Standard and Quick Response Sprinklers
(Model: NS001 to NS006)
Standard response spray sprinklers are intended for use in the sprinkler systems designed in accordance with
the standard installation rules recognized by the applicable listing or approval agency. They are available in
pendent, upright, recessed, horizontal sidewall styles.
Quick response spray sprinkler are designed with a 3mm glass-bulb to react quicker at the speci ied temperature.
They are available in pendent, upright, horizontal sidewall styles.
During a ire conditions, the thermal-sensitive liquid in the glass bulb expands, causing the bulb to shutter,
releasing the button and spring seal assembly. Water lowing through the sprinkler ori ice strikes the sprinkler
de lector, forming a uniform spray pattern to extinguish or control the ire.
Standard and Quick responders are designed for use in a wild range of applications including of ice, buildings,
libraries, hotels, restaurants, banks, band shells, theaters, factories and storehouse.
Model NS001 / NS002 Model NS003 / NS004 Model NS005 / NS006
5/3mm Bulb Type, K=5,6 5/3mm Bulb Type, K=5,6 5/3mm Bulb Type, K=5,6
Horizontal Sidewall Sprinkler
Upright Sprinkler Pendent Sprinkler
Response: Standard / Quick Response: Standard / Quick Response: Standard / Quick
Coverage: Coverage: Coverage:
Water discharge is directed primarily Produce a hemispherical water Produce a hemispherical water
outward and downward in a quarter distribution pattern below the de lator. distribution pattern below the de lator.
spherical pattern, a portion of the spray
is also directed towards the back wall. Installation: Installation:
Installation: Upright installed in accordance with the Pendent installed in accordance with the
Designed for installation along wall or standard installation rules recognized standard installation rules recognized
the side of a beam just beneath a by the applicable Listing or Approval by the applicable Listing or Approval
smooth ceiling. (Ref. NFPA 13) agency. (Ref. NFPA 13 Requirements) agency. (Ref. NFPA 13 Requirements)
Ori ice Size: 1/2” 115mm Ori ice Size: 1/2” 115mm
Ori ice Size: 1/2” 115mm Thread Size: 1/2” Pipe Thread Thread Size: 1/2” Pipe Thread
Thread Size: 1/2” Pipe Thread Temp Rating: Temp Rating:
Temp Rating: 135°F/57°c, 155°F/68°c, 135°F/57°c, 155°F/68°c,
135°F/57°c, 155°F/68°c, 175°F/79°c, 200°F/93°c 175°F/79°c, 200°F/93°c
175°F/79°c, 200°F/93°c Maximum Service Pressure: Maximum Service Pressure:
Maximum Service Pressure: 175 psig / 1.2 Mpa (12 Bar) 175 psig / 1.2 Mpa (12 Bar)
175 psig / 1.2 Mpa (12 Bar) Listings and Approvals: Listings and Approvals:
Listings and Approvals: UL Listed UL Listed
UL Listed Finishes: Finishes:
Finishes: Natural Brass, Chrome Plate Natural Brass, Chrome Plate
Natural Brass, Chrome Plate
www.newage-india.in
Address : “NKB House”, P. O. Box No.: 14, Mehta Market, Surendranagar - 363 001, Gujarat, India
Phone No. : +91 2752 288 000, +91 99250 63730 | Fax : +91 11 66173355 | Email : [email protected]