The words you are searching are inside this book. To get more targeted content, please make full-text search by clicking here.

Catalog RMU RM6 2020 (แผ่นพับ)

Discover the best professional documents and content resources in AnyFlip Document Base.
Search
Published by MaY NanNaPat, 2020-11-03 04:39:16

Catalog RMU RM6 2020 (แผ่นพับ)

Catalog RMU RM6 2020 (แผ่นพับ)

Set series

RM6

Catalog 2020
Gas Insulated Ring Main Unit
Up to 24 kV

se.com/rm6

Overview EcoStruxure ready

IoT connected MV equipment

RM6 connected Advanced: suitable for complex
and smart grids

Advanced features

Effective asset management, increased safety, 24/7 connectivity,
network management

The RM6 Connected Advanced solution is designed to leverage solution benefits,
in addition to bringing the best IoT capabilities for reliable and efficient asset
management.
The RM6 Connected Advanced solution contributes to an open and transparent
information solution for smart grid medium voltage distribution networks.

The RM6 Connected Advanced cubicle is a complete integrated solution that
consists of:
• A proven and robust RM6 RMU with voltage and current sensors
• An RTU (T300) located in an LV cabinet, located on top of the RM6
• A fully tested solution for peace of mind
• Plug and play installation

PM104881 PM106733

PM 106308 Easergy T300 PM107093 VPIS PM106311
Thermal sensor LPVT

PM106327 PM106309

Bushing CT Measurement
CTs

RM6 Connected Advanced - Customized version *
* Contact us for further details

schneider-electric.com RM6 catalog | 21

Range General characteristics
description

RM6 is an indoor gas-insulated switchgear Electrical characteristics
up to 24kV for secondary distribution
networks. Rated voltage Ur (kV) 12 17.5 24
Frequency f (Hz) 50 or 60
Insulation level 50
PM107098 Insulation (1) Ud (kV rms) 28 38 60
PM107099 Industrial frequency 125
50 Hz 1 mn Isolation (2) Ud (kV rms) 32 45 145
Impulse 1.2/50 μs
Insulation (1) Up (kV peak) 75 95
Tank internal arc withstand
Seismic Withstand Isolation (2) Up (kV peak) 85 110

Vibration Withstand 20 kA 1 s

Severity class 2, acceptance class 2
as per IEC62271-210 (2013)

NF EN60068.2.6.2 (2008) (3)

(1) Phase-to-phase, phase-to-earth
(2) Across the isolating distance
(3) Please contact Schneider Electric for details

RM6 meets the definition of a "sealed 3
pressure system" as laid out by the 5
IEC standard.
4
RM6 is made up of the following elements:
1
1. A stainless steel tank filled with SF6 gas
(at 0.23 bar relative pressure), sealed for life 2
and containing the busbar and all live switching 2
components such as the switch disconnector, the
earthing switch, the fuse switch combination or the
circuit breaker

2. O ne to four (five optional) cable compartments
with interfaces to connect to the network or the
transformer

3. User interface with single line diagram, actuators
and LV components

4. Manual or motorized operating mechanism
compartments

5. Earthing circuit with visible earthing contacts

2

28 | RM6 catalog schneider-electric.com

Range General characteristics
description
Cubicle Width (mm) Depth (mm) Height (mm) Weight (kg)
Complete board 1142 135
configuration table NE-I 472 670 1142 135
1142 135
schneider-electric.com NE-B 572 670 1142 135
1142 135
NE-D 572 670 1142 135
1142 185
DE-I 532 670 1142 145
1142 145
DE-B 632 670 1142 420
1142 135
DE-D 632 670 1142 135
1142 135
DE-Q 632 670 1142 155
1142 180
DE-Ic 632 670 1142 180
1142 180
DE-Bc 632 670 1142 155
1142 240
DE-Mt 1106 840 1142 250
1142 240
DE-O 532 670 1142 275
1142 240
LE-O 502 670 1142 250
1142 240
RE-O 502 670 1142 275
1142 240
NE-II 829 670 1142 250
1142 240
NE-BI 829 670 1142 275
1142 320
NE-DI 829 670 1142 330
1142 340
NE-QI 829 670 1142 330
1142 340
RE-II 859 670 1142 355
1142 390
NE-III 1186 670 1142 320
1142 330
NE-IBI 1186 670 1142 330
1142 340
NE-IDI 1186 670 1142 340
1142 355
NE-IQI 1186 670 1142 390
1142 320
RE-III 1216 670 1142 330
1142 330
RE-IBI 1216 670 1142 355
1142
RE-IDI 1216 670 1142 450 to 530 (2)
1142 455 to 535 (2)
RE-IQI 1216 670 460 to 540 (2)

DE-III 1246 670

DE-IBI 1246 670

DE-IDI 1246 670

DE-IQI 1246 670

NE-IIII 1619 670

NE-IIBI 1619 670

NE-BIBI 1619 670

NE-IIDI 1619 670

NE-DIDI 1619 670

NE-IIQI 1619 670

NE-QIQI 1619 670

RE-IIII 1649 670

RE-IIBI 1649 670

RE-IIDI 1649 670

RE-BIBI 1649 670

RE-DIDI 1649 670

RE-IIQI 1649 670

RE-QIQI 1649 670

DE-IIII 1679 670

DE-IIBI 1679 670

DE-IIDI 1679 670

DE-IIQI 1679 670

NE-I_I_I(1) 2000 670

RE-/LE-I_I_I (1) 2030 670

DE-I_I_I (1) 2060 670

(1) 5 function tanks
(2) Weight depends on the choice of function

RM6 catalog | 29

Range General characteristics
description
Available functions

Basic unit characteristics

Rated voltage (kV) 12 12 12 12 17.5 17.5 17.5 17.5 24 24 24 24 24 24 24 24 24 24

Short-time withstand (kA rms) 21 21 25 25 21 21 21 21 12.5 12.5 12.5 16 16 16 20 20 20 20
current
Duration (s) 1 1 1 1 1 3 1 3 1 1 1 1 1 1 1 3 1 3

Rated current (A) 200 630 200 630 200 200 630 630 200 400 630 200 400 630 200 200 630 630

Extensions Functions

I p p pp pp p

D ppp ppp

P p pp pp

QI p p p p p p

DI p p p p p p

PI p pp pp

II p p p p p p

IQI pp pp p pp pp

NE IIQI pp pp p pp pp
QIQI pp pp p pp pp

IDI p pp pp pp pp

IIDI p pp pp pp pp

DIDI p pp pp pp pp
III p pp pp
IIII p pp p pp pp
IPI p pp pp
IIPI p pp p pp pp
PIPI p pp pp
O pp pp p p
IQI pp pp pp
IIQI pp pp p pp
QIQI pp pp pp
IDI p pp p
IIDI p pp pp
RE DIDI p pp p pp pp
II p pp
III p p p pp p
IIII p pp pp
IPI p pp p pp pp
IIPI p pp pp
PIPI p pp p pp pp
LE O pp pp pp
pp pp pp p

pp pp

pp pp

p pp

p pp

p pp

p

p

p

p pp

I p pp p pp pp

PC pp p pp

IC pp p pp

O pp p p p pp p

Q p p pp p p pp
p pp
D p pp p p pp
p p pp
P p pp p p pp
p pp
DE IQI pp pp p pp
IIQI p pp
pp pp p pp
p pp
IDI p pp p pp
p pp
IIDI p pp

III p pp

IIII p pp

IPI p pp

IIPI p pp

Mt pp

N.B.: D and Q functions limited to 200 A
NE: non-extensible, RE: right-extensiblet, LE: left-extensible, DE: double-extensible.
All performances are available for RM6 Free Combination cubicles.

32 | RM6 catalog schneider-electric.com

Function/ Functional overview
module description
Choice of functional units

A wide choice of RM6 functions

RM6 benefits from a wide choice of MV functions enabling:
• The connection, power supply and protection of transformers on a radial or

open-ring network via 200 A circuit breakers with an independent protection
chain, or via combined fuse-switches
• The protection of lines by a 630 A circuit breaker
• MV Metering of private MV/LV substations.

The RM6 functions are described in the table below.

Function Network Line feeder Transformer feeder Network coupling Cable MV metering
switch
Functional connection
unit
Device I BDQ IC BC O Mt
Switch
630 A 630 A 200 A Combined 630 A
switch circuit breaker
circuit breaker circuit breaker fuse-switch

DE59759b
DE59735b
DE59736b
DE59737b
DE59738b
DE59739b

DE59740
DE59741
630 A 200 A 630 A

Single
line
diagrams

PM107091 Scalability of RM6

To support the evolution of your distribution network, RM6 can be extended with
a range of functions making it a truly scalable system.
The addition of one or more functional units can be carried out by simply adding
modules that are connected to each other via the busbar using dedicated field
bushings.
There are different types of extensible RM6:
• Right-extensible (-RE type)
• Left-extensible (-LE type)
• Extensible on both sides (-DE type)
• Non-extensible (-NE type)

44 | RM6 catalog schneider-electric.com

Components Components list
and accessories

Function type I B D Q O Ic Bc DE-Mt
p p (2)
Motorization for remote Motorization including auxiliary contacts

operation (LSBw 2 NO-2 NC and ESw 1 O/C)

Motorization including shunt trip coil and auxiliary contacts pp p (2)
circuit breaker (CB 2 NO – 2 NC and ESw 1 O/C)

Motorization including auxiliary contact fuse-switch p (1)
combinations
(LBSw 2 NO – 2 NC)

Auxiliary contacts alone For main switch position indication, LSBw 2 NO – 2 NC and p p (1)
(this option is included in ESw 1 O/C pp p (1)
remote operation option) p (1)
For circuit breaker position indication, CB 2 NO – 2 NC and pp (1)
ESw 1 O/C pp p

For fuse-switch combinations position indication, LBSw 2 NO
– 2 NC

Front door of cable Bolted - Removable with ESw interlocking - Removable with

connection compartment ESw interlocking and LSBw interlocking

Self-powered fault Flair 21D - Flair 22D - Flair 23D - Flair 23DM - Amp 21D

passage and load current p (1)

indicators (1)
(1)
Key locking devices Type R1 - Type R2 pp p
pp p (1)
Type R6 - Type R7 - Type R8
(1)
Shunt trip coil for 24 VDC - 48/60 VDC - 120 VAC - 110/125 VDC – 220 VAC - p pp p (1)
external tripping 220 VDC/380 VAC (1)
(1)
Undervoltage coil 24 VDC - 48 VDC - 125 VDC - 110-230 VAC p pp p (1)
(1)
Protection relay for CB VIP 40 p (1)
transformer protection VIP 45 (1)
p (1)
(1)
VIP 400 pp p (1)
(1)
VIP 410 pp p (1)

Voltage detection VPIS pp ppppp

VDS pp ppppp

Forbidden closing under fault 1NC pp p

Auxiliary contact D or B tripping pp p

Auxiliary contact for fuse blown p

With or without earthing switch pp

Arc Killer: RM6 arc short-circuiting device (2) p

Screened Voltage Transformers (phase-to-phase or phase-to-earth)  p

(1) See specific page for DE-Mt
(2) Available for non extensible cubicles

52 | RM6 catalog schneider-electric.com

Components Protection relays
and accessories
VIP 40, 45, 400, 410 selection guide
VIP relay to be added
PM104606 VIP series
58 | RM6 catalog
Integrated self-powered protection optimized for RM6.

Transformer protection: General protection:
• V IP 40 • VIP 400
• VIP 45 • VIP 410

VIP

ANSI code 40 45 400 410

Protection functions

Phase overcurrent 50-51 pppp
ppp
Earth fault phase Standard (sum of 51N
current method) p

High sensitivity pp
(earth fault CTs) p

Thermal overload 49

Cold load pick-up

Control and monitoring functions

CB tripping Mitop Mitop Mitop Mitop
p p p p
Trip circuit supervision 74TC p p

Time-tagged events Local on display (5
last trips)

External tripping input p
p
Cumulative breaking current, number of
trip orders

Overcurrent and Number of phase pp
breaking profile and earth trips (2)

Serial communication Modbus RS485 p
port

Logic relay inputs (except TCS) used for: 1

External tripping 1

Logic relay outputs used for: 3

Watchdog By
modbus

Customized output 3
via setting

Measurement functions

Phase current pppp

Earth current ppp

Phase peak demand current pppp

Phase peak demand current p

Power supply

Type of supply Self-powered or auxiliary Self Self Self DUAL

Power

(1)

Minimum 3 phase load 4 A 4 A 7 A (3)
currents
to activate the VIP

(1) The protection is self-powered. Auxiliary power is only used for communication and very
sensitive earth fault protection.

(2) The number of trips is displayed in 4 levels:
For D01 and D02: < 200 A, < 2 kA, < 8 kA, > 8 kA
For D06 and D06H: < 630 A, < 10 kA, < 20 kA, > 20 kA.

(3) 14 A with 630 A CBs

p Function available

schneider-electric.com

Installation and Dimensions and
connection installation conditions

1 function module DE59778

Function Weight (kg) Length (mm)

Regular RM6

I L = 572

NE D 135 L = 572 1142
703
B L = 572 437

I L' = 472 + 30 + 30 = 532 703 30 L 30
L'
DE D 135 L' = 572 + 30 + 30 = 632
B
L' = 572 + 30 + 30 = 632

Q 185 L' = 472 + 30 + 30 = 532

RE L' = 472 + 30 = 502

LE O 135 L' = 472 + 30 = 502 670
710
DE L' = 472 + 30 + 30 = 532

DE Ic 145 L' = 572 + 30 + 30 = 632
Bc L' = 572 + 30 + 30 = 632

2 function modules DE59779_2

Function Weight (kg) Length (mm)

Regular RM6

Q I 180 L = 829
NE D I, B I L = 829

I I 155 L = 829 1142

RE I I 155 L' = 829 + 30 = 859 703
Free Combination
RM6 Free Combination 703 145 145 145 145 example
NE L = 1052

LE L' = 1052 + 30 = 1082

RE L' = 1052 + 30 = 1082

DE L' = 1052 + 30 + 30 = 1112

670 30 L 30
710 L'

3 function modules

Function Weight (kg) Length (mm) DE59780

Regular RM6

I Q I 275 L = 1186

NE I I I 240 L = 1186
I D I L = 1186

I B I 250 L = 1186 1142
703
I Q I 275 L' = 1186 + 30 = 1216
30
RE I I I 240 L' = 1186 + 30 = 1216
I D I 703L' = 1186 + 30 = 1216 LE: left-extensible
107 107 145 145 DE: left- and right-extensible
I B I 250 L' = 1186 + 30 = 1216

I Q I 275 L' = 1186 + 30 + 30 = 1246

DE I I I 240 L' = 1186 + 30 + 30 = 1246
I D I L' = 1186 + 30 + 30 = 1246

I B I 250 L' = 1186 + 30 6+7300 = 1246 30 L
RM6 Free Combination L = 1532 710 L'
NE
Type of tank
LE L' = 1532 + 30 = 1562 NE: non-extensible
RE: right-extensible
RE L' = 1532 + 30 = 1562

DE L' = 1532 + 30 + 30 = 1592

RM6 Free Combination with bus coupler

RE L' = 1532 + 30 = 1562

DE L' = 1532 + 30 + 30 = 1592

82 | RM6 catalog schneider-electric.com

Installation and Dimensions and
connection installation conditions

4 function modules

Function Weight (kg) Length (mm) DE59781

Regular RM6

I I Q I 355 L = 1619

I I I I 320 L = 1619

NE I I D I 330 L = 1619 1142
I I B I 330 L = 1619 703
30
Q I Q I 390 L = 1619
30
B I B I 340 L70=31619 145 145 107 107
I I Q I 355 L' = 1619 + 30 = 1649 1606
1174
I I I I 320 L' = 1619 + 30 = 1649

RE I I D I 330 L' = 1619 + 30 = 1649
I I B I 330 L' = 1619 + 30 = 1649

Q I Q I 390 L' = 1619 + 30 = 6176049 30 L

D I D I 340 L' = 1619 + 30 =7110649 L'

I I Q I 355 L' = 1619 + 30 + 30 = 1679

DE I I I I 320 L' = 1619 + 30 + 30 = 1679
I I D I 330 L' = 1619 + 30 + 30 = 1679

I I B I 330 L' = 1619 + 30 + 30 = 1679

5 function modules DE59789

Function Weight (kg) Length (mm)

Regular RM6 470 L = 2000
520 L = 2000
IDIDI 495 L = 2000 1142
475 L'7=032000 + 30 = 2030 107 107
NE IQIQI 455 L' = 2000 + 30 = 2030
480 L' = 2000 + 30 + 30 = 2060 30
IBIQI 495 L' = 2000 + 30 + 30 = 2060

RE IDIDI 145 145
IIIII

DE IDIDI
IIIQI

670 L
710 L'

Metering cubicle

Function Weight (kg) Length (mm)DE59783
DE59782
RM6 metering cubicle with LV compartment

DE DE-Mt 420 L = 1106

RM6 metering cubicle without LV compartment

DE DE-Mt 400 L = 1106

Arrester option

175

1142

710 840 1106
859 880
901

schneider-electric.com RM6 catalog | 83

Installation and Civil works
connection

For connection to a “network” or “transformer” via a circuit breaker

Cable Cable Cross-section Bending Cable entry through a trench Cable entry through a duct
insulation Single (mm2) radius
Three P (plug-in) P (disconnectable) P (plug-in) P (disconnectable)
Dry y 150 500
insulation 185 to 300 600 400 400
y 150 550
185 650 520 520
y 150 500
185 to 300 675 660 660
y 95 635
150 to 300 835 770 770

Paper Single 580 580
impregnated Three
non-draining 800 800
type
750 750

970 970

The “network” cables can be run either: DE58060

• Through trenches, passages, ducts
• Through the left or right side

40 min. 70 min.
50 max. 80 max.

P P
40 min. R
50 max.
90 min.
120 max.

Trench depth P or RM6 without plinth

Note: trench depths can be reduced and sometimes eliminated by adding a plinth.

For “transformer” connection via a fuse-switch

Cable Cable Cross-section Bending Plug-in Plug-in Disconnectable (2)
insulation (mm2) radius Elbow connector Straight connector P

Dry Single 16 to 35 335 100 520 335
insulation 50 to 70 400 100 520 440
440 100 550 440
95 to 120 435 520 725
500 520 800
Three 35 545 550 860

50 to 70

95
(1) Leave a clearance of 100 mm

(2) 520 mm plinth must be used

DE57962

• The cross-sections of “transformer” cables are (1)
generally smaller than those of the “network”
cables. All the cables are then run through the
same space

• When straight MV connectors are used, the
depth P indicated below can be greater than
that of the “network” cables

schneider-electric.com RM6 catalog | 87

Installation and Cable connections
connection
Selecting bushings and connectors

• The profiles, contacts and dimensions of the Appropriateness for use
RM6 connection interfaces are defined by the
IEC 60137 standard. T he bushings carry the electrical current from the outside to the inside
of the enclosure, which is filled with SF6 gas, ensuring insulation between
• 1 00% of the epoxy resin interfaces undergo the live conductors and the frame.
dielectric testing at power frequency and There are 3 types of bushing, which are defined by their short-time withstand
partial discharge tests. current:
• Type A: 200 A: 12.5 kA 1 s and 31.5 kA peak (plug-in)
• A n insulated connector must be used in order • Type B: 400 A: 16 kA 1 s and 40 kA peak (plug-in)
to guarantee the dielectric performance over • Type C: 630 A: 25 kA 1 s, 21 kA 3 s and 62.5 kA peak (disconnectable M16)
time. Schneider Electric recommends using
nkt connectors.

MT55039 How to define the connection interface

type A type B / C The connection interfaces depend on specific criteria, such as:

Types of connection interface Installation
• Current rating of the connected equipment: 200, 400, 630 A
• S hort-time withstand current for 12.5 kA, 16 kA, 25 kA switch and circuit breaker

functions
• For the fuse-switch combination function, as the short-circuit current is limited

by the fuse, the connection interface will be of type A (200 A)
• Minimum phase expansion length
• Connection type:

--plug-in: multicontact ring
-- disconnectable: bolted
• Output position: straight, elbow.

Cable
• Specified voltage:

--of the cable
-- of the network

• Type of conductor:
-- aluminium
-- copper

• Cross section in
• Insulation diameter
• Cable composition:

-- single-core
-- 3-core

• Insulation type:
-- dry
-- paper impregnated (non-draining type)

• Type of screen
• Armature

This information must be provided to give a full explanation of the connection
interfaces.

88 | RM6 catalog schneider-electric.com


Click to View FlipBook Version