The words you are searching are inside this book. To get more targeted content, please make full-text search by clicking here.
Discover the best professional documents and content resources in AnyFlip Document Base.
Search
Published by nhumsamshuk, 2023-01-09 23:55:24

Ultra Sonic Manual

Ultra Sonic Manual

-1-

Contents

1 . I n t r o d u c t i o n .............................................................................................................................- 1 -
§ 1.1 Preface.............................................................................................................................. - 1 -
§ 1.2 Features............................................................................................................................ - 1 -

2 . P r o d u c t I n t r o d u c t i o n .........................................................................................................- 2 -
§ 2.1 Data Sheet........................................................................................................................ - 2 -
§ 2.2 Dimension&Weight......................................................................................................... - 3 -
§ 2.3 Performance Error Curve.............................................................................................. - 4 -
§ 2.4 Flow Range.......................................................................................................................- 5 -
§ 2.5 Pressure Loss Curve......................................................................................................- 5 -

3 . I n s t a l l a t i o n I n s t r u c t i o n ....................................................................................................- 6 -
§ 3.1 Choose the installation point........................................................................................ - 6 -
§ 3.2 Installation Method..........................................................................................................- 6 -
§ 3.3 Communication and Signal Output............................................................................. - 7 -

4 . M e n u W i n d o w s ...................................................................................................................... - 8 -
§ 4.1 Display and Operation....................................................................................................- 8 -
§ 4.2 Operation Method........................................................................................................... - 9 -
§ 4.3 Digital Display Table..................................................................................................... - 10 -
§ 4.4 Main Menu...................................................................................................................... - 12 -
§ 4.5 Secondary Menu 1........................................................................................................- 14 -
§ 4.6 Secondary Menu 2........................................................................................................- 17 -
§ 4.7 Month Cumulative Data Menu....................................................................................- 19 -
§ 4.8 Date Cumulative Data Menu...................................................................................... - 19 -
§ 4.9 Batch Controller and Time-accumulated Menu......................................................- 20 -

5 . H o w To ...................................................................................................................................... - 24 -
§ 5.1 How to modify the unit................................................................................................. - 24 -
§ 5.2 How to modify the cumulative flow of the decimal point position.......................- 24 -
§ 5.3 How to reset the time................................................................................................... - 24 -

- -2--
§ 5.4 How to judge the water meter works properly........................................................ - 24 -
§ 5.5 How to operate the calibration windows.................................................................. - 25 -
§ 5.6 How to operate the built-in batch controller............................................................ - 26 -
§ 5.7 How to modify time point of the time-accumulator................................................ - 26 -
§ 5.8 How to modify the communication address............................................................ - 27 -
§ 5.9 How to reset the secondary address of M-BUS.....................................................- 27 -
§ 5.10 How to modify the infrared communication rate.................................................. - 28 -
§ 5.11 How to modify communication rate of RS485/M-bus..........................................- 28 -
6 . C o m m u n i c a t i o n ................................................................................................................... - 29 -
§ 6.1 Manual wireless Meter Reading................................................................................ - 29 -
§ 6.2 Wireless Network Meter Reading Automatically.................................................... - 29 -
7 . F a u l t H a n d l i n g ...................................................................................................................... - 30 -
§ 7.1 Fault Handling................................................................................................................- 30 -

T3 series Ultrasonic Water Meter -3-

1. Introduction

§ 1.1 Preface

The T3 series is specially designed for urban water supply and building-use
according to the GBT 778.1-2007、ISO-4064、JJG162-2009 standard.
The conventional water meters suffer from the drawbacks that they are only
operable at a higher flow rate and are insensitive to a small flow rate. However, the
water meter can help tackle the bottleneck. And the meter is highly adaptable to
diversified industrial conditions.
The water meter be adapted by the company’s newly-developed unique advanced
transit-time measurement technology , with the remarkable features of low power
consumption, wide measuring range ratio, stable and reliable measurement.
In the structure, the components take the IP68 program, that is, each component is of an
IP68 protection level, to ensure long time operation though water in the inside
meter.The wireless power and various communication interface can be matched to
the meter to achieve remote meter reading.
This series of water meter’s production process is automatic or semi-automatic, including
automatic detection of circuit boards, the automation of the circuit board’s high-low
temperature test machine, the automation of potting and calibration process, ensuring that
every machines out of the factory are qualified.

§ 1.2 Features

 Double beam ultrasonic sensors for high accuracy and reliable operation
 Less than 0.01 m/s starting velocity
 Multi line 9 digital LCD accumulative flow and 4 digital for instantaneous flow
 Automatic power saving function under the empty pipe or long-term fluid

stationary state
 IP68 protection, ensure long-term operation though water in the inside meter
 Date cumulative record and data acquisition function
 Various kinds of communication interface:TTL levels pulse output and USART

interface,convenient to connect the low power consumption equipment; RS485;
Infrared communication interface; support CJ-188 communication
 Support MODBUS,M-BUS ,HART communication protocol
 Output: Two way isolated pulse output(pulse equivalent and output pulse can be
arbitrary programmed); two-wired system 4-20mA output
 Software online upgrade function
 With the two way PT1000 temperature transducer, which can realize the heat
measurement
 Built-in batch controller and time accumulator
 Various of Units selected, including Cubic meter, USA gallon, Cubic feet and Liter
 Built-in Lithium battery for 6 years life expectancy

T3 series Ultrasonic Water Meter - 4 -

2. Product Introduction

§ 2.1 Data Sheet

Item Specification
Water, Sewage, Seawater(Other liquid need to
Measurement Range customized),liquid should be full of the pipeline
0.1-30℃
Medium Temperature Tempe rat ur e : -10~ 4 5 ℃ ; Hum id it y ≤ 100% ( RH )
Working Environment 1.6MPa/2.5Mpa optional
Working Pressure
The sensitivity of U3
upstream flow field
The sensitivity of D0
downstream flow field
Climatic and mechanical C class
environment class
Electromagnetic E2 class
compatibility class
Communication Interface RS485/USART/Infrared
Output Signal Two way OCT output/TTL pulse output/4-20mA output
Power supply Built-in Lithium battery(3.6V)/ External DC 8~36V
Protection Class IP68
Multi line 9 digital LCD display accumulative flow, 4
Digital Display digital display for instantaneous flow, state prompt and
units
Data Storage EEPROM/FLASH
Measuring:1 times/second(2~4 times/second
Measurement Cycle optional);Verification:4 times/second

Power Consumption <2.7AH/Year, 6 years life expectancy

T3 series Ultrasonic Water Meter -5-

§ 2.2 Dimension&Weight

DN50-DN300

W1 W2

L C D2D1D
H2 f
2 Unit:mm
H 1
1 H
H
L
W1 W2

Dimension Flange Dimension

Nominal Flange Bolt Hole Bolt hole Sealing Flange Weight Pressure
Size
DN(mm) L H1 H2 W1 W2 Diameter Center *Quantity surface thickness kg MPa

D D1 φ * n D2 f c

DN50 200 70 131 76 76 165 125 18×4 102 2 19 10.0 1.6

DN65 200 75 135 79 79 185 145 18×4 122 2 20 11.5 1.6

DN80 225 94 132 94 94 200 160 18×8 138 2 20 13.6 1.6

DN100 250 104 140 104 104 220 180 18×8 158 2 22 18.6 1.6

DN125 275 117 148 117 117 250 210 18×8 188 2 22 23.5 1.6

DN150 300 134 155 114 114 285 240 22×8 212 2 24 30.0 1.6

DN200 350 165 254 165 165 340 295 22×12 268 2 26 35.5 1.6

DN250 450 197 269 197 197 405 355 26×12 320 2 29 58.0 1.6

DN300 500 223 287 223 223 460 410 26×12 370 2 32 76.0 1.6

DN15-DN40 T3 series Ultrasonic Water Meter - 6 -

L

2
W
1
W

Nominal Dimension Thread Connection
Size
DN(mm) Thread Thread Thread Weight Press.

L H1 H2 W1 W2 Connection Connection Length kg MPa

AB

DN15 110 17.5 168 58 90 G3/4B G3/4B 10 2.2 2.5

DN20 130 24 173 58 90 G1B G1B 12.5 2.3 2.5

DN25 160 25 175 58 90 G11/4B G11/4B 13 2.5 2.5
DN32 180 31 177 58 90 G11/ 2 B G11/ 2 B 14.5 2.8 2.5

DN40 200 181 31 58 90 G2B G2B 18 3.3 2.5

§ 2.3 Performance Error Curve

T3 series Ultrasonic Water Meter -7-

§ 2.4 Flow Range

Nominal Flow rate (m³/h)

Diameter R Starting Minimum Transitional Permanent Overload
Flowrate
( mm) Flowrate Flowrate Flowrate Flowrate
Q4
Q1 Q2 Q3
3.125
DN15 200 0.003 0.0125 0.020 2.500 4.000
5.000
DN20 200 0.0035 0.016 0.030 3.200 7.875
25.000
DN25 200 0.007 0.020 0.030 4.000 50.000
78.750
DN32 200 0.010 0.032 0.0504 6.300 125.000
200.000
DN40 200 0.015 0.100 0.160 20.000 250.000
312.500
DN50 100 0.030 0.400 0.640 40.000 500.000
500.000
DN65 100 0.059 0.630 1.008 63.000 787.500

DN80 100 0.064 1.000 1.600 100.000

DN100 100 0.094 1.600 2.560 160.000

DN125 100 0.120 2.000 3.200 200.000

DN150 100 0.270 2.500 4.000 250.000

DN200 100 0.315 4.000 6.400 400.000

DN250 100 0.508 4.000 6.400 400.000

DN300 100 0.770 6.300 10.080 630.000

§ 2.5 Pressure Loss Curve

T3 series Ultrasonic Water Meter - 8 -

3. Installation Instruction

§ 3.1 Choose the installation point

Correct installation point Wrong installation point

ps:Arrow direction is fluid flow direction.

§ 3.2 Installation Method

(1)Cut the pipeline on the installation point, the cutting length according to the
water meter dimension(Water meter length L+sealing gasket thickness+10mm)

(2)Pls choose 3 point on the flange to be spot-welded, then take off the water
meter, finish full welding the flange

T3 series Ultrasonic Water Meter -9-

(3)After the welding flange cooling, pls install the water meter between the

flange with sealing washer and fasten the screw

ps: Arrow direction is fluid flow direction.

§ 3.3 Communication and Signal Output

Standard:
1 485+(A)
12标23配4484D8:558-C+(5(8BA--))(36BV)
3 44G-2N0mDA+

4 4-2 0mA-

Can complete the wiring junction without opening the water meter cover

Provide below communication interface and output
1. RS485
2. M-BUS
3. DC8-36V
4. Two-wired system 4-20mA output
5. OCT1(open collector output 1)
6. OCT2(open collector output2)
7. C1(TTL level pulse output 1)
8. C2(TTL level pulse output 2)
PS: when ordering, you can choose any two of the above communication interface or
output, lead to the external junction box

T3 series Ultrasonic Water Meter - 10 -

4. Menu Windows

§ 4.1 Display and Operation Support Bi-directional Flow Measurement

58×22mm LCD Can measure instantaneous flow
Display the instantaneous and accumulative flow under the
flow,accumulative flow, time forward and backward direction
and various kinds of working
status separately

Smart Touch Key m³ Various of Units Selected
Easy for operation with m³/h
finger Accumulative flow: m³, ft3, GAL, L
Instantaneous Flow:m³/h, GPM, L/m

Infrared Communication Interface

Support CJ-188 communication, support
the M-BUS and MODBUS communication,

and support upgrade software

Display Description Leak Detector
Alarm/Error Communication
Wireless Power Supply Battery Low Warning
Permanent Fault
Liquid Direction Current Loop Connection
Pulse Output

T3 series Ultrasonic Water Meter - 11 -

§ 4.2 Operation Method

V51 ultrasonic water meter is equipped with two capacitive touch keys, easy for
operation. Due to operation through the thick glass, press the keys hard with your fingers
and contact wide surface of the glass ensure capacitive keys responsive

Two capacitive keys, include “” and “”.
Key “” and “” is up and down when under the modification states;
Key“” makes the Menu number increased, when enter Key “”, Menu number move
in sequential, display recycled on this level Menu windows
Key “” makes the cursor move to next character position, when enter Key “”, Menu
number move in sequential, display recycled on this level Menu windows
Press and hold the key “” , do not release the key“”, then press key “”, that is the
key “”, called modification key. Key“” means enter into the next level menu windows,
or means enter into modification states
Press and hold the key “”, do not release the key “”, then press key “”, that is the
key“”, called exit key. Press key “” will back to M00, or exit from the modification
states.
If there is no typing a key in 2 hours, the display will be back to M00 automatically
In order to the power saving, when there is no typing a key for more than 10 minutes,
quick key scan will be changed into slow key scan (1 seconds per times), which the key
may appear unresponsive, under this situation, press long key(press any keys for more
than 3 seconds and loosen called Long key) to activate the quick key scan, then is the
normal operation

Keyboard mnemonic: left click”” is up; right click”” is down; left-right click””
is modification ; right-left click”” is exiting

T3 series Ultrasonic Water Meter - 12 -

§ 4.3 Digital Display Table

Windows NO. Windows Functions Description

Water meter: Display Net cumulative flows and

M00 instantaneous flows Key , enter into
Heat meter:Display POS (positive)cumulative heats and Month cumulative

instantaneous heats

M01 Display POS cumulative flows and instantaneous flows
(water meter without this Menu)

Display the supply and return water temperature and

M02 temperature difference(water meter without this Menu, unit

is only ℃ )

Main Menu M03 Calendar, first line display date and week; Second line Key, enter into
display the hour and minute M10

M04 First line display two way signal strength,failure error Key ,enter into
code;Second line display two way signal quality data cumulative

Key, enter into

M05 Calibration menu constant-current

calibration

M06 Batch controller (irrigation controller) Key, enter into
controller setting

M10 Display the ESN(Electronic Serial numbers) and the
software version number

M11 Display the calendar, date and time Key, can be
modified

M12 Display the date of setting up parameters and battery
voltage(in volts)

Key, main

M13 Display the M-BUS second address and main address address can be

Secondary M14 Display the bound rate of RS485 and infrared interface modified
Menu 1 M15 Display the total work time(in hours) and fluid velocity

M16 Display the failure time(in hours) and CPU temperature

M17 Display the time of negative flow and Coefficient of the module

Display temperature transducer equivalent resistance value
M18 and frequency coefficient

Display the LCD segment code , is used to check defective Key, enter into
M19 display
M20

M20 Display the negative cumulative flow and the pipe diameter

T3 series Ultrasonic Water Meter - 13 -

M21 Display the negative cumulative heats and instrument factor

M22 Display Today’s POS (positive)cumulative flows and the
number of transducer channel

M23 Display current Month’s POS (positive)cumulative flows
and number of measurement per second

M24 Display Year ’s POS (positive)cumulative flows and low cut
off flow value
Secondary
Menu 2 M25 Display the data record dates and hardware delay time

M26 Display Today’s POS (positive)cumulative heats and the
power on times

M27 Display Month’s POS (positive)cumulative heats and the
current valve from the current loop

M28 Display the first failure time Press key  to
clear

M29 Display current Reynolds number and Renault correction
factor

M2A Display the total transmission tim e (us) and time difference Press
(nS) password“1111” to
modify

M30 Batch controller switch control Key, can be
modified

M31 Batch controller enable-control (under the enable-control state, it Key, can be

will take OCT 2 as signal output ) modified

M32 Set the controller point value, such as 2.00 m³, can be set by Key, can be
keypad modified

Batch M33 Set up #T1 batch controller start time Key, can be
Control M34 Set up #T2 batch controller start time modified
Menu Key, can be
modified

M35 Set up #T3 batch controller start time Key, can be
modified

M36 Set up #T4 batch controller start time Key, can be
modified

M37 Set up #T5 batch controller start time Key, can be
modified

Time- M38 Display #2 time-accumulator and instantaneous flow or
instantaneous heat
accumulated
Menu M39 Display #3 time-accumulator and instantaneous flow or
instantaneous heat

T3 series Ultrasonic Water Meter - 14 -

M3A Set up #2 and #3 time-accumulator stop time Key, can be
modified

M3B Set up #2 time-accumulator start time(#3 time-accumulator Key, can be
stop) modified

M3C Set up #3 time-accumulator start time(#2 time-accumulator stop) Key, can be
modified

M4X Display month cumulative flow

M5X Display day cumulative flow

Menu introduction:

T3-1series ultrasonic water meter include 5 kinds of menus: main menu, secondary
menu1, secondary menu2, batch control menu and time-accumulated menu. Under the
main menu, you can enter into any menu by the modification key””.

Example:

M00, press “” enter into the month cumulative flow;
M03, press “” enter into secondary menu1 (M10~M19);
Under the M19 of the secondary men1, press “   ” enter into secondary menu2
(M20~M2A);
M04, press “” enter into date cumulative flow;
M05, start-stop method calibration state; press “   ” enter into constant-current
method calibration state;
M06, press “” enter into batch control and time-accumulated menu(M30~M3C);

§ 4.4 Main Menu

V51 water meter is consist of 7 main menu windows(as a water meter, only display 5
main menu windows. The 7 main menu windows is M00, M01, M02, M03, M04, M05, M06
respectively.

Key “”or“”, display the 7 menu windows cyclical. Example: in the M00, if press key
“”, will enter into M06, in the M06, if press key “”, will back to M00.

Please note that the 7 menu windows are with the special differences, example:
M00, there is the cumulative flow and instantaneous flow or heats unit
on the right display
M02, there is the temperature unit ℃
M03, there is the symbol “-” between date, time , year and month

T3 series Ultrasonic Water Meter - 15 -

M04, there is no any unit symbol, when in normal operation,
the first line 8 character is 00000000
M05, there is the character “1” or “P”,“C” displayed on the left
M06, there is the character of “bC” displayed on the left

Below the windows function:

Windows No. Windows Function
M00
Main Water meter: Display Net cumulative flows and instantaneous
Menu M01 flows
M02 Heat meter:Display POS (positive)cumulative heats and
M03 instantaneous heats
M04 Display POS cumulative flows and instantaneous flows
M05 (water meter without this Menu)
Display the supply and return water temperature and
temperature difference(water meter without this Menu, unit is
only ℃ )
Calendar, first line display date and week; Second line display
the hour and minute
First line display two way signal strength,failure error
code;Second line display two way signal quality

Calibration menu

M06 Batch controller (irrigation controller)

Below detailed description of the main menu:

M00 Water meter: Net cumulative flows/instantaneous flows
Heat meter: Positive cumulative heats/instantaneous heats
If is set to water meter, display Net cumulative flows and
instantaneous flows; If is set to heat meter, display POS (positive)cumulative heats
and instantaneous heats. Units and cumulative flow of decimal point position can be
modified only by the special parameter software, pls refer to §8.1 and §8.2. If the
second line display “U”, means the instantaneous heats is less than the cut off value.

T3 series Ultrasonic Water Meter - 16 -

M01 POS cumulative flows and instantaneous flows
(water meter without this Menu)

Display POS cumulative flows and instantaneous flows.
Units and cumulative flow of decimal point position can be modified only by the
special parameter software, pls refer to §5.1 and §5.2. If the second line display “U”,
means the instantaneous heats is less than the cut off value.

M02 Supply and return water temperature and
temperature difference(water meter without this Menu,
unit is only ℃ )

(Display the supply and return water temperature and temperature difference

M03 Calender, Date,Week/ Hour and Minute
Display the Date, time, week, the behind of the Date is week,
example, 3 is Wednesday.

M04 Two way signal strength,failure error code/
Two way signal quality
The first number of the first line(example:6) display two way
signal strength alternately, the max value of the signal strength is 9; the last 8 digits of the
first line is error code, it displays “00000000” under the normal working status. The second
line display two way signal quality, the max value is 99, the larger of the value, the better of
the signal quality.

M05 Calibration Menu
Calibration menu, pls refer to § 5.5

M06 Batch controller Menu(irrigation controller)
Batch controller (irrigation controller),pls refer to § 5.6

§ 4.5 Secondary Menu 1

Under the Calender windows, M03, press and hold the key “” , do not release the

T3 series Ultrasonic Water Meter - 17 -

key“”, then press key “”, that is the key “”, called modification key, will display the

below :

Press key“  ” to increase the number of the flashing point until the numbers you
required, press key“  ”, the flashing will move to next number, and press“  ” again,
operation repeatedly until you finished what you want exactly.

If you want to quit, press “” , the display will back to M00.
The password is “1111” if you want to enter into the secondary menu.
There are 10 sub menu under the secondary menu 1.
Press key“” or key “”, will display the 10 sub menu in cycle.
If the menu can be modified, press and hold the key “  ” , do not release the
key“”, then press key “”, will enter into the modification states. If the menu cannot be
modified, will enter into the next sub menu.

Windows NO. Windows Function Can be modified
M10 Display the ESN(Electronic Serial numbers) and the
Secondary M11 software version number Main address
Menu 1 M12 Display the calendar, date and time can be modified
Display the date of setting up parameters and battery
M13 voltage(in volts)
M14
M15 Display the M-BUS second address and main address
M16
M17 Display the bound rate of RS485 and infrared interface
Display the total work time(in hours) and fluid velocity
M18 Display the failure time(in hours) and CPU temperature
Display the working time of negative cumulative flow and
M19 Coefficient of the capacitor module
Display temperature transducer equivalent resistance
value and frequency coefficient
Display the LCD segment code , is used to check
defective display

Below detailed description of the secondary menu 1:
M10 ESN(Electronic Serial numbers)

T3 series Ultrasonic Water Meter - 18 -
and the software version number
The first line display the ESN; The second line display the software version number, 51
means the version 51 circuit board

M11 Calender, Date, Time and Week
Calender, press key“”, means press and hold key“”,
don’t release key “”, then press key“”,

which can modify the Date and Time

M12 The date of setting up parameters and battery
voltage(in volts)
Display the date of setting up parameters and battery
voltage(in volts)

M13 M-BUS second address and main address
Display M-BUS second address and
main address(press “” can be modified)

M14 Bound rate of RS485 and infrared interface
The first line is RS485 bound rate, the “n” is None Parity,

the second line is infrared interface bound rate, the last “n” of
the first line is infrared interface None Parity.

M15 Total work time(in hours) and fluid velocity
Display the total work time(in hours) and fluid velocity, unit
is m/s.

M16 Failure time(in hours) and CPU temperature
Display failure time(in hours), the second line display CPU
temperature(℃)

M17 Working time of negative cumulative flow
and Coefficient of the capacitor module
The first line display negative cumulative working time,
the second line display the capacitor module coefficient.

M18 Temperature transducer equivalent resistance
value and frequency coefficient

The first line display the equivalent temperature
resistance value(the actual value should be add 600 );
Second line is frequency coefficient , this value should be <2.0

M19 LCD segment code , is used to check defective
display
Display LCD segment code, used for checking. This windows

T3 series Ultrasonic Water Meter - 19 -
is also the entrance of M2X.

§ 4.6 Secondary Menu 2

Under the M19, press and hold the key “” , do not release the key“”, then press
key “”, that is the key “”, called modification key, then will enter into secondary menu
2. There are 11 sub menu totally under the secondary menu 2:

Windows No. Windows Function

Secondary M20 Display negative cumulative flow and the pipe diameter
Menu 2 M21
M22 Display the negative cumulative heats and instrument
M23 factor Press key  to
M24 Display Today’s POS (positive)cumulative flows clear
M25 and the number of transducer channel
M26 Display current Month’s POS (positive)cumulative Press
M27 flows and number of sampling per second password“1111”
M28 Display Year ’s POS (positive)cumulative flows and to modify
M29 low cut off flow value
Display the data record dates and hardware delay
M2A time
Display Today’s POS (positive)cumulative heats
and the power on times
Display Month’s POS (positive)cumulative heats
and the current valve from the current loop

Display the first failure time

Display current Reynolds number and Renault
correction factor

Display the total transmission time(us) and time
diffe r e n ce (nS)

Below detailed description of the secondary menu 2:
M20 Display negative cumulative flow and the pipe diameter
The first line display negative cumulative flow
The second line display pipe diameter

M21 Negative cumulative heats and instrument factor
Display the negative cumulative heats and instrument factor

M22 Today’s POS (positive)cumulative flows and
the number of transducer channel
Display Today’s POS (positive)cumulative flows and the

T3 series Ultrasonic Water Meter - 20 -

number of transducer channel

M23 Month’s POS (positive)cumulative flows and number
of sampling per second
Display Month’s POS (positive)cumulative flows and number
of sampling per second

M24 Year’s POS (positive)cumulative flows
and low cut off flow value

Display Year ’s POS (positive)cumulative flows
and low cut off flow value(starting flow)

M25 Data record dates and hardware delay time
Display the data record dates and hardware delay time(nS)

M26 Today’s POS (positive)cumulative heats and the
power on times
Display Today’s POS (positive)cumulative heats and the
power on times.

M27 Month’s POS (positive)cumulative heats and the
current valve from the current loop
Display Month’s POS (positive)cumulative heats and the
current valve from the current loop(mA).

M28 First failure time
Display the first failure time

M29 Reynolds number and Renault correction factor
Display current Reynolds number and Renault correction
factor

M2A Display the total transmission time(us) and time
di f f e r e n c e (nS)
Display the total transmission time(us) and time difference
(nS).
Press key “”, then pres password “1112”, can be operated to Zero

§ 4.7 Month Cumulative Data Menu

In M00, press key “”, will enter into the Month cumulative data display menu.
Press key “”, display the last month cumulative value; press key “”, display the next

T3 series Ultrasonic Water Meter - 21 -

month cumulative value .

V51can record the cumulative data up to 128 months, each month data with 32 bytes,

the data structures pls refer to the communication protocol part.

Key operation, it only display 3 items in cycle: 1.Year and Month; 2. Month positive

cumulative flows; 3. Month positive cumulative heats, display as below:

2012.12 means the data in October., 2012

00 means the normal working status.

The second line “0” means the ordinal number. It can up to 256

numbers of data from ordinal number “0-255”"

First line display month positive cumulative flow

Second line display data ordinal number. Press“  ”, display

last month data, the ordinal number will be 1

First line display month positive cumulative heats

Second line display data ordinal number. Press“  ”, display

last month data, the ordinal number will be 1

Due to too many months, if want back to ordinal number 0,

press the key “” ; if want to exit the cycle display, press “”, back to M00.

§ 4.8 Date Cumulative Data Menu

In M04, press key“”, will enter into the Date cumulative menu.
Press key “”, display the last day cumulative value; press key “”, display the next
day cumulative value .
V51can record the cumulative data up to 512 working days, each day data with 32
bytes, the data structures pls refer to the communication protocol part.

Key operation, it only display 3 items in cycle: 1.Year and
Month and Date; 2. Date positive cumulative flows; 3. Date
positive cumulative heats, display as below:

2013.09.21means the data in 21th, September.2013.
The second line “0” means the ordinal number. It can up to
512 numbers of data from ordinal number “0-511”.

T3 series Ultrasonic Water Meter - 22 -
First line display Today positive cumulative flow
Second line display data ordinal number. Press“  ”, display last day data, the ordinal
number will be 1

The first line display Today positive cumulative heat
Second line display data ordinal number. Press“”,

display last day data, the ordinal number will be 1
Due to too many months, if want back to ordinal number 0, press the key “” ;
if want to exit the cycle display, press “”, back to M00.
if want to exit the cycle display, press “”, back to M00

§ 4.9 Batch Controller and Time-accumulated Menu

In M06, press key “”, then enter into batch controller menu .
(If there is the a password required, enter 1111)
There are 10 sub menu under the Batch controller, from M30 to M3C.
If the batch controller work automatically, it is necessary to set up 3 parameter control:
Batch control enable-control, batch control value, batch controller starting time.
OCT2 will be connected to a solenoid valve driver, which will be used to control the
valve switch according to the batch controller
When the batch accumulator less than the set value, batch controller is in running
states and OCT2 is in high level, therefore, OCT2 is in closed states, the solenoid valve
also in closed states, valve is opened.
When the batch accumulator larger than the set value, batch controller is in stopping
states and OCT2 is in low level, therefore, OCT2 is in opened states, the solenoid valve
also in opened states, valve is closed.
There are 5 internal timer under the batch controller, including #T1,#T2,#T3,#T4,#T5.
User can set up the time controller at any time
Batch controller operation method, pls refer to §5.6
In V51, there are 2 time-accumulators, TARI2 and TARI3, can finish the automatic
cumulative within a period of time, the start-stop time also can be set in this menu.
Time-accumulator operation method, pls refer to:§5.7

T3 series Ultrasonic Water Meter - 23 -

Windows NO. Windows Function
M30
Secondary M31 Batch controller switch control can be modified
Menu 2 can be modified
M32 Batch controller enable-control (under the can be modified
M33 enable-control state, it will take OCT 2 as signal output ) can be modified
M34 Set the controller point value, such as 2.00 m³, can be
M35 set by keypad
M36
M37 Set up #T1 batch controller start time
M38
Set up #T2 batch controller start time can be modified
M39
M3A Set up #T3 batch controller start time can be modified
M3B
Set up #T4 batch controller start time can be modified
M3C
Set up #T5 batch controller start time can be modified

Display #2 time-accumulator and instantaneous flow can be modified
or instantaneous heat can be modified
Display #3 time-accumulator and instantaneous flow can be modified
or instantaneous heat

Set up #2 and #3 time-accumulator stop time

Set up #2 time-accumulator start time(#3
time-accumulator stop)
Set up #3 time-accumulator start time(#2
time-accumulator stop)

M30 Batch controller switch control
If the batch controller is “on”, press“” can turn on or turn
off the batch controller,When the batch controller start, the OUT2
will light up.
M31 Batch controller enable-control (under the
enable-control state, it will take OCT 2 as signal output )
Batch controller switch control, press“” switch between “En”

T3 series Ultrasonic Water Meter - 24 -
and “no”. When under the enable-control state, OCT2 only as the batch control signal
output

M32 Set the controller point value
Set up the batch controller point value, when enter into a
decimal point, pls be patient with the right decimal point number
appeared

M33 Set up #T1 batch controller start time
The first line after equal sign”=””, number “0010001” means seven
days whether be allowed to be set up the start time from Sunday to
Saturday in sequence. Press “” to editor the states and working time. “0” means not
allowed, “1” means allowed. This left figure means that the water meter will start the batch
controller at 08:52 automatically on Tuesday and Saturday.

M34 Set up #T2 batch controller start time
This left figure means that the water meter will start the batch
controller at 23:52 automatically on Wednesday and Saturday.
(under the enable-control state)

M35 Set up #T3 batch controller start time
This left figure means that the water meter will start the batch
controller at 08:52 automatically on Sunday,Wednesday and
Saturday.(under the enable-control state)

M36 Set up #T4 batch controller start time
This left figure means that the water meter will start the batch
controller at 98:52 automatically on Tuesday and Saturday. But
98:52 is not exist at actual time, this setting is invalid

M37 Set up #T5 batch controller start time

T3 series Ultrasonic Water Meter - 25 -
This left figure means there is no setting for everyday,

therefore the batch controller do not work

M38 Display #2 time-accumulator and instantaneous flow or
instantaneous heat
On the left figure, decimal point followed “8” means time-accumulator #2 is working, not
under closed state, while the time-accumulator #3 is under closed state.

M39 Display #3 time-accumulator and instantaneous flow
or instantaneous heat
On the left figure, decimal point followed “9” means
time-accumulator #3 is working, not under closed state, while the time-accumulator #2 is
under closed state.

M3A Set up #2 and #3 time-accumulator stop time
The left figure means 8:30 am, 12th, January. If the month or date
is “0”, take an example, ‘00-00-18:00” only mean 18:00 everyday

M3 B Set up #2 time-accumulator start time
(#3 time-accumulator stop)

The left figure means water meter start time is 18:30 everyday

M3C Set up #3 time-accumulator start time
(#2 time-accumulator stop)

The left figure means water meter start time is 00:30 everyday.

T3 series Ultrasonic Water Meter - 26 -

5. How To

§ 5.1 How to modify the unit

It should be modified by the customized parameter software
Flow cumulative unit: m3, ft3, GAL, L.
Instantaneous flow unit: m3/h, GPM, L/m.
Heat cumulative unit: KWh, GJ, kBTU
Instantaneous heat unit: kW, GJ/h, kBTU/h
In future, we will add the unit Acre feet and Refrigeration Ton

§ 5.2 How to modify the cumulative flow of the decimal point
position

It can be modified by the special parameter setting software, the decimal point position
of the cumulative flow, can be set from 0 to 7.

§ 5.3 How to reset the time(year, month, date, hour, minute,
second and week)

1)Press “” or “”, move to M03 windows
2)Press “”,will enter into M10
3)Press “”, will enter into M11
4)Press“”, there will be the flashing number of the year location.
5)Press“” number increased, press“”, the flashing number will move to next.
6)Repeat the step 5 until the last number modified, press “” to finish operation.
If there is any mistakes during the operation, please press “” to exit editor states,
then reenter from step 4.

It is not necessary to modify the week as the water meter will calculate the week
automatically. The week setting only be used for the batch controller windows.

§ 5.4 How to judge the water meter works properly(according to
the status code to check the problem)

In M04, the first line display the water meter working status code. For the detailed
description of these code, please refer to §7.1
If the last 8 digital numbers of status code are “0”, means the water meter works properly.
If there exist the number not “0”, according to the §7.1 to check the specific faults.

T3 series Ultrasonic Water Meter - 27 -

§ 5.5 How to operate the calibration windows

There are two kinds of calibration method of T3 water meter, including the start-stop

method and constant-current method

3.1 Start-Stop Method
Start-stop method be defined in the stationary states, start and stop the calibration

device(standard water meter) and tested water meter simultaneously, is a calibration
method by the measured accumulative flow

Please go to Menu 05, you are no need to operate the keypad during the calibration
process. When the static fluid is more than 20 seconds, the left side of the window will
display “1”; Then open the valve, “P” will be flashing, means during the calibration process,
calibration accumulator to Zero and begin to count immediately. When meet the
requirement of accumulative flow value, close the valve, flow will be reduced gradually until
the “P” without flashing, it will display “1” when the fluid in stationary states. Finish the
above process, you can read out the calibrate value from the accumulator, divide water
volume of the standard container, that is the relative error. For the start-stop method, the
start duration should be more than 60 seconds each time. The shorter duration, the more
relative error caused.

3.2 Constant-Current Method
Constant-current method be defined at the set of flow point, make the calibration

device(standard water meter) and tested water meter into stable flow state, is a calibration
method by the measured accumulative flow at the same time.

Please go to Menu 05, press “ “ into constant-current window. the lest side of the
window display capital letter “C”. Constant-current method is no need the static flow. When
flow stable, press ““, calibration accumulator begin to count, lowercase letter “c” will be
flashing, when require to stop, press ““ again.

In the calibration window, second line on the display is average instantaneous flow
rate of the calibration period time, rather than the instantaneous flow rate instantly. Its
formula is : average instantaneous flow rate= accumulative flow rate of calibration period
time ÷ calibration period time.In the constant-current window, press “ “, means exiting
and entering into start-stop method window

According to the simulate keypad operation, also can achieve the constant-current
method calibration by RS485 or infrared interface. Calibrate accumulator valve and
calibrate accumulator operation time can be read out by computer and calculate the
relative error automatically, there is the correction factor, which will download to the water
meter automatically to realize calibration process automation.

T3 series Ultrasonic Water Meter - 28 -

§ 5.6 How to operate the built-in batch controller

Version 51 with the built-in Batch Controller(abbreviated BC), also called irrigation
controller. Can set up the time controller automatically or manually, so as to finish the batch
water irrigation. Batch controller can be operated by key or serial command.

Batch controller can be operated automatically . It can turn on automatically on a
setting time, when finish the batch irrigation, it will turn off automatically.

There are two kinds of timing control method, one is according to the Day and another
is Week. For the Week, you can choose at any time from Sunday to Saturday, there are 35
timing point maximum for your selection per week. For the Day, there are 5 timing point for
your selection per day, and 150 timing point maximum per month for your selection.

If the batch controller not in use,the enable control should be closed in order to make
the OCT 2 for other function.

For the key operation, the time control only be set up according to the Week(time
control method).

The batch controller hardware output is realized by OCT2, if connect the solenoid
value driver to the OCT 2, it can realize the value on-off.

Setup steps of batch controller start time automatically:
1)M31, turn on the batch controller enable-control.
2)M32, set up the value, such as 5.00 m3.
3)From M33 to M37, set up the start time point.

Setup steps of batch controller start time by keyboard:
1)From M33 to M37, setup a time value that does not exist, such as 24:15.
2)M32, set up the value, such as 5.00 m3
3)M31, turn on the batch controller enable-control
4)M30, press “”, to start batch controller manually. In condition of batch controller

has started, press “” again, to stop batch controller
In the process of batch controller running, OCT2 output is light on LCD.

§ 5.7 How to modify time point of the time-accumulator

T3 series Ultrasonic Water Meter - 29 -

Time-accumulator is to realize the flow accumulation at a set period time, to finish the

gradient rate.

Time-accumulator is not only finish the daily flow accumulation in two period cycle

function, but also can finish from 1 minute to 1 year period time flow accumulation

Time-accumulator , including TARI2 and TARI3 , is controlled by three time point. The

three time point is TARI2 start time, TARI3 start time (TARI2 stopped) and TARI3 stop time.

Three time point format is month-day-hour-minute

If you fill 0 in month or day or fill the non existing month or day, that mean it will work

everyday at the hour-minute.

§ 5.8 How to modify the communication address

V51 communication address, is several communication protocol address, also is
M-BUS main address, is a single-byte address between 0 and 255

Factory default is “1” of this address, this address can be modified by infrared or
RS485, also can be modified by keypad.

Modification step by keypad:
1)Move to M03(display the calendar)
2 )press modified key”   ”, there is a password windows(if operate again within 2
hours, will display the step 4 directly )
3)input password “1111”, end the last flashing number, will enter into M10.
4 ) Press key”  ” 3 times, will enter into M13, display secondary address and main
communication address.
5)Press“”, there will be flashing number on the second line of screen.
6)Press “” to increase the value of digital, or press “” to move the cursor to next
character , enter the new address.
7)Input the last number, that finished.

§ 5.9 How to reset the secondary address of M-BUS

M-BUS secondary address is suitable to be used with M-BUS communication protocol,
according to the secondary address, can search devices on the bus by PC software
automatically, and main address rearrangement.

The secondary address and serial number are the same and can be modified.

T3 series Ultrasonic Water Meter - 30 -

If want to modify the secondary address, the modification of the secondary address can
be made by M-BUS communication

When modify the secondary address, if the new address be set up to 00000000, that
means the new address is same with ESN.

§ 5.10 How to modify the infrared communication rate

It can be modified the communication rate permanent according to special parameter
setting software.

If be modified temporary, also can according to the M-BUS baud rate command , more
detailed information please refer to the M-BUS communication protocol.

§ 5.11 How to modify communication rate of RS485/M-bus

It can be modified the communication rate permanent according to special parameter
setting software.

If be modified temporary, also can according to the M-BUS baud rate command , more
detailed information please refer to the M-BUS communication protocol.

T3 series Ultrasonic Water Meter - 31 -

6. Communication

§ 6.1 Manual wireless Meter Reading

T3 series water meter is available with the RF shoot-distance wireless communication
module and portable wireless meter reading, can realize manual wireless meter reading.

§ 6.2 Wireless Network Meter Reading Automatically

This networking system is suitable for large water supply management and water
resource monitoring, you can use the wireless network meter reading automatically
anywhere as long as the GSM network signal coverage.

T3 series Ultrasonic Water Meter - 32 -

7.Fault Handling

§ 7.1 Fault Handling

Error code displayed on M0A.

M0A, the left digits on the upper line, is the signal strength and range from 0-9.

The remaining 8 hexadecimal digits is the error code, the meaning of the code as

following.

X XX XX XX XX

|||| |

| | | | BIT 0 Heat totalizer error

| | | | BIT1 T1 temperature transducer error

| | | | BIT2 T2 temperature transducer error

| | | | BIT3 Flow meter error

| | | | BIT4 Reverse flow direction

| | | | BIT5 Poor signal strength

| | | | BIT6 Slow work condition, means flow meter be in static fluid or

empty pipe more than 2 hours

| | | BIT0 ERR_CH1 Channel 1 error, or channel 1 is not set up to enable state

| | | BIT1 ERR_CH2 Channel 2 error, or channel 2 is not set up to enable state

| | | BIT2 ERR_BATT Low battery voltage

| | | BIT3 ERR_FNEGT Return water temperature lower than

supply water temperature error

| | | BIT4 PT1000_T1_S T1 transducer short circuit fault

| | | BIT5 PT1000_T1_O T1transducer open circuit fault

| | | BIT6 PT1000_T2_S T2transducer short circuit fault

| | | BIT7 PT1000_T2_O T2transducer open circuit fault

| | BIT0 ERR_DELTA_BIT Time difference detection circuit fault

| | BIT1 ERR_DISCHARGE Time difference capacitance discharge fault

| | BIT2 ERR_DCAP_BIT Time difference capacitance short circuit fault

| | BIT3 ERR_7474_BIT Integrated circuit 74AHC74 fault

| | BIT4 ERR_RCVER_BIT Ultrasonic transceiver circuit fault

| | BIT5 ERR_WINDOW_BIT Ultrasonic receive windows signal fault

| | BIT6 ERR_TEMPI_BIT Temperature detection circuit, constant current fault

| | BIT7 ERR_TSW_BIT Temperature detection circuit,analog switch fault

T3 series Ultrasonic Water Meter - 33 -

| BIT0 ERR_FREQ_BIT CPU low frequency clock or high

frequency clock error

| BIT1 ERR_PARITY Data calibration error in parameters

| BIT2 ERR_ROM Firmware code calibration error

| BIT3 ERR_EPROM_BIT EPROM read or write error

| BIT4 PT1000_S1_S Temperature measurement circuit low-end,

reference resistor short circuit fault

| BIT5 PT1000_S1_O Temperature measurement circuit low-end,

reference resistor open circuit fault

| BIT6 PT1000_S2_S Temperature measurement circuit high-end,

reference resistor short circuit fault

| BIT7 PT1000_S2_O Temperature measurement circuit high-end,

reference resistor open circuit fault

0~9 is the ultrasonic signal strength. 0 indicates no signal and 9 being the most. This

value is effective only when pipe with full liquid and water meter powered on after 1~ 2

minutes.

For the dual channel, it will display two channel signal strength alternative.
In general, it means no error if the last eight digits is “0”; it need to “decode” according
to the above table to check the fault if the last eight numbers appears none “ 0”

For example, “400000100” means fault in channel 1, “400000200” means fault in
channel 2, “000000304” means fault in both channel

For example, “40000A006” means open circuit for both temperature transducer, the
similar false default will appear when treat the flow meter as heat meter without the
temperature transducer.

If you are familiar with the Hexadecimal encoding,It’s easy to find out the fault. Also
you can download the software “V49_ERRCODE.EXE” to get the meaning of the error from
our company website

Part One

V51 Serial Communication Interface Instruction

1. Introduction
V51 is equipped with 2 serial communication interfaces, one is IrDA interface, the other is RS485/USART.

USART, that is a serial interface of logic level, suitable to directly communicate with other external MCU
communication, low power consumption.

2. Default setting

RS485/USART 9600,N,8,1

IR 9600,N,8,1

3. Change the default setting

All the serial parameters setting can be done with a software named V49_SETUP.

The current serial parameters can be shown in M0E.

4. Communication protocol
a. HART
b. MODBUS
c. M-BUS
d. CJ188
e. Protocols used by Huizhong

Part Two
HART Protocol

1. Referenced Documents Version 8.1
SCF_SPEC-054 FSK Physical Layer Specification Version 8.0
SCF_SPEC-081 Data Link Layer Specification Version 6.0
SCF_SPEC-127 Universal Command Specification Version 8.0
SCF_SPEC-051 Common Practice Command Specification Version 13.0
SCF_SPEC-081 Common Tables Specification Version 5.0
SCF_SPEC-307 Command Response Code Specification Version 8.0
SCF_SPEC-099 Command Summary Specification

2. Expanded Device Type cod

Manufacturer ID =252 (0xFC, unknown)

Manufacturers’ Device Type Code =245 (0xF5)

3. Communication Setups

FSK on Current Loop Baud Rate 1200, Even, 8,1

RS485 Baud Rate 300~9600, Even, 8,1

IR Communicator Baud Rate 300~9600, Even, 8,1

Address by Manufacturer 1

Initial Hart Tag TSF-V49C

Burst Mode do not support

4. General Transmitter Information

4.1 Variables Map

Code Variable Unit
0 flow rate m3/h
1 flow positive total M3, Liter, Gallon, Cubit feet
2 heat(energy) rate kW
3 heat positive total kWh, BTU,MJ
4 Temperature T1 Degree Celsius
5 Temperature T2 Degree Celsius
6 Temperature difference Degree Celsius
7 Flow velocity m/s
8 T1 sensor resistance Ohm
9 T2 sensor resistance Ohm
10 CPU temperature Degree Celsius
11 Frequency percentage %
12 Battery voltage Volt
13 Total travel time Seconds
14 Delta travel time Seconds
15 Negative total flow rate M3, Liter, Gallon, Cubit feet

16 Total Flow rate today M3, Liter, Gallon, Cubit feet

17 Total Flow rate this month M3, Liter, Gallon, Cubit feet

18 Total Flow rate this year M3, Liter, Gallon, Cubit feet

19 Calibration total M3, Liter, Gallon, Cubit feet

20 Negative total heat kWh, BTU,MJ

21 Total heat rate today kWh, BTU,MJ

22 Total heat rate this month kWh, BTU,MJ

23 Total heat rate Tariff 2 kWh, BTU,MJ Not realized yet

24 Total heat rate Tariff 3 kWh, BTU,MJ Not realized yet

25 Pipe outer diameter mm

26 Total working Hours hour

27 Total Failure hours hour

28 Calibration Duration seconds

4.2 Current Loop Mapping
Current loop can be only mapped on Instant flow rate.

4.3 Non-lost data storage
4.3.1 All accumulated data can be automatically stored in EEPROM every 2 minutes.
4.3.2 HART Tag is stored in EEPROM. ( location: 0x700-0x7FF)
4.3.3 The device address will be stored in EEPROM after setting within 2 minutes. Order 42 will lead an
automatic storage in EEPROM.
4.3.4 The number of leading characters will be stored in EEPROM after setting within 2 minutes. Order 42
will lead to an automatic storage in EEPROM.
4.4 Multi-drop Mode
V49 do not support Multi-drop Mode
4.5 Burst Mode
V49 do not support Burst Mode

5 Orders supported
5.1 General Orders
0 Read Unique Identifier
1 Read Primary Variable (i.e. flow rate)
2 Read
3 Read Dynamic Variables and Loop current
6 Write polling address
7 Read loop configuration
8 Read Dynamic Variables Classifications
9 Read device Variables and status
11 Read unique identifier associated with Tag
12 Read message
13 Read Tag, descriptor and Date
14 Read Primary Variable transducer information
15 Read Device Information

16 Read Final assembly number

17 Write message

18 Write Tag, descriptor and Date

19 Write Final assembly number

20 Read Long Tag

21 Read unique identifier associated with Long Tag

22 Write Long Tag

5.2 Common orders

33 Read Device Variables

42 Perform device reset

40 Enter/exit fixed current mode

43 Set Primary variable zero (to perform a Zero Setting

45 Trim Current Loop Zero (to adjustment current loop to 4mA)

46 Trim Current Loop Gain (to adjustment current loop to 20mA)

59 Write number of the response preamble

Part Three

MODBUS Protocol

1. MODBUS factory default settings

1.1 RS485 (optional: 300,600,1200,2400,4800,9600)
Baud rate 9600

Checksum None (optional: None, Even, Odd)

Address 1

1.2 IR 9600 (optional: 300,600,1200,2400,4800,9600)
Baud rate

Checksum None (optional: None, Even, Odd)

Address 1

Above parameters are displayed in M0E and M10

2. MODBUS other details

2.1

2.2

2.3

2.4

3. MODBUS address list of common register

Register address Register Register Name Data format Description

number Unit: m3/h
Unit: kW
0001-0002 2 Instant flow rate IEEE754 Unit: m/s

0003-0004 2 Instant flow rate IEEE754

0005-0006 2 Flow velocity IEEE754

0009-0010 2 Positive accumulated flow LONG Unit:m3,L,GAL,ft3
0011-0012 2
Note 1

Decimal part of the positive IEEE754

0013-0014 2 accumulated flow LONG Unit:m3,L,GAL,ft3
0015-0016 2 Negative accumulated flow IEEE754 Single floating-point
Decimal part of negative number, also known as
accumulated flow rate FLOAT format.
Unit: kWh, GJ, KBTU
0017-0018 2 Positive accumulated heat LONG
0019-0020 2 Decimal part of positive IEEE754 Unit: kWh, GJ, KBTU
accumulated heat rate
0021-0022 2 Negative accumulated heat rate LONG Unit:m3,L,GAL,ft3
0023-0024 2 Decimal part of negative IEEE754
accumulated heat rate Unit: kWh, GJ, KBTU
0025-0026 2 Net accumulated flow LONG
0027-0028 2 Decimal part of net IEEE754 Unit: ℃
accumulated flow rate Unit: ℃
0029-0030 2 Net accumulated heat LONG
0031-0032 2 Decimal part of net IEEE754
accumulated heat rate
0033-0034 2 Supply water temperature T1 IEEE754
0035-0036 2 Return water temperature T2 IEEE754

0053-0055 3 Calendar(date and time) BCD Writable. 6 byte BCD
represent SMHDMY,
0056 1 BCD low bit is in front.
Writable.
Date and time storage i.e. 0512H means
automatically 12:00 of 5th
0012H means 12:00
0057 1 Input the protect password Integer daily
0058 1 Code of sleep mode Integer Writable
Writable.
0059 1 Write in with keyboard Integer Write in 0x5A58F can
0060 1 Display the number of moving Integer be in sleep mode.
to the menu Writable
0061 1 current menu Integer Writable
0062 1 Main Integer
communication address Writable
0063 1 BC timer Integer Writable,
0064 1 OCT pulse 1 Integer maximum 255
0065 1 OCT pulse 2 Integer Write in 0 to start BC

0071 1 complementary error code Bits note 4

0072 1 Error code Bits note 5
0077-0078 2 T1 resistance value IEEE754 Unit:Ω
0079-0080 2 T2 resistance value IEEE754 Unit:Ω
0081-0082 2 Total transit time IEEE754
0083-0084 2 Transit time IEEE754 Unit: uS

0092 1 Unit: nS
0093 1
0094 1 Signal quality Integer Channel 1 in the low
0095 1 #1 channel signal strength Integer Range:0~4095
#2 channel signal strength Integer
0099-0100 2 Battery power Integer V=REG95*(2.5/4096)
0101-0102 2
Reynolds number IEEE754
Reynolds correction IEEE754
coefficient

0105-0106 Total working time Long Unit: Seconds
0107-0108 Times of power on Long Unit: ℃
0109-0110 CPU temperature IEEE754
0113-0114
0115-0116 2 Net accumulated flow rate IEEE754 Unit: m3/h
0117-0118 2 (floating point format) IEEE754 Signal Accuracy.
0119-0120 2 Positive accumulated flow rate IEEE754
0121-0122 2 (floating point format) IEEE754 Not Recommended
0123-0124 2 Negative accumulated flow rate IEEE754 to read these Registers
0125-0126 2 (floating point format) IEEE754 with new
0127-0128 2 Net accumulated heat rate IEEE754 developments due to
0129-0130 2 (floating point format) IEEE754 limited accuracy
0131-0132 2 Positive accumulated heat rate LONG
0133-0134 2 (floating point format) IEEE754
0135-0136 2 Negative accumulated heat rate LONG
2 (floating point format) IEEE754
Daily net accumulated flow rate
(floating point format)
Monthly net accumulated flow
rate (floating point format)
time-share accumulator
Tariff 2
Decimal part of time-share
accumulator Tariff 2
time-share accumulator
Tariff 3
Decimal part of time-share
accumulator Tariff 3

0137-0138 2 Daily accumulated flow rate LONG 9 Digits
0139-0140 2 Daily decimal part of IEEE754
accumulated flow rate
0141-0142 2 Monthly accumulated flow rate LONG
0143-0144 2 Monthly decimal part of IEEE754
accumulated flow rate
0144-0145 2 Accumulated flow of this year LONG
0147-0148 2 Decimal part of IEEE754
accumulated flow of this
0149-0150 2 year LONG
0151-0152 2 Daily accumulated heat rate IEEE754
Decimal part of
0153-0154 2 accumulated heat rate LONG
0155-0156 2 Monthly accumulated heat rate IEEE754
Monthly decimal part of
accumulated heat rate

0162 1 Daily accumulated data pointer Integer
0163 1
Monthly accumulated data Integer
pointer

0165-0166 Fault running time Long Unit: Seconds
Unit: ℃
0181-0182 2 Temperature difference IEEE754
0185-0186 Frequency coefficient IEEE754 Unit:m3,GAL,ft3,L
0187-0188 Automatically store the Long Unit: kWh, GJ, KBTU
total time Long
0189-0190 Automatically store the IEEE754
positive accumulated flow Long
0191-0192 Automatically store the
instant flow Long
0193-0194 Automatically store the Long
total working time of IEEE754
0195-0196 2 negative flow rate long
0197-0198 2 Automatically store the
0199-0200 2 negative flow rate
0201-0202 Verification of flow
accumulator
Verification of the decimal part
of flow accumulator
Verification of heat
accumulator

0203-0204 2 Verification of the decimal part IEEE754

0205 1 of heat accumulator

0221-0222 2 Verification time integer Unit: in 250mS

0259-0260 2 Inside pipe diameter IEEE754 Unit:mm
0261-0262 2
0263-0264 2 Monthly max instant flow IEEE754 Unit: m3/h
Monthly max instant heat IEEE754 Unit: kW
0265-0266 2 Monthly max inflow IEEE754
temperature
0267-0268 2 Monthly max outflow IEEE754
0269 1 temperature
0270 1
0271-0272 2 Transit-time IEEE754 In unit nS
0273-0274 2 M-bus secondary address BCD In unit seconds
0275-0276 2 Negative flow long
measurement time
0277-0280 4
0281-0282 2 Daily max instant flow IEEE754 Unit : m3/h
0283-0284 2 Daily max instant heat IEEE754 Unit : kW
0285-0286 2 Daily max supply water IEEE754 Unit : ℃
0287-0288 2 temperature
0289-0290 2 Daily max return water IEEE754 Unit : ℃
temperature
0291-0292 2
User code BCD Low byte
0293-0294 2 Stop time of time-share BCD
0295-0296 2 accumulator BCD
0297-0298 2 Start time of time-share BCD
accumulator tariff2 BCD
0299-0300 2 Start time of time-share
accumulator tariff3 BCD
0301-0302 2 The status of time-share BCD
accumulator and
0303 0.5 quantitative controller
#1 start time of
0303-0304 1.5 quantitative controller
0305-0306 1,5 #2 start time of
quantitative controller

0306-0307 1,5 #3 start time of BCD
0307-0308 1,5 quantitative controller BCD
0309-0310 1,5 #5 start time of BCD
0311-0312 2 quantitative controller IEEE754
#5 start time of
quantitative controller
Quantitative controller
setting

0361-0362 2 Always display 361.00 IEEE754 For test
Note 2
0363-0364 2 Always display 363348858 long
0365-0366 2 Always display-987654321 long

1438 1 Unit code of accumulated flow INTEGER 0=cubic meter 1=liter
2=gallon 5=cubic foot
1439 1 Multiple factor of Integer n:(-4..3), note1

1440 1 accumulated flow Integer n:(-3..4), note1

1441 1 Multiple factor of Integer 0=GJ , 2=KWh
1=Kilo BTU
1491 1 accumulated heat Integer EN1434-3
1527 1 Integer
Unit code of accumulated heat Value=0x1188
1528 1 Integer MSB first
1529 2 Instrument types BCD
Software version
Note 3
Manufacturer Note3
ESN

Note 1: (1)For all cumulants, a long integer represents the integer part and a real number represent the
decimal part. In most applications, users just need to read the long integer part, do not have to read the
decimal part.

If N means the long integer value(for example the positive accumulated flow, the bit value of 32 in REG
0009,0010 is a long integer)
Nf means the decimal part(for example the positive accumulated flow, 32 bit floating point number in REG
0011, 0012)
n means the decimal point position (for example the accumulated flow, REG 147).

Then,

The final total accumulated flow = (N+Nf ) ×10-n

REG 148 value range from 0~3, determines the unit of accumulated flow.

0 cubic meter (m3)

1 liter (L)

2 American gallon (GAL)

3 Cubic feet (CF)

For example, if REG0009=123456789, REG0010=0.123, and REG147=3, REG148=0
Then the total flow = 123456.789123 m3

For heat accumulator:

The energy flow rate =(N+Nf )×10n-4
n is determined by REG01440.
Unit of accumulated heat is determined by REG 1441.

Note 2: REG361 is specially designed for communication test. If the number you read in REG361 is
not 361.0, but ‘0’ or ‘250.264’, which means your read address is wrong. Please consult relevant
MODBUS protocol standard. More details could be found on Internet.

Note 3: The register of software version and manufacturer is used to identify the register table.

4. MODBUS monthly accumulated flow address list

Data address Reg no Variable name format note

Blk Integer Range: 0-127
Integer 0~65535
No Integer
Integer Month in low byte
n/a 0163 1 Monthly Pointer BCD Record for checking
LONG Of this month
0 29953 1 Data block no LONG Of this month
LONG Recorded
1 29954 1 State LONG Recorded
LONG Recorded
0 2 29955 1 Failure days LONG Recorded
LONG Recorded
3 29956 1 Month, Year LONG Recorded
LONG
4 29957 2 Working hours LONG ……
REAL4
6 29959 2 Failure hours REAL4 ……
REAL4
8 29961 2 Month Total flow REAL4
Integer
10 29963 2 Month Total energy Integer
Integer
12 29965 2 Positive flow BCD
LONG
14 29967 2 Negative flow LONG
LONG
16 29969 2 Positive energy LONG
……
18 29971 2 Negative energy REAL4
REAL4
20 29973 2 Tariff2
Integer
22 29975 2 Tariff3 Integer
……
24 29977 2 Max flow rate REAL4
REAL4
26 29979 2 Max energy rate

28 29981 2 Max inlet temperature

30 29983 2 Max outlet temperature

2 0 29985 1 Data block no

1 29986 1 State

2 29987 1 Failure days

3 29988 1 Month, Year

4 29989 2 Working hours

6 29991 2 Failure hours

8 29993 2 Month Total flow

10 29995 2 Month Total energy

… …… …… ……

28 30013 2 Max inlet temperature

30 30015 2 Max outlet temperature

n Monthly data block n

127 0 38113 1 Data block no

1 38114 1 State

… …… …… ……

28 38141 2 Max inlet temperature

30 38143 2 Max outlet temperature

5. MODBUS daily accumulated flow address list

Data address Reg Variable name format note

Blk no Integer Range 0-511
Integer 0~65535
No Integer In high byte
Integer Month in Lower byte
n/a 0162 1 Daily pointer BCD
LONG Of the day
1 0 5377 1 Data block no LONG Of the day
LONG Recorded at the last sec.
1 5378 1 State of the day LONG Recorded at the last sec
LONG Recorded at the last sec
2 5379 1 day LONG Recorded at the last sec
LONG Recorded at the last sec
3 5380 1 Month, year LONG Recorded at the last sec
LONG
4 5381 2 Working hours LONG 0~65535
REAL4
6 5383 2 Failure hours REAL4 0~32767
REAL4
8 5385 2 Daily Total flow REAL4
Integer
10 5387 2 Daily Total energy Integer
Integer
12 5389 2 Positive flow ……
REAL4
14 5391 2 Negative flow REAL4
REAL4
16 5393 2 Positive energy REAL4

18 5395 2 Negative energy

20 5397 2 Tariff2

22 5399 2 Tariff3

24 5401 2 Max flow rate

26 5403 2 Max energy rate

28 5405 2 Max inlet temperature

30 5407 2 Max outlet temperature

2 0 5409 1 Data block no

1 5410 1 State of the day

2 5411 1 day

… …… …… …….

24 5433 2 Max flow rate

26 5435 2 Max energy rate

28 5437 2 Max inlet temperature

30 5439 2 Max outlet temperature

n Data block n

511 0 21729 1 Data block no Integer
1 21730 1 State of the day Integer
… …… …… ……. ……
28 21757 2 REAL4
30 21759 2 Max inlet temperature REAL4

Max outlet temperature



6. MODBUS power-on time table

Data address Reg Variable name format note
Blk no
No Daily pointer Integer Range 0-255
n/a 0162 1 Data block no Integer 0~65535
1 0 28929 1 Minute, Second BCD Second in low byte
1 Day, Hour BCD Hour in low byte
1 28930 1 Year, Month BCD Month in low byte
2 28931 1 Data block no BCD
3 28932 1 Minute, Second BCD
2 0 28933 1 Day, Hour BCD
1 28934 1 Year, Month BCD
2 28935 1
3 28936 Data block no BCD
n Data block n Minute, Second BCD
Day, Hour BCD
255 0 29949 1 Year, Month BCD
1 29950 1
28 29951 1
30 29952 1

Part Four

M-BUS Communication Protocol

1. Interface
(A)RS-485
(B)IR
(C)logic level USART

2. Default settings

Telegram format: IEC 870-5-1, DIN EN1434-3

Baud rate: IR 2400

RS-485, USART: 9600

Odd-even check: Even

Data bits: 8 bits

3. References

“The M-BUS:A Documentation” which can be downloaded from www.m-bus.com

“TKB3417 Description of the MBUS module for Ultraheat”

4. Special function

* Available to set date and time

* Available to set Baud rate

* Available to set main address

* Include the secondary address

* Choice promotion

* Available to set data telegram according to personal demands

Table 1 Master=>Slave telegrams

Main unit request Format
command

C域 A CS

Initialization (SEND_NKE) 10h 40h A CS 16h
Data request (SEND_UD2) CS 16h
Delete the use of public address 10h 5Bh/7Bh A CS 16h
Warning protocol (SEND_UD1) CS 16h
Communication test 10h 40h FDh CS 16h
Search the main address CS 16h
10h 5Ah/7Ah A

10h 4Ah/6Ah A

10h 49h FDh

LL C 域 A CI 域 CS
CS
Select secondary 68h 0Bh 0Bh 68h 53h/73h FDh 52h ID1-4 M1-2 G Med
address secondary 68h
Select 0Bh 0Bh 68h 53h/73h FDh 56h ID4-1 M2-1 G Med CS
address

Enhance to select 68h 11h 11h 68h 53h/73h FDh 52h ID1-4 M1-2 G Med 0CH 78H SN1-4 CS

secondary address

Modify the main 68h 06h 06h 68h 53h/73h A 51h 01h 7Ah NN CS

address

Modify the 68h 09h 06h 68h 53h/73h A 51h 0Ch 79h SA1-4 CS

secondary address

Modify the 68h 0Dh 0Dh 68h 53h/73h A 51h 07h 79h SA1-4 xxh,xxh,xxh,xxh CS

secondary address

Set the secondary 68h 09h 06h 68h 53h/73h A 51h 0Ch 79h 00h 00h 00h 00h C

address as ESN

Set the secondary 68h 0Dh 0Dh 68h 53h/73h A 51h 07h 79h 00h 00h 00h 00h xxh,xxh,xxh,xxh C

address as ESN

LL C域 A CI 域 CS

Change baud rate 68h 03h 03h 68h 53h/73h A B8h CS 16h
Change baud rate 68h 03h 03h 68h 53h/73h A B9h CS 16h
Change baud rate 68h 03h 03h 68h 53h/73h A BAh CS 16h
Change baud rate 68h 03h 03h 68h 53h/73h A BBh CS 16h
Change baud rate 68h 03h 03h 68h 53h/73h A BCh CS 16h
Change baud rate 68h 03h 03h 68h 53h/73h A BDh CS 16h
Change baud rate 68h 03h 03h 68h 53h/73h A B7h CS 16h

Note Machine
response
C domain=control domain A domain=address domain CS=checksum,
CI domain E5h
Release public address, set as normal status, default baud rate RSP_UD
Request the slave user’s data of slave send response E5h
All slave release public address FDh, convenient for later use. E5h
Respond the warning check at full throttle E5h
To test whether communication line works
To respond the main address

16h ID1-4 is ID of 4 bits4, M1-2=88h,11h G=1 Med=4 return water heat meter is E5h

in front*

16h High-order is in front, others same as above-message. E5h
(Med=0Ch is inflow heat meter) *

16h Add 0Ch 78h +4 byte serial number than above two message * E5h

16h NN means the new address of single byte, range from 1-250 E5h

16h SA1-4 means the new address of 4 byte, to avoid two same address in one E5h

system.

16h SA1-4 means the secondary address of 4 byte. E5h

CS 16h M-BUS secondary address is set as ESB by default setting, and it is E5h

available to modify the secondary address.

CS 16h To solve the problem of same secondary address E5h

Note, change of baud rate should be behind the response of the previous baud

rate.

Change baud rate to 300 become the system default after power on again E5h

Change baud rate to 600 become the system default after power on again E5h

Change baud rate to 1200 become the system default after power on again E5h

Change baud rate to 2400 become the system default after power on again E5h

Change baud rate to 4800 become the system default after power on again E5h

Change baud rate to 9600 become the system default after power on again E5h

Restore baud rate to default E5h


Click to View FlipBook Version