Industrial Generator Set Accessories
Weather/Sound Enclosure and
Subbase Fuel Tank Package
Enclosure with Standard Subbase Fuel Tank Applicable to the following:
20--40REOZJC
Enclosure with State Code Subbase Fuel Tank 50/60REOZJD
80/100/150/180/200REOZJF
Available Approvals and Listings 125/180REOZJG
40/50/230--275REOZJE
- UL 2200 Listing 300REOZJ
- CSA Certified
- IBC Seismic Certification Weather Enclosure Standard Features
- California OSHPD Approval
- cUL Listing (fuel tanks only) D Internal-mounted silencer and flexible exhaust
NOTE: Some models may have limited third-party connector.
approvals, see your local distributor for details.
D Lift base or tank-mounted, steel construction with
hinged doors.
D Fade-, scratch-, and corrosion-resistant Kohlerr
Power Armort cream beige automotive-grade textured
finish.
D Enclosure has four large access doors which allow for
easy maintenance.
D Lockable, flush-mounted door latches.
D Vertical air inlet and outlet discharge to redirect air and
reduce noise.
D Certified to withstand 241 kph (150 mph) wind load
rating.
Sound Enclosure Standard Features
D Includes all of the weather enclosure features with the
addition of acoustic insulation material.
D Lift base or tank-mounted, steel or aluminum
construction with hinged doors. Aluminum enclosures
are recommended for high humidity and/or high salt/
coastal regions.
D Acoustic insulation that meets UL 94 HF1 flammability
classification and repels moisture absorption.
D Sound attenuated enclosure that uses up to 51 mm
(2 in.) of acoustic insulation.
Subbase Fuel Tank Features
D The fuel tank has a Power Armor Plust textured
epoxy-based rubberized coating.
D The above-ground rectangular secondary containment
tank mounts directly to the generator set, below the
generator set skid (subbase).
D Both the inner and outer tanks have emergency relief
vents.
D Flexible fuel lines are provided with subbase fuel tank
selection.
D The secondary containment generator set base tank
meets UL 142 tank requirements. The inner (primary)
tank is sealed inside the outer (secondary) tank. The
outer tank contains the fuel if the inner tank leaks or
ruptures.
D State tanks with varying capacities are an available
option. Florida Dept. of Environmental Protection
(FDEP) File No. EQ-634 approved.
G6-99 5/14aa Page 1
Weather and Sound Enclosure
Fade-, scratch-, and Hinged doors Lockable, flush- Enclosed exhaust silencer Vertical air
corrosion- resistant for ease of mounted door latches for improved safety and discharge through
Power Armort finish servicing noise reduction an air outlet grille
prevent tampering
ADV-7429-
Alternator Rodent guards and Fixed air Oil drain Acoustic insulation
access skid end caps flow inlet and radiator meeting UL 94 HF1
panel flammability classification
prevent animal entry grille drains
Note: 20--40REOZJC models shown, other models are similar. Refer to the respective ADV drawings for details.
Enclosure Features
D Available in steel (14 gauge) formed panel, solid D Interchangeable modular panel construction. Allows
construction. Preassembled package offering corrosion complete serviceability or replacement without
resistant, dent resilient structure mounting directly to lift compromising enclosure design.
base or fuel tank.
D Cooling/combustion air intake with a horizontal air inlet.
D Power Armort automotive-grade finish resulting in advanced Sized for maximum cooling airflow.
corrosion and abrasion protection as well as enhanced edge
coverage and color retention. D Service access. Multi-personnel doors for easy access to
generator set control and servicing of the fuel fill, fuel gauge,
D Internal exhaust silencer offering maximum component life oil fill, and battery.
and operator safety.
NOTE: Installing an additional length of exhaust tail pipe may D Cooling air discharge. Weather protective design featuring a
increase backpressure levels. Please refer to the generator set vertical air discharge outlet grille. Redirects cooling air up
spec sheet for the maximum backpressure value. and above enclosure to reduce ambient noise.
Additional Sound Enclosure Features
D Available in steel (14 gauge) or aluminum 3.2 mm (0.125 in.) D Cooling air discharge. The sound enclosures include
formed panel, solid construction. acoustic insulation with urethane film.
D Attenuated design. Acoustic insulation UL 94 HF1
listed for flame resistance offering up to 51 mm (2 in.)
mechanically restrained acoustic insulation.
G6-99 5/14aa Page 2
Subbase Fuel Tank
Electrical Removable Emergency Normal Low Additional fitting Power Armor Plust coating
stub-up area engine supply inner tank vent fuel level for optional for advanced corrosion and
open to bottom diptube relief vent accessory
switch abrasion protection
Fuel leak Removable fuel Fuel fill with Fuel level Emergency outer Basin
detection switch return diptube lockable cap and gauge tank relief vent drain
203 mm (8 in.) riser
Note: 20--40REOZJC models shown, other models are similar. Refer to the respective ADV drawings for details. ADV-7430-
Standard Subbase Fuel Tank Features
D Extended operation. Usable tank capacity offers full load D Emergency pressure relief vents. Vents ensure adequate
standby operation of up to 72 hours. venting of the inner and outer tank under extreme pressure
and/or emergency conditions.
D Power Armor Plust textured epoxy-based rubberized
coating that creates an ultra-thick barrier between the tank D Normal vent with cap. Vent is raised above lockable fuel fill.
and harsh environmental conditions like humidity, saltwater, D Low fuel level switch. Annunciates a 50% low fuel level
and extreme temperatures, and provides advanced corrosion
and abrasion protection. condition at generator set control.
D UL listed. Secondary containment generator set base tank D Leak detection switch. Annunciates a contained primary tank
meeting UL 142 requirements. fuel leak condition at generator set control.
D NFPA compliant. Designed to comply with the installation D Electrical stub-up.
standards of NFPA 30 and NFPA 37.
D Integral external lift lugs. Enables crane with spreader-bar
lifting of the complete package (empty tank, mounted
generator set, and enclosure) to ensure safety.
G6-99 5/14aa Page 3
State Code Subbase Fuel Tank
Electrical Fuel leak Additional fitting Low Power Armor Plust coating Emergency Additional fitting Basin
stub-up area detection for optional fuel level for advanced corrosion and inner tank for optional drain
open to bottom accessory relief vent accessory
switch switch abrasion protection
Removable Removable Normal Top fluid Fuel fill with Fuel level Emergency outer
engine supply fuel return vent containment lockable cap and gauge tank relief vent
51 mm (2 in.) riser
diptube diptube drain
Note: 20--40REOZJC models shown, other models are similar. Refer to the respective ADV drawings for details. ADV-7594-B
State Code Subbase Fuel Tank Features
D State tank designed to comply with the installation standards D Includes all of the Standard Subbase Fuel Tank Features.
of the Florida Dept. of Environmental Protection (FDEP) File
No. EQ-634.
State Code Subbase Fuel Tank Options
Bottom Clearance Fuel Supply Options
- I-beams, provides 106 mm (4.2 in.) of ground clearance - Fire safety valve (installed on fuel supply line)
- Ball valve (installed on fuel supply line)
Fuel in Basin Options
- Fuel in basin switch, Florida Dept. of Environmental High Fuel Level Switch
- High fuel level switch
Protection (FDEP) File No. EQ-682 approved - High fuel level switch, Florida Dept. of Environmental
Fuel Fill Options Protection (FDEP) File No. EQ-682 approved
- Fill pipe extension to within 152 mm (6 in.) of bottom of fuel
Normal Vent Options
tank. - 3.7 m (12 ft.) above grade (without spill containment)
- 18.9 L (5 gallon) spill containment with 95% shutoff - 3.7 m (12 ft.) above grade (with spill containment)
- 18.9 L (5 gallon) spill containment
- 18.9 L (5 gallon) spill containment fill to within 152 mm (6 in.) Tank Marking Options
- Decal, Combustible Liquids -- Keep Fire Away (qty. 2)
of bottom of fuel tank - Decal, NFPA 704 identification (qty. 2)
- 28.4 L (7.5 gallon) spill containment, Florida Dept. of - Decal, tank number and safe fuel fill height (qty. 2)
- Decal, tank number and safe fuel fill height, NFPA 704
Environmental Protection (FDEP) File No. EQ-345 approved
- 28.4 L (7.5 gallon) spill containment with 95% shutoff, identification
Florida Dept. of Environmental Protection (FDEP) File No.
EQ--345/ EQ-257 approved
G6-99 5/14aa Page 4
Enclosure and Subbase Fuel Tank Specifications
Enclosure and Subbase Fuel Tank Sound
Pressure at
Fuel Tank Est. Fuel Max. Dimensions, mm (in.) Max. Weight, kg (lb.) * Fuel Tank 60 Hz with
Capacity, Supply Hours Height, Full Load at
at 60 Hz with Length Width Height With Steel With Aluminum mm (in.) 7 m (23 ft.),
L (gal.) Enclosure Enclosure
Full Load, 152 (6) Weather/
Nominal/Actual 305 (12) Sound dB(A)
406 (16)
20REOZJC without IBC Seismic Certification 559 (22) 78/65
78/65
No Tank 0 1438 (56.6) 943 (2080) 830 (1830) 100 (4) 78/65
254 (10) 78/65
295 (78) 24/41 1722 (67.8) 1167 (2572)* 1053 (2322)* 358 (14) 78/65
424 (112) 36/58 2320 (91.3) 1077 (42.4) 1824 (71.8) 1201 (2647)* 1087 (2397)* 508 (20) 78/65
78/65
621 (164) 48/86 1976 (77.8) 1251 (2759)* 1138 (2509)* 358 (14) 78/65
432 (17)
20REOZJC with IBC Seismic Certification 686 (27)
No Tank 0 1384 (54.6) 943 (2080) 830 (1830) 152 (6)
305 (12)
295 (78) 24/41 1671 (65.8) 1272 (2806)* 1159 (2556)* 406 (16)
428 (113) 36/59 2320 (91.3) 1077 (42.4) 1773 (69.8) 1321 (2913)* 1208 (2663)* 559 (22)
625 (165) 48/86 1925 (75.8) 1393 (3073)* 1280 (2823)* 100 (4)
254 (10)
20REOZJC with State Code Fuel Tank[ 358 (14)
508 (20)
439 (116) 24/61 1671 (65.8) 1362 (3003)* 1249 (2753)*
358 (14)
556 (147) 48/77 2896 (114) 1077 (42.4) 1849 (72.8) 1459 (3217)* 1346 (2967)* 432 (17)
686 (27)
958 (253) 72/133 2103 (82.8) 1514 (3338)* 1401 (3088)*
152 (6)
30REOZJC without IBC Seismic Certification 406 (16)
559 (22)
No Tank 0 1438 (56.6) 1007 (2220) 894 (1970) 813 (32)
295 (78) 24/27 1722 (67.8) 1230 (2712)* 1117 (2462)* 100 (4)
424 (112) 36/40 2320 (91.3) 1077 (42.4) 1824 (71.8) 1264 (2787)* 1151 (2537)* 358 (14)
508 (20)
621 (164) 48/58 1976 (77.8) 1315 (2899)* 1202 (2649)* 762 (30)
30REOZJC with IBC Seismic Certification
No Tank 0 1384 (54.6) 1007 (2220) 894 (1970)
295 (78) 24/27 1671 (65.8) 1336 (2946)* 1223 (2696)*
428 (113) 36/40 2320 (91.3) 1077 (42.4) 1773 (69.8) 1385 (3053)* 1271 (2803)*
625 (165) 48/58 1925 (75.8) 1457 (3213)* 1344 (2963)*
30REOZJC with State Code Fuel Tank[
439 (116) 24/41 1671 (65.8) 1424 (3139)* 1311 (2889)*
556 (147) 48/52 2896 (114) 1077 (42.4) 1849 (72.8) 1521 (3353)* 1408 (3103)*
958 (253) 72/90 2103 (82.8) 1576 (3474)* 1463 (3224)*
40REOZJC without IBC Seismic Certification
No Tank 0 1438 (56.6) 966 (2130) 853 (1880)
424 (112) 24/32 1824 (71.8) 1223 (2697)* 1110 (2447)*
621 (164) 48/48 2320 (91.3) 1077 (42.4) 1976 (77.8) 1274 (2809)* 1161 (2559)*
946 (250) 72/73 2230 (87.8) 1555 (3429)* 1442 (3179)*
40REOZJC with IBC Seismic Certification
No Tank 0 1384 (54.6) 966 (2130) 853 (1880)
428 (113) 24/33 2320 (91.3) 1077 (42.4) 1773 (69.8) 1344 (2963)* 1231 (2713)*
625 (165) 48/48 1925 (75.8) 1416 (3123)* 1303 (2873)*
958 (253) 72/74 2179 (85.8) 1736 (3826)* 1622 (3576)*
40REOZJC with State Code Fuel Tank[
439 (116) 24/34 2896 (114) 1077 (42.4) 1671 (65.8) 1451 (3199)* 1338 (2949)* 358 (14) 78/65
958 (253) 48/74 2103 (82.8) 1575 (3472)* 1462 (3222)* 686 (27)
Note: Data in table is for reference only, refer to the respective ADV drawings for details.
Note: Refer to TIB-114 for generator set sound data.
* Max. weight includes the generator set (wet) using the largest alternator option, enclosure with acoustic insulation added, silencer, and tank (no fuel).
[ State code fuel tank specifications (height and weight) include I-beam option.
G6-99 5/14aa Page 5
Enclosure and Subbase Fuel Tank Specifications (continued)
Enclosure and Subbase Fuel Tank Sound
Pressure at
Est. Fuel Max. Dimensions, mm (in.) Max. Weight, kg (lb.) * 60 Hz with
Supply Hours Full Load at
Fuel Tank at 60 Hz with Length Width Height With Steel With Aluminum Fuel Tank 7 m (23 ft.),
Capacity, Enclosure Enclosure Height,
Full Load, mm (in.) Weather/
L (gal.) Nominal/Actual Sound
0 (0) dB(A)
40REOZJE 406 (16) 78/67
660 (26) 78/67
No Tank 0 1451 (57.1) 1188 (2620) 1085 (2393) 914 (36) 78/66
78/66
432 (114) 24/30 2320 (91.3) 1077 (42.4) 1857 (73.1) 1446 (3190)* 1343 (2963)* 381 (15) 78/66
715 (189) 36/51 2111 (83.1) 1522 (3357)* 1419 (3130)* 610 (24) 78/67
889 (35) 78/67
1071 (283) 48/76 2365 (93.1) 1612 (3555)* 1509 (3328)* 78/68
152 (6) 78/68
40REOZJE with State Code Fuel Tank 406 (16) 78/68
559 (22)
473 (125) 24/33 1832 (72.1) 1613 (3558)* 1510 (3331)* 813 (32)
886 (234) 48/63 2896 (114.0) 1077 (42.4) 2061 (81.1) 1753 (3867)* 1650 (3640)* 100 (4)
358 (14)
1302 (344) 72/92 2340 (92.1) 1914 (4220)* 1811 (3993)* 508 (20)
762 (30)
50REOZJD without IBC Seismic Certification
358 (14)
No Tank 0 1438 (56.6) 1027 (2265) 914 (2015) 686 (27)
914 (36)
424 (112) 24/26 2320 (91.3) 1824 (71.8) 1285 (2832)* 1171 (2582)*
621 (164) 36/38 1077 (42.4) 1976 (77.8) 1335 (2944)* 1222 (2694)* 0 (0)
406 (16)
946 (250) 48/58 2230 (87.8) 1555 (3429)* 1442 (3179)* 660 (26)
914 (36)
50REOZJD with IBC Seismic Certification
381 (15)
No Tank 0 1384 (54.6) 1027 (2265) 914 (2015) 610 (24)
889 (35)
428 (113) 24/26 2320 (91.3) 1773 (69.8) 1405 (3098)* 1292 (2848)*
625 (165) 36/38 1077 (42.4) 1925 (75.8) 1477 (3258)* 1364 (3008)* 152 (6)
457 (18)
958 (253) 48/58 2179 (85.8) 1736 (3826)* 1622 (3576)* 686 (27)
813 (32)
50REOZJD with State Code Fuel Tank[
100 (4)
439 (116) 24/26 1824 (71.8) 1529 (3371)* 1416 (3121)* 406 (16)
635 (25)
958 (253) 48/58 2896 (114) 1077 (42.4) 2103 (82.8) 1653 (3644)* 1540 (3394)* 762 (30)
1408 (372) 72/86 2332 (91.8) 1804 (3977)* 1691 (3727)* 432 (17)
686 (27)
50REOZJE 914 (36)
No Tank 0 1451 (57.1) 1188 (2620) 1085 (2393)
432 (114) 24/24 2320 (91.3) 1857 (73.1) 1446 (3190)* 1343 (2963)*
715 (189) 36/41 1077 (42.4) 2111 (83.1) 1522 (3357)* 1419 (3130)*
1071 (283) 48/61 2365 (93.1) 1612 (3555)* 1509 (3328)*
50REOZJE with State Code Fuel Tank
473 (125) 24/27 1832 (72.1) 1613 (3558)* 1510 (3331)*
886 (234) 48/50 2896 (114.0) 1077 (42.4) 2061 (81.1) 1753 (3867)* 1650 (3640)*
1302 (344) 72/74 2340 (92.1) 1914 (4220)* 1811 (3993)*
60REOZJD without IBC Seismic Certification
No Tank 0 1438 (56.6) 1164 (2566) 1051 (2316)
492 (130) 24/26 2320 (91.3) 1824 (71.8) 1438 (3170)* 1324 (2920)*
783 (207) 36/41 1077 (42.4) 2103 (82.8) 1514 (3338)* 1401 (3088)*
946 (250) 48/50 2230 (87.8) 1555 (3429)* 1442 (3179)*
60REOZJD with IBC Seismic Certification
No Tank 0 1384 (54.6) 1164 (2566) 1051 (2316)
492 (130) 24/26 2320 (91.3) 1077 (42.4) 1773 (69.8) 1566 (3452)* 1452 (3202)*
795 (210) 36/42 2052 (80.8) 1687 (3719)* 1574 (3469)*
958 (253) 48/50 2179 (85.8) 1736 (3826)* 1622 (3576)*
60REOZJD with State Code Fuel Tank[
556 (147) 24/29 1849 (72.8) 1616 (3563)* 1503 (3313)*
958 (253) 48/50 2895 (114) 1077 (42.4) 2103 (82.8) 1767 (3896)* 1654 (3646)*
1408 (372) 72/74 2332 (91.8) 1918 (4228)* 1805 (3978)*
G6-99 5/14aa Page 6
Enclosure and Subbase Fuel Tank Sound
Pressure at
Est. Fuel Max. Dimensions, mm (in.) Max. Weight, kg (lb.) * 60 Hz with
Supply Hours Full Load at
Fuel Tank at 60 Hz with Length Width Height With Steel With Aluminum Fuel Tank 7 m (23 ft.),
Capacity, Enclosure Enclosure Height,
Full Load, mm (in.) Weather/
L (gal.) Nominal/Actual Sound
152 (6) dB(A)
80REOZJF without IBC Seismic Certification 508 (20) 83/69
813 (32) 83/69
No Tank 0 1575 (62) 1483 (3269) 1351 (2979) 83/69
1766 (3894)* 1635 (3604)* 102 (4) 82/69
791 (209) 24/30 2821 (111.1) 1156 (45.5) 1930 (76) 1882 (4150)* 1751 (3860)* 457 (18) 82/69
1317 (348) 48/50 2235 (88) 762 (30) 82/69
87/73
80REOZJF with IBC Seismic Certification 432 (17) 87/73
762 (30) 86/75
No Tank 0 1525 (60) 1483 (3269) 1351 (2979) 86/75
1851 (4080)* 1719 (3790)* 152 (6)
757 (200) 24/28 2821 (111.1) 1156 (45.5) 1880 (74) 2108 (4647)* 1976 (4357)* 508 (20)
1313 (347) 48/50 2185 (86) 813 (32)
80REOZJF with State Code Fuel Tank[ 102 (4)
457 (18)
814 (215) 24/31 3400 (133.9) 1156 (45.5) 1855 (73) 1996 (4400)* 1864 (4110)* 762 (30)
1571 (415) 48/60 2185 (86) 2236 (4929)* 2104 (4639)*
432 (17)
100REOZJF without IBC Seismic Certification 762 (30)
No Tank 0 2821 (111.1) 1156 (45.5) 1575 (62) 1592 (3510) 1461 (3220) 0 (0)
791 (209) 24/25 1930 (76) 1875 (4134)* 1744 (3844)* 483 (19)
2235 (88) 2070 (4564)* 1939 (4274)* 914 (36)
1696 (448) 48/54 3400 (133.9)
483 (19)
100REOZJF with IBC Seismic Certification 838 (33)
No Tank 0 2821 (111.1) 1156 (45.5) 1525 (60) 1592 (3510) 1461 (3220) 0 (0)
757 (200) 24/24 1880 (74) 1960 (4320)* 1828 (4030)* 483 (19)
2185 (86) 2345 (5170)* 2214 (4880)* 914 (36)
1699 (449) 48/54 3400 (133.9)
483 (19)
100REOZJF with State Code Fuel Tank[ 838 (33)
814 (215) 24/26 3400 (133.9) 1855 (73) 2105 (4641)* 1974 (4351)*
1571 (415) 48/50 1156 (45.5) 2185 (86) 2345 (5170)* 2214 (4880)*
125REOZJG 0 1753 (69) 1651 (3632) 1515 (3333)
No Tank 2400 (5280)* 2264 (4981)*
2751 (6052)* 2615 (5753)*
1128 (298) 24/30 3532 (139.0) 1153 (45.4) 2236 (88)
2207 (583) 48/58 2667 (105)
125REOZJG with State Code Fuel Tank[
1196 (316) 24/31 4414 (173.8) 2236 (88) 2382 (5240)* 2446 (4941)*
2252 (595) 48/60 1153 (45.4) 2591 (102) 2654 (5839)* 2500 (5511)*
150REOZJF
No Tank 0 1753 (69) 1860 (4101) 1724 (3800)
2609 (5752)* 2473 (5452)*
1128 (298) 24/25 3532 (139.0) 1153 (45.4) 2236 (88) 2960 (6526)* 2824 (6226)*
2207 (583) 48/49 2667 (105)
150REOZJF with State Code Fuel Tank[
1196 (316) 24/27 4414 (173.8) 2236 (88) 2591 (5712)* 2455 (5412)*
2252 (595) 48/50 1153 (45.4) 2591 (102) 2890 (6361)* 2727 (6012)*
Note: Data in table is for reference only, refer to the respective ADV drawings for details.
Note: Refer to TIB-114 for generator set sound data.
* Max. weight includes the generator set (wet) using the largest alternator option, enclosure with acoustic insulation added, silencer, and tank (no fuel).
[ State code fuel tank specifications (height and weight) include I-beam option.
G6-99 5/14aa Page 7
Enclosure and Subbase Fuel Tank Specifications (continued)
Enclosure and Subbase Fuel Tank Sound
Pressure at
Fuel Tank Est. Fuel Max. Dimensions, mm (in.) Max. Weight, kg (lb.) * Fuel Tank 60 Hz with
Capacity, Supply Hours Height, Full Load at
at 60 Hz with Length Width Height With Steel With Aluminum mm (in.) 7 m (23 ft.),
L (gal.) Enclosure Enclosure
180REOZJF Full Load, 0 (0) Weather/
Nominal/Actual 483 (19) Sound dB(A)
No Tank 889 (35)
1514 (400) 0 4094 (161.2) 1338 (52.7) 2057 (81) 1928 (4250) 1780 (3925) 87/72
2869 (758) 24/29 2540 (100) 2861 (6307)* 2713 (5981)*
48/55 2946 (116) 3255 (7176)* 3107 (6850)*
180REOZJF with State Code Fuel Tank[
1556 (416) 24/30 5008 (197.2) 1338 (52.7) 2585 (102) 3162 (6971)* 3014 (6646)* 457 (18) 87/72
2896 (765) 48/56 2890 (114) 3488 (7690)* 3340 (7363)* 762 (30)
180REOZJG 0 4094 (161.2) 1338 (52.7) 2057 (81) 1928 (4250) 1780 (3925) 0 (0) 85/72
No Tank 24/31 2540 (100) 2861 (6307)* 2713 (5981)* 483 (19)
48/58 2946 (116) 3255 (7176)* 3107 (6850)* 889 (35)
1514 (400)
2869 (758)
180REOZJG with State Code Fuel Tank[
1556 (416) 24/32 5008 (197.2) 1338 (52.7) 2585 (102) 3162 (6971)* 3014 (6646)* 457 (18) 85/72
2896 (765) 48/59 1338 (52.7) 2890 (114) 3488 (7690)* 3340 (7363)* 762 (30) 87/75
1338 (52.7) 87/75
200REOZJF 1338 (52.7) 2057 (81) 2309 (5090) 2161 (4764) 0 (0) 87/75
1338 (52.7) 2540 (100) 3242 (7147)* 3094 (6821)* 483 (19) 87/75
No Tank 0 1338 (52.7) 2946 (116) 3636 (8016)* 3488 (7690)* 889 (35) 89/75
1338 (52.7) 89/75
1514 (400) 24/26 4094 (161.2) 1338 (52.7) 2585 (102) 3543 (7811)* 3395 (7485)* 457 (18) 89/75
1338 (52.7) 2890 (114) 4050 (8930)* 3721 (8203)* 762 (30) 89/75
2869 (758) 48/49
2157 (84.9) 2654 (5850) 2540 (5600) 0 (0)
200REOZJF with State Code Fuel Tank[ 2659 (104.7) 3561 (7850)* 3447 (7600)* 762 (30)
1575 (416) 24/27 5008 (197.2) 2792 (109.9) 3895 (8587)* 3782 (8337)* 635 (25)
2896 (765) 48/50 3071 (120.9) 4504 (9930)* 4391 (9680)* 914 (36)
230REOZJE 2157 (84.9) 2699 (5950) 2585 (5700) 0 (0)
2659 (104.7) 3606 (7950)* 3493 (7700)* 762 (30)
No Tank 0 4121 (162.3)
1787 (472) 24/29 2792 (109.9) 3940 (8687)* 3827 (8437)* 635 (25)
3071 (120.9) 4550 (10030)* 4436 (9780)* 914 (36)
230REOZJE with State Code Fuel Tank[
2157 (84.9) 2835 (6250) 2722 (6000) 0 (0)
2101 (555) 24/34 5009 (197.2) 2659 (104.7) 3742 (8250)* 3629 (8000)* 762 (30)
3573 (944) 48/58 5325 (209.7) 2792 (109.9) 4076 (8987)* 3963 (8737)* 635 (25)
3071 (120.9) 4686 (10330)* 4572 (10080)* 914 (36)
250REOZJE
No Tank 0 4121 (162.3)
1787 (472) 24/26
250REOZJE with State Code Fuel Tank[
2101 (555) 24/31 5009 (197.2)
3573 (944) 48/53 5325 (209.7)
275REOZJE
No Tank 0 4121 (162.3)
1787 (472) 24/24
275REOZJE with State Code Fuel Tank[
2101 (555) 24/28 5009 (197.2)
3573 (944) 48/48 5325 (209.7)
Note: Data in table is for reference only, refer to the respective ADV drawings for details.
Note: Refer to TIB-114 for generator set sound data.
* Max. weight includes the generator set (wet) using the largest alternator option, enclosure with acoustic insulation added, silencer, and tank (no fuel).
[ State code fuel tank specifications (height and weight) include I-beam option.
G6-99 5/14aa Page 8
Enclosure and Subbase Fuel Tank Specifications (continued)
300REOZJ
No Tank 0 2157 (84.9) 2835 (6250) 2722 (6000) 0 (0) 89/75
2067 (546) 24/24 4121 (162.3) 1338 (52.7) 2735 (107.7) 3770 (8311)* 3656 (8061)* 838 (33)
300REOZJ with State Code Fuel Tank[
2101 (555) 24/25 5009 (197.2) 2792 (109.9) 4076 (8987)* 3963 (8737)* 635 (25)
4065(1074) 48/48 5588 (220.0) 1338 (52.7) 3071 (120.9) 4644 (10238)* 4530 (9988)* 914 (36) 89/75
Note: Data in table is for reference only, refer to the respective ADV drawings for details.
Note: Refer to TIB-114 for generator set sound data.
* Max. weight includes the generator set (wet) using the largest alternator option, enclosure with acoustic insulation added, silencer, and tank (no fuel).
[ State code fuel tank specifications (height and weight) include I-beam option.
G6-99 5/14aa Page 9
KOHLER CO., Kohler, Wisconsin 53044 USA Kohler Power Systems
Phone 920-457-4441, Fax 920-459-1646 Asia Pacific Headquarters
For the nearest sales and service outlet in the 7 Jurong Pier Road
US and Canada, phone 1-800-544-2444 Singapore 619159
KOHLERPower.com Phone (65) 6264-6422, Fax (65) 6264-6455
DISTRIBUTED BY:
Availability is subject to change without notice. Kohler Co. reserves the 2008, 2009, 2010, 2011, 2012, 2013, 2014 by Kohler Co. All rights reserved.
right to change the design or specifications without notice and without any
obligation or liability whatsoever. Contact your local Kohlerr generator
set distributor for availability.