Title : ELECTRICAL SAFETY AUDIT

Client Name : DECATHLON SPORTS INDIA,

Address : M/s. Decathlon Sports India Pvt Ltd., Kalena Agrahara, Bhannerghatta Road,
Bangalore - 560036

Audit Date : 26th & 27th November 2012

Version :0

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

BUREAU VERITAS (INDIA) PVT. LTD.
No.272/D/12, "Harekrishna Mansion",
37th Cross, 1st Main, 8th Block,
Jayanagar, Bangalore - 560 082
Phone Nos: +91 80 2244 7770 Fax No: +91 80 2244 7765
Email: [email protected]

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

ELECTRICAL SAFETY AUDIT
DECATHLON SPORTS INDIA PVT. LTD., SPORTS STORE AT

Kalena Agrahara, Bhannerghatta Road, Bangalore-560036.

Vinod BHALEKAR D. GNANA SKANDAN 0 10/12/2012
Revision Status Date
Prepared by: Validated by:
(Name, Signature) (Name, Signature)

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

PREAMBLE:

This report deals with the Electrical Safety Audit of Decathlon Sports India Pvt. Ltd., Sports
Store at Kalena Agrahara, Bhannerghatta Road, Bangalore-560036. The report presents
conditions as well as results of the Electrical Safety Audit carried out as per scope of work
given below.

SCOPE OF WORK:
The proposed electrical safety audit was carried out as per the scope given below:

• Review the Electrical Safety aspects in the substations, electrical equipment.
• Audit / Review of compliance to Statutory requirements as per the Electricity Act

& the Indian Electricity Rules & relevant Indian standards & Codes of practice
including IS- 3043.
• Review of Statutory Electrical documents & records.
• Review of personnel protective equipments.
• Review/Audit of protection schemes, protective devices and Emergency push
buttons of the installation.
• Verification of periodical checking of the earthing as per IS-3043 and suggest
suitable recording.
• Training on Electrical fire safety & identifying the training needs.
• Review & Audit of Electrical preventive maintenance. (EPM).

• Audit of installation lighting.
• Review of corrective actions taken on last audit findings.
• Any other safety aspect as may be warranted after review.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

OBJECTIVES:

• Identify existing /potential fire and safety hazards in store.

• Study adequacy of existing measures, procedure and systems at place for
controlling identified hazards.

• Suggest required control measures in addition to existing ones accordingly to
minimize the risk.

• Improve compliance with relevant statutory provisions, standards and codes of
practices.

Following are the Exclusions from Bureau Veritas Scope:

The Bureau Veritas Scope does not cover the following:

• BV services are limited to the ware house premises only. Any and all other
facilities / areas of RPG shall be beyond BV scope.
Any aspects of Design or its modifications.
Structural Solidity & Seismic aspects of the facility
Fire & Personal Safety measures of the above specified areas.
Electro – Magnetic – compatibility (EMC) of the area.
All aspects of Testing, measurement, conformity assessment and functional
safety of the equipment and accessories being serviced by the facility.
Technical adequacy of the installations in terms of HVAC, Electrical, Fire
Safety, lifts, equipment etc., in the above specified areas.
All aspects of Energy Conservation.
Any tests or measurements those may be warranted as a part of safety audit.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

CONTENTS

1. Brief Description About Decathlon Sports India Page No.
2. Audit findings: 07 to 09

2. 01. Checklist with Observations and Recommendations 10 to 14
2.02. Examples of some observed practices with photograph 15 to 20
2.03 Document reviews, Statutory & mandatory records
2.04. Test Witnessed 21
2.05. Legends 22
2.06 List of Records and Documents Reviewed & Enclosed 22
3. List of Acts, Codes and Standards followed for this report 23
4. List of persons present during the meeting/visit 24
25

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

1. Brief Description about Decathlon Sports India.

Decathlon Sports India Ltd offers India's ever increasing need for sporting goods,
accessories and facilities.
The Decathlon Sports India unit at Bangalore is store where it allow you to find less than
one roof equipment for enthusiasts of all sports: Cricket, hockey, lacrosse, football, rugby,
and basket ball. Badminton, squash, tennis, table tennis, paddle and outcourt. Fitness,
gymnastics, yoga, dance and combat sports. Walking, trekking, mountaineering, skiing and
snowboarding. Running, cycling, roller-skating. Swimming, diving and surfing. Rowing
and sailing. Horse-riding, golf and archery.

Name and Address of M/s Decathlon Sports India Pvt. Ltd., Bangalore.
the Organization:

Kalena Agrahara, Bhannerghatta Road, Bangalore-560036.
Name and address of M/s. Electro Line, Bangalore.
Electrical Contractor:

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

**** PROPERTY DETAILS ***

Address where audit was conducted Decathlon Sports India Pvt Ltd.

Kalena Agrahara, Bhannerghatta Road,

Bangalore-560036.
Owner Or Person In Charge of Decathlon

Building 1. Mr. Michel Aballea (CEO)

(M) 919740577644

2. Mr. Franck Lejeune

(Country Operation Manager)

2. Mr. Sri Vyas - Stores Operation

(M) 095387 14860.

Building Owner
Mr. Reddy.

Fire Safety Director ,Deputy Fire Safety 1. Mr. Sri Vyas - Stores Operation

Director Name And Telephone No 2. Mr. Franck Lejeune

(Country Operation Manager)

Certificate of occupancy, Location License under Karnataka Shops And

where posted and duplicate attached. Establishment Rules is available and displayed.

Height Of building ,area ,class of Two Basement +Ground Floor + Five Floor +

construction Terrace
Area :-

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

Total Plot Area: 5964 Sq. m.
Building Area: 2564 Sq. m.
Store Floor : First Floor
Service Equipment in Use (Owner 01. Transformer 500 KVA, 11 Kv, Underground

Property) & connected Load. cable system.

02. Metering cubicle: 11 Kv RMU.

03. Transformer: 11/0.433 kV, 500 KVA.

04. Main Power Control Center-01 No.

Service Equipment in Use (Decathlon 01. Main LT Panel:

Property) & connected Load. 02. Change over panel: EB to DG.

03. AHU Panels- 2Nos.

04. Lighting/Raw power/UPS Distribution

Boards: 63 A, 4 pole.

05. UPS- 30 KVA. - 1No.

06. Air Condition System – One Split AC for

server and UPS system

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

Audit Findings:

2.01 Checklist with Observations and Recommendations

Electrical Safety Inspection Checklist Yes No N/A REMARKS

1. INSTALLATION AND GROUNDING.

01. Installations of all electrical equipments are a Reviewed & found
in order.
completed as per plan. Fire Pump Electrical
panels & Motors are
02. Have all electrical equipments are provided a to be earthed.
Earth pits are to be
with grounding connections? clearly identified &
to be maintained.
03. All Earthing pits were constructed and a Provided.

maintained as per IS 3043- 1987: Code of

practice for Earthing.

04. Have HT switchgear and Transformer yard a

provided with fencing?

05. Have areas with 500 volts or greater been a Provided. Wherever

posted with safety signs indicating "HIGH Yellow color

VOLTAGE”? background used to

be replaced with

Red background.

06. Is installed electrical equipment free from a Found In order.
recognized hazards likely to cause death or
serious physical harm to employees?

07. Switch, outlet, receptacle, device, and a Found In order.
junction boxes are of sufficient size to
provide free space for all conductors
enclosed in the box.

08. Is each service, feeder and branch circuit, at a Satisfactory.
its disconnecting means or over current
device legibly marked to indicate its
purpose?

09. Are disconnecting means provided to a Identification tags
disconnect conductors from the service to be provided for
entrance conductors easily accessible? cables wherever
found missing.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

Electrical Safety Inspection Checklist Yes No N/A REMARKS

10. Have technicians, involved with electrical a Trained. Copy of
License given by
equipment, circuits, or transmission lines, Local License Body
for Electrician to be
been trained by qualified personnel in safety kept in record.

and the proper techniques of first aid, Provided.

including rescue?

11. Sufficient access/approach and working a

space is provided and maintained around

electrical equipment such as panel boards,

switch boards and safety switches.

12. Are live parts of electrical equipment a Satisfactory.

operating at fifty (50) volts or more guarded

against accidental contact by being enclosed

in suitable cabinets or enclosures?

13. Are all electrical plugs of the dead front type a Provided.

plug and have all plugs with a removable

front been equipped with a protector?

14. Do plugs fit firmly when inserted into a Fits firmly.

mating connector or receptacle?

15. Electric panel boards, cabinets, boxes, and a Found in order.

switch enclosures are covered or isolated.

16. Illumination is provided for all working a Provided. Fire

space around service equipment, Pump Panel area

switchboards, or motor control centers lamps to be kept on

installed indoors. continuous.

17. Have all electrical equipments and lighting a In order.

circuits properly identified marked and easy

access for isolation during emergencies?

18. All disconnecting means, service, feeder and a Tag Out system to
be implemented.
branch circuits are legibly marked to

indicate its purpose, unless located and

arranged so the purpose is evident.

19. Test reports for the major electrical items like a Test reports for
Transformer, Metering Panel, Power Control cables & panels
& Distribution Panel, Cables etc., were were not available.
available?

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

Electrical Safety Inspection Checklist Yes No N/A REMARKS

20. Are records maintained in the maintenance, a Recent records
repair or calibration facility attesting to
adequacy of the ground of the electrical related to
system?
Measurement of

earth pit resistance

to be kept in record.

21. Are flexible cords and cables protected from a Found in order.
accidental damage?

22. Does each electrical outdoor installations a Satisfactory.
like, motor, starter, junction boxes, switch
boards and cabinet have an installed gland
plate, cover or canopy cover and are unused
openings in cabinets and boxes effectively
closed?

23. Is water or moisture prevented from entering a Prevented.
and accumulating within electrical cabinets,
panel boards and junction boxes?

24. Are weatherproof enclosures used in outside a Provided.
locations or wet locations?
Found in order. Fire
25. Is motor / machine operated equipment a Pump Motors to be
properly grounded? earthed.

26. Are flexible cords and cables prohibited from a Satisfactory.
use as a substitute for permanent wiring of a
structure, and prohibited from being run
through holes in walls, ceilings, or floors,
running through doorways, windows, or
similar openings?

27. Are flexible cords used only in continuous a Found in order.
lengths without splices or taps?

28. Are cable route marker is provided in the a DG Cable & Main
path of the main power cables which are laid Transformer HT
under the ground? cable to be provided
with Route Marker.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

Electrical Safety Inspection Checklist Yes No N/A REMARKS
Safety Protective Appliances

29. Are all 235 volt, single phase, lighting circuit a To be provided
with 30mA Leakage
protected by a ground-fault circuit current ELCB.

interrupter (GFCI)? To be provided
wherever not
30. In electrical shops where 80V dangerous a a found.

voltage exists is flooring and work surfaces

protected with a non-conductive material i.e.

safety rubber or vinyl matting as per IS…?

1.1. General & Statutory Requirements

31. Health & Safety policy seen? a Health & Safety
Policy to be
32. Are the premises registered with the Local a displayed.
Registered.
Electrical Authority Yes.
No to be Carried
33. Are fire extinguishers appropriate and a out.

serviced? Not applicable.

34. Are fire drills carried out? a In order.

35. Have the premises provided with protection a a Not Applicable.
against lightning? a a Found in order.
a
36. Fire Hydrant System is in place and hose reel
are placed within 75 Meters apart. a

Portable Tools

37. Portable tools are properly grounded,
unless double insulated and identified as
such.

39. Grounding adapters are green-colored rigid
ear, lug, or similar device.

Hazardous (Classified) Locations

40. Electrical equipment used in a hazardous
area is specifically designed for that area.

41. Electrically heated appliances are kept away
from combustible materials.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

2. 02. Examples of some observed practices with photographs, the risks &

suggestions

I. Transformer Yard:

Sl. No. Details of Observations Suggestions/Remarks Criticality (Critical

01. Earth Pits are found in open /Major / Minor)
condition. Even Funnel is
found damaged. Earth Pits are to be maintained as

per IS: 3043 Earthing Standard.

Major

02. Feeder Pillar is found earthing Any Electrical Equipment should

done at one side only. be earthed at two points

connected to two separate earth

pits.

Major

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

Sl. No. Details of Observations Suggestions/Remarks Criticality (Critical
/Major / Minor)

03. HT Cable Route Marking not HT cable Route Marking should

done. be done to avoid cable

damage/accident during

excavation.

Critical

II. Main LT Panel Area. Suggestions/Remarks Criticality (Critical
Sl. No. Details of Observations /Major / Minor)
Glanding should be done
01. AHU Panel: Glanding is not properly. Over diameter hole or Minor
done properly. under size glands should not be
preferred.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

Sl. No. Details of Observations Suggestions/Remarks Criticality (Critical

02. Utility Panel- Rubber mat is /Major / Minor)
not provided.
Rubber mats should be provided

to each switch Board.

Major

03. Main LT Panel: Cable cores Cable cores bending should not

are found with sharp bend. be sharp to avoid heating at

bending position. Cable

Manufacturer’s Guideline should Major

be followed.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

Sl. No. Details of Observations Suggestions/Remarks Criticality (Critical
04. Proper earthing should be done. /Major / Minor)

Major

Improper earthing connection
is found for AHU Panels.

III.DG set : Suggestions/Remarks Criticality (Critical
Sl. No. Details of Observations /Major / Minor)
For Battery connections, Caps to
01. be provided.

Major

Battery Earth connections are

found in open condition.

02. DG Neutral connection is not DG Neutral connection with

accessible. Earthing Pit connection strip

should be kept accessible.

Major

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

IV.Earth Pits: Suggestions/Remarks Criticality (Critical
Sl. No. Details of Observations /Major / Minor)
For Earth Pit joints should be
01. provided with conducting unti- Major
rusting solution & funnel should
be kept clean.

DG Earth Pits are found with Major
rusted joints & blocked
funnel.
02. All the Earth Pits should be

identified with No., date of
calibration, Resistance value &
Due date.

No identification has provided
for Earth Pits.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

V. Store Area: Suggestions/Remarks Criticality
Sl. No. Details of Observations For Human safety point of ELCB (Critical /Major /
Minor)
01.

with 30mA Leakage current

sensing device should be used.

Critical

Ground Fault sensing units Junction box & unused entries
(ELCB) are not used for should be closed to avoid entries
distribution system. of insects.
02.

Major

At some places, Junction box is

found open.

03. Tools for Electrical maintenance Decathlon Standard for

to be ensure for Decathlon Electrical maintenance tools Major.
Standard.

should be followed.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

VI.Pump Room: Suggestions/Remarks Criticality
Sl. No. Details of Observations All Electrical equipments should (Critical /Major /
Minor)
01.

be earthed at two points. Major

Motors & Fire Pump Panel are Indicating lamps should be kept
found without earthing. healthy to avoid
02. misunderstanding.

Major

Indication Lamp is found not
glowing.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

2.03. Document reviews, Statutory & mandatory records:

Sl. No. Details of Observations Suggestions/Remarks

01. Checklist should be filled fully with
details if required.

Checklists are found not filled fully.

02. Installation & commissioning reports of Installation & commissioning reports

all Electrical Equipments are not found of all Electrical Equipments should be

available. kept in records.

03. Earth pit resistance measurement record Earth pit resistance measurement

is not found available. record should be kept in records.

04. Manufacturer’s Test certificates for Test certificates of all purchased Major

Cables, Transformers are not found Electricals equipments should be kept

available. in records.

05. Any equipment defects mentioned in Any problems should be closed &

the check list is found not recorded for recorded with date time.

close.

06. Certificate of Accoustics Enclosure for Certificate of Accoustics Enclosure for

DG complying with Central Pollution DG complying with Central Pollution

Control Board Norms/ Requirements is Control Board Norms/ Requirements

not found available. should be kept in records.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

2.04 Test Witnessed:

Earth Resistance Measurement Test.

2.05 Legends:
Critical: Most essential, to be required immediately.
Major: Advise to attend without delay.
Minor: To be attended as Engineering practice & rules.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

2.06. LIST OF RECORDS AND DOCUMENTS REVIEWED.

1. General arrangement drawing & Single line diagram for the Electrical installations.
2. Manufacturer test report for Switchboards.
3. Field service report for UPS.
4. Field service report for DG Set.
5. Zone Classification of store area.
6. Daily inspection check list for Electrical system.
7. Annual Maintenance planning.

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

03. List of Acts, Codes and Standards followed for this report :

1. IS 5216-1969; Guide for safety procedure & practices in electrical work.
2. IS 3043:1987 – Code of Practice for Earthing
3. IS 1886-1961; Code of practice for installation & maintenance of Transformer.
4. IS 5424-specification for Electrical earth mat.
5. IS 2309:1989 – Code of Practice for Protection Buildings and Allied Structures against

Lightning
6. IS 1913(part-1):1978 – General & Safety Requirements for Luminaries.
7. IS 5578:1984 – Guide for Marking of Insulated Conductors.
8. National Building Code.
9. IS-3770 Specification for safety gloves.
10. IS-15301; Code of practice for installation & maintenance of fire pump.
11. IS-2878: Specification for Co 2 type fire extinguisher confirming to IS 2878

ELECTRICAL SAFETY AUDIT OF DECATHLON SPORTS INDIA PVT. LTD.,
Kalena Agrahara, Bhannerghatta Road, Bangalore- 560036
Bureau Veritas Project No. IND.B.7.12.094

04. List of persons present during the meeting/visit

1. Mr. Sri Vyas - Stores Operation (M) 095387 14860.
----------- End of Report ----------