OSHPD Fire Resistive Standard Details

MAX 1" MAX 1" NON-RATED ASSEMBLY Code : OPD No: Agency Stamp: Section Title : Sheet Title : Issue Date : Revision : Date : OSHPD FIRE RESISTIVE STANDARD ...

6/25/2013 11:32:09 AM STRUCTURAL STEEL COLUMN W/ SPRAY
APPLIED FIREPROOFING. REFER
STRUCTURAL DRAWINGS

COLD FORMED METAL STUD. REFER
ARCHITECTURAL DRAWINGS FOR WALL
TYPE.

COLD FORMED SHAFT STUD. REFER
ARCHITECTURAL DRAWINGS FOR WALL
TYPE.

GYPSUM BOARD. REFER ARCHITECTURAL
DRAWINGS FOR WALL TYPE.

COMPRESSED MINERAL WOOL

OR FIRE SEALANT

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FR0.02
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title :

GRAPHICS LEGEND

6/25/2013 11:32:09 AM

1 HOUR RATED GYPSUM WALLBOARD ASSEMLY
CONSTRUCTION PER CBC-720 OR TESTED LISTING

CONTINUOUS RATED ASSEMBLY

1" 1" STRUCTURAL STEEL
MAX MAX COLUMN W/ SPRAY
APPLIED FIREPROOFING
TYPICAL FIRE RESISTIVE JOINT PER CBC-721 OR TESTED
COMPRISED OF 4 PCF MINERAL LISTING
WOOL COMPRESSED 50% W/ UL
CLASSIFIED (ANSI/UL 1479) LINE OF NON-RATED FINISH
SEALANT COVER MIN 5/8' OVER CONSTRUCTION AROUND
GYP. BD. AND 2" OVER COLUMN COLUMN (OPTIONAL)
FIREPROOFING. TYPICAL ALL
COLUMN INTERSECTIONS.

NOTES:
1. MAXIMUM SEPARATION BETWEEN SIDE OF GYPSUM
WALLBOARD AND FACE OF FIREPROOFING IS 1".
2. THE FIRE RESISTIVE RATING OF STEEL COLUMN MUST BE
EQUAL OR GREATER THAN WALL RATING.
3. "WET" THICKNESS OF SEALANT TO BE MIN. 1/8" TESTED IN
ACCORDANCE WITH ASTM E1966 (ANSI/UL 2079).

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title : FR1.10

INTERSECTION OF 1-HR-FR PARTITION, WALL
AND BARRIER AT PROTECTED COLUMN

6/25/2013 11:32:09 AM

1 HOUR RATED GYPSUM WALLBOARD ASSEMLY
CONSTRUCTION PER CBC-720 OR TESTED LISTING

NON-RATED ASSEMBLY

1" 1" STRUCTURAL STEEL
MAX MAX COLUMN W/ SPRAY
APPLIED FIREPROOFING
TYPICAL FIRE RESISTIVE JOINT PER CBC-721 OR TESTED
COMPRISED OF 4 PCF MINERAL LISTING
WOOL COMPRESSED 50% W/ UL
CLASSIFIED (ANSI/UL 1479) LINE OF NON-RATED
SEALANT COVER MIN 5/8' OVER FINISH CONSTRUCTION
GYP. BD. AND 2" OVER COLUMN AROUND COLUMN
FIREPROOFING. TYPICAL ALL (OPTIONAL)
COLUMN INTERSECTIONS.

NOTES:
1. MAXIMUM SEPARATION BETWEEN SIDE OF GYPSUM
WALLBOARD AND FACE OF FIREPROOFING IS 1".
2. THE FIRE RESISTIVE RATING OF STEEL COLUMN MUST BE
EQUAL OR GREATER THAN WALL RATING.
3. "WET" THICKNESS OF SEALANT TO BE MIN. 1/8" TESTED IN
ACCORDANCE WITH ASTM E1966 (ANSI/UL 2079).

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title : FR1.10 ALT

INTERSECTION OF 1-HR-FR PARTITION, WALL
AND BARRIER AT PROTECTED COLUMN

6/25/2013 11:32:10 AM

1 HOUR RATED GYPSUM WALLBOARD ASSEMLY
CONSTRUCTION PER CBC-720 OR TESTED LISTING

CONTINUOUS RATED ASSEMBLY

1" 1"
MAX MAX

TYPICAL FIRE RESISTIVE JOINT STRUCTURAL STEEL
COMPRISED OF 4 PCF MINERAL COLUMN W/ SPRAY
WOOL COMPRESSED 50% W/ UL APPLIED FIREPROOFING
CLASSIFIED (ANSI/UL 1479) PER CBC-721 OR TESTED
SEALANT COVER MIN 5/8' OVER LISTING
GYP. BD. AND 2" OVER COLUMN
FIREPROOFING. TYPICAL ALL LINE OF NON-RATED
COLUMN INTERSECTIONS. FINISH CONSTRUCTION
AROUND COLUMN
(OPTIONAL)

NOTES:
1. MAXIMUM SEPARATION BETWEEN SIDE OF GYPSUM
WALLBOARD AND FACE OF FIREPROOFING IS 1".
2. THE FIRE RESISTIVE RATING OF STEEL COLUMN MUST BE
EQUAL OR GREATER THAN WALL RATING.
3. "WET" THICKNESS OF SEALANT TO BE MIN. 1/8" TESTED IN
ACCORDANCE WITH ASTM E1966 (ANSI/UL 2079).

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title : FR1.11

INTERSECTION OF 1-HR-FR PARTITION, WALL
AND BARRIER AT PROTECTED COLUMN

6/25/2013 11:32:10 AM

1 HOUR RATED GYPSUM WALLBOARD ASSEMLY
CONSTRUCTION PER CBC-720 OR TESTED LISTING

NON-RATED ASSEMBLY

1" 1"
MAX MAX

TYPICAL FIRE RESISTIVE JOINT STRUCTURAL STEEL
COMPRISED OF 4 PCF MINERAL COLUMN W/ SPRAY
WOOL COMPRESSED 50% W/ UL APPLIED FIREPROOFING
CLASSIFIED (ANSI/UL 1479) PER CBC-721 OR TESTED
SEALANT COVER MIN 5/8' OVER LISTING
GYP. BD. AND 2" OVER COLUMN
FIREPROOFING. TYPICAL ALL LINE OF NON-RATED
COLUMN INTERSECTIONS. FINISH CONSTRUCTION
AROUND COLUMN
(OPTIONAL)

NOTES:
1. MAXIMUM SEPARATION BETWEEN SIDE OF GYPSUM
WALLBOARD AND FACE OF FIREPROOFING IS 1".
2. THE FIRE RESISTIVE RATING OF STEEL COLUMN MUST BE
EQUAL OR GREATER THAN WALL RATING.
3. "WET" THICKNESS OF SEALANT TO BE MIN. 1/8" TESTED IN
ACCORDANCE WITH ASTM E1966 (ANSI/UL 2079).

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title : FR1.11 ALT

INTERSECTION OF 1-HR-FR PARTITION, WALL
AND BARRIER AT PROTECTED COLUMN

6/25/2013 11:32:12 AM

1 HOUR RATED GYPSUM WALLBOARD ASSEMLY
CONSTRUCTION PER CBC-720 OR TESTED LISTING

CONTINUOUS RATED ASSEMBLY

STRUCTURAL STEEL
COLUMN W/ SPRAY
APPLIED
FIREPROOFING PER
CBC-721 OR TESTED
LISTING

1"
MAX 1" MAX

TYPICAL FIRE RESISTIVE JOINT LINE OF NON-
COMPRISED OF 4 PCF MINERAL RATED FINISH
WOOL COMPRESSED 50% W/ UL CONSTRUCTION
CLASSIFIED (ANSI/UL 1479) AROUND COLUMN
SEALANT COVER MIN 5/8' OVER (OPTIONAL)
GYP. BD. AND 2" OVER COLUMN
FIREPROOFING. TYPICAL ALL
COLUMN INTERSECTIONS.

NOTES:
1. MAXIMUM SEPARATION BETWEEN SIDE OF GYPSUM
WALLBOARD AND FACE OF FIREPROOFING IS 1".
2. THE FIRE RESISTIVE RATING OF STEEL COLUMN MUST BE
EQUAL OR GREATER THAN WALL RATING.
3. "WET" THICKNESS OF SEALANT TO BE MIN. 1/8" TESTED IN
ACCORDANCE WITH ASTM E1966 (ANSI/UL 2079).

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title : FR1.12

INTERSECTION OF 1-HR-FR PARTITION, WALL
AND BARRIER AT PROTECTED COLUMN

6/25/2013 11:32:12 AM
NON-RATED .ASSEMBLY
1 HOUR RATED GYPSUM WALLBOARD ASSEMLY
CONSTRUCTION PER CBC-720 OR TESTED LISTING

NON-RATED ASSEMBLY

1" STRUCTURAL STEEL
MAX 1" MAX COLUMN W/ SPRAY
APPLIED
TYPICAL FIRE RESISTIVE JOINT FIREPROOFING PER
COMPRISED OF 4 PCF MINERAL CBC-721 OR TESTED
WOOL COMPRESSED 50% W/ UL LISTING
CLASSIFIED (ANSI/UL 1479)
SEALANT COVER MIN 5/8' OVER 1 HOUR RATED
GYP. BD. AND 2" OVER COLUMN GYPSUM
FIREPROOFING. TYPICAL ALL WALLBOARD
COLUMN INTERSECTIONS. ASSEMLY
CONSTRUCTION
LINE OF NON- PER CBC-720 OR
RATED FINISH TESTED LISTING
CONSTRUCTION
AROUND COLUMN
(OPTIONAL)

NOTES:
1. MAXIMUM SEPARATION BETWEEN SIDE OF GYPSUM
WALLBOARD AND FACE OF FIREPROOFING IS 1".
2. THE FIRE RESISTIVE RATING OF STEEL COLUMN MUST BE
EQUAL OR GREATER THAN WALL RATING.
3. "WET" THICKNESS OF SEALANT TO BE MIN. 1/8" TESTED IN
ACCORDANCE WITH ASTM E1966 (ANSI/UL 2079).

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS FR1.12 ALT

Sheet Title :

INTERSECTION OF 1-HR-FR PARTITION, WALL
AND BARRIER AT PROTECTED COLUMN

6/25/2013 11:32:12 AM1 HOUR RATED GYPSUM WALLBOARD ASSEMLY
CONTINUOUS RATED ASSEMBLYCONSTRUCTION PER CBC-720 OR TESTED LISTING

CONTINUOUS RATED ASSEMBLY

STRUCTURAL STEEL
COLUMN W/ SPRAY
APPLIED
FIREPROOFING PER
CBC-721 OR TESTED
LISTING

1"
MAX 1" MAX

TYPICAL FIRE RESISTIVE JOINT 1 HOUR RATED
COMPRISED OF 4 PCF MINERAL GYPSUM
WOOL COMPRESSED 50% W/ UL WALLBOARD
CLASSIFIED (ANSI/UL 1479) ASSEMLY
SEALANT COVER MIN 5/8' OVER CONSTRUCTION
GYP. BD. AND 2" OVER COLUMN PER CBC-720 OR
FIREPROOFING. TYPICAL ALL TESTED LISTING
COLUMN INTERSECTIONS.

LINE OF NON-
RATED FINISH
CONSTRUCTION
AROUND COLUMN
(OPTIONAL)

NOTES:
1. MAXIMUM SEPARATION BETWEEN SIDE OF GYPSUM
WALLBOARD AND FACE OF FIREPROOFING IS 1".
2. THE FIRE RESISTIVE RATING OF STEEL COLUMN MUST BE
EQUAL OR GREATER THAN WALL RATING.
3. "WET" THICKNESS OF SEALANT TO BE MIN. 1/8" TESTED IN
ACCORDANCE WITH ASTM E1966 (ANSI/UL 2079).

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title : FR1.13

INTERSECTION OF 1-HR-FR PARTITION, WALL
AND BARRIER AT PROTECTED COLUMN

6/25/2013 11:32:13 AM
NON-RATED
ASSEMBLY
1 HOUR RATED GYPSUM WALLBOARD ASSEMLY
CONSTRUCTION PER CBC-720 OR TESTED LISTING

NON-RATED ASSEMBLY

1" MAX

1"
MAX

.

1" STRUCTURAL STEEL
MAX 1" MAX COLUMN W/ SPRAY
APPLIED
TYPICAL FIRE RESISTIVE JOINT FIREPROOFING PER
COMPRISED OF 4 PCF MINERAL CBC-721 OR TESTED
WOOL COMPRESSED 50% W/ UL LISTING
CLASSIFIED (ANSI/UL 1479)
SEALANT COVER MIN 5/8' OVER 1 HOUR RATED
GYP. BD. AND 2" OVER COLUMN GYPSUM
FIREPROOFING. TYPICAL ALL WALLBOARD
COLUMN INTERSECTIONS. ASSEMLY
CONSTRUCTION
LINE OF NON- PER CBC-720 OR
RATED FINISH TESTED LISTING
CONSTRUCTION
AROUND COLUMN
(OPTIONAL)

NOTES:
1. MAXIMUM SEPARATION BETWEEN SIDE OF GYPSUM
WALLBOARD AND FACE OF FIREPROOFING IS 1".
2. THE FIRE RESISTIVE RATING OF STEEL COLUMN MUST BE
EQUAL OR GREATER THAN WALL RATING.
3. "WET" THICKNESS OF SEALANT TO BE MIN. 1/8" TESTED IN
ACCORDANCE WITH ASTM E1966 (ANSI/UL 2079).

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS FR1.13 ALT

Sheet Title :

INTERSECTION OF 1-HR-FR PARTITION, WALL
AND BARRIER AT PROTECTED COLUMN

6/25/2013 11:32:13 AM

1-HOUR PARTITION AS
SCHEDULED - SEE
ARCHITECTURAL
DRAWINGS FOR WALL
TYPE
RECESSED MEP ITEM -
SEE MEP DRAWINGS

(2) #10 SELF-TAPPING
SCREWS EACH SIDE OF
CABINET TYPICAL
5-SIDE GYPSUM WALLBOARD
WRAP. FIRETAPE @ INSIDE
CORNERS

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FR3.32
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title :

RECESSED M.E.P. CABINETS

6/25/2013 11:32:13 AM MECHANICAL DUCT
WHERE OCCURS. SEE
MECHANICAL DRAWINGS 4 PSF MINERAL
WOOL FILLING
STRUCTURAL CAVITY
CONCRETE SLAB. SEE COMPLETELY
STRUCTURAL DRAWINGS
DIAGONAL
FIRE RESISTIVE JOINT BRACING PER
SPRAY O/ MINERAL DETAILS
WOOL

GYPSUM WALLBOARD
AT VERTICAL PER WALL
TYPE

1" CORE BOARD
PER UL ASSEMBLY

SHAFT STUDS PER
WALL/CEILING TYPE

1" CORE BOARD
PER UL ASSEMBLY

3 LAYERS GYP. BD. AT
HORIZONTAL PER
SPECIFIED REPORT. SEE
ARCHITECURAL
DRAWINGS

11'-0" X 19'-0" MAXIMUM ENCLOSURE AREA

NOTES:
1. DETAIL BASED ON ICBO EVALUATION REPORT ER-3579.
2. REPORTS NER-258, NER-506, ER-2541, AND ER-4924 MAY BE
SUBSTITUTED FOR ER-3579 WITH APPROPRIATE ALTERATIONS
TO HORIZONTAL DRYWALL CONFIGURATION.
3. PROVIDE REPORT ON DOCUMENTS OF RECORD AND
REFERENCE LOCATION.

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FR4.12
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title :

VERTICAL DUCT SHAFT BOTTOM DETAILS

8/14/2013 1:36:34 PM

6
1

2 54

3

1. CONCRETE FLOOR OVER METAL DECKING ASSEMBLY (MINIMUM 2-1/2" THICK)
(2HR. FIRE-RATING).
2. CAST IRON CLOSET FLANGE SIZED TO ACCOMMODATE DRAIN PIPE AND
SECURED TO CONCRETE FLOOR WITH CONCRETE ANCHORS.
3. MAXIMUM 4" NOMINAL DIAMTER CAST IRON PIPE.
4. MINERAL WOOL (MIN. 4 PCF DENSITY) TIGHTLY PACKED AND RECESSED FROM
BOTTOM OF CONCRETE FLOOR TO ACCOMMODATE SEALANT.
5. MINIMUM 1/2" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT.
6. FLOOR MOUNTED VITREOUS CHINA WATER CLOSET.

NOTES: 1. MAXIMUM DIAMETER OF OPENING = 5"
2. ANNULAR SPACE = MINIMUM 3/8"

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FARA4A.240
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title :

FTLoOileOt DReStaLilAB PENETRATION OR WATER
CLOSET WASTE LINE

8/14/2013 1:36:34 PM

PARTITION AS SCHEDULE
SEE PLANS FOR TYPES

3" FLANG KING STUD OR
DOUBLE STUD

1/2" TYP.

16 GA. HOLLOW METAL WRAP-
AROUND DOUBLE RABBET
DOOR FRAME

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FR3.30
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS 1AHARA5

Sheet Title :

HOLLOW METAL DOOR - AROUND DOOR
FRAME @ NON-RATED & 1 HR-RATED WALLS

8/14/2013 1:36:34 PM

PARTITION AS SCHEDULE
SEE PLANS FOR TYPES
3" FLANG KING STUD OR
DOUBLE STUD

16 GA. HOLLOW METAL WRAP-
AROUND DOUBLE RABBET
DOOR FRAME

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FR3.30
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS 2AHARA6

Sheet Title :

HOLLOW METAL SINGLE RABBET DOOR FRAME
@ 2HR-RATED WALL

8/14/2013 2:10:15 PM 713.4.1.1.2 Through-penetration firestop system. Through penetrations shall be
protected by an approved through-penetration firestop system installed and tested in
accordance with ASTM E 814 or UL 1479, with a minimum positive pressure
differential of 0.01 inch of water (2.49 Pa). The system shall have an F rating/T rating
of not less than 1 hour but not less than the required rating of the floor penetrated.

Exception: Floor penetrations contained and located within the cavity of a wall above
the floor or below the floor do not require a T rating.

CHASE WALL PARTITION
AS SCHEDULED - SEE
ARCHITECTURAL
DRAWINGS FOR WALL
TYPE

CHASE WALL ASSEMBLY

MEP PENETRATION INTO
WALL CAVITY

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FR4.23
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title :

CHASE WALL PENETRATIONS

8/13/2013 2:59:28 PM

CONCRETE FLOOR - SEE
STRUCTURAL DRAWINGS

MEP SYSTEM PER DRAWINGS

OCCUPIED FINISH CEILING MEP
FLOOR AREA WHERE OCCURS SHAFT

2 HR RATED
SHAFTWALL ASSEMBLY

(U400 OR V400)

FIRE PROTECTED MEMBRANE
PENETRATIONS
(SINGLE SIDE)
SEE MEP FIRE PROTECTION
DRAWINGS FOR PROTECTION
ASSEMBLY

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FRA3A.A40
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title :

SHAFT WALL MEMBRANE PENETRATIONS

8/16/2013 3:40:41 PM 5/8" GYP BD. TYP 1/2" TYP. VINYL CONTROL JOINT, TYP.
3" MIN 1 HR PARTITION

ACOUSTICAL INSULATION MINERAL WOOL, SAFB
METAL STUD AS SCHEDULED

1/2" TYP.

2 LAYERS VINYL CONTROL JOINT, TYP.
5/8" GYP BD. TYP

3 " MIN

2 HR PARTITION

ACOUSTICAL INSULATION MINERAL WOOL, SAFB
METAL STUD AS SCHEDULED

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FARA3A.590
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title :

Control Joint Details

8/16/2013 3:40:41 PM 1/2" TYP. METAL CONTROL JOINT
5/8"
SEE PLAN FOR PARTITION TYPE

2 LAYERS OF 5/8" TYPE X GYP.
BD. ATTACH TO STUD W/ #10
S.M.S @ 24" OC

1 & 2-HR FIRE RATED
CONTROL JOINT BASED ON GA
DESIGN NO. GA-234-08

1/2" TYP. METAL CONTROL JOINT
5/8"
SEE PLAN FOR PARTITION TYPE

2 LAYERS OF 5/8" TYPE X GYP.
BD. ATTACH TO STUD W/ #10
S.M.S @ 24" OC

1 & 2-HR FIRE RATED
CONTROL JOINT BASED ON GA
DESIGN NO. GA-234-08

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FARA3A.1501
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title :

Control Joint Details

8/21/2013 2:54:50 PM

CONCRETE SLAB -
SEE STRUCTURAL
DRAWINGS

MECHANICAL SUPPORT THROUGH 2"
FIRESPRAY - SEE MEP DRAWINGS
FOR SUPPORT TYPE AND FLUTE STRAP - SEE
LOCATIONS STRUCTURAL DRAWINGS
FOR TYPE AND SPACING.

RATED PARTITION - SEE
ARCHITECTURAL
DRAWINGS FOR ASSEMBLY
TYPE

Agency Stamp: Issue Date : XX/XX/XX OPD No:
Revision : Date :
Code : 2010 CBC FARA3A.670
Section Title : OSHPD FIRE RESISTIVE STANDARD DETAILS

Sheet Title :

PENETRATION REPAIR AT TOP OF WALL