKLQJXSVWDQG
$UFKLWUDYHRUJURRYHGOLQHU PPGULSHGJHWRFDYLW\FORVXUH
UHIHU1=%&($67DEOHIRU
3DFNLQJDVUHTXLUHG H[WUDKLJKZLQG]RQHV
7LOWLQJILOOHWZKHUHUHTXLUHGIRU
VXSSRUW
2SWLRQDO-HQNLQ$OLJQZHDWKHUKHDG
ZLWKGULSWRERWWRPHGJH
PPPLQFRYHU
+HDGIODVKLQJE\MRLQHU\
PDQXIDFWXUHUZLWKVORSHDQG
PPVWRSHQGWRH[WHQGPP
PLQEH\RQGRXWHUHGJHRIMDPE
IDFLQJRUVFULEHU
$OXPLQLXPMRLQHU\SURILOH
/LQHRI-HQNLQ$OLJQSUHFXW
[PPVFULEHU
-HQNLQ$OLJQ'HWDLOV 9HUVLRQ $OO'LPHQVLRQVDUHWR
EHVLWHFKHFNHG
ILJBFYBDOXBZLQGBKHDGGZJ 6FDOHDW$ EHIRUHFRQVWUXFWLRQ
0DUFK DQGLQVWDOODWLRQ
58 © JenkinTimber Ltd. 2012
)LJDFigure 2.11a Cavity fixed – window head facing (option A)
)LJD%HYHOEDFNZHDWKHUERDUGFDYLW\IL[HGZLQGRZKHDGIDFLQJRSWLRQ$
%HYHOEDFNZHDWKHUERDUGFDYLW\IL[HGZLQGRZKHDGIDFLQJU:HYDRHOSODXWOLQRIGOHQH[ULO$EDO\HWIXODUQVHKGLQLJQWWRDSIUHDPDWLQJ
-HQNLQ$OLJQFDYLW\EDWWHQ F:RUDQOHOUXVQGHUOD\WXUQHGLQWRIUDPLQJ
:UHDYOHODXOQGIOHHU[ODLE\OHIODIOSDVODKSLQSJHWGDSRHYHDUW
-PHPQNLPQL$QFOILOJODDQGVGKFLLQQDJJYLFXW\RSYEVHWDDUWQWWHRGQ IFODRVUKQLHQUJV
4XPLFNPIODPVLKQFIOODDFGVDGKYLLQQLWJJ\FFXROSRYVVHWXDUUQHWRG 2ZI:OLSDWKDWVLROKOGQLXUQDLQSJOG-WHRHUQOEDNR\LWQWIRO$DPSOLHOJDGQSJSHZHGHDRWYKHHUUKHDG
-2HSQWNLRLQQ$DOO-LJHQQNELQHY$HOOLEJDQFNZHDWKHUKHDG
4XLFNIODVKFDYLW\FORVXUH ZZHLWDKWKGHUULSERWRDUEGRWWRPPPHGFJOHDGGLQJ
,QWHUQDOOLQLQJ UFH-IUHFHD-ZRH[HRHI[FPHYWQHIUPYWLQHHQDNUDUHPNDUULJWP1QULKK1QWKZGHR=WL$JGR=L$UUJ%LKKULEG%SKKLO&HSLRWO&JZHLKJHDZDQHD(LQGGUW(QLGGRGQJGIJJGHOIEV$DUHO]$DXHR]VW6RVRWLY6RRKWRQPKHYQLFHQLOHFHP7QEDVJ7DGVJDDYDYFXLEFWXLEO\SWNOD\HSOVHGFVWFOGDWRODRLQIVQQRIVGXRJGUXUUUHH
$LUVHDORYHUEDFNLQJURG 7-LHOWLQQNJLQILO$OHWOLJZQKHJUHURURHYTHXGLUHGIRU
,QWHUQDOOLQLQJ VIXDSFSLQRJUWZLGWKWRVXLW
$LUVHDORYHUEDFNLQJURG
PP PP
PLQ
$UFKLWUDYHRUJURRYHGOLQPHPU 7LPOWLQPJPILOLOQHWFZRYKHHUUHUHTXLUHGIRU
$UFKLW3UDDYFHNLRQUJJDURVRUYHHTGXLOULHQGHU PP +VHXDSGSRIOUDWVKLQJE\MRLQHU\
PLQ PDPQXPIDPFWXLQUHFURZYHLWUKVORSHDQG
3DFNLQJDVUHTXLUHG EVM+DPVWHRWPH\RDSDRSEQGQHXHSGQIIQUDOGRDRGFIVXWWLXRWOKWHRHULHQHUH[JUH[WZHWGEHQLJ\WQKGHGMRRLQIHPDPUOV\PXPORPSPLPQHLQLLXQDPQG
Elevation $EOHX\PRLQQGLXRPXWMRHLUQHHGU\JHSURRIILDOHOXPLQLXP
/MLDQPHERIS-URHIQLONHLQ$OLJQSUHFXW
PP X/$QLOQGX[HHPURVLQILGPL-XHHPPQRNIVMRLFZQLUQHL$EHDHUWO\KULJHWSQRUUKRHHSI[LDUOWHHHGQFGXWWR
[PPVFULEHUWRH[WHQGWR
XQGHUVLGHRIZHDWKHUKHDG
-HQNLQ$OLJQZHDWKHUKHDGZLWK PP
GULSWRERWWRPHGJH
PP
-HQNLQ$+HOLJDQGIZODHVDKWLQKJHUEK\HDMRGLQZHUL\WK PP
PDQXIDFWXUHUGZULLWSKWRERVWWORRSPHHDGQJGH
EPHD\VVRWQRWQXRSGISDHRFHQ+WXQXGHWGUHDWHURWGURHHZIHGO[DL[JWWVKHWHHKQQRLGQGMIDJDPVEOXPOE\RPPSPSMRPLHQULRQLPXDPIHLPQLOUQHLGQ\
EH\RQGRXWHUHGJHRIDOXPLQLXP
MDPESURILOH
6FULEHU
-HQNLQ$OLJQJURRYHGIDFLQJ6ZFULLGEWHKU (OHYDWLRQ
WRVXLW
-HQNLQ$OLJQJURRYHGIDFLQJZLGWK
WRVXLW
(OHYDWLRQ
-HQNLQ$OLJQ'HWDLOV 9HUVLRQ $OO'LPHQVLRQVDUHWR
EHVLWHFKHFNHG
ILJDBFYBDOXBZLQGBKHDGGZJ 6FDOHDW$ EHIRUHFRQVWUXFWLRQ
0D\ DQGLQVWDOODWLRQ
-HQNLQ$OLJQ'HWDLOV 9HUVLRQ
$OO'LPHQVLRQVDUHWR
ILJDBFYBDOXBZLQGBKHDGGZJ 6FDOHDW$ EHVLWHFKHFNHG
0D\ EHIRUHFRQVWUXFWLRQ
DQGLQVWDOODWLRQ
© JenkinTimber Ltd. 2012 59
)LJEFigure 2.11b Cavity fixed – window head facing (option B)
)LJE%HYHOEDFNZHDWKHUERDUGFDYLW\IL[HGZLQGRZKHDGIDFLQJRSWLRQ%
%HYHOED-FHQNNLZQH$DOLWJKQHUFEDRYLDW\UEGDWWHFQDYLW\IL[HGZLQGRZKHDGIDFLQJRSU:WHLRYDHQOODXO%QIGOHH[UOLDE\OHWXIODUQVHKGLQLJQWWRDSIUHDPDWLQJ
PPPLQFODGGLQJFRYHUWR :DOOFXRQUQGHHUUVOD\WXUQHGLQWRIUDPLQJ
-HQNLQ$OLJQFIODDYVLKW\LQEJDXWWSHVQWDQG UHYH:DODIOOOHX[QLEGOHHUOIDOD\VIKODLQSJODWDSSSHHGDWRYHU
FRUQIHODUVVKLQJ
PP4XPLFLNQIOFDOVDKGGLQJFDFYRLYW\HUFOWRRVXUH PP :IODDVOKOG-LXHQULQQJSGNWHLRQUOE$DR\WOLWIJRODQPSZHODGHSJDSHWHKGHURKYHHDUGZLWK
IODVKLQJXSVWDQG PLQ -HQN-LQHQ$NLOQLJ$QOLZJQHDWEKHHYUHKOHEDDGFNZLWK
GULSZWRHEDRWKWWHRUPERHDGUGJHPPFODGGLQJ
+HDGIODVKLQJE\MRLQHU\ F-ZRHHPYQDHNUHFWPULHKRQ[IHWPWYHGRU$UHDUUEPKLUS1ROKHLWJDGR=LHDJQUU%GGGKKLSJ&HIEZHOHDDH(LGGVWYQRPJKHGIHLOOF$PQDE]DJVWD6RRYKFFQXLOLWNFHDQ\S7DVGJVFDYGWOXLDERLWQ\SQOVHJVGXFWUODRHQIVRGXUUH
4XLFPNIDODQVXKIDFWXFUHDUYLZW\LWFKORVXUHVORSH UHIHU-1HQ=N%LQ&$(OLJ$Q6JU7RDREYHOHGIRU
PDQ+XHIDDDFQGWGXIOUVDHWVRURKXZSLWQHLHWJKUQHEGG\WJRMRHVHLQRO[RHIWSHUIH\DQFGLQWRJ H[WUDIDKFLLJQKJZZLLQGGWK]WRRQVHXVLW
DQGVWRSHQGWRH,Q[WWHHUQQGDOWROLQLQJ -HQNLQP$POLJPQLQJFURYRHYUHG
RXWHUHGJHRIIDFLQJ
$LUVHDORYHUEDFNLQJURG
,QWHUQDOOLQLQJ
$LUVHDORYHUEDFNLQJURGPP
$UFKLWUDYHRUJURRYPHGPOLQHU PP IDFLQ7JLOWZLQLGJWKILOOWHRWVZXKLWHUHUHTXLUHGIRU
PLQ PVPXSPSLRQUFW RYHU
$UFKLWUDYH3RDUFJNURLQRJYHDGVUOLHQTHXU LUHG 7LOWLQ$JOXILPOOHLQWLZXPKHMURHLQUHTU\XLSUHURGILIOHRU
3DFNLQJDVUHTXLUHG VXSS/RLQUWHRI-HQNLQ$OLJQSUHFXW
$OXPLQL[XPMPRLPQHVU\FUSLEURHIULOWHRH[WHQGWR
Elevation /LQHXRQIG-HHUQVLNGLQH$RIOZLJHQDWSKUHHUKFHXDW G
[PPVFULEHUWRH[WHQGWR
XQGHUVLGHRIZHDWKHUKHDG
-HQNLQ$OLJQZHDWKHUKHDGZLWKGULS PP
WRERWWRPHGJH PP
-HQNLQ$OLJQZHDWKHUKHDGZLWKGULS
WRERWWRPHGJH
6FULEHU
6FULEHU
+HDGIODVKLQJE\MRLQHU\PDQXIDFWXUHU
ZLWKVORSHDQGVWRSHQGWRH[WHQG
+HDGIODVKLQJE\MRLQWRHUR\XPWHDUQHXGIJDHFWRXIUHIDU FLQJ
ZLWKVORSHDQGVWRSHQGWRH[WHQG
WRRXWHUHGJHRIIDFLQJ
(OHYDWLRQ
(OHYDWLRQ
-HQNLQ$OLJQ'HWDLOV 9HUVLRQ $OO'LPHQVLRQVDUHWR
EHVLWHFKHFNHG
ILJEBFYBDOXBZLQGBKHDGGZJ 6FDOHDW$ EHIRUHFRQVWUXFWLRQ
0DUFK DQGLQVWDOODWLRQ
-HQNLQ$OLJQ'HWDLOV
9HUVLRQ $OO'LPHQVLRQVDUHWR
ILJEBFYBDOXBZLQGBKHDGGZJ EHVLWHFKHFNHG
6FDOHDW$ EHIRUHFRQVWUXFWLRQ
0DUFK DQGLQVWDOODWLRQ
60 © JenkinTimber Ltd. 2012
)LJ
Figure 2.12 Cavity fixed – aluminium window – jamb (option A)
%HYHOEDFNZHDWKHUERDUGFDYLW\DOXPLQLXPZLQGRZMDPE
,QWHUQDOOLQLQJ -HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUG
$LUVHDORYHUEDFNLQJURG
PP :DOOXQGHUOD\WXUQHGLQWR
IUDPLQJUHYHDOVDQGWDSHGDW
)LJD$UFKLWUDYHRUJURRYHGOLQHU FRUQHUV
3DFNLQJDQGZLQGRZVXSSRUW PPJDSWRZHDWKHUERDUG
EUDFNHWVDVUHTXLUHG RSWLRQDO
%HYHOEDFNZHDWKHUERDUGFDYLW\DOXPLQLXPZLQGRZMDPE -HQNLQ$OLJQSUHFXW
[PPVFULEHU
H[WHQGLQJWRXQGHUVLGHRI
ZLQGRZKHDGIDFLQJ
-HQNLQ$OLJQFDYLW\EDWWHQ
PPPLQIODQJHFRYHUWR
ZHDWKHUERDUG
$OXPLQLXPMRLQHU\SURILOH
)URQWHGJHRIZHDWKHUKHDG
/LQHRIKHDGIODVKLQJH[WHQGLQJ
WRRXWHUHGJHRIMDPEIDFLQJV
DQGRUVFULEHUVE\PP
Figure 2.12a Cavity fixed – aluminium window – jamb (option B)
:DOOXQGHUOD\WXUQHGLQWR 9HUVLRQ $OO'LPHQVLRQVDUHWR -HQNLQ$OLJQEHYHOEDFN
IUDPLQJUHYHDOVDQGWDSHGDW EHVLWHFKHFNHG ZHDWKHUERDUG
6FDOHDW$ EHIRUHFRQVWUXFWLRQ -HQNLQ$OLJQSUHFXW
FRUQHUV $SULO DQGLQVWDOODWLRQ [PPVFULEHU
,QWHUQDOOLQLQJ H[WHQGLQJWRXQGHUVLGHRI
ZLQGRZKHDGIDFLQJ
$LUVHDORYHUEDFNLQJURG -HQNLQ$OLJQ[PP
PP JURRYHGIDFLQJ
-HQNLQ$OLJQFDYLW\EDWWHQ
$UFKLWUDYHRUJURRYHGOLQHU
PPJDSWRZHDWKHUERDUG
-HQNLQ$OLJQ'HWDLOV RSWLRQDO
PPPLQIODQJHFRYHUWR
3DFNLQJDQGZLQGRZVXSSRUW ZHDWKHUERDUG
ILJBFYBDOXBEZUDLQFGNBHMDWVPDEVGZUHJTXLUHG $OXPLQLXPMRLQHU\SURILOH
)URQWHGJHRIZHDWKHUKHDG
/LQHRIKHDGIODVKLQJH[WHQGLQJ
WRRXWHUHGJHRIMDPEIDFLQJV
© JenkinTimber Ltd. 2012 61
Fig 2-13
FigureB2e.1v3elCbaavciktywfiexaetdhe– rabluomaridni-ucmavwitiynd-oawlu–msiinlliu(omptwioinndAo)w - sill
Packing and window Aluminium joinery profile,
support brackets as flange to provide 10mm min
cover to weatherboard
required
Architrave or grooved liner Packing cut to suit
7.5 - 10mm Window support bar
Air seal over backing rod Jenkin A-lign® pre-cut 36 x
18mm scriber
Jenkin A-lign® cavity batten Wall underlay turned into
framing reveals, flexible
Fig 2-13aWall underlay flashing tape to sill trimmer,
turn up 100mm at trimming
Bevelback weaItnhteerrnbaol lainrindg- cavity - aluminium window - sill stud and 50mm onto face of
underlay
Jenkin A-lign® bevelback
weatherboard
Figure 2.13a Cavity fixed – aluminium window – sill (option B)
Packing and window sill Version 2.0 All Dimensions are to Aluminium joinery profile,
support bar as required be site checked flange to provide 10mm min
Scale at A4 1:5 before construction cover to weatherboard
Architrave or grooved liner 4 October 2012 and installation
7.5 - 10mm Jenkin A-lign® pre-cut 36 x
18mm scriber
Jenkin AAliirgsne®alDoevtearilbsacking rod
H3.1 treated timber planted
fig2-13_cv_alu_wind_sill.dwg sill as required
Jenkin A-lign® cavity batten Wall underlay turned into
Wall underlay framing reveals, flexible
flashing tape to sill trimmer,
Internal lining turn up 100mm at trimming
stud and 50mm onto face of
underlay
Jenkin A-lign® bevelback
weatherboard
62 © JenkinTimber Ltd. 2012
)LJ
Figure 2.14 Cavity fixed – timber window – head
%HYHOEDFNZHDWKHUERDUGFDYLW\WLPEHUZLQGRZKHDG
:DOOXQGHUOD\WXUQHG PP :DOOXQGHUOD\IODSODSSHGRYHU
LQWRIUDPLQJUHYHDOV PLQ KHDGIODVKLQJ
ZLWKIOH[LEOHIODVKLQJ
PP -HQNLQ$OLJQEHYHOEDFN
WDSHDWFRUQHUV PLQ ZHDWKHUERDUGZLWKPPGULS
HGJHWRFDYLW\FORVXUH
-HQNLQ$OLJQFDYLW\
EDWWHQ -HQNLQ$OLJQ WLOWLQJILOOHWZKHUH
UHTXLUHGIRUVXSSRUW
4XLFNIODVK&RGH
FDYLW\FORVXUH 2SWLRQDO-HQNLQ$OLJQ
ZHDWKHUKHDGIL[HGRYHU
3DFNLQJDQGZLQGRZVXSSRUW ZHDWKHUERDUGVKDSHGWRVKHG
EUDFNHWVDVUHTXLUHG ZDWHUZLWKGULSWRERWWRPHGJHDQG
WKLFNHUWKDQMDPEIDFLQJVE\PP
,QWHUQDOOLQLQJ PLQ
PP
PPPLQFRYHU
$UFKLWUDYH
$LUVHDORYHUEDFNLQJURG +HDGIODVKLQJE\MRLQHU\
PDQXIDFWXUHUZLWKVORSHDQG
7LPEHUZLQGRZKHDGWR PPVWRSHQGWRH[WHQGPP
1=6 PLQEH\RQGRXWHUHGJHRIMDPE
IDFLQJRUVFULEHU
-HQNLQ$OLJQMDPEIDFLQJ
ILWWHGWRXQGHUVLGHRI
ZLQGRZKHDG
)LJ
Figure 2.15 Cavity fixed – timber window – jamb
%HYHOEDFNZHDWKHUERDUGFDYLW\WLPEHUZLQGRZMDPE
:DOOXQGHUOD\ -HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUG
,QWHUQDOOLQLQJ :DOOXQGHUOD\WXUQHGLQWRIUDPLQJ
$LUVHDORYHUEDFNLQJURG UHYHDOZLWKIOH[LEOHIODVKLQJWDSHDW
FRUQHUV
$UFKLWUDYH
PP -HQNLQ$OLJQFDYLW\EDWWHQ
7LPEHUMDPESURILOHWR -HQNLQ$OLJQSUHFXW[PP
1=6 VFULEHU
-HQNLQ$OLJQ'HWDLOV -HQNLQ$OLJQ[PP
JURRYHGIDFLQJ
ILJ3BDFFYNBLQWLPJBDZQLGQGZBKLQHGDRGZGZVJXSSRUW
EUDFNHWVDVUHTXLUHG /LQHRIRSWLRQDO-HQNLQ$OLJQ
/LQHRIKHDGIODVKLQJ ZHDWKHUKHDGRYHU
9HUVLRQ $OO'LPHQVLRQVDUHWR
EHVLWHFKHFNHG
6FDOHDW$ EHIRUHFRQVWUXFWLRQ
'HFHPEHU DQGLQVWDOODWLRQ
© JenkinTimber Ltd. 2012 63
Fig%uHreY2H.O1E6DCFaNvZityHDfiWxKeHdU–ERtimDUbGerwFDinYdLWo\w–WLPsilEl HUZLQGRZVLOO
6LOOERDUG /LQHRI-HQNLQ$OLJQIDFLQJ
7LPEHUWULP 6LOOWR1=6
&RQWLQXRXVSDFNLQJDV 4XLFNIODVKPRGLILHG&RGH
DLUVHDO 7LPEHUVLOOIODVKLQJZLWK
PLQLPXPVORSHDQGVWRSHQG
,QWHUQDOOLQLQJ ODSSHGXQGHUMDPESDFNHU
)UDPLQJ PPFRYHUWRZHDWKHUERDUG
-HQNLQ$OLJQFDYLW\ )OH[LEOHIODVKLQJWDSHDFURVV
EDWWHQ VLOOWULPPHUDQGWXUQHGXS
PPHDFKHQGDQGPP
RQWRIDFHRIZDOOXQGHUOD\
-HQNLQ$OLJQ [PP
JURRYHGIDFLQJFXWWRVXLW
:DOOXQGHUOD\WXUQHGLQWR
IUDPLQJUHYHDOV
-HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUG
Figure 2.17 Cavity fixed – meter box
-HQNLQ$OLJQ'HWDLOV 9HUVLRQ $OO'LPHQVLRQVDUHWR
EHVLWHFKHFNHG
ILJBFYBWLPBZLQGBVLOOGZJ 6FDOHDW$ EHIRUHFRQVWUXFWLRQ
'HFHPEHU DQGLQVWDOODWLRQ
64 © JenkinTimber Ltd. 2012
Figure 2.18 Cavity fixed – external corner – prefabricated box – stucco
-HQNLQ$OLJQSUHFXW[PP PPPLQ -HQNLQ$OLJQSUHIDEULFDWHGER[
VFULEHU FRYHU FRUQHUWRJLYHPPPLQFODGGLQJ
FRYHU
-HQNLQ$OLJQEHYHOEDFN -HQNLQ$OLJQFDYLW\EDWWHQ
ZHDWKHUERDUG
%DFNIODVKLQJZLWKPPFODGGLQJ
FRYHUUHIHU1=%&($67DEOH
IRUH[WUDKLJKZLQG]RQHV
)LJ-HQNLQ$OLJQFDYLW\EDWWHQ 6WXFFR
%DFNLQJQRQULJLGRUULJLGZLWKVOLS
OD\HU
%HYHOEDFNZHDWKHUERDUGFDYLW\LQWHUQDOFRUQHUSUHFXWV:FUDLEOOHXQUGHUVODWX\FFFRQRWLQXRXVDURXQG
FRUQHU
1RWH5XQZDOOXQGHUOD\FRQWLQXRXVO\DURXQGLQWHUQDODQGH[WHUQDOFRUQHUVGRQRWMRLQWPDWHULDODW
FRUQHUV
Figure 2.19 Cavity fixed – internal corner – pre-cut scriber – stucco
-HQNLQ4$XLOFLJNQIODV'KH&WDRGLOVHRIIVHW 9HUVLRQ $OO'LPHQVLRQVDUHWR :DOOXQGHUOD\FRQWLQXRXVDURXQG
EHVLWHFKHFNHG FRUQHU
ILJBFYPBHFP[RWBUPQEHLRQU[BFEFODDUQFGBNGVLIWQOXDJFVGFKZRLQYJJHU 6FDOHDW$ EHIRUHFRQVWUXFWLRQ
0DUFK DQGLQVWDOODWLRQ -HQNLQ$OLJQFDYLW\EDWWHQ
-HQNLQ$OLJQFDYLW\EDWWHQ
-HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUG
-HQNLQ$OLJQSUHFXW[PP
WUDQVLWLRQVFULEHU
)RUPJDSWRVWXFFRZLWKWHPSRUDU\
VSDFHUDQGSURYLGHVHDODQWMRLQW
ZLWKEDFNLQJURG
6WXFFR
© JenkinTimber Ltd. 2012 65
Figure 2.20 Cavity fixed – above stucco
-HQNLQ$OLJQFDYLW\ -HQNLQ$OLJQEHYHOEDFN
EDWWHQ ZHDWKHUERDUG
)ODSRIZDOOXQGHUOD\ODSSHGRYHU
IODVKLQJXSVWDQG
4XLFNIODVK&RGHFDYLW\ PP )ODVKLQJZLWKFURVVIDOOPP
FORVXUHZLWKPPGULS FODGGLQJFRYHUWRXSVWDQG
HGJHWRZHDWKHUERDUG
)LJ-HQNLQ$OLJQFDYLW\ PPZHDWKHUERDUGFOHDUDQFHWR
EDWWHQ IODVKLQJ
6WXFFR
%HYHOEDFNZHDWKHUERDUGFDYLW\H[WFRUQHUSUHIDEER%[DFNSLQUJRIQLORHQGULPJLGHWRDUOULJLGZLWKVOLS
OD\HU
:DOOXQGHUOD\
Figure 2.21 Cavity fixed – external corner – prefabricated box – profiled metal
-HQNLQ$OLJQSUHFXW PPPLQ -HQNLQ$OLJQSUHIDEULFDWHGER[
[PPVFULEHU FRYHU FRUQHUVL]HGWRJLYHPPPLQ
FODGGLQJFRYHU
-HQNLQ$OLJQ-'HQHNWLDQLO$VOLJQEHYHOEDFN 9HUVLRQ $OO'LPHQVLRQVDUHWR
EHVLWHFKHFNHG 0DLQWDLQPPPLQJDSEHWZHHQ
ZHDWKHUERDUG 6FDOHDW$ EHIRUHFRQVWUXFWLRQ HQGRIFODGGLQJDQGIODVKLQJUHWXUQ
'HFHPEHU DQGLQVWDOODWLRQ
ILJBFYBDERYHBVWXFGZJ
%DFNIODVKLQJZLWKPPPLQ
-HQNLQ$OLJQFDYLW\EDWWHQ FODGGLQJFRYHU
3URILOHGIRDPVHDOLQJVWULS
6FULEHUFXWWRVXLW
3URILOHGPHWDOFODGGLQJ
:DOOXQGHUOD\FRQWLQXRXVDURXQG
FRUQHU
66 © JenkinTimber Ltd. 2012
Figure 2.22 Cavity fixed – internal corner – pre-cut scriber – profiled metal
-HQNLQ$OLJQFDYLW\ :DOOXQGHUOD\FRQWLQXRXV
EDWWHQ DURXQGFRUQHU
4XLFNIODVK&RGHRIIVHW -HQNLQ$OLJQEHYHOEDFN
FRUQHUEDFNIODVKLQJ ZHDWKHUERDUG
PPPLQFODGGLQJFRYHU
)LJ6HDODQWRYHUEDFNLQJURG -HQNLQ$OLJQSUHFXW
[PPWUDQVLWLRQVFULEHU
%HYHOEDFNZHDWKHUERDUGFDYLW\DERYHSURILOHGPHWDO
(QGFDSIODVKLQJWRSURILOHG
-HQNLQ$OLJQFDYLW\ PHWDOFODGGLQJE\RWKHUV
EDWWHQ
3URILOHGIRDPVHDOLQJVWULS
3URILOHGPHWDOFODGGLQJ
Figure 2.23 Cavity fixed – above profiled metal
-HQNLQ$OLJQ'HWDLOV 9HUVLRQ $OO'LPHQVLRQVDUHWR -HQNLQ$OLJQEHYHOEDFN
EHVLWHFKHFNHG ZHDWKHUERDUG
ILJBFYBLQWBFUQBSBPHWGZJ 6FDOHDW$ EHIRUHFRQVWUXFWLRQ )ODSRIZDOOXQGHUOD\ODSSHGRYHU
'HFHPEHU DQGLQVWDOODWLRQ IODVKLQJXSVWDQGPPFODGGLQJ
,QWHUQDOOLQLQJ FRYHUUHIHU1=%&($67DEOH
IRUH[WUDKLJKZLQG]RQHV
-HQNLQ$OLJQFDYLW\EDWWHQ -HQNLQ$OLJQWLOWLQJILOOHW
4XLFNIODVK&RGHFDYLW\ )ODVKLQJZLWKFURVVIDOO
FORVXUHZLWKPPGULS PPZHDWKHUERDUGFOHDUDQFHWR
HGJHWRZHDWKHUERDUG IODVKLQJ
:DOOXQGHUOD\ )ODVKLQJFUHVWVPLQFRYHUE\
FODGGLQJVXSSOLHU
3URILOHGPHWDOFODGGLQJ
-HQNLQ$OLJQFDYLW\EDWWHQ
© JenkinTimber Ltd. 2012 67
Figure 2.24 Cavity fixed – below profiled metal
-HQNLQ$OLJQFDYLW\EDWWHQ 3URILOHGPHWDOFODGGLQJ
)ODSRIZDOOXQGHUOD\ODSSHGRYHU
KHDGIODVKLQJXSVWDQGPPPLQ
FODGGLQJFRYHU
)ODVKLQJZLWKFURVVIDOO
PPFOHDUDQFHWRIODVKLQJ
)LJ4XLFNIODVK&RGHFDYLW\ PP
FORVXUHZLWKPPGULS
HGJHWRFODGGLQJ
3DFNLQJWRVXLW
%HYHOEDFNZ,QHWHDUWQKDHOOULEQLRQJDUGFDYLW\DEXWWLQJSURILOHGPHWDO -HQNLQ$OLJQ EHYHOEDFN
ZHDWKHUERDUG
:DOOXQGHUOD\ -HQNLQ$OLJQFDYLW\EDWWHQ
Figure 2.25 Cavity fixed – abutting profiled metal
3URILOHGIRDPVHDOLQJVWULS 9HUVLRQ $OO'LPHQVLRQVDUHWR 3URILOHGPHWDOFODGGLQJ
EHVLWHFKHFNHG 6FULEHUFXWWRVXLW
-HQNLQ$OLJQ)'ODHVKWDLQLOJVWRJLYHPPPLQ 6FDOHDW$ EHIRUHFRQVWUXFWLRQ 3DFNLQJWRVXLW
'HFHPEHU DQGLQVWDOODWLRQ PPJDSEHWZHHQFODGGLQJV
FODGGLQJFRYHUUHI($6
ILJBFYBEHORZ7BDSEBOHPHWIGRZUJH[WUDKLJKZLQG -HQNLQ$OLJQ[PP
JURRYHGIDFLQJ
]RQHV
-HQNLQ$OLJQSUHFXW[PP
,QWHUQDOOLQLQJ VFULEHU
-HQNLQ$OLJQFDYLW\EDWWHQ
-HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUG
:DOOXQGHUOD\
68 © JenkinTimber Ltd. 2012
Figure 2.26 Cavity fixed – external corner – masonry veneer
-HQNLQ$OLJQSUHFXW -HQNLQ$OLJQ[PPJURRYHG
[PPVFULEHUILWWHG IDFLQJZLGWKWRJLYHPPPLQ
FRYHUWRFODGGLQJ
WLJKWWRZHDWKHUERDUG
6HDODQWRYHUEDFNLQJURG
0DVRQU\YHQHHU
-HQNLQ$OLJQEHYHOEDFN
ZHDWKHUERDUG
Fig 2-27-HQNLQ$OLJQFDYLW\EDWWHQ 0DVRQU\YHQHHUFDYLW\
:DOOXQGHUOD\FRQWLQXRXV
DURXQGFRUQHU
Bevelback weatherboard - cavity - internal corner - masonry veneer
.HHSHQGVRIZHDWKHUERDUG
PPEDFNIURPPDVRQU\
YHQHHUVHDOHQGVRIERDUGV
PP
Figure 2.27 Cavity fixed – internal corner – masonry veneer
Keep ends of masonry 12mm9HUVLRQ $OO'LPHQVLRQVDUHWR Wall underlay continuous
back 12mm from EHVLWHFKHFNHG around corner
weatherboard 6FDOHDW$ EHIRUHFRQVWUXFWLRQ Maintain 6mm gap
DQGLQVWDOODWLRQ between flashing and
Masonry veneer cavity 'HFHPEHU weatherboard (seal ends
of boards)
-HQNLQ$OLJ4Q0-'7H5mWDmLOV(50mm min 30mm Quickflash modified Code
03 metal flashing
ILJBFYBH[WBFQUBPreBcYoHmQGmZeJnded) Jenkin A-lign® cavity
batten
Masonry veneer
Jenkin A-lign® bevelback
Jenkin A-lign® pre-cut weatherboard
66 x 18mm transition scriber
© JenkinTimber Ltd. 2012 69
Figure 2.28 Cavity fixed – above masonry veneer :DOOXQGHUOD\IODSODSSHG
RYHUIODVKLQJXSVWDQG
-HQNLQ$OLJQFDYLW\EDWWHQ -HQNLQ$OLJQEHYHOEDFN
4XLFNIODVK&RGHFDYLW\ ZHDWKHUERDUGPPPLQ
FRYHUWRIODVKLQJXSVWDQGDQG
FORVXUH PPGULSHGJHWRFDYLW\
,QWHUQDOOLQLQJ FORVXUH
0HWDOIODVKLQJFURVVIDOODQG -HQNLQ$OLJQWLOWLQJILOOHW
PPFRYHUWRVLOOEULFN 0DLQWDLQPPJDS
PPJDS 0DVRQU\YHQHHU
:DOOXQGHUOD\
Figure 2.29 Cavity fixed – abutting masonry veneer
-HQNLQ$OLJQ'HWDLOV 9HUVLRQ $OO'LPHQVLRQVDUHWR
EHVLWHFKHFNHG
ILJBFYBDERYHBPBYHQGZJ 6FDOHDW$ EHIRUHFRQVWUXFWLRQ
'HFHPEHU DQGLQVWDOODWLRQ
70 © JenkinTimber Ltd. 2012
)LJ
Figu%reH2Y.H3O0EDCFavNitZy HfiDxeWKdH–UEpRipDeUGpenFeDtrYaLtWi\onSLSHSHQHWUDWLRQ
:DOOXQGHUOD\ 7LPEHUILOOHWEDFNLQJWRVXLWIL[HG
-HQNLQ$OLJQFDYLW\ RYHUVHDODQWWR-HQNLQ$OLJQ
ZHDWKHUERDUG
EDWWHQ
-HQNLQ$OLJQWLOWLQJILOOHW )ODQJHWRSURWHFWVHDODQWIURP
H[SRVXUHWRVXQOLJKW
$LUVHDODOOURXQG )OH[LEOHIODVKLQJWDSHDGKHULQJ
DURXQGSLSHDQGRQWRZDOOXQGHUOD\
:KHUHSRVVLEOHSURYLGH PPODSWRXQGHUOD\DQGPP
RXWZDUGVIDOOWRSLSHZRUN WRSLSH
IRUZDWHUUXQRII 6HDODQWZLWKEDFNLQJURG
$LUVHDODOOURXQG
6ROLGEORFNLQJDURXQG 3LSHZLWKVORSH
SLSHSHQHWUDWLRQ -HQNLQ$OLJQEHYHOEDFN
-HQNLQ$OLJQFDYLW\ ZHDWKHUERDUG
:DOOXQGHUOD\
EDWWHQ
Fig 2-31
BeFivgeulrbea2c.3k1 wCaevaittyhfeixrebdo–aardbo-vecawvaitteyrp-roaobfodveeckwaterproof deck
Jenkin A-lign® bevelback
weatherboard
Internal lining Wall underlay lapped over
membrane upstand
Jenkin A-lign® cavity batten
Jenkin A-lign® bevelback base
-HSQoNliLdQs$uOpLJpQort'toHWwDLaOVterproof board
ILJBFYBSLSHBSHQHmGeZmJ brane
Quickflash Code 06 cavity
35mm min clearance closure
to decking high point
9HUVLRQ $OO'LPHQVLRQVDUHWR 15mm drip edge
(from E2/AS1) EHVLWHFKHFNHG
6FDOHDW$ EHIRUHFRQVWUXFWLRQ Membrane roofing, provide
'HFHPEHU DQGLQVWDOODWLRQ 150mm min upstand at roof
edges and 100mm step down
from internal floor surface to
deck
© JenkinTimber Ltd. 2012 71
Figure 2.32 Cavity fixed – reverse raked soffit
Flashing with drip edge and
75mm minimum cover to top
weatherboard
Fig 2-33 Take underlay under eaves
to provide an air barrier
Bevelback weatherboard - cavity - apron flashing
Soffit lining with end
Internal lining setback 6mm to provide
an anti-capillary space
Framing
Jenkin A-lign® 42 x 18mm
eaves mould bevelled to
suit
Jenkin A-lign® bevelback
weatherboard
Jenkin A-lign® cavity batten
Wall underlay
Figure 2.33 Cavity fixed – apron flashing
Wall underlay lapped Jenkin A-lign® bevelback
over flashing weatherboard
Jenkin A-lign® cavity batten Jenkin A-lign® bevelback
base board or bevelback
Jenkin Align® Details weatherboard with Jenkin
A-lign® tilting fillet
fig2-32_cv_rev_rake_sof.dwg
35mm min Version 2.0 All Dimensions are to Quickflash Code 06 cavity
Support nog 75mm be site checked closure with 15mm drip edge
Framing Scale at A4 1:5 before construction to weatherboard
4 October 2012 and installation
110mm flashing upstand
with 10mm hem
Roofing material
Roof framing
5mm gap max for
notched downturn
Underlay carried up
face of framing behind
flashing upstand
Note: Refer to NZBC Acceptable Solution E2/AS1 Table 7 for apron flashing cover over roofing
72 © JenkinTimber Ltd. 2012
FBigeuvreel2b.3a4cCkawvietyaftixheedrb–oaaprrodn-flcaashviintyg –- satpoproenndflashing - stop end
Spouting to stop 10mm Jenkin A-lign® bevelback
min from finished wall weatherboard
cladding Wall underlay
Jenkin A-lign® cavity batten
Apron flashing
Apron flashing upstand
behind cladding, cavity
and building underlay
50 x 50mm transition tray Tapered stop-end to divert
apron flashing water into
Fig 2-35behind fascia or seal Fall gutter
between fascia and
coated cladding
Bevelback weatherboard - cavity - parapet - balustrade - wall junction Roofing
Gutter
Note: Refer to NZBC Acceptable Solution E2/AS1 Table 7 for apron flashing cover over roofing
Figure 2.35 Cavity fixed – parapet – balustrade – wall junction
40mm 40mm
Wall framing Drain formed in corner
Jenkin A-lign® Version 2.0 All Dimensions are to Parapet or balustrade
bevelback be site checked building underlay lapped
Scale at A4 1:10 before construction around corner
weatherboard scribed 4 October 2012 and installation Jenkin A-lign® cavity
to each other batten
150mm min to face of window Jenkin A-lign® bevelback
or door jamb stud weatherboard
Option with Jenkin A-lign®
Jenkin Align® Details pre-cut 36 x 36mm
internal scriber
fig2-34_cv_Laipnreono_fsstolopp.dinwggpHac3k.1ertraebaotevde
Quickflash Code 03
Parapet or balustrade wall corner back flashing,
framing 50mm cladding cover to
flashing - refer NZBC
E2/AS1 Table 7 for extra
high wind zones
Wall underlay
© JenkinTimber Ltd. 2012 73
)LJ
Figure 2.36 Cavity fixed – parapet – balustrade – saddle flashing
%HYHOEDFNZHDWKHUERDUGFDYLW\SDUDSHWEDOXVWUDGHVDGGOHIODVKLQJ
:DOOXQGHUOD\ :DOOIUDPLQJ
-HQNLQ$OLJQFDYLW\
-HQNLQ$OLJQFDYLW\EDWWHQ EDWWHQ
SRVLWLRQHGWRIRUPFOHDUFKDQQHO
EHWZHHQVORSHGWLPEHUFDSSLQJ PPPLQ
)UDPLQJ
DQGEDWWHQ :DOOXQGHUOD\
)OH[LEOHIODVKLQJWDSHGUHVVHGXS
DQGVHFXUHO\DGKHUHGWREXLOGLQJ
XQGHUOD\DWUHDURIFDYLW\
)OH[LEOHIODVKLQJWDSHGUHVVHG
PPPLQGRZQIDFHRIEDWWHQV
)LJ
%HYHOEDFNZHDW-KHHQUNELQR$DUOGLJQFFDDYYLWL\W\EDWWSHDQUDSHWEDOXVWUDGHVDGGOHLQVWDOO
6ORSHGSDFNHUWRH[WHQG
DFURVVFDYLW\DWZDOOMXQFWLRQ
PLQVORSH
Figure 2.37 Cavity fixed – parapet – balustrade – saddle install
)UDPLQJ :DOOXQGHUOD\
:DOOXQGHUOD\
PPPLQ -HQNLQ$OLJQ%HYHOEDFN
ZHDWKHUERDUG
PLQVORSH /RZHUHGJHRIFODGGLQJ
-HQNLQ$OLJQ /LQHRIVDGGOHIODVKLQJ
FDYLW\EDWWHQ EHKLQG
&DSSLQJIODVKLQJ
7ZROLQHVRIVHDODQW
5LYHWWKURXJKVHDODQW
4XLFNIODVKRU
7ZROLQHVRIVHDODQWWR
PPPLQ FDSSLQJDQGIODVKLQJ
)UDPLQJ
-HQNLQ$OLJQ'HWDLO[VPPFRUQHUIODVKLQJ 9HUVLRQ :DOOXQGHUOD\DJDLQVW
RQIDFHRIEDWWHQVEHKLQG IUDPLQJ
ILJBFYBVDGGOHBIOVKGZJ 6FDOHDW$ $OO'LPHQVLRQVDUHWR %DWWHQFDYLW\
VDGGOHIODVKLQJ 'HFHPEHU EHVLWHFKHFNHG
PPPLQ EHIRUHFRQVWUXFWLRQ
DQGLQVWDOODWLRQ
-HQNLQ$OLJQFDYLW\EDWWHQ
74 © JenkinTimber Ltd. 2012
FiBguervee2l.b3a8 cCkavwityeafixtheder–bhooarirzdon-taclacvaivtiyty-johiontrizontal cavity joint
Wall underlay lapped Jenkin A-lign® bevelback
over flashing upstand weatherboard, 50mm cover to
flashing upstand
Equal
Jenkin A-lign® cavity batten
Quickflash Code 06 cavity closure
Jenkin A-lign® tilting fillet
15mm drip edgeEqual
5mm gap
Quickflash Code 12 horizontal
flashing 15° cross fall, 35mm cover
to cladding
Wall underlay lapped under
horizontal flashing
Note: Horizontal drained joints must be provided to limit cavities to 2-storeys or maximum
7m in height in accordance with NZBC Acceptable Solution E2/AS1 paragraph 9.1.9.4(b)
Figure 2.39 Cavity fixed – internal corner – 135 degrees – scribed
Jenkin Align® Details Version 2.0 All Dimensions are to
be site checked
fig2-38_cv_hori_joint.dwg Scale at A4 1:5 before construction
4 October 2012 and installation
© JenkinTimber Ltd. 2012 75
Figure 2.40 Cavity fixed– internal corner – 135 degrees – flashed
Figure 2.41 Cavity fixed – external corner – 135 degrees – mitred
76 © JenkinTimber Ltd. 2012
Figure 2.42 Cavity fixed– nailing
)L[HDFKERDUGZLWKRQHQDLO )L[HDFKERDUGZLWKRQHQDLO
SHUERDUGDWHYHU\VWXGRU SHUERDUGDWHYHU\VWXGRU
EDWWHQORFDWHIL[LQJPP EDWWHQORFDWHIL[LQJPP
DERYHWKHERWWRPHGJHRI
DERYHWKHERWWRPHGJHRIWKH WKHRYHUODSERDUGWRDOORZ
RYHUODSERDUGWRDOORZIRU IRUH[SDQVLRQDQG
FRQWUDFWLRQ
H[SDQVLRQDQGFRQWUDFWLRQ
PP
PP
-HQNLQ$OLJQ'HWDLOV 9HUVLRQ $OO'LPHQVLRQVDUHWR
EHVLWHFKHFNHG
ILJBFYBQDLOLQJBEHYGZJ 6FDOHDW$ EHIRUHFRQVWUXFWLRQ
'HFHPEHU DQGLQVWDOODWLRQ
© JenkinTimber Ltd. 2012 77
78 © JenkinTimber Ltd. 2012
© JenkinTimber Ltd. 2012 79
Jenkin Timber Limited –
Quality
Jenkin quality assurance standards
To constantly deliver products that perform at the highest level
demands excellent standards of quality in every area of business:
from the training of our people, to product improvement, to
concern for the environment.
We at Jenkin Timber Limited are proud of our reputation for
quality and integrity. A reputation that has been proven for
generations. Our investment in quality is core to our company
philosophy. Out of that dedication, innovation flows – and
excellence continues year after year.
Our most recent certifications and standards are shown here.
We will update these regularly. We strive to not just follow the
strictest standards of our profession but to keep ahead of them.
That way you, our customer, know that whenever you choose a
Jenkin product or service, you are choosing real quality.
Forest Stewardship Council – chain of custody
Jenkin Timber has been independently certified by Scientific
Certification Systems (SCS) in accordance with the rules of the
Forest Stewardship Council A.C. (FSC).
SCS Certification Registration Number SCS-COC-00538
Timber Preservation Quality Manual. License Number 080
New Zealand Forest Industries Council
Jenkin Timber was awarded the champion training company for
solid wood processing in 2001. The certificate was awarded by
Forest Industries Training and Education Council.
Refer to www.jenkin.co.nz for information on quality
control methods.
For more information about our independent third
party quality audit process email us at:
[email protected]
80 © JenkinTimber Ltd. 2012
© JenkinTimber Ltd. 2012 81
For more information call
the Jenkin Helpline Toll Free
0800 25 44 61
Monday to Friday 8am–5pm
© Jenkin Timber Ltd 2007 – 2012. All rights reserved. All intellectual property and images included in this Technical Manual and in the A-lign solution are owned by Jenkin Timber Ltd and cannot be used without (written) consent of the copyright owner. No material in this document may be copied without the express (written) consent of Jenkin Timber Ltd All applications for
reproduction, in any form, should be made to Jenkin Timber Ltd Jenkin Timber Ltd reserves the right to revise, without notice, any information contained in this document. Although every effort has been made to ensure the information contained in this document complies with existing building standards and recognised codes of practice, no responsibility is accepted for
any errors and omissions in this document, nor for any specifications or work based upon this information. Some of these images depict Jenkin Tru-Pine weatherboards. These boards are nearly identical to those used in the A-lign solution and differ only slightly in size to the A-lign weatherboards and differ in certain construction features which are not visible externally.