Do you know the importance of an oxygen scavenger in an HRSG? HRSG cycle chemistry training program by Combined Cycle Solutions. By adding an oxygen scavenger, boiler water chemistry changes from oxidizing to reducing. Train your vendors for water treatment chemicals in the best practices by HRSG cycle chemistry training program. Visit website and contact us now!
Visit - https://www.ccgt-solutions.com/chemistry.html
Visit - https://www.ccgt-solutions.com/

Discover the best professional documents and content resources in AnyFlip Document Base.
Search
Published by Combined Cycle Solutions, 2022-12-20 02:46:39

Contact For The Best Power Plant Consulting Solutions

Do you know the importance of an oxygen scavenger in an HRSG? HRSG cycle chemistry training program by Combined Cycle Solutions. By adding an oxygen scavenger, boiler water chemistry changes from oxidizing to reducing. Train your vendors for water treatment chemicals in the best practices by HRSG cycle chemistry training program. Visit website and contact us now!
Visit - https://www.ccgt-solutions.com/chemistry.html
Visit - https://www.ccgt-solutions.com/

Most combined-cycle power plants add an oxygen scavenger to their condensate &
feedwater system. Indeed, 3 of my 4 combined cycle plants used an oxygen
scavenger. The exception was a new plant where I set up the boiler water chemistry
program. There are several different oxygen scavengers with hydrazine and
carbohydrazide being the most commonly used.

Now, do you need to add an oxygen scavenger? What if I told you the use of oxygen
scavengers often leads to tube failures in the Heat Recovery Steam Generator
(HRSG)?

Most power plant operators were taught oxygen, in a boiler tube, causes corrosion.
That statement, by itself, is untrue. While the presence of oxygen in a low pH
environment is a recipe for corrosion; it turns out oxygen, in the presence of a high
pH, actually prevents corrosion. This occurs because oxygen – with a high pH –
produces hematite (Fe2O3) and magnetite (Fe3O4). These produce a tough, corrosion-
resistant oxide layer on the HRSG tube surfaces.

Adding an oxygen scavenger changes the boiler water chemistry conditions from
oxidizing to reducing. Now, the hematite formed is reduced to magnetite and the
magnetite is further reduced, becoming soluble in the boiler water. This results in
removing the protective oxide layer with corrosion and thinning of the tubes
occurring. There is a flow component and this type of corrosion is known as single-
phase Flow Accelerated Corrosion (FAC). In the HRSG, the susceptible areas are the
low-pressure (LP) and intermediate-pressure (IP) section economizers and
evaporators. As of the last publicly available EPRI HRSG Chemistry Guidelines, FAC
still ranked in the top two for HRSG tube failures.

The Electrical Power Research Institute (EPRI) discourages the use of oxygen
scavengers in combined-cycle. The exception is where the HRSG contains copper-
bearing components. In these rare occurrences, an oxygen scavenger is required. If
your plant adds an oxygen scavenger, the addition should be feedback controlled,
using an ORP (Oxidation-Reduction Potential) analyzer, and the feed controlled to
keep the ORP in the range of -300 to -350 mV. This will reduce the potential for FAC.
Dissolved iron levels < 5 ppb are confirmation that minimal FAC is occurring.

Since the vast majority of HRSGs do not contain copper-bearing components, an
oxygen scavenger isn’t needed. The boiler water oxygen should be removed by
deaeration (Deaerator or LP Drum). The remaining oxygen – under proper pH control
– will form hematite and magnetite on the tube surfaces, resulting in a tough oxide
layer resistant to corrosion.

So go ahead and ditch your oxygen scavenger!

Combined Cycle Solutions, LLC offers HRSG boiler water chemistry consulting
solutions based on EPRI guidelines.

Read More: https://www.ccgt-solutions.com/does-your-hrsg-need-an-oxygen-
scavenger.html