1500VDC

READY

WD3 Power Inverters

1500 Vdc High-Capacity Modular Inverters

EXTREME POWER CAPACITY TO DESIGNED FOR
OPTIMIZE PV / ESS PROJECTS UTILITY-SCALE NEEDS

• Minimize design costs while provide the higher efficiency • Easy integration to any grid: advanced power control
to obtain the best performance. functions that ensures complete stability.

• Flexible power operation ranges up to 7,6 MVA in SmartPV • Remote control of active and reactive power
and EnergyStorage Inverter Stations.
• Ramp rate response of programmable power in order to
• Wide DC operation range: Maximum input current up to guarantee the grid balance.
4170 A.
• Instant power regulation according to frequency
• Voltage DC input ready for 1500Vdc variations, with optional STATCOM functions.

• Maximum power at extreme ambient conditions with • Comes with NEMA 3R, IP54 standard protection expandable
advanced cooling system, ensuring the higher reliability. to IP65. Work under the harshest environmental conditions.

Joining Central+Modular Advantages

High-Capacity Modular Flexibility

Head Module Power Units

Communication & Control DC/AC Conversion Stage Local
Central Unit
embedded DSP Control
AC Output Bridge
Electrical Protections
Additional protections and
functions Special Filters and Fan units to
preserve power stacks.
AC Busbar Connection
Integrated Auxiliary Services Independent Busbar connection
for each module
Available space for customer
requests

Different MPPT Options: Maximizing the Performance

The possibility of choosing between different DC input connection options enables WD3 to adapt the conversion stage,
achieving the finest performance according to the selected module technology and final plant configuration.

Single Master&Slave MPPT Multi-MPPT

DC DC Input #1 DC Input #2 DC Input #3
Input

AC AC
Output Output

Single MPPT for centralized inverter function, Multi-MPPT optimizes the connection of
joining and optimizing conversion with several PV fields with independent DC
Master&Slave Configuration.
inputs.

Quick Installation and Easy Maintenance

Self-Supporting Optimized to reduce MTTR Minimum Connection Time

Prepared to pick and place in the final Front & Rear Access door with direct access in High quality busbar for Plug&Play
destination with a minimum pre- AC and DC sides to >90% of critical elements. transformer connection. Simple, fast
installation Optimize the routine maintenance of the and with less tooling requirements.
equipment, making it easier and faster.

Best Performance even in the Hottest Place

New fan system with vertical top-bottom air flow. Optimize the cooling capacity with advanced features to ensure temperature
regulation in the most demanding conditions:

• Filters to protect Inputs and Outputs from moisture
and dust.

• Regulated ventilation flow: Ensure maximum
power saving depending on inverter's instant loads.

• AC-Decoupled from grid voltage: Isolated from
external instabilities.

• Cooling System entrances are automatically closed
while the system is not working to avoid dust.

Ruggerized Outdoor Design for Harsh Environments

From design to component assembly, every phase is carried out with close attention to the real working conditions, especially
for extreme-hot and dust requirements, obtaining as result a rugged device conceived for a long-term operation life.

Dust WD Family is able to work Internal electronics and Sealing elements and
protected with the best conditions in Components are coated standard IP54 enclosure
remote high-altitude to resist corrosive salty Protection for rain and
Filters and protections to mountain region conditions. humidity
avoid dust entrance
combined with its top-
bottom cooling system

2-level Control System with Cutting-Edge Algorithms

WD3 control systems are based on the unique experience of GPTech in energy management systems, with more than 15 years of
development. WD3 Control is built on a 2-level Control architecture:

o Local-Module Control layer provides the finest management of
main parameters (Q, V, I...) for each power unit. DSP-Embedded
Algorithms have the faster response to real-time working
conditions.

o Central Control layer manages the complete power station,
consisting of power electronics devices, ancillary services,
medium voltage equipment (transformer and switch gears) and
ESS (batteries, ultracaps).

o Its gateway for external monitoring and control is adapted to
main communication protocols. it can be easily integrable
with external SCADA systems through a unique node.

READY WD3-1500V

Smart conversion with for Advanced Energy Management

Energy Management & Control Features

Power control features

Anti-islanding protection Yes

Active power curtailment Yes

Active power ramp rate constraint Yes

Reactive power close-loop control Yes

Power factor close-loop control Yes

Frequency Ride Through (FRT) capability Yes

Voltage Ride Through (VRT) capability Yes

Over frequency active power response Yes

Reactive power injection for VRT Yes

STATCOM mode: Reactive injection at night Optional

Interfaces

Touch-HMI Optional

Communication channel Ethernet port for external communications (SCADA or Energy
Management System)

Communication port connector RJ45 Female or Fiber (optional)

Communication protocol Modbus TCP and NTP

Luminous indicator, start/stop control and emergency stop Yes

Dimensions

1x Power Module 1650 mm.
1M-WD3-VYYY 1050 mm.

2460 mm.
2000 mm.

2973 m.

2x Power Module 1650 mm.
2M-WD3-VYYY 1050 mm.

3x Power Module 2460 mm.
3M-WD3-VYYY 2000 mm.

4273 m.

1650 mm.
1050 mm.

2460 mm.
2000 mm.

5573 m.

WD3 1500V - 1x Power Module

560 Vac 575Vac 590Vac 605Vac 620Vac

1M-WD3-V560 1M-WD3-V575 1M-WD3-V590 1M-WD3-V605 1M-WD3-V620

DC input

Voltage range [Vdc] 835-1500 857-1500 880-1500 902-1500 924-1500

Voltage range @ full power [Vdc] (1) 835-1500 857-1500 880-1500 902-1500 924-1500

Max. DC voltage [Vdc] 1500

Rated input current at Vdc_min [A] @35ºC 1385 1385 1385 1385 1385

Max. Short circuit input current [A] (2) 1700

Number of MPPT Inputs 1
DC Cabinet

Switch type DC load break switch

DC overvoltage protection SPD (type 2)

Number of DC Inputs up to 12

DC input protection (3) Fuses

Integrated DC monitoring Optional
AC output

Nominal AC voltage 560V 575V 590V 605V 620V

Max. AC voltage range (4) 90%-110%

Frequency 50/60Hz

Frequency operation range 47 – 63Hz

Rated AC power @ 50ºC [kVA] @ 1250vdc [5] 1018,4 kVA 1045,7 kVA 1073,0 kVA 1100,3 kVA 1127,6 kVA

Rated AC power @ 35ºC [kVA] @ 1250vdc [5] 1136,4 kVA 1166,9 kVA 1197,3 kVA 1227,8 kVA 1258,2 kVA

Maximum output current [A] 1318 A 1322 A 1326 A 1330 A 1334 A

Total Harmonic Distortion (THD) < 3%

Power factor Adjustable

AC Cabinet Integrated

Switch type AC circuit breaker

Number of handling switches 1

AC overvoltage protection SPD (type 2)

Integrated AC monitoring Optional
Efficiency

Maximum Peak Efficiency (7) >98.6%

European Efficiency (7) >98.4%

CEC Efficiency (7) >98.5%

Self-consumption in standby [W] <250W

Self-consumption in operation (8) [kW] <4kW

Daily Self-consumption 12h. (European / CEC) [Kw] <2kW / <2.4kW
Ambient conditions

Operation ambient temperature (9) 14ºF / 140ºF (-10ºC / 60ºC)

Operation ambient temperature (without de- 14ºF / 122ºF (-10ºC / 50ºC)
rating)

Storage and transport temperature -40ºF / 149ºF (-40ºC / 65ºC)

Maximum relative humidity 100%

Fresh air consumption 5750 m3/h

Max. altitude above sea level without derating 1000 masl

Max. altitude above sea level allowed 4000 masl
Mechanical Characteristics

Dimensions ( W x D x H) 2615 x 1760 x 2460 [mm]

Weight <3000kg

Protection degree (10) NEMA 3R, IP54

Legal standards

Designed and manufactured according IEC62019-1, IEC62109-2, IEC61000-3-4, IEEE1547 (6), UL1741 (6), UL840 (6). Ask for Details

Notes

(1) At 100% Uac_nom, full power and cos ϕ = 1 (6) At f=60Hz

(2) Higher values under request (7) Self-consumption is not considered in the efficiency measurement

(3) 250A to 400A. Different DC fuse sizes are available (8) At rated AC power @ 35ºC (95 ºF)

(4) Other voltage configurations are possible under request (9) A extended operating temperature range is possible under request

(5) At f=50Hz (10) IP65 under request

WD3 1500V - 2x Power Module

560 Vac 575Vac 590Vac 605Vac 620Vac

2M-WD3-V560 2M-WD3-V575 2M-WD3-V590 2M-WD3-V605 2M-WD3-V620

DC input

MPPT Voltage range [Vdc] 835-1500 857-1500 880-1500 902-1500 924-1500

MPP Voltage range @ full power [Vdc] (1) 835-1500 857-1500 880-1500 902-1500 924-1500

Max. DC voltage [Vdc] 1500

Rated input current at Vdc_min [A] @35ºC 2770 2770 2770 2770 2770

Max. Short circuit input current [A] (2) 3400

Number of MPPT Inputs up to 2
DC Cabinet

Switch type DC load break switch

DC overvoltage protection SPD (type 2)

Number of DC Inputs up to 24

DC input protection (3) Fuses

Integrated DC monitoring Optional
AC output

Nominal AC voltage [V] 560V 575V 590V 605V 620V

Max. AC voltage range (4) 90%-110%

Frequency 50/60Hz

Frequency operation range 47 – 63Hz

Rated AC power @ 50ºC [kVA] @ 1250vdc [5] 2036,9 kVA 2091,5 kVA 2146,0 kVA 2200,6 kVA 2255,1 kVA

Rated AC power @ 35ºC [kVA] @ 1250vdc [5] 2273 kVA 2333,8 kVA 2394,7 kVA 2455,5 kVA 2516,4 kVA

Maximum output current [A] 2636 A 2644 A 2652 A 2660 A 2668 A

Total Harmonic Distortion (THD) < 3%

Power factor Adjustable

AC Cabinet Integrated

Switch type AC circuit breaker

Number of handling switches 2

AC overvoltage protection SPD (type 2)

Integrated AC monitoring Optional
Efficiency

Maximum Peak Efficiency (7) >98.6%

European Efficiency (7) >98.4%

CEC Efficiency (7) >98.5%

Self-consumption in standby [W] <400W

Self-consumption in operation (8) [kW] <7kW

Daily Self-consumption 12h. (European / CEC) [Kw] <3.5kW / <4.1kW
Ambient conditions

Operation ambient temperature (9) 14ºF / 140ºF (-10ºC / 60ºC)

Operation ambient temperature (without de- rating) 14ºF / 122ºF (-10ºC / 50ºC)

Storage and transport temperature -40ºF / 149ºF (-40ºC / 65ºC)

Maximum relative humidity 100%

Fresh air consumption 11500 m3/h

Max. altitude above sea level without derating 1000 masl

Max. altitude above sea level allowed 4000 masl
Mechanical Characteristics

Dimensions ( W x D x H) 3915 x 1760 x 2460 [mm]

Weight <4750kg

Protection degree (10) NEMA 3R, IP54

Legal standards

Designed and manufactured according IEC62019-1, IEC62109-2, IEC61000-3-4, IEEE1547 (6), UL1741 (6), UL840 (6). Ask for Details

Notes

(1) At 100% Uac_nom, full power and cos ϕ = 1 (6) At f=60Hz

(2) Higher values under request (7) Self-consumption is not considered in the efficiency measurement

(3) 250A to 400A. Different DC fuse sizes are available (8) At rated AC power @ 35ºC (95 ºF)

(4) Other voltage configurations are possible under request (9) A extended operating temperature range is possible under request

(5) At f=50Hz (10) IP65 under request

WD3 1500 V - 3x Power Module

560 Vac 575Vac 590Vac 605Vac 620Vac

3M-WD3-V560 3M-WD3-V575 3M-WD3-V590 3M-WD3-V605 3M-WD3-V620

DC input

MPPT Voltage range [Vdc] 835-1500 857-1500 880-1500 902-1500 924-1500

MPP Voltage range @ full power [Vdc] (1) 835-1500 857-1500 880-1500 902-1500 924-1500

Max. DC voltage [Vdc] 1500

Rated input current at Vdc_min [A] @35ºC 4155 4155 4155 4155 4155

Max. Short circuit input current [A] (2) 5100

Number of MPPT Inputs up to 3
DC Cabinet

Switch type DC load break switch

DC overvoltage protection SPD (type 2)

Number of DC Inputs up to 36

DC input protection (3) Fuses

Integrated DC monitoring Optional
AC output

Nominal AC voltage [V] 560V 575V 590V 605V 620V

Max. AC voltage range (4) 90%-110%

Frequency 50/60Hz

Frequency operation range 47 – 63Hz

Rated AC power @ 50ºC [kVA] @ 1250vdc [5] 3055,3 kVA 3137,2 kVA 3219,0 kVA 3300,9 kVA 3382,7 kVA

Rated AC power @ 35ºC [kVA] @ 1250vdc [5] 3409,3 kVA 3500,7 kVA 3592,0 kVA 3683,3 kVA 3774,6 kVA

Maximum output current [A] 3954 A 3966 A 3978 A 3990 A 4002 A

Total Harmonic Distortion (THD) < 3%

Power factor Adjustable

AC Cabinet Integrated

Switch type AC circuit breaker

Number of handling switches 3

AC overvoltage protection SPD (type 2)

Integrated AC monitoring Optional
Efficiency

Maximum Peak Efficiency (7) >98.6%

European Efficiency (7) >98.4%

CEC Efficiency (7) >98.5%

Self-consumption in standby [W] <550W

Self-consumption in operation (8) [kW] <10kW

Daily Self-consumption 12h. (European / CEC) [Kw] <4.9kW / <5.9kW
Ambient conditions

Operation ambient temperature (9) 14ºF / 140ºF (-10ºC / 60ºC)

Operation ambient temperature (without de- 14ºF / 122ºF (-10ºC / 50ºC)
rating)

Storage and transport temperature -40ºF / 149ºF (-40ºC / 65ºC)

Maximum relative humidity 100%

Fresh air consumption 16500 m3/h

Max. altitude above sea level without derating 1000 masl

Max. altitude above sea level allowed 4000 masl
Mechanical Characteristics

Dimensions ( W x D x H) 5215 x 1760 x 2460 [mm]

Weight <6500kg

Protection degree (10) NEMA 3R, IP54

Legal standards

Designed and manufactured according IEC62019-1, IEC62109-2, IEC61000-3-4, IEEE1547 (6), UL1741 (6), UL840 (6). Ask for Details

Notes

(1) At 100% Uac_nom, full power and cos ϕ = 1 (6) At f=60Hz

(2) Higher values under request (7) Self-consumption is not considered in the efficiency measurement

(3) 250A to 400A. Different DC fuse sizes are available (8) At rated AC power @ 35ºC (95 ºF)

(4) Other voltage configurations are possible under request (9) A extended operating temperature range is possible under request

(5) At f=50Hz (10) IP65 under request

Inverter Stations

The Outdoor Modular solution for up to 1500 V Modules using the WD3 family of inverter

READY TO RUN

Turnkey outdoor solutions specially designed to offer complete conversion stations with an extended DC input
voltage range and power range over 7,5 MVA per Station
These solutions include all necessary components to ensure a good performance and availability of the power
generation, including protections, inverters of the WD3 series and a customized MV Skid with MV transformer
and switchgear mounted on one platform ready for installation.
Inverter Station components can be integrated directly into a concrete slab or similar structure, fulfilling the
minimum requirements of each of the components.

Achieve extreme power conversion capacity with the flexibility of
a modular composition.

3 WD3 Power Units

WD3 - Created for Large-Scale Projects

Turnkey outdoor solutions especially
designed to offer complete conversion
stations with an extended DC input voltage
range and power range up to 7,6MVA.

GPTech WD3.0 is the best option for plants
development operating with the new
generation of 1500Vdc solar modules and
ESS

The best option to solve the challenges of
Utility-Scale projects.

Certifications Optional Services and
Warranty
• UL1741, UL840 • Reactive power compensation at
• IEEE 1547 night. No extra devices needed for • Global After Sales Service, Maintenance
• CEC/CIS Performance Testing VAR support and Technical Assistance 24/7

(California) • Up to 36 DC inputs protected by • Warranty Services
• IEC fuses (see configurations)
• EMC • Preventive Maintenance Programs
• CE Marking (Ask for details) • Remote monitoring
• Training Programs
• Extended warranty according to
customer needs

Offices

SPAIN USA
Headquarter
501 W Broadway, Suite 800
Avenida de Camas, 26-28 92101
PIBO San Diego California
41110 Bollullos de la
Mitación CHILE
Seville
Cerro El Plomo 5680
SOUTH AFRICA Departamento 301
Cómuna Las Condes
Floor Lancaster Gate, Hyde Santiago, Chile
Park Lane
Cnr. William Nicol Dr. & Jan
Smits Ave Hyde Park
Sandton 2196 Johannesburg


Click to View FlipBook Version