TYPE VPR SERIES
VACUUM CIRCUIT BREAKERS 3.6 24kV
Innttrroodduucciinngg tthhee VVPPRR--DD SSeerriieess
rraatteedd aatt 2244kkVV 1166//2255kkAA
Above-mentioned VCBs utilizes a new, low-maintenance
and more simple and compact operating mechanism
(BH-1H mechanism).
VPR-D series conforms to the latest JEC-2300 and
IEC 62271-100.
Also now available with a rated current of 2,500A.
Type 20-VPR-16D/25D 630,1250A VCB
Vacuum Circuit Breaker Vacuum Switch Tube
Each Vacuum Switch Tube (VST) is insulated by a molded frame Mitsubishi Electric has more than 40 years of experience
that allows minimal separation between pole units. manufacturing VSTs and is currently producing
The frame is made of an anti-tracking bulk mold compound that approxima, tely 140,000 units per year.
has been specially developed for breakers. Mitsubishi s VST design integrates a vast of amount of test data
The moving contacts are mechanically connected to the lower based o,n thousands of studies and electrical field analysis.
conductors by flexible conductors to prevent rubbing damage. VPR-D s (rated at 24kV 16/25kA) VSTs use spiral-type
contacts to provide the lowest resistance.
16 1 Upper terminal
2 Vacuum interrupter Internal structure of VSTs
2 3 Flexible conductor
7 4 Lower terminal
5 Closing spring
3 6 BH-1H mechanism
7 Opening spring
4 8 Auxiliary switch
8 9 Secondary junction
59
Construction of type
20-VPR-16D/25D 630,1250A VCB
Operating Mechanism
,
Mitsubishi s BH-1H mechanism design is
based on simple operating principles with 1 Closing spring charging motor
a compact construction and is suitable for 9 2 Closing spring charging 9 1
a wide range of ratings. 10 mechanism
The mechanism is used for auto-reclosing 1 8
and multi-shot applications without any 3 Closing spring
additional parts. 4 Closing spring charged 2
The BH-1H uses a universal charging indicator
motor (AC / DC). 8 4 5 Operation mechanism 4
Special surface treatments are used in 2 6 ON-OFF indicator
the moving parts that extend the 7
maintenance interval of the unit. 3 5 10
The use of long-life grease extends the 7 Auxiliary switch 5
mechanism inspection intervals from 6
three to six years and reduces 6 8 Mechanically operation counter 3
maintenan,ce costs.
Mitsubishi s BH-1H unit is engineered for 9 Manual closing button
safety. The manual charging device for (Closing control coil)
the closing spring prevents impact to the
10 Manual tripping button
(Tripping control coil)
7 Opening spring
(iItn,scianssetaollfetdhein BcHro-s1sHbaarnsdidBeH.)-2,
operator even when the electric motor is BH-1H operation mechanism BH-2 operation mechanism
energized or if the breaker is operated (For type 20-VPR-16D/25D 630, 1250A VCB)
during manual charging. (Reference: For existing VPR-C series and type 20-VPR-25D 2500A VCB)
1
Innttrroodduucciinngg tthhee 1100--VVPPRR--5500CC((DD))
rraatteedd aatt 1122kkVV 4400//5500kkAA 44000000AA
10-VPR-50C(D) VCB is installed with the BH-2H
operating mechanism for a larger capacity breaker.
10-VPR-50C(D) VCB designed to the latest JEC-2300,
IEC 62271-100, and Chinese standards.
4,000 A rated current without cooling fans.
Type 10-VPR-50C(D) 4000A VCB
Vacuum Circuit Breaker Vacuum Switch Tube
Mounting the VSTs vertically increases the efficiency of the Mitsubishi Electric has over 40 years of experience
natural convection cooling cycle. manufacturing VSTs and currently produces about 140,000
In addition, the unit has heat sinks that increase the heat units per year.
transfer characteristics which make the use of additional cooling Mitsubishi VSTs design integrates vast amounts of test data
devices, such as fans, unnecessary. b1a0s-VePd Ro-n50thCo(uDs)a,sndVsSoTfssutusdeieasxiaanl dmealgencetrtiiccafliefiledl-dtyapnealysis.
The circuit breaker is suitable for operations in the most severe contacts to be applied for large current ratings.
environmental conditions. The design exceeds applicable IEC
requirements for creepage and insulation distance.
13 1 Upper terminal
1 2 Vacuum switch tube
3 Lower terminal
2 4 Flexible conductor
5 Insulated rod
3 6 Contact pressure spring
7 Cross-bar
10 12 (inside) 4 8 Secondary junction Internal structure of VSTs
11 9 Auxiliary switch
Construction of type 5 10 BH-2H mechanism
9 10-VPR-50C(D) 4000A VCB 6 11 Closing spring
7 12 Opening spring
8 13 Heat sink
Operating Mechanism 18 4 1 Closing spring charging motor
2 Closing spring charging mechanism
The BH-2H operating mechanism,s design
incorporating simple operating principles 3 Closing spring
and is suitable for a wide range of ratings. 9
The mechanism is used for auto-reclosing 2 4 Closing spring charged indicator
and multi-shot applications without any
additional parts. 10 5 Operation mechanism
The BH-2H uses a universal charging motor
(AC / DC). 6 ON-OFF indicator
Gears are treated with a greaseless, low-
friction coating. A special long-life grease is 7 Auxiliary switch
used on the other surfaces to extend the
mThaeinMteintsaunbcisehiin,steBrvHa-l2. H unit is engineered 7 8 Mechanically operation counter
for safety. The manual charging device for
the closing spring prevents impact to the 9 Manual closing button
operator even when the electric motor is 3 (Closing control coil)
energized or if the breaker is operated
during manual charging. 5 10 Manual tripping button
(Tripping control coil)
6
BH-2H operation mechanism
(For type 10-VPR-50C(D) 4000A VCB)
2
EQUIPMENT
Standard equipment Additional standard equipment on withdrawable breaker
■ Trip and close control circuit including auxiliary ■ Mechanical and electrical interlock device for
switches, solenoids and anti-pumping relay withdrawing
■ Electric charging motor and control circuit ■ Shutter control devices
■ Manuals push button for trip and close ■ Breaker wheels for withdrawing
■ ON/OFF indicator
■ Indicator for charging condition of closing spring
■ Operation counter
■ Auxiliary contacts for customer----5a5b
■ (10-VPR-40C(D) 4000A, when secondary
connector code is B----6a6b)
■ (10-VPR-50C(D) 4000A, when secondary
connector code is B----10a10b)
Options
■ Mechanical interlock device for control circuit plugs for withdrawable breakers
■ Auxiliary contact for spring charged indication - - 1C (max 2C)
FEATURES
Increased Dielectric Performance
The 10-VPR-40C(D)/50C(D) 4000AVCB exceeds IEC standard applicable requirements including longer
creepage and longer insulation distance that ensures breaker operation even under the most severe
environmental conditions.
New Technology Improves Maintenance
The design of the BH-1H incorporates low maintenance technology such as a newly developed low friction
greaseless surface treatment and long-life lubrication (lubrication cycle of six years).
Safety firs, t
Mitsubishi s design features multiple mechanical and electric interlock systems that ensure safe operation
and maintenance.
Our proven supply record proves our top quality
More than 500,000 Mitsubishi Vacuum Circuit Breakers have been produced since 1969.
Design for worldwide applications
The compact design of the VCB and optional mounting frame with shutter makes the unit suitable for a wide
range of replacements for existing or obsolete metal-clad and switchboard units.
3
FRAME SIZE
■ 3/6/10/20-VPR series
3.6kV 600/630A to 24kV 2000A circuit breakers are either L, M or H size. 12kV 4000A and 24kV 2500A
circuit breakers are R size.
Rated current
Rated voltage / Rated 600/630A 1200/1250A 1600A 2000A 2500A 3000/3150A 4000A
short-circuit breaking current
20kA L size
3.6kV 25kA
31.5kA
40kA
20kA L size M size
7.2kV 25kA
31.5kA
40kA
25kA
12kV 31.5kA
40kA, 40/50kA R size
24kV 16kA H size R size
25kA
SELECTION CRITERIA
■ BASIC DESIGNATION (Example:10-VPR-25C)
Rated voltage Type name Rated short-circuit Series code Type of VST Mounting
breaking current configuration
10 VPR C –
25 D
(see Note 5)
3 3.6kV 16 16kA L Fixed (with wheels)
6 7.2kV 20 20kA C Withdrawable (with Class CW mounting frame)
10 12kV 25 25kA D Withdrawable (with Class PW mounting frame)
20 17.5kV, 24kV 32 31.5kA C C Series G Withdrawable (with Class MW mounting frame)
40 40kA D D Series (see Notes 3,4)
50 40/50kA – Standard
G Low surge
(see Notes 1,2)
Notes: 1. Different VSTs are installed on standard type and low surge type VCBs.
2. Low surge types are only available for 600/630/1200/1250A of 3/6-VPR VCBs except 6-VPR-25C(S).
3. Mounting configuration “L” is available for 600/630/1200/1250 and 2000A VCBs except 20-VPR.
4. For 20-VPR, only mounting configurations “C” and “D” are available.
5. Type 20-VPR, refer to table 1 for details.
■ SELECTION CRITERIA
Table 1 IEC, JEC standard (see Note 1)
Rated voltage Rated short-circuit 16kA 20kA 25kA 31.5kA 40kA 40/50kA
breaking current 3-VPR-32C
6-VPR-32C
3.6kV 3-VPR-20C 3-VPR-25C 10-VPR-32C 3-VPR-40C
7.2kV 6-VPR-20C 6-VPR-25C (For 1600, 2000A) 6-VPR-40C
12kV 6-VPR-25C(S) (For 600~1250A)
10-VPR-40C
10-VPR-25C 10-VPR-40C(D) (For 4000A) 10-VPR-50C(D)
10-VPR-25C(F) (For 600~1250A)
17.5kV 20-VPR-16D 20-VPR-25D (For 600~1250A and 2500A)
24kV 20-VPR-25C (For 2000A)
Notes: 1. IEC : International standards, IEC 60056 (1987, Insulation level series ) and IEC 62271-100 (2003, Insulation level series )
JEC : Japanese standard, JEC-2300 (1998)
Remarks: 1. Consult your dealer for information on the applicability of other foreign standards, including U.S. standard ANSI and Chinese standards GB, DL.
2. Refer to the catalog (A-AL1-5-C1283-B) for VCBs of rated voltage 36kV.
4
RATINGS
■ Table 2 Ratings and Performance (JEC/IEC standards)
Standard 3-VPR-20C 3-VPR-25C 3-VPR-32C 3-VPR-40C 6-VPR-20C 6-VPR-25C(S)
3-VPR-25CG 3-VPR-32CG 3-VPR-40CG 6-VPR-20CG
Type name 3-VPR-20CG (Note 2)
Low surge 600 / 630 6-VPR-25C
1200 / 1250 –
(Note 1)
1600 600 / 630
Closing operation mechanism 2000 JEC-2300/IEC 60056 1200 / 1250
Standards (Note 5)
Rated voltage (kV) 20 3.6 1600
50 2000
Rated current (A) 20 600 / 630 600 / 630 600 / 630 600 / 630
1200 / 1250 1200 / 1250 1200 / 1250 1200 / 1250 25
63
1600 1600 1600 1600 25
2000 2000 2000 2000
2500 2500 3
3000 / 3150 3000 / 3150
Rated frequency (Hz)
Rated short-circuit breaking current (kA) 25 31.5 40 20
63 80 100 50
Rated making current (kA) 25 20
31.5 40
Rated short-time withstand current (kA, 3sec.)
Rated opening time (sec.)
Rated breaking time (cycles)
Rated withstand AC 16
45
voltage (kV) Impulse
Operating duty
No-load closing time (sec.)
Closing operation Charging motor 1 (8sec.) ... 600~1250A 1.2 (6sec.) 1 (8sec.) ... 600~1250A
and control Current (Time) 1.2 (6sec.) ... 1600, 2000A 1.2 (6sec.) ... 1600, 2000A
current (A) 4
Control current 2.4 ... 600~1250A 2.4 ... 600~1250A
(Note 6) (CC coil) 4 ...... 1600, 2000A 4 4 ...... 1600, 2000A
Tripping device 2 ... 600~1250A Fixed (L) ......................... 600~2000A 2 ... 600~1250A
4 ... 1600, 2000A Withdrawable (C, D, G) ... 600~3150A 4 ... 1600, 2000A
Opening control current (A)
(STC coil) (Note 6) Fixed (L) 120 (600~1250A) 5a5b
Withdrawable (C, D, G) 140 (1600, 2000A)
External aux. contacts (Note 7,8) 190 (2500~3150A) Fixed (L)
55 (600/630A) Withdrawable (C, D, G)
Operating counter (Mechanically) 62 (1200/1250A)
140 (1600, 2000A) 55 (600/630A)
Mounting configuration 62 (1200/1250A)
140 (1600, 2000A)
Mass (kg) (Note 9)
Notes: 1. Different VSTs are installed on standard type and low surge type VCBs.
2. For 600/630A and 1200/1250A 6-VPR-25C, “(S)” is added to the end of the type name.
3. For 600/630A and 1200/1250A 10-VPR-25C, “(F)” is added to the end of the type name.
4. For 4000A 10-VPR-40C, “(D)” is added to the end of the type name.
5. IEC : International standards, IEC 60056 (1987, Insulation level series ) and IEC 62271-100 (2003, Insulation level series )
JEC : Japanese standard, JEC-2300 (1998)
6. Closing operation, control and tripping control currents indicated are based on DC100V.
7. Additional auxiliary contacts cannot be added.
8. For 600/630A and 1200/1250A of 3-VPR-20C, 3-VPR-25C, 6-VPR-20C, and 6-VPR-25C, when the control voltage is AC•DC200/220V 4a4b contacts only are
available.
9. The mass of the circuit breaker only is indicated.
10. Consult your dealer for information on the applicability of other foreign standards, including U.S. standard ANSI and Chinese standards GB, DL.
11. Refer to the catalog (A-AL1-5-C1283-B) for VCBs of the rated short-circuit breaking current 50kA or the rated voltage 36kV.
12. The application standard of 20-VPR-25C(2000A) is JEC-2300/IEC 60056.
13. The number of auxiliary contacts shows the maximum when the secondary connector code is B.
5
6-VPR-32C 6-VPR-40C 10-VPR-25C(F) 10-VPR-32C 10-VPR-40C 10-VPR- 20-VPR-16D 20-VPR-25D
20-VPR-25C
(Note 3) (Note 4, 13) 50C(D)
(Note 12)
10-VPR-25C (Note 13)
6-VPR-32CG 6-VPR-40CG – – – –– –
Motor-spring charged mechanism
JEC-2300/IEC 62271-100 JEC-2300/IEC 60056 JEC-2300/IEC 62271-100 (Note 12)
7.2 12 24
600 / 630 600 / 630 600 / 630 600 / 630 600 / 630 4000 600 / 630 600 / 630
1200 / 1250 1200 / 1250 1200 / 1250 1200 / 1250 1200 / 1250 1200 / 1250 1200 / 1250
1600 1600 1600 1600 1600 2500
2000 2000 2000 2000 2000
2500 2500 2500 2500 2500 2000
3000 / 3150 3000 / 3150 3000 / 3150 3000 / 3150 3000 / 3150
50 / 60
31.5 40 25 31.5 40 40 40/50 16 25
63 80 100 100 104/130 40 63
80 100 25 16 25
31.5 40 40 40/50
31.5 40
0.03
22 28 3 3
75 28 (42) 50
60 125
75
O-0.3sec.-CO-1min.-CO (R)
O-1min.-CO-3min.-CO (A)
CO-15sec.-CO (B)
0.1 1.2 (6sec.) 6 (6sec.) 1.5 (10sec.) 1 (6sec.) 1 (6sec.) ... 600~1250A
1.2 (6sec.) 5 3.2 3 1.2 (6sec.) ... 2000A
4 1 (5sec.) ...... 2500A
4
Voltage-tripping device (STC) 4 3 ...... 600~1250A
3.4 ... 2000A
4 Fixed (L) ......................... 600~2000A 4.5 ... 2500A
Withdrawable (C, D, G) ... 600~3150A
Standard equipment 5 3.2 3 ...... 600~1250A
Fixed (L) ....................... 600~2000A 120 (600~1250A) 6a6b 10a10b
Withdrawable (C, D, G) ... 600~3150A 140 (1600, 2000A) 3 3.4 ... 2000A
120 (600~1250A) 190 (2500~3150A)
140 (1600, 2000A) 4 ...... 2500A
190 (2500~3150A)
5a5b
Withdrawable Withdrawable (C, D)
(C, D, G)
510 440 94 (600/630A) 95 (600/630A)
107 (1200/1250A) 110 (1200/1250A)
135 (2000A)
330 (2500A)
6
OUTLINES AND DIMENSIONS (Dimension in mm)
■ Frame size L
■ 600/630A : 3/6-VPR-20C/25C (Circuit breaker)
3/6-VPR-20C L,3-VPR-25C L,6-VPR-25C(S)L (Fixed: Type L)
2- φ14 Hole
25
50
453 Vacuum interrupter (50) 40
(Detail of main-circuit terminal)
Manual charging 34 396.5
handle aperture Upper terminal
140 140 Front plate
Manual close
button Operation counter Handle 6
190
Manual trip Closing spring
button charge indicator
478
ON-OFF 287 110 Lower terminal
indicator
253
Secondary
437 junction 130 76 Wheel
30
478 4- φ14 Hole(Installing hole) 222
(Installing hole pitch) (Installing hole pitch) 286.5 φ8.5 Hole(Earth terminal hole)
509 Fig. 1
3/6-VPR-20C ,3-VPR-25C ,6-VPR-25C(S) (Withdrawable: Type C, D, and G)
Manual charging Vacuum interrupter
handle aperture
453 Operation counter 34 392.5
Manual close
button 140 140 Closing spring Front plate Upper terminal
(with the cover) charge indicator (t=1.6)
Lower terminal
Manual trip Secondary Handle
button junction Shutter guide
φ60 (On shutter-equipped
ON-OFF 478
indicator (D,G)type)
287 110 Wheel
Draw-out handle 253 190
aper ture
10 67 10 222 30
Interlock lever 22 437 218.5 286.5
Earth terminal
Interlock pin
Fig. 2
7
■ 600/630A : 3/6-VPR-20C/25C (Mounting frame)
(Class CW: Type C) 40 20
2- φ14Holes100
(Detail of main-circuit terminal)6 25
550 Test and disconnected Connected 256 190 50
position position 600
524 2-M8 screw
Protect plate 450 (For partition)
400 Provided for 170 (P=400)
switchgear Shutter
(2-M8 screw for partition) 150 1 Primary terminal
Minimum distance 25
140 140 from the grounding
part
100 400 600 Position switch
(2✕2-M8 screw for partition) 481 (Option)
230
68
Bolt for anti dropping 280 4- φ14Holes 144 310 2✕2-M8 screw
(M8 bolt) 500 (For M12 bolt) 640 (For partition)
(P=280✕310) 96 (P=524✕400)
M8 screw
Fig. 3 (For earth terminal)
(Class PW: Type D) 40 20
Test and disconnected Connected 2-φ14Holes100 3
position position (Detail of main-circuit terminal)94 6
550 Protect plate 450 256 190 25
Provided for 50
524 switchgear 170 Shutter 2-M8 screw
600 (For partition)
400 Minimum distance 150 (P=400)
from the grounding 25
(2-M8 screw for partition) part Barrier(Insulator)
140 140
1 Primary terminal
100 400 600 Position switch
(2✕2-M8 screw for partition) 481 (Option)
230
68
Bolt for anti dropping 280 4-φ14Holes 144 310 2✕2-M8 screw
(M8 bolt) 500 (For M12 bolt) 640 (For partition)
96
(P=280✕310) M8 screw (P=524✕400)
(For earth terminal)
(Class MW: Type G) 40 20
Bolt for anti-dropping 2- φ14Holes 25 238 226 50
(M8 bolt) (Detail of main-circuit terminal)
550 Test and disconnected Connected 2-M8 screw
position position (For partition)
524 170 (P=400)
400 Protect plate 450
Provided for 150 Barrier(Metal)
(2-M8 screw for partition) switchgear Shutter 25
Direction of
140 140 Minimum distance connecting terminal
from the grounding
Part 23
13
100 400 100 2.5 112 Primary terminal
(2✕2-M8 screw for partition) 6
600 Position switch
481 (Option)
230
68 Direction of
connecting terminal
280 4- φ14Holes 144 310
500 (For M12 bolt) 640 2-M8 screw
(P=280✕310) 96 (For partition)
M8 screw (P=140)
Fig. 4 (For earth terminal)
2✕2-M8 screw
(For partition)
(P=524✕400)
8
OUTLINES AND DIMENSIONS (Dimension in mm)
■ Frame size L
■ 1200/1250A : 3/6-VPR-20C/25C (Circuit breaker)
3/6-VPR-20C L,3-VPR-25C L,6-VPR-25C(S)L (Fixed: Type L)
2- φ14 Hole
32.5
65
(50) 40
453 Vacuum interrupter (Detail of main-circuit terminal)
Manual charging 155 155 Front plate 34 396.5 Upper terminal
handle aperture
Operation counter Handle 12
Manual close 190
button Closing spring
charge indicator
Manual trip
button 478 Lower terminal
287 110
ON-OFF Secondary 250
indicator junction
437 4- φ14 Hole(Installing hole) 130 76 Wheel
(Installing hole pitch) 30
478 222
(Installing hole pitch) Fig. 5 286.5 φ8.5 Hole(Earth terminal hole)
509
3/6-VPR-20C ,3-VPR-25C ,6-VPR-25C(S) (Withdrawable: Type C, D, and G)
Manual charging 453 Operation counter Vacuum interrupter
handle aperture
Closing spring 34 392.5
Manual close charge indicator Front plate
button 155 155 Upper terminal
(with the cover) Secondary (t=1.6)
junction
Manual trip Handle
button
φ60 Lower terminal
ON-OFF 478
indicator Shutter guide
287 110 (On shutter-equipped
Draw-out handle 250 190
aper ture (D,G)type)
10 10 Wheel
Interlock lever
22 67 218.5 222 30
Earth terminal 437 286.5
Interlock pin
Fig. 6
9
■ 1200/1250A : 3/6-VPR-20C/25C (Mounting frame)
(Class CW: Type C)
40 25
CL
4- φ14Holes
(Detail of main-circuit terminal)
625 100
599 Test and disconnected Connected 12 40 2-M8 screw
position position (For partition)
569 170 253 190 75(P=400)
Protect plate 450 600
400 Provided for 150
switchgear Minimum distance 25
(2-M8 screw for partition) from the grounding
part
165 165
1 Primary terminal
100 400 600 Position switch
(2✕2-M8 screw for partition) 481 (Option)
230
68
Bolt for anti dropping 280 4- φ14Holes 144 310 2✕2-M8 screw
(M8 bolt) 500 (For M12 bolt) 640 (For partition)
(P=280✕310) 101 (P=599✕400)
M8 screw
(For earth terminal)
Fig. 7
(Class PW: Type D) 40 25
CL
4- φ14Holes
(Detail of main-circuit terminal)
600 40
625 Test and disconnected Connected 75
599 position position
569 Protect plate 170 450 2-M8 screw
Provided for (For partition)
400 switchgear Shutter 150 (P=400)
25 Barrier(Insulator)
(2-M8 screw for partition) Minimum distance
from the grounding 1 Primary terminal
165 165 part
100 400 600 Position switch 100 3
(2✕2-M8 screw for partition) 481 (Option) 97 12
230
68 253 190
Bolt for anti dropping 280 4- φ14Holes 144 310 2✕2-M8 screw
(M8 bolt) 500 (For M12 bolt) 640 (For partition)
(P=280✕310) 101 (P=599✕400)
(Class MW: Type G) M8 screw
(For earth terminal)
Bolt for anti-dropping
(M8 bolt) 40 25
75
CL
4- φ14Holes 40
(Detail of main-circuit terminal)
625 2-M8 screw
(For partition)
599 Test and disconnected Connected (P=400)
position position
569 170 Barrier(Metal)
Protect plate 450
400 Provided for 150 Direction of
switchgear Shutter 25 connecting terminal
(2-M8 screw for partition)
Minimum distance
165 165 from the grounding
part
23
13
100 400 100 121 12 Primary terminal
(2✕2-M8 screw for partition) 2.5
600 Position switch 229 238
481 (Option)
230
68 Direction of
connecting terminal
280 4- φ14Holes 144 310
500 (For M12 bolt) 640 2-M8 screw
(P=280✕310) 114 (For partition)
M8 screw (P=165)
(For earth terminal)
2✕2-M8 screw
(For partition)
(P=599✕400)
Fig. 8
10
OUTLINES AND DIMENSIONS (Dimension in mm)
■ Frame size M (Circuit breaker)
■ 600/630A and 1200/1250A : 10-VPR-25C(F)
10-VPR-25C(F)-L (Fixed: Type L)
Rating plate 2- φ14 Holes 6540 20
142.5
Manual charging 550 Detail of main-circuit terminal12 12 65
handle aperture 320 320
200 200 34 431.5 90 692.5Upper
Manual close terminal
button
Front plate Vacuum interrupter
Manual trip
button Operation Lower
counter terminal
ON-OFF
indicator Closing spring
charge indicator
693 693 Secondary
φ60 junction
φ60 Handle
Wheels
505 210 93
534 397
4- φ14 564 123
Mtg holes
φ8.5 Hole
10-VPR-25C(F)- for earth terminal
Rating plate Fig. 9
Manual charging (Withdrawable: Type C, D, and G)
handle aperture
Manual close 550 34 573.5
button
(with the cover) 185 185 Upper
Manual trip terminal
button Front plate
ON-OFF Vacuum
indicator interrupter
Operation 320 Lower
counter 692.5 terminal
Closing spring
charge indicator
Secondary
junction
Handle
Interlock 320
lever
142.5
Wheels 505 26 397 175
Earth contact
Draw-out Shutter guide
handle Fig. 10
Interlock pin aper ture
11
■ 600/630A and 1200/1250A : 10-VPR-25C(F) (Mounting frame)
(Class CW: Type C) Air clearance for ventilation 2-M8 tap screw for partition 300
(more than 500cm2) (pitch=300) 655
Par tition
(Out of supply) 300 20 10 Par tition 2x2-M8 tap screw for partition 300
2x2-12 mm dia. holes for mounting (Out of supply) (pitch=320x655)
(pitch=300x450) 320 190
410 Earthing terminal 2-M8 tap screw for partition 200.5 250 250
4-12 mm dia. holes for mounting A (10 mm dia. holes) (pitch=300) 33 37
(pitch=630,450)
40.5 484
Dim.B doesn't exeed 31mm 32
7.5 Earthing bar(Cu;6x32)
See-A 12.5
2-entrance holes
390 for control wire
80
50 340 100 325.5
450 40 Par tition Rear view 18✕38 hole for earthing bar
630 2-10 mm dia. holes (Out of supply)
4-M12 tap screw
696 Test and disconnected position Conductor (depth=22)
Connected position
B Main-circuit terminal
17.5
10
34 195
1018.5 20 Par tition 275.5 80 260 80 15 45 20 20 45 15 M12 bolt
C (Out of supply) Torque=
10 35N • m
698.5 35 210 210
126 126 Length=
18~20
DE
Shown side Dim. C Dim. D Dim. E 152 30 30 30
Other side 260 214 68 50 80 130 80 130
270 222 67 80
7 710 Detail of main-circuit terminal
Fig. 11
(Class PW and MW: Type D and G) 2-M8 tap screw for partition 300
(pitch=300)
Air clearance for ventilation
(more than 500cm2)
Par tition 300 20 10 Par tition
(Out of supply) (Out of supply)
320 190 655
2x2-12 mm dia. holes for mounting 40.5 410 Earthing terminal 2x2-M8 tap screw for partition 300 200.5 250 250
(pitch=300x450) 32 A (10 mm dia. holes) (pitch=320x655) 33 37
7.5
4-12 mm dia. holes for mounting 12.5 Earthing bar(Cu;6x32) 2-M8 tap screw for partition 484
(pitch=630,450) (pitch=300)
390 2-entrance holes
80 for control wire
100
50 340 325.5
40
450 2-10 mm dia. holes Par tition Rear view 18✕38 hole for earthing bar
630 Test and disconnected position (Out of supply)
Connected position 4-M12 tap screw
696 Conductor (depth=22)
Dim.B doesn't exeed 31mm
See-A M12 bolt
B Main-circuit terminal Torque=
17.5 35N • m
10
34 Shutter device
195
1018.5 20 Par tition 275.5 80 260 80 15 45 20 20 45 15 Length=
(Out of supply) 18~20
10
35 210 210
126 126
C DE
698.5
Shown side Dim. C Dim. D Dim. E 152 30 30 30
Other side 260 214 68 50 80 130 80 130 80
270 222 67
7 710 Detail of main-circuit terminal
7
Fig. 12
12
OUTLINES AND DIMENSIONS (Dimension in mm)
■ Frame size M
■ 600/630A, 1200/1250A : 3/6/10-VPR-32C/40C (Circuit breaker)
Min.25 4025
3/6/10-VPR-32C/40C L (Fixed: Type L) 65
142.5
Rating plate 4- φ14 Holes
12 12 40
Manual charging Detail of main-circuit terminal 320 320 75
handle aperture
550 692.5Upper
terminal
180 180 34 431.5 125
Front plate
Manual close Operation Vacuum interrupter
button counter
Lower
Manual trip Closing spring terminal
button charge indicator
ON-OFF Secondary
indicator junction
693 Handle
693
Wheels
505 φ60 210 93
534 φ60 397
4- φ14 564 158
Mtg holes
550 φ8.5 Hole
Type of 3/6-VPR-32C/40C for earth terminal
505
Rating plate 534 Min.25 4025 210
564 40
Manual charging 75
handle aperture
4- φ14 Holes
Manual close Detail of main-circuit terminal
button
34 431.5 125 Upper
Manual trip Front plate terminal
button
Operation Vacuum interrupter65
ON-OFF counter 142.5
indicator Closing spring Lower
charge indicator terminal12 12
Wheels 320 320
4- φ14 Secondary
Mtg holes junction 692.5
Type of 10-VPR-32C/40C Handle
210 93
397
158
Fig. 13
φ8.5 Hole
for earth terminal
3/6/10-VPR-32C/40C (Withdrawable: Type C, D, and G)
550
Rating plate 180 180 Front plate 34 579 Upper
terminal
Manual charging
handle aperture Operation Vacuum interrupter
Manual close counter
button Closing spring 320 Lower
(with the cover) charge indicator 692.5 terminal
Manual trip 693 Secondary
button junction
320
ON-OFF Handle
indicator
Interlock
Draw-out lever
handle
aper ture 142.5
φ60
505 26 397 179.5
Earth contact Shutter guide
Wheels Interlock pin
Fig. 14
13
■ 600/630A, 1200/1250A : 3/6/10-VPR-32C/40C (Mounting frame)
(Class CW: Type C) Air clearance for ventilation 2-M8 tap screw for partition 300
(more than 500cm2) (pitch=300) 655
Par tition 300
(Out of supply) 300 20 10 Par tition 2✕2-M8 tap screw for partition
2✕2-12 mm dia. holes for mounting (Out of supply) (pitch=320x655)
(pitch=300✕450) 320 190
40.5 410 Earthing terminal 2-M8 tap screw for partition 200.5 250 250
4-12 mm dia. holes for mounting 32 A (10 mm dia. holes) (pitch=300) 33 37
(pitch=630,450) 7.5
12.5 Earthing bar(Cu;6x32) 484
Dim.B doesn't exeed 31mm
390 2-entrance holes
See-A 80 for control wire
100
50 340 325.5
40
450 2-10 mm dia. holes Par tition Rear view 18✕38 hole for earthing bar
630 Test and disconnected position (Out of supply)
Connected position 4-M12 tap screw
696 Conductor (depth=22)
B Main-circuit terminal M12 bolt
17.5 Torque=
10 35N • m
34 195
DE 20 Par tition 275.5 80 260 80 15 45 20 20 45 15
(Out of supply)
1018.5 10 Length=
35 210 210 18~20
126 126
C
Shown side Dim. C Dim. D Dim. E 698.5 152 30 30 30
Other side 260 214 68 50 80 130 80 130 80
270 222 67
7 710 Detail of main-circuit terminal
Fig. 15
(Class PW and MW: Type D and G) 2-M8 tap screw for partition 300
(pitch=300)
Air clearance for ventilation
(more than 500cm2)
Par tition 300 20 10 Par tition
(Out of supply) (Out of supply)
320 190 655
2✕2-12 mm dia. holes for mounting 410 Earthing terminal 2✕2-M8 tap screw for partition 300 200.5 250 250
(pitch=300✕450) A (10 mm dia. holes) (pitch=320✕655) 33 37
4-12 mm dia. holes for mounting 40.5 2-M8 tap screw for partition 484
(pitch=630,450) 32 (pitch=300)
7.5 Earthing bar(Cu;6✕32)
12.5
2-entrance holes
390 for control wire
80
50 340 100 325.5
40
450 2-10 mm dia. holes Par tition Rear view 18✕38 hole for earthing bar
630 Test and disconnected position (Out of supply)
Connected position 4-M12 tap screw
696 Conductor (depth=22)
Dim.B doesn't exeed 31mm
See-A M12 bolt
B Main-circuit terminal Torque=
17.5 35N • m
Shutter device 10
34 195
1018.5 C 20 Par tition 275.5 80 260 80 15 45 20 20 45 15 Length=
698.5 (Out of supply) 18~20
10
35 210 210
126 126
DE
Shown side Dim. C Dim. D Dim. E 152 30 30 30
Other side 260 214 68 50 80 130 80 130 80
270 222 67
7 710 Detail of main-circuit terminal
7
Fig. 16
14
OUTLINES AND DIMENSIONS (Dimension in mm)
■ Frame size M
■ 1600A, 2000A : 3/6-VPR-20C, 3/6/10-VPR-25C/32C/40C (Circuit breaker)
3/6-VPR-20C-L,3/610-VPR-25C/32C/40C-L 25(minimum) 40 25
(Fixed: Type L) 20 20 40 320 320 75
692.5
Rating plate 4-14 mm holes
Detail of main-circuit terminal
Manual charging 550
handle aperture
180 180 34 431.5 125 Upper
terminal
Front plate
Manual close Operation Vacuum interrupter
button counter
Lower
Manual trip Closing spring terminal
button charge indicator
ON-OFF Secondary
indicator junction
693 693 Handle Earthing terminal
(8.5 mm dia. hole of center)
Wheels
3/6-VPR-20C, 4-14 mm dia. 505 φ60 φ60 210 93 65
holes for mounting 534 397 210
(P=534X210) 564 40 142.5158
3/6-VPR-25C/32C/40C
Min.25 4025
75
6✕4- φ14 holes
Rating plate Detail of main-circuit terminal
Manual charging 550
handle aperture
180 180 34 431.5 125 Upper
Manual close terminal
button Front plate
Manual trip Operation Vacuum interrupter 20 20 320 320
button counter 692.5
Lower
ON-OFF Closing spring terminal
indicator charge indicator
φ8.5 hole
Secondary for earth terminal
junction
Handle
Wheels
65
142.5
505 210 93
534 397
10-VPR-25C/32C/40C 4- φ14 564 158
Mtg holes
Fig. 17
3/6-VPR-20C- ,3/6/10-VPR-25C/32C/40C- (Withdrawable: Type C, D, and G)
550
Rating plate 180 180 Front plate 34 579 Upper
terminal
Manual charging Vacuum 397 320
handle aperture interrupter Shutter guide Lower692.5
Operation terminal
Manual close counter
button Closing spring 179.5
(with the cover) charge indicator
Manual trip Secondary
button junction
693 Handle
ON-OFF Interlock 320
indicator lever
Draw-out φ60 142.5
handle aperture
505 26
Wheels Earth contact
Interlock pin
Fig. 18
15
■ 1600A, 2000A : 3/6-VPR-20C, 3/6/10-VPR-25C/32C/40C (Mounting frame)
(Class CW: Type C) Air clearance for ventilation 2-M8 tap screw for partition 300
(more than 500cm2) (pitch=300) 655
Par tition 300
(Out of supply) 300 20 10 Par tition 2✕2-M8 tap screw for partition
2✕2-12 mm dia. holes for mounting (Out of supply) (pitch=320x655)
(pitch=300✕450) 320 190
40.5 410 Earthing terminal 2-M8 tap screw for partition 200.5 250 250
4-12 mm dia. holes for mounting 32 A (10 mm dia. holes) (pitch=300) 33 37
(pitch=630,450) 7.5
12.5 Earthing bar(Cu;6x32) 484
Dim.B doesn't exeed 31mm
390 2-entrance holes
See-A 80 for control wire
100
50 340 325.5
40
450 2-10 mm dia. holes Par tition Rear view 18✕38 hole for earthing bar
630 Test and disconnected position (Out of supply)
Connected position 4-M12 tap screw
696 Conductor (depth=22)
B Main-circuit terminal M12 bolt
17.5 Torque=
10 35N • m
34 195
DE 20 Par tition 275.5 80 260 80 15 45 20 20 45 15
(Out of supply)
1018.5 10 Length=
35 210 210 18~20
126 126
C
Shown side Dim. C Dim. D Dim. E 698.5 152 30 30 30
Other side 260 214 68 50 80 130 80 130 80
270 222 67
7 710 Detail of main-circuit terminal
Fig. 19
(Class PW and MW: Type D and G)
Air clearance for ventilation 2-M8 tap screw for partition 300
(more than 500cm2) (pitch=300) 655
300
Par tition 300 20 10 Par tition 2✕2-M8 tap screw for partition
(Out of supply) (Out of supply) (pitch=320✕655)
2✕2-12 mm dia. holes for mounting 325.5 320 190
(pitch=300✕450) 410 Earthing terminal 2-M8 tap screw for partition 200.5 250 250
A (10 mm dia. holes) (pitch=300) 33 37
4-12 mm dia. holes for mounting
(pitch=630,450) 40.5 484
32
Dim.B doesn't exeed 31mm 7.5 Earthing bar(Cu;6x32)
12.5
See-A 2-entrance holes
390 for control wire
80
50 340 100
40
450 2-10 mm dia. holes Par tition Rear view 18✕38 hole for earthing bar
630 (Out of supply)
Test and disconnected position 4-M12 tap screw
696 Connected position Conductor (depth=22)
B Main-circuit terminal M12 bolt
17.5 Torque=
10 35N • m
34 195 Shutter device
1018.5 20 Par tition 275.5 80 260 80 15 45 20 20 45 15 Length=
10 (Out of supply) 18~20
35
C DE 210 210
698.5 152 126 126
Shown side Dim. C Dim. D Dim. E 50 30 30 30
Other side 260 214 68 80 130 80 130 80
270 222 67
7 710 Detail of main-circuit terminal
Fig. 20
16
OUTLINES AND DIMENSIONS (Dimension in mm)
■ Frame size M
■ 2500A, 3000/3150A : 10-VPR-25C, 3/6/10-VPR-32C/40C (Circuit breaker)
10-VPR-25C- ,3/6/10-VPR-32C/40C- (Withdrawable: Type C, D, and G)
550 34 579
Rating plate 200 200 Insulating
barrier
Manual charging Front plate Upper terminal
handle aperture
Manual close Vacuum Lower
button interrupter terminal
(with the cover)
Operation
Manual trip counter
button Closing spring
charge indicator
ON-OFF 783
indicator φ60Secondary
junction
Draw-out 142.5
handle 320 320Handle
aper ture 692.5 90.5
Interlock
Wheels lever
505 26 397 179.5
Earth contact Shutter guide
Interlock pin
Fig. 21
17
■ 2500A, 3000/3150A : 10-VPR-25C, 3/6/10-VPR-32C/40C (Mounting frame)
(Class CW: Type C) Air clearance for ventilation 2-M8 tap screw for partition 300
(more than 500cm2) (pitch=300) 755
Par tition 300
(Out of supply) 10 Par tition 2✕2-M8 tap screw for partition
2✕2-12 mm dia. holes for mounting (Out of supply) (pitch=320✕755)
(pitch=300✕450) 300 20 320 190
410 Earthing terminal 2-M8 tap screw for partition 200.5 250 250
4-12 mm dia. holes for mounting (10 mm dia. holes) (pitch=300) 33 37
(pitch=730,450) 40.5
32 484
Dim.B doesn't exeed 31mm 7.5 Earthing bar(Cu;6x32)
12.5
See-A A 2-Entrance holes
390 for control wire
50 340 80 325.5
C 100
450 40 Par tition Rear view 18✕38 hole for earthing bar
730 2-10 mm dia. holes788.5 (Out of supply)
Test and disconnected position
Connected position
B Conductor 4-M16 tap screw M16 bolt
17.5 Main-circuit terminal (depth=30) Torque=
78N • m
34 195 10
DE 20 Par tition 265.5 90 260 90 20 50 20 20 50 20 Length=
10 (Out of supply) 24~28
1018.5
35
102
160
126.5 126.5
50
Shown side Dim. C Dim. D Dim. E 40 45 40 45 40
Other side 260 214 68 100 127.5 100 127.5 100
270 222 67
796 7 710 Detail of main-circuit terminal
Fig. 22
(Class PW and MW: Type D and G)
Air clearance for ventilation 2-M8 tap screw for partition 300
(more than 500cm2) (pitch=300) 755
Par tition 10 Par tition 2✕2-M8 tap screw for partition 300
(Out of supply) (Out of supply) (pitch=320✕755)
300 20 320 190
2✕2-12 mm dia. holes for mounting 410 Earthing terminal 2-M8 tap screw for partition 200.5 250 250
(pitch=300✕450) A (10 mm dia. holes) (pitch=300) 33 37
4-12 mm dia. holes for mounting 7.540.5 Earthing bar(Cu;6✕32) 484
(pitch=730,450) 12.532
390 2-Entrance holes
for control wire
50 340 80 325.5
C
450 40 Par tition Rear view 18✕38 hole for earthing bar
730 2-10 mm dia. holes100 (Out of supply)
Dim.B doesn't exeed 31mm 788.5
See-A 796 Test and disconnected position
Connected position
B 34 195 Conductor 4-M16 tap screw M16 bolt
17.5 Main-circuit terminal (depth=30) Torque=
78N • m
221.3 10
D Shutter device 20 50 20 20 50 20
E
1018.5 20 Par tition 265.5 90 260 90 Length=
10 (Out of supply) 24~28
35 102
160 126.5 126.5
Dim. C Dim. D Dim. E 50 45 45
260 214 68
Shown side 270 222 67 40 40 40
Other side
100 127.5 100 127.5 100
7 710 Detail of main-circuit terminal
7
Fig. 23
18
OUTLINES AND DIMENSIONS (Dimension in mm)
■ Frame size R
■ 4000A : 10-VPR-40C(D)
Circuit breaker (Withdrawable: Type C, D, and G)
Manual close button 840 Face plate
Rating plate
Manual trip button 275 275 825 Upper terminal
Handle
Closing spring Vacuum
charge indicator Operation interrupter
ON-OFF indicator counter
Interlock lever
Secondary
junction
φ80
Manual charging 948 Lower terminal
handle aperture
406 400
Wheels 944
Interlock pin
813 Earth contact 619
Draw-out handle aperture Shutter guide
Mounting frame (Class CW, PW, and MW: Type C, D, and G)
(Class CW: Shutter device is not equipped.)
Earthing terminal (10mm dia. holes) Partition(Out of supply) 2-M8 tap screw for partition 950
Partition(Out of supply) (pitch=500)
315 32 4-M12 tap screw 500
2✕2-M8 tap screw for partition
1000 55.5 (pitch=400✕950) 430 430
45 50
Conductor
50 400 400 50 411.5 400 398.5 325 328
150 43 32
(Detail of Primary Terminal)
249 368
3-M8 tap screw for partition
(pitch=430)
Connected position
550 Test and
disconnected
6-14mm dia. holes for mounting position 279 714 REAR VIEW
275
275 100
Shutter device (25) Conductor
Main-circuit terminal
15
1250 1050 40 25 (25) 20.5 6
954.5 70 70
150
411.5 400
3 1000 3 1000 45 161 1250
Fig. 24
19
■ Frame size R
■ 4000A : 10-VPR-50C(D)
Circuit breaker (Withdrawable: Type C, D, and G)
Rating plate 840
275 275 Barrier Upper terminal
Manual charging Operation Face plate Vacuum
handle aperture counter Handle interrupter
Manual close button 406 400
Closing spring 918
Manual trip button charge indicator
ON-OFF indicator Secondary
junction
Interlock lever φ80
Wheels 161
245
830 470 Lower terminal
774 Shutter guide
Mounting frame (Class CW, PW, and MW: Type C, D, and G)
(Class CW: Shutter device is not equipped.)
Earthing terminal (10 mm dia. holes) 155 2-M8 top screw for partition (pitch =500) 950
32 500
(1000) 55.5 4-M12 top screw, Conductor
30 depth
50 400 400 45 50 (411.5) (400) 398.6
50
150
(Detail of Primary Terminal)
550 3-M8 top screw for partition (pitch =430)
6-14 mm dia. holes for mouting REAR VIEW
Test and CONNECTED position Conductor
disconnected Main-circuit terminal
position 279 713.7
275 275 100
shutter device (25)
15
25 12.4 6
617 70 70
1050 954.4 40 (25)
200 411.5 400
1250
3 1000 3 1000 161
45
Fig. 25
20
OUTLINES AND DIMENSIONS (Dimension in mm)
■ Frame size H
■ 600/630A, 1200/1250A : 20-VPR-16D/25D (Circuit breaker)
20-VPR-16D/25D- (Withdrawable: Type C, D)
650 607
Manual close 210 210 Primary
button junctions
(with the cover) Face plate
Vacuum
Manual charging 766 Manual trip 315 interrupter
handle aperture φ48 button 758
Primary
Closing spring Handle Interlock junctions
charge indicator lever
Secondary
ON-OFF junction 350
indicator Raiting
plate
Wheels
22 349
617 607
Interlock pin Draw-out Shutter guide
handle aperture
Fig. 26
21
■ 600/630A, 1200/1250A : 20-VPR-16D/25D (Mounting frame)
(Class CW and PW: Type C and D)
(Class CW: Shutter device is not equipped.)
M8 tap screw for earthing cable 2-M12 tap screw
1.5 (depth=18)
M8 tap screw Par tition
(Out of supply)
Conductor
80 275 275 Detail of point A Detail of point B356.5 315 60
514 Detail of main-circuit terminal
540 2✕3-12mm dia. holes for mounting 73 710
759 30
Test and disconnected
position 942
Connected 2-M8 tap screw 210 210
position for mounting
A
35 260 Shutter device Par tition
(Out of supply)
960 B
2-M8 tap screw
for partition
(pitch=600)
90
763 223 25mm dia. 300
hole for
1055 Fig. 27 earthing cable 600
22
OUTLINES AND DIMENSIONS (Dimension in mm)
■ Frame size H
■ 1600/2000A : 20-VPR-25C (Circuit breaker)
20-VPR-25C- (Withdrawable: Type C, D)
Rating plate 550 34 552
Manual charging 185 185 Front plate
handle aperture
Manual close Vacuum Upper terminal
button interrupter
(with the cover) Lower
Operation counter terminal
Manual trip
button Closing spring
charge indicator
ON-OFF
Indicator Secondary
junction
803.5
φ60Handle
139Interlock
420 298lever
802
Wheels 570.5 390
Earth contact Earth contact 552
Draw-out Shutter guide
Interlock pin handle aperture
Fig. 28
23
■ 1600/2000A : 20-VPR-25C (Mounting frame)
(Class CW: Type C)
50 550 50
Earthing terminal(#38-8 60 225 60 225 60
pressure terminal supplied)
Conductor 4-M8 BOLT-NUT
2✕3-12mm dia. (Out of supply) (Out of supply)
holes for mounting
32 160 75 160 Detail of point C Detail of point D
31 70.5 84 12 Par tition 1.5
70 315 315 72 (Out of supply) M8 tap screw
510
672 20φ43 φ43 φ43 Detail of point E
711.2 70
16
23
47
23
70
151
2-12 mm dia. Detail of point B
holes for mounting
Section A-A 6✕3-M12
tap screws
2-M8 tap screws 633
for mounting 285
170 151 285
E
Test and disconnected Connected Main-circuit
position position terminal
37.4 290 A A
Par tition 332 28 28 22 28 28 28
(Out of supply) 28 28 28 550 28 2828
993.5
1010 1010 B 28 D
84 C
110 408
572.3
706.6 767.5 255 25mm dia.
holes for earthing cable
(Class PW: Type D)
Fig. 29
31
60 225 60 225 60 Conductor 50 550 50
510 (Out of supply)
672
711.2 Earthing terminal(#38-8 160 75 160 4-M8 BOLT-NUT
pressure terminal supplied) 32 (Out of supply)
70.5 20 Detail of point C Detail of point D
70 315 315 70
2✕3-12mm dia. 84 12 Partition 1.5
holes for mounting 23 72 (Out of supply) M8 tap screw
47
23
70
151
φ43 φ43 φ43
Detail of point E
2-12 mm dia. 16
holes for mounting
Section A-A
Detail of point B
Test and disconnected 2-M8 tap screws 633 6✕3-M12
position for mounting tap screws
170 151 285
Connected E 285
position
Main-circuit
37.4 290 Shutter device terminal
A
A
Partition 332 28 28 22 28 28 28
(Out of supply) 28 28 28 28
550 993.5
B
572.3 D
84 1056 C 28 28 28
408
110
706.6 767.5 255 25mm dia.holes
for earthing cable
Fig. 30
24
OUTLINES AND DIMENSIONS (Dimension in mm)
■ Frame size R
■ 2500A : 20-VPR-25D (Circuit breaker)
20-VPR-25D- (Withdrawable: Type C, D)
850
275 275 34 915
Face plate Upper
terminal
Manual charging Rating plate
handle aperture Vacuum
Manual close button Handle interrupter
Manual trip button
ON-OFF indicator Operation 323 Lower
Interlock lever counter 900 terminal
Wheels Closing spring
charge indicator
Interlock pin
Draw-out handle 905
aper ture Secondary
junction
459
Shutter guide
764 φ80 566
Earth contact
Fig. 31
25
■ 2500A : 20-VPR-25D (Mounting frame)
(Class CW and PW: Type C and D)
(Class CW: Shutter device is not equipped.)
Earthing terminal 2-14mm dia. holes 961
(#38-8 pressure terminal supplied) 900
50 36
Partition (Out of supply)
143.5
40 25 43
298.5 36 36
90 275 455 ( Detail of Primary Terminal ) 953.5
2-M8 tap screw for partition 1069
25mm dia. REAR VIEW
hole for earthing cable
203.5 Test and disconnected 1.5 M8 tap screw
position Partition (Out of supply)
687 Connected position
6-12mm dia. holes for mounting 280 749.5
275 275 103 Detail of point A
Shutter device A 15
Partition (Out of supply)
464.5 323
B 629
1085
1085 910.5
130
57
Detail of point B
1112 Main-circuit terminal
1532
1000
Fig. 32
26
CONNECTION DIAGRAM
■ 3/6-VPR-20C/25C (600/630A, 1200/1250A)
■ Withdrawable: Standard connection diagram (AC•DC100~125V) (Note: There is no LS0 in a fixed type.)
Command Auxiliary switch 5a5b
9 11 13 15 17 19 21 23 25
13 5 7
Inside the control board Used for the
internal circuit
J5 J5
J3 J4
52a
LS2 52X
J1
AC ZNR1 J3 52Y ZNR3 D6 52X LS1 52a 8 10 12 14 16 18 20 22 24 26
or D1 D2 J2 D5 J4 CC STC
ZNR2 Command The voltage trip coil is for DC only.
DC D3 D4 52Y M R2 52b CTD Conversion to DC must be performed with
LS0 the capacitor trip device in the case of AC
J2 D7 D8 52X J1 Capacitor 10 1
52Y ZNR4 Tripping Device *operation.( Rated Voltage AC100/110V) 11 2
AC1 AC2 DC+ DC– 12 3
D9 13 4
AC input 5
AC or DC J5 ZNR5 14 6
13P 17PJ5157
16 8
17 9
2 4 6 DC output 25 18
26 19
In the above wiring diagram; M : Motor (For charging the closing spring) 52a/b : Auxiliary switch for circuit breaker
20
Circuit breaker : Open condition CC : Closing coil STC : Voltage trip coil LS0 : Limit switch (For detecting VCB's position) 21
22
Closing spring : Discharged condition 52Y : Auxiliary relay (For motor) LS1 : Limit switch (For detecting the charging 23
24
Motor circuit : No-voltage condition 52X : Auxiliary relay (For prevention of pumping) of the closing spring) (Connector code A)
LS2 : Limit switch (For starting up motor) ★If the auxiliary switch is a micro-current type.★
The terminals 7 ~ 18 (3a3b) are the standard contacts.
The terminals 19 ~ 26 (2a2b) are the micro-current contacts.
Fig. 33-1
■ 3/6-VPR-20C/25C (1600A, 2000A) ■ 10-VPR-25C ■ 10-VPR-50C(D)
■ 3/6/10-VPR-32C/40C ■ 20-VPR-25C (1600A, 2000A) ■ 20-VPR-16D/25D
■ Withdrawable: Standard connection diagram (AC•DC100~125V) (Note: There is no LS0 in a fixed type.)
Control Circuit ON OFF Note
Plug Terminal No. 3 5 1.Capacitor trip device should be installed to panel.
1 J5 (+) VCB Auxiliary Switch 5a5b ( 27 ~ 30 non)
J5
7 9 11 13 15 17 19 21 23 25 27 29
J3 in the control J4
board 52a
52X
LS2 J1
J3 52X LS1 52a
J4 CC
ZNR1 ZNR3 It uses for the
D1 D2 52Y D5 D6 inner circuit
ZNR2 R1 J2 R2 R3 STC 8 10 12 14 16 18 20 22 24 26 28 30
M 52X R4 52b 17P
D3 D4 D7 D8 It is not attached to the VCB. Auxiliary Switch 6a6b, for 10-VPR-40C(D) . 10 1 13P
J5 ZNR4 ✽1 Separately, please order. 4000A of secondary connector code B. 11 2
Auxiliary Switch 10a10b, for 10-VPR-50C(D) 12 3
52Y 52b Capacitor of secondary connector code B. 13 4
✽1 Trip Device ( 31 ~ 46 are added) 5
AC1 AC2 DC+ DC– 14 6
J2 D9 LS0 Front View of The VCB 15 7
J1 16 8
ZNR5 52a 17 9
52Y
J5 25 18
26 19
24 (–)
6 20
21
22
23
24
Secondary Junction
In the above wiring diagram; M : Motor (For charging the closing spring) 52a/b : Auxiliary contacts for circuit breaker (Connector code A)
Circuit breaker : Open condition
Closing spring : Discharged condition CC : Closing coil STC : Voltage tripping coil 52Y : Auxiliary relays (For motor) 1 8 15 22 29 (Secondary junction for
Motor circuit : No-voltage condition 2 9 16 23 30 connector code B)
LS0 : Limit switch (For interlock of electric closing) 52X : Auxiliary relays (For prevention of pumping) 3 10 17 24
4 11 18 25
LS1 : Limit switch (Close when closing-spring charged) R1/2/3/4 : Resistor (R1,R3,R4 is provided only 5 12 19 26
6 13 20 27
LS2 : Limit switch (For starting up and stopping motor) in the case of 200V) 7 14 21 28
✽1, 52b: only one for 20-VPR-16D/25D Fig. 33-2
27
ACCESSORIES
■ Table 3 Accessories
For 10-VPR-50C(D) For 10-VPR-50C(D)
For 20-VPR-16D/25D . 600~1250A For 20-VPR-16D/25D . 600~1250A
➀Secondary connector For 3/6/10-VPR . 1600A~3150A and
3/6/10-VPR-32C/40C (Exclude 4000A.)
(For connector code A, with lead
wires : 1.25mm2, length 1.5m) ➂Draw-in/draw-out handle
(For withdrawable VCBs)
For 10-VPR-50C(D)
➁Manual charging handle ➃Wipe gauge For 3/6/10-VPR . 1600A~3150A and
3/6/10-VPR-32C/40C (Exclude 4000A.)
(Shape is different for (Shape is different for 10-VPR-40C(D) . 4000A,
10-VPR-40C(D) . 4000A) 20-VPR-25C, and 20-VPR-25D . 2500A) ➄Lifting adapter
(Shape is different for 10-VPR-40C(D) . 4000A,
20-VPR-25C, and 20-VPR-16D/25D)
■ Table 4 Accessories
Circuit breaker 3-VPR-20C/25C 10-VPR-25C(F) 3/6-VPR-20C/25C 10-VPR-25C 10-VPR-40C(D) 20-VPR-25C 20-VPR-16D
Type name 6-VPR-20C/25C(S) 600~1250A 1600A, 2000A 3/6/10-VPR-32C/40C 10-VPR-50C(D) 1600A, 2000A 20-VPR-25D
2500A, 3000/3150A
Accessories 600~1250A 3/6/10-VPR-32C/40C 4000A 20-VPR-25D
600~2000A 2500A
➀Secondary connector 1 unit per each VCB (Please specify length when the lead wire of the length of 2m or more is necessary.)
➁Manual charging handle 1 per 1~5 VCBs (min. 1)
➂Draw-in/draw-out handle 1 per 1~5 VCBs (min. 1) 1 per 1~5 VCBs (min. 1)
➃Wipe gauge 1 per 1~5 VCBs (min. 1)
➄Lifting adapter Not shown 1 per 1~5 VCBs (min. 1)
in list above.
(Eyebolt M12) 2pcs
➅Sloped platform Not shown in list above.
Notes: 1. The bolt, washer and the nut for the connection of main circuit of fixing frame are not attached.
2. Please order separately if a higher quantity than indicated above required.
■ Table 5 (10a10b for 10-VPR-50C(D) of the secondary connector code B)
Auxiliary switch (6a6b for 10-VPR-40C(D) • 4000A of the secondary connector code B)
(5a5b for 10-VPR-40C(D) • 4000A of the secondary connector code A and others)
Rated insulation voltage (V) AC/DC250
Rated operational voltage (V) AC/DC220
5 (power factor 0.3~0.4)
Standard contact Rated operational current AC AC100~110 5 (power factor 0.3~0.4)
(A) DC AC200~220 5 (time constant 40 ms)
1 (time constant 40 ms)
Minimum operational current AC/DC DC48 0.5 (time constant 40 ms)
(mA) DC100~110
DC200~220 30
Rated continuous current (A) 50
AC/DC100
For micro Rated operational voltage (V) AC/DC24 5
current AC/DC220
Rated operational current AC AC24~220
DC24~220 1~200
(mA) DC 1~200
Rated continuous current (A) 2
Avoid use for DC48V/200mA or less in the case of standard contact.
Notes: 1. Additional auxiliary contacts can not be added to the standard 5a5b or 6a6b or 10a10b contacts.
2. For 600/630/1200/1250A of 3-VPR-20C, 3-VPR-25C, 6-VPR-20C and 6-VPR-25C(S), when the control voltage is AC•DC200/220V 4a4b contacts only are available.
28
OPTIONAL ACCESSORIES
■ Closing Spring Charged Indication Switch (Option for circuit breaker) 13P 17P
Standard control
circuit plug
(Multiple connector
(AMP)-Not an
interlock type.)
27 Table 6 Ratings of limit switch
LS3 28 Rated voltage (V) Resistive load Inductive load
29 6A
NC 28 AC/DC 125 10A
NO 29
Notes: 1. Refer to page 27 for an internal connection of VCB.
2. In Fig. 34, closing spring is in discharged condition.
3. LS3 is OMRON type X-10GW22-B.
COM 27
Fig. 34
■ Capacitor Trip Power Device (CTD) Sold Separately
The installation and the performance of KF-100CD and KF-200CD are compatible with past KF-100C and KF-200C.
14.3 2-M6 Table 7 Constant of element of CTD
13 Mounting screws
4-M4 Type name Capacitor C Resistance R1 Resistance R2 Resistance R3
Terminal screws KF-100CD 820μF 10W300Ω 10W100Ω 0.5W240kΩ
KF-200CD 820μF 10W300Ω 10W100Ω 0.5W240kΩ
27 φ100
Protect cover
4-R6 75 16 Table 8 Ratings of CTD KF-100CD KF-200CD
110.6 87
110 Item
Rated voltage (V)
Rated frequency (Hz) AC100/110 AC200/220
Rated output voltage (V)
130 50 φ7 Burden (VA) 50/60
35
70
4 - φ7 90 (Pitch) DC140/155
15
φ104 1 or less
120 Notes: 1. When a Type KF device is specified with a VCB, a panel-
90 mounting type will be supplied, however no device-mounting
fixture is included.
90 2.3 φ7✕9 oval hole
2. The device-mounting fixture allows mounting of the device
pointing left, right, up or down.
Fig. 35 Dimension of CTD and the device-mounting fixture Warning
The KF-200CD type converts the input voltage The output voltage of the KF-200CD is DC140/155V, and it can not open circuit
200V into 100V with the transformer. breakers with tripping control voltage of DC200/220V which may result in
accidents.
2-φ7 holes
AC φ104 hole 45 45
power
supply
45 45
Fig. 36 Connection diagram of CTD Fig. 37 Example of the device-mounting fixture
29
■ Position Switch (Option for mounting frame of 3/6-VPR-20C/25C 600/630A, 1200/1250A)
Test Connected Table 9 Ratings of limit switch
position position
13.5±5 Rated voltage (V) Resistive load (A) Inductive load (A)
Connected NO (ON) AC100~125 15 10
position switch DC100~125 0.5
0.05
NC (ON)
80.5±5
Test position NO (ON) 1 Unit Each 1C for test and connected position
switch VCB insert/withdraw stroke 170 2 Units Only the switch of No.1 is installed for 2C.
Each 2C for test and connected position
NC (ON) No.1 and No.2 are installed for 4C.
625 (1250A) 1.25mm2
550 (630A) (Yellow)
L6 L5 L4 L3 L2 L1 Terminal block
TE-K2-6
(M3.5 screws)
Position switch L5 L6 L4 L2 L3 L1
324.5 NO NO
126.5
42 230 COM COM
600 NC (+) NC (+)
Test position Connected position
switch switch
Position switch wiring (For 2C)
No.1 SW No.2 SW 640 Note 1. The terminal code of No.2 switch are R1~R6.
Fig. 38
■ Position Switch (Option for mounting frame of 3/6-VPR-20C/25C 1600, 2000A, 10-VPR-25C,
10-VPR-32C/40C, 20-VPR-16C/25C, 20-VPR-25C, 20-VPR-16D/25D)
Table 10 Ratings of limit switch
Test and Connected Rated voltage (V) Resistive load (A) Inductive load (A)
disconnected position AC100~125 15 10
position DC100~125 0.5
0.05
8.5±3
NC (ON) NO (ON) 1 Unit For 2C No.1 SW
2 Units For 4C No.1 and No.2 SW
195
VCB insert/withdraw strork
(This stroke is not applied to 20-VPR-25C
and 20-VPR-16D/25D.)
1.25mm2 ; yellow
L1 L4 R1 R4
L2 L5 R2 R5
L3 L6 R3 R6
No.1 SW No.2 SW
Position switch wiring
connection diagram
No.1 SW No.2 SW
Fig. 39
30
■ Arresters (for 3.6kV, 7.2kV) Sold Separately
Table 11 Ratings of Arrester
Brand name Otowa GL arrester
Usage
Indoor
Type name
Rated voltage (kV) GLI-3G GLI-6G
Applicable circuit voltage (kV)
AC discharge starting 4.2 8.4
235±8 voltage (kV crest) 3.3 6.6
60 Impulse discharge starting
6.3 12.6
8.2 90 voltage (kV peak)
90 φ15 Official discharge current (A)
143
φ8.5 Mass (kg) 17 33
Line terminal
2500 2500
φ66 Cap 1.2 1.3
Porcelain housing
Warning
Disconnect wiring to perform withstand voltage test.
Fixing band
Earth terminal 12
M6✕14
Fig. 40 Arrester (Type GL)
■ Arresters (for 12kV, 24kV) Sold Separately
If information on the arrester of this class is necessary, please consult your dealer.
31
■ Surge absorbing capacitor (CR suppressor) Sold Separately
620
598
C
R 1.6 322±2
C A 80±1110110 4-φ8 Installation holes 540
Earth terminal 122±2
M6 screw M6 screw 640
B 605
Terminal detail 140
25 220
Inner R7.5 180 180
C 105(Installation foot)
150
Porcelain Name plate M12 screw
insulator
φ15✕20
oval holes
Earth terminal
M8 screw
350±1 Fig. 42-2 Type CR-12
370±2
Fig. 42-1 Type CR-3 and CR-6
Table 13 Ratings of CR suppressor 3. Application to circuit where higher harmonics wave is included
The effect value of a synthetic current including the higher harmonics wave
Type name CR-3 CR-6 CR-12 should be below the value of the table below (1.3 times the ratings value) when
11 used for such a circuit.
Applicable circuit voltage (kV) 3.3 6.6
–
A 150 200 Type name CR-3 CR-6 CR-12
430
Dimensions B 237 337 0.1/φ Permissible value of synthetic current 0.05Arms 0.1Arms 0.37Arms
100/φ including higher harmonics wave /phase /phase /phase
C 16 20 31 4. Attention on withstand voltage test
Fig. 42-2 When the capacity of the transformer of the withstand voltage test is small, it is
Rated capacitance (μF) 0.05/φ 0.05/φ not likely to be able to test by a lot of currents' flowing too much.
When the withstand voltage test is executed with the CR suppressor
Series resistance (Ω) 100/φ 100/φ installed in the panel, it is necessary to cut off the CR suppressor from a
main circuit.
Mass (kg) 8.5 10
Figure Fig. 42-1
Warning Permissible testing voltage of CR suppressor
1. Remove connecting wires of CR suppressor during withstand voltage testing. Type name CR-3 CR-6 CR-12
2. Note: Separately consultation is required when high electric strength performance 13.2kV 24kV
Rated AC Between T-T 1 minute 6.6kV 14.2kV 28kV
is necessary. testing Between T-C 10 minutes 7.6kV 18kV
voltage Between T-C 4.95kV 9.9kV
T: Terminal, C: Case
5. Replacement recommendation service life
When 15 years have passed since it manufactured it.
■ Vacuum checker Sold Separately 136
Carrying knob
320 Remote control High voltage Earth Ammeter
140 20 150 box storage lead terminal terminal
portion 192
235 Output voltage Warning 120
Panel portion selection label
switch
Removable cover Warning
Input voltage label
selection
switch Pilot lamp
Power supply Power
outlet switch
66 Test
switch
Fuse Remote control
Foot outlet
(10) (Made of rubber)
136 192
Outline Arrangement of panel Remote control unit
Table 14 Specifications of Vacuum Checker
Type name Input voltage (V AC) Output voltage (kV AC)
V-1C
V-2C 100/110/120 20 (For 3/6/10-VPR)
V-3C
200/220/240 20 (For 3/6/10-VPR)
100/110/120/200/220/240 30 (For 20-VPR-25C and 20-VPR-16D/25D)
Fig. 43 Vacuum checker
32
■ Lifter Sold Separately
For 3/6-VPR-20C/25C 600~1250A
Minimum rotation 105 (2-φ20 holes)
radius approx. 1056 40 160
740 415
Sheep 490
600 Guide roller 530
Wire roper 595
45 640 45
730
Wire cover
Winch handle Main mast
(1232)
19 75
Down Up 8 40
Winch handle (92) 770 0~1800
Safety catcher 495 2300
Winch box 105 Hanging pin
(Install the 2-φ12
Guide roller (1146) (259)
887 pins on the panel
Free wheel with rubber side.)
(2-φ100) 50
Front wheel
Rear wheel
Floor
Fig. 44 Type F-2C lifter
33
■ Lifter Sold Separately
For 3/6-VPR-20C/25C 1600,2000A, 10-VPR-25C, 3/6/10-VPR-32C/40C
Minimum rotation radius approx.1050
2-φ20
holes
Safety catcher Sheep
Guide roller
Wire cover Center load
2450N
Wire rope
Winch box Main mast Lifting stroke
Note: It is not applicable in 10-VPR-40C (D) 4000A Steering handle Fixed wheel
Floor lock made of plastic
(One-touch pedal type) (2-φ150)
Free wheel with rubber
(2-φ125)
Fig. 45 Type F-3C lifter
For 20-VPR-25C
If information on the lifter for 20-VPR-16D/25D is necessary, please consult your dealer.
15
2520 15 2-φ16 hole
790
6301256
557733
Sheep 391
37.5 75 225 80
650218 Center load
W = 2450N
(2055) 395
Lifting stroke 0-2000928
Winch box Main mast
Steering
handle
Wheel 578 350
stopper 860
Free wheel Fixed wheel
with rubber made of plastic
(2-φ150) (2-φ150)
Fig. 46 Lifter for 20-VPR-25C
34
Technical Information
■ Operation and control circuit
■ Electrical closing and tripping operation
Fig. 47, shows the circuit breaker in an opened circuit state ●Trip Free Operation
and with the closing spring in a discharged state. If the closing command and trip command are given
●Closing Operation simultaneously when the circuit breaker is in an
➀When the power supply is connected, auxiliary relay 52Y opened state and the closing spring is in a charged
is excited via the limit switch LS2 and the contact of state (closing preparation):
auxiliary relay 52Y closes which activates the motor via ➀Operation takes place in order of ➁, ➂ and ➃ of the
LS2 and the contact of auxiliary relay 52Y starts to electrical (closing) operation. Then because the trip
charge the closing spring. When the closing spring is command is being continued, operation ➀ of the
completely charged, limit switch LS2 opens and the electrical (trip) operation takes place.
motor stops and the limit switch LS1 closes(the closed ➁Electrical (circuit closing) operation ➀ is returned but
control circuit is formed). since the auxiliary relay 52X is continuously being
➁By closing the closing command switch CS1 in this state, excited, closed circuit is not formed by contact 52Xb and
the circuit remains in the opened state.
the closing coil CC is excited and the closing latch at the
operating mechanism is released and the circuit breaker ➂When performing the closing operation, it is necessary to
closes by the charged closed spring energy. The release the closing command by closing command
discharging of the closed spring, LS2 is closed and LS1 switch CS1 and restore auxiliary relay 52X .
is opened. If the closing command and trip command are given
➂By the limit switch LS2 closing, the motor activates and simultaneously when the circuit breaker is in a
performs charging of the closing spring and to prepare closed state and the closing spring is in a charged
for the next closing operation. state (closing preparation):
➃W h e n t h e c i r c u i t b r e a k e r i s c l o s e d , c i r c u i t b r e a k e r ➀Since the auxiliary contact 52b is opened, closed control
auxiliary contact 52b opens and shuts off excitation of circuit is not formed and electric (trip) operation ➀
closing coil CC . At the same time auxiliary contact 52a occurs.
closes and forms a trip circuit of the voltage tripping coil ➁Electrical (circuit closing) operation ➁ is returned but
STC and at the same time excites the auxiliary relay (for since the auxiliary relay 52X is continuously being
anti-pumping prevention) 52X . excited, closed circuit is not formed by contact 52Xb and
●Tripping Operation the circuit remains in the opened state.
➀By closing the trip command switch CS2, the voltage
tripping coil STC is excited and engagement of tripping ➂When performing the closing operation, it is necessary to
release the closing command by closing command
latch at the operating mechanism is released and the switch CS1 and restore auxiliary relay 52X .
circuit breaker opens.
Fig. 47 Basic control circuit diagram ➀ ➂ (ON) (OFF)
J5 CS1 ➄ CS2
Notes: The right control circuit diagram indicates: In the control
VCB: Opened state ZNR1 substrate
Closing spring: Discharged state D1 D2
Motor circuit: No-voltage D3 D4 J5
M: Motor (for charging the closing spring)
CC: Closing coil J5 J3 J4 52X
STC: Voltage tripping coil 52a J1
LS0: Limit switch (for detection of position as to the mounting LS2
frame)
LS1: Limit switch (closing spring charge detection contact) J3 52a
LS2: Limit switch (for motor start up/stop)
52a/b: Auxiliary contacts of circuit breaker 52Y ZNR3 52X LS1
52Y: Auxiliary relay (for motor) D5 D6 J4 CC
52X: Auxiliary relay (for anti-pumping prevention) R1 J2 R3
R1/2/3/4: Resistance (R1,3 and 4 are equipped only for 200V) D7 D8 52b
ZNR2 ZNR4
D9
M
52Y 52X R4 LS0 STC
J2 ZNR5
52Y J1
J5
➁ ➃➅
35
■ Operation and control voltages (currents)
●Table 15 Operation and control voltage fluctuation range
Classification Standard JEC-2300 IEC 60056 and IEC 62271-100
Closing operation/control voltage 75~125%
Tripping control voltage DC 85~110% 85~110%
AC 70~110%
DC 60~125% 85~110%
AC
●Table 16 Closing and tripping control current vs. current-flow time (see Fig. 48)
Current (A), Time (sec.) Control voltage (V) DC (V)
100
Closing
VCB type name Tripping I (A) T (sec.)
Closing 2.4 0.05
3/6-VPR-20C/25C 600~1250A Tripping 2 0.03
Closing 4 0.05
3/6-VPR-20C/25C 1600A, 2000A Tripping 4 0.03
10-VPR-25C, 3/6/10-VPR-32C/40C Closing 5 0.05
Tripping 2.2
10-VPR-40C (D) 4000A Closing 3.2 0.035
Tripping 3.2 0.08
10-VPR-50C (D) Closing 3.4 0.03
Tripping 3.4 0.05
20-VPR-25C 1600A, 2000A Closing 3.4 0.03
Tripping 3 0.05
20-VPR-16D/25D 600~1250A 4.5 0.03
4 0.05
20-VPR-25D 2500A 0.03
●Table 17 Motor-operation control current vs. current-flow time (see Fig. 49)
Control voltage (V) DC (V)
Current (A), Time (sec.) 100
VCB type name
I1 (A) I2 (A) T1 (sec.) T2 (sec.)
8
3/6-VPR-20C/25C 600~1250A 5 1 0.1
3/6-VPR-20C/25C 1600A, 2000A 5 1.8 0.1 5
10-VPR-25C, 3/6/10-VPR-32C/40C
20-VPR-25C 1600A, 2000A
10-VPR-40C (D) 4000A 11.5 6 0.1 6
10-VPR-50C (D) 6 1.5 0.1 10
20-VPR-16D/25D 600~1250A 4 1 0.1 6
20-VPR-25D 2500A 5 1 0.1 5
I (Current) I1
(Surge
current)
T (Time) I2
Fig. 48 (Steady-state
current)
T1
T2 (Spring-charging time)
Fig. 49
36
■ Operation and control voltages (currents)
●Table 18 Burden VA of Closing Coil and Electrifying Time in ●Table 19 Motor burden VA and Drive Time in Alternating
Alternating Current (AC) Operation Current (AC) Operation
Control Voltage (V) AC100/110V Control Voltage (V) AC100/110V
Model name Burden (VA) Electrifying time (sec) Model name Burden (VA) Electrifying time (sec)
3/6-VPR-20C/25C 600~1250A 480 0.05 3/6-VPR-20C/25C 600~1250A 150 8
Excluding the above 680 0.05 Excluding the above 180 6
●Table 20 VT Capacity, and Number of VCBs Operable at the same time in Alternating Current (AC) Operation
VT type name PD-50/100HF PD-200KFH Notes: 1. For PD-50/100HF, all-time load of 50VA is considered in addition to VCB
(Notes1,3) (Notes2,3) operation.
Model name 2 units 3 units
2. For PD-200HF, all-time load of 200VA is considered in addition to VCB
3/6-VPR-20C/25C 600~1250A 1 unit 2 units operation.
Excluding the above 3. The operation duty of O-1min-CO-3min-CO or O-3min-CO-3min-CO is
considered. If operated more than this, keep enough interval.
4. 10-VPR-40C(D) 4000A is not included in the above-mentioned table.
Applicable Standards
■ Special Environment and Application ●Table 21
●Operation Environment Normal operation condition
VPR type vacuum circuit breaker conforms to the JEC-2300 and IEC
6 0 0 5 6 or IEC 62271-100 (high voltage alternating current circuit breaker) and 1. Altitude: 1,000 m or less
designed/manufactured as an indoor unit. Therefore, this circuit breaker 2. Ambient temp: –5°C ~ 40°C
should be operated under normal environments specified in table 21. Daily and
periodical check and maintenance should be carried out enough according to (The average temperature for 24 hours must not
VCB's instruction manuals. If it is necessary to operate this circuit breaker exceed 35°C.)
under special condition not listed in table 21, consult the manufacture.
3. Relative humidity: 45% ~ 85%
●Instructions for Installation (Relative humidity; there must be no dew condensation.)
If it is necessary to operate this circuit breaker in a dusty place, a place with
corrosive gas, at a location exposed to abnormal vibration or impact, or in an 4. Degree of pollution: There must be no pollution.
outdoor panel environment, etc., special care must be paid to deal with items (As a guideline, the equivalent salt deposit density
such as dust, corrosion, vibration, impact, water drops, condensation, and etc. should be less than 0.01 mg/cm2)
5. Poisonous gas etc.: There must be no corrosive gas.
6. Powder dust: There must be no excessive powder dust.
(As a guideline, the powder dust should be less
than 2 mg/m3)
■ Application of Surge Protection Device
For the actual applications of vacuum circuit breaker, the surge protection standards for the load circuit so used, and actual
application will be shown as table 22. Use the as table 22 of standard bellows as reference when selecting models.
●Surge Protection Standards
●Table 22
VCB type Load Generator Motor Dry-type Oil transformer Mitsubishi molded Phase-advance
CR suppressor CR suppressor transformer transformer and oil capacitor
General purpose 3/6/10-VPR-C Not applicable Not applicable Not required transformer (Note 4)
product 10-VPR-50C(D) Lightning arrester (Note 1) Not required
(Note 1) Ditto Not required (Notes 1,2)
20-VPR-C/D (10-VPR is not Not required
Ditto applicable)
Not applicable
Low-surge product (3/6-VPR-CG) Not required Not required (Note 3) Not required Ditto Not required Not required
37 Notes: 1. To directly switch the semiconductor rectifier unit (for example, electric power thyristor rectifier unit) in the secondary side of a transformer, use the transformer with
contact-protective plate. Provide a general-purpose arrester in the primary side and the surge protective device such as a filter capacitor in the secondary side.
2. Avoid interrupting the no-load excitation inrush current of molded transformer. When such currents must be interrupted, apply general-purpose arrester. To use
any molded transformer made by other manufactures, consult the manufacturer. However, low-surge VCBs require no general-purpose arrester.
3. For motors in applications where inching is the predominant switching duty (cranes, conveyor, etc.), use CR suppressor.
4. Mitsubishi molded transformer and oil transformer are for 6kV with the impulse withstand voltage 60kV and for 3kV with the impulse withstand voltage 45kV.
5. In case of kondorfer starting system, carry out the switching operation of the neutral point of the auto-transformer after the starting current become the
stationary.
■ Fig.50 Surge Protection Standards (In case of general-purpose VCB)
If the motor is switched directly (full-voltage starting and reduced voltage starting) In case of the private generator In case of semiconductor rectifier In case of the dry-type transformer
VCB VCB VCB VCB VCB
CR LA
VCB VCB
M VCB VCB M VCB CR LA
Full-voltage starting CR CR CR T (with short-
proofing
T VCB platc)
CR
VCB
M M
Reactor starting Kondorfer Star-delta starting
■ Service Life and Application
The service life of vacuum circuit breaker is specified in the terms of the vacuum service life of vacuum switch tubes,
electrical and mechanical service lives.
●Vacuum Service Life of Vacuum Switch Tubes (VST)
Since the vacuum circuit breaker maintains the switching characteristics and insulation characteristics by using high
vacuum in VST, it is most important to maintain such vacuum. VST produced by our own original quality control is
checked severely by full-lot testing, and therefore can be operated safely for a long time. It is also possible to check the
vacuum in a simple way by voltage-resistance method in periodical maintenance. Portable type vacuum checkers are
also available.
●Electrical Service Life of VST (see Table 23)
The electrical service life of VST is determined by the electrode consumption and the number of switchings. In VCB,
such service life can be judged by the number of load switchings, because the electrode consumption is extremely small.
●Mechanical Service Life (see Table 23)
This can be determined by the operation counter provided in the vacuum circuit breaker (provided in all types as
standard specification).
●Replace when having reached at the service life
When it reached mechanical life or 20 years have passed since it was manufactured, it is necessary to replace the VCB.
●Table 23 List of switching service lives ●Table 24 List of capacities for which capacitor is applicable
Item Load switching Mechanical Item Max. switching Multiple switching
service life switching service capacity (kvar) capacity (kvar)
Model name (times) life (times) Model name
3-VPR 10,000 10,000 3-VPR 2,500 1,500
6-VPR 6-VPR 5,000 3,000
10-VPR 10-VPR 7,000 4,000
20-VPR 20-VPR-16D 12,000 6,000
20-VPR-25C, 20-VPR-25D 17,000 8,500
Remarks: 1. W h e n t h e s w i t c h i n g t i m e s r e a c h e d t h e v a l u e o f t a b l e 2 3 , i t i s Remarks: 1. The electrical service life for the max. switching capacity is about
necessary to replace the VCBs. 2,000 times, and multiple switching capacity is 10,000 times.
2. Applicable capacities with 6 ~ 13% series-connected reactor are
shown.
■ Polarity of Main Circuit Connection
It is needless to classify the polarity in the power/load sides in connecting the top and bottom main circuit terminals of the
vacuum circuit breaker. (Electrical or mechanical performance is not changed whether it is connected to the power side or
load side.)
38
39
3/6/10/20-VPR SeriesVCB
10VPR25C- ID12111A01
ORDERING INFORMATION
Type name code Selection specification
Closing spring
chargedVPR
indication switch
Auxiliary switch
Secondary
connector
Position switch
Tripping control
voltage(STC)
Closing
operation/control
voltage
Rated current
Mounting
configuration
Standard met
VST selection
Series name
Rated
short-circuit
breaking
current
Type name
Rated voltage
03 : 3.6kV VPR 20 : 20kA C – : Standard J : JEC L:Fixed type 06 : 600/630A 1 : DC100/110V 0 : None [Standard] 0 : Standard 0 : None
06 : 7.2kV 25 : 25kA
10 : 12kV 32 : 31.5kA I : IEC P:With out 12 : 1200/1250A 2 : DC200/220V A :Without
20 : 24kV 40 : 40kA mounting
50 : 40/50kA D G : Low frame 16 : 1600A 7 : DC24V 1 : 1 unit interlock S :With 1 :With 1C
surge C:With CW 20 : 2000A (2C) [Option] contact
class 25 : 2500A 8 : DC48V B :With for small
mounting 30 : 3000/3150A
frame 40 : 4000A 5:AC 3:AC 2 : 2 units interlock current
D:With PW 100/110V 100/110V [Option]
with CTD (4C) C : Automatic
class -self
mounting
frame 6:AC 4:AC aligning
G:With MW 200/220V 200/220V
class ∗Code B and
mounting with CTD C cannot be
frame selected for
fixed type.
Specification list
– 06,12 A
20 C G J, I L, B
P, C, D,G
– 16,20 A
B
C
– 06,12 A
25 C G J, I L, 06,12 B
P, C, D,G
A
– 16,20 B
C
– 11
12 2 2
G L,
53
P, C, D,G
32 C J, I 16,20 6 4 0 A
– 771B00
3 VPR P, C, D,G 25,30 882CS1
– 12
G L,
40 C P, C, D,G
J, I 16,20
–
P, C, D,G 25,30
– 06,12 A
B
20 C G J, I L, A
P, C, D,G B
– 16,20 C
C(S) L, 06,12 A
– P, C, D,G B
25 J, I A
B
C 16,20 C
11
– 12 2 2 0 00
G L, 5 3 1 S1
6 VPR 6 4 2
P, C, D,G 7 7
32 C J, I 16,20
– 88
P, C, D,G 25,30 A
– 12 B
G L, C
40 C P, C, D,G
J, I 16,20
–
P, C, D,G 25,30
C(F) 06,12
L,
25 – J, I P, C, D,G 16,20
C
P, C, D,G 25,30
L, 06,12 1 1
2 2
32 C – J, I P, C, D,G 16,20 5 3 A
6 4 B
7 7 0 C
8 8 1
10 VPR P, C, D,G 25,30 2 0 0
S 1
06,12
L,
P, C, D,G
C 16,20
40
– J, I P, C, D,G 25,30
C(D) 40 11 A
50 C(D) C, D, G 22 B
53
40 64
16 06,12
11
D – J, I P, C, D 06,12 2 2 0 A 0 0
25 5 3 1 B S 1
20 VPR 25 6 4 2
7 7
88
25 C – J, I P, C, D 16,20
40
Memo
41
42
L-AL1-3C6531-E HQ 0803 (MDOC) HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
http://Global.MitsubishiElectric.com
Safety Warning
To ensure proper use of the products listed in this catalog,
please be sure to read the instruction manual prior to use.
New publication effective March 2008.
Specifications subject to change without notice.